Draft_Salient_Characteristics_1.pdf

PDF 344 KB Posted

Attached to
Weschler Meters and Parts
Solicitation number
140R8122Q0224
Issued by

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient characteristics:

1. Battery Charger Amperage Meter (for BSD AM)

Form-Factor 4 ½” Square meter face (4” diameter panel cutout) Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 50 Votls DC Meter Power 24 Volts DC Scale (meter face) 0 – 200 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) DC AMPS, BATT CHRGR BSD, MARY'S LAKE PP, (Blank), 0-200(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXABA7XXXXXT) will meet these specifications.

2. Battery Bus Amperage Meter (for B AM) Form-Factor 4 ½” Square meter face (4” diameter panel cutout) Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 100 Votls DC Meter Power 24 Volts DC Scale (meter face) 0 – 150 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) DC AMPS, 125V BATTERIES, MARY'S LAKE PP, (Blank), 0-150(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXABC7XXXXXT) will meet

3. Battery Charger Amperage Meter (for BSC AM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 50 Votls DC Meter Power 24 Volts DC Scale (meter face) 0 – 200 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) DC AMPS, BATT CHRGR BSC, MARY'S LAKE PP, (Blank), 0-200(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXABA7XXXXXT) will meet

4. Battery Charger Voltage Meter (for BSD VM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 150 Votls DC Meter Power 24 Volts DC Scale (meter face) 0 – 150 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED

Artwork (per line) DC VOLTS, BATT CHRGR BSD, MARY'S LAKE PP, (Blank), 0-150(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXABE7XXXXXT) will meet

5. 125 Volt Battery Bank Voltage Meter (for B VM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 150 Votls DC Meter Power 24 Volts DC Scale (meter face) 0 – 150 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) DC VOLTS, 125V BATTERIES, MARY'S LAKE PP, (Blank), 0-150(Scale)

6. Battery Charger Voltage Meter (for BSC VM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 150 Votls DC Meter Power 24 Volts DC Scale (meter face) 0 – 150 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) DC VOLTS, BATT CHRGR BSC, MARY'S LAKE PP, (Blank), 0-150(Scale)

7. DC Bus Ground Meter (for BG VM)

Zero Position (meter face) Middle Top Display Color Red Input Range +/-150 Votls DC Meter Power 24 Volts DC Scale (meter face) -150 – 0 – +150 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) DC VOLTS, BATTERY GROUND, MARY'S LAKE PP, (Blank),-

150/0/+150(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4HRXXABE7XXXXXT) will meet

8. Emergency Station Service Transformer Amperage (for KSB AM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 5 Amps AC

Meter Power 24 Volts DC Scale (meter face) 0 – 800 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) AC AMPS, EMERG. STA SVC, MARY'S LAKE PP, (Blank), 0-800(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXDAV7XXXXXT) will meet

9. Station Service Bus Voltage (for SS VM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 150 Volts AC Meter Power 24 Volts DC Scale (meter face) 0 – 600 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) AC VOLTS, STATION SVC., MARY'S LAKE PP, (Blank), 0-600(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXCBE7XXXXXT) will meet

10. Normal Station Service Transformer Amperage (for KSA AM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 5 Amps AC Meter Power 24 Volts DC Scale (meter face) 0 – 800 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) AC AMPS, NORMAL STA SVC, MARY'S LAKE PP, (Blank), 0-800(Scale)

11. Exciter Null/Balance Meter (for Balance Meter)

Zero Position (meter face) Middle Top Display Color Red Input Range +/-10 Votls DC Meter Power 24 Volts DC Scale (meter face) -10 – 0 – +10 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) DC VOLTS, EXCTR BALANCE, MARY'S LAKE PP, (Blank), -10/0/+10(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4HRXXAAW7XXXXXT) will meet

12. Generator Power Meter (for G MW)

Zero Position (meter face) Bottom Left

Display Color Red Input Type Watts, three phase, three wire, two element Current / Voltage Ratios CT ratio 1200:5, PT ratio 7200:120 System Configuration Delta Meter Power 24 Volts DC Trend Indicator Yes Scale (meter face) -10 – 0 – +10 Bar Graph 101-segment red LED Artwork (per line) MEGAWATTS, GENERATOR, MARY'S LAKE PP, (Blank), 0-15(Scale) Weschler BG-241 Circular Bargraph Meter (Part# 4B4XXH337XXTXX) will meet these specifications.

13. Generator Phase A Amperage (for GA AM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 5 Amps AC Meter Power 24 Volts DC Scale (meter face) 0 – 1200 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) AC AMPS, GEN. PHASE A, MARY'S LAKE PP, (Blank), 0- 1200(Scale)

14. Generator Field Amperage (for F AM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 4 – 20 mA DC Meter Power 24 Volts DC Scale (meter face) 0 – 800 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) FIELD AMPS, GENERATOR, MARY'S LAKE PP, (Blank), 0-800(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXPAK7XXXXXT) will meet

15. Generator VAR Meter (for G VARM)

Zero Position (meter face) Middle Top Display Color Red Input Type VARS, three phase, three wire, two element Current / Voltage Ratios CT ratio 1200:5, PT ratio 7200:120 System Configuration Delta Meter Power 24 Volts DC Trend Indicator Yes Scale (meter face) -9 – 0 – +9

Bar Graph 101-segment red LED Artwork (per line) MEGAVAR, GENERATOR, MARY'S LAKE PP, (Blank),-9 – 0 – +9(Scale) Weschler BG-241 Circular Bargraph Meter (Part# 4B4XXZ337XXTXX) will meet these specifications.

16. Generator Voltage Meter (for G VM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 150 Volts AC Meter Power 24 Volts DC Scale (meter face) 0 – 9 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) AC VOLTS, GENERATOR, MARY'S LAKE PP, 1000, 0-9(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXCBE7XXXXXT) will meet

17. Generator Phase B Amperage (for GB AM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 5 Amps AC Meter Power 24 Volts DC Scale (meter face) 0 – 1200 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) AC AMPS, GEN. PHASE B, MARY'S LAKE PP, (Blank), 0- 1200(Scale)

18. Generator Field Voltage (for F VM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 4 – 20 mA DC Meter Power 24 Volts DC Scale (meter face) 0 – 200 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) FIELD VOLTS, GENERATOR, MARY'S LAKE PP, (Blank), 0-200(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXPAK7XXXXXT) will meet

19. Generator Elapsed Time (for G ETM) Form-Factor 1 ½” Square meter face Read-out (meter face) 6-digit, no reset, tamper-proof, mechanical dials Input 120 Volts AC

Simpson Model 112ET, Catalog # SI/03622 will meet these specifications.

20. Generator Phase C Amperage (for GB AM)

Zero Position (meter face) Bottom Left Display Color Red Input Range 0 – 5 Amps AC Meter Power 24 Volts DC Scale (meter face) 0 – 1200 Bar Graph 50-segment, programmable, tri-color (green/amber/red) LED Artwork (per line) AC AMPS, GEN. PHASE C, MARY'S LAKE PP, (Blank), 0- 1200(Scale) Weschler Tri-Color BG-241TC Circular Bargraph Meter (Part# 4BRXXDAV7XXXXXT) will meet these specifications.

Provide seven (7) each of the following Modbus master displays with the following salient characteristics.

Modbus master digital display

Form-Factor 96mm x 48mm x 93mm (92.6mm x 45.6mm panel cutout) Communications RS-485 Protocol Modbus RTU Master (Must be capable of displaying values sent to it from a

Programmable Logic Controller (PLC)) Readout (display) 5-digit LED display, indication range from -19999 to 99999, three color

(red, green and orange) Input Power 20 – 60 Volts DD A LUMEL N30B Digital Panel Recorder (Part# N30B-200000E0) will meet these specifications.

File details come from the government source that posted it. Updated .