Generac Mobile Products LLC l 800-926-9768 l 920-361-4442 l www.generacmobileproducts.com

MMG25IF4

ENGINE

• Isuzu® 4LE2TAGV-03 - turbocharged, aftercooled diesel engine o Prime – 36.2 hp, 27.0kWm @ 1800 rpm o Standby – 41.2 hp, 30.0 kWm @ 1800 rpm o 4 cylinder o 2.2 L displacement o EPA Final Tier 4 approved o *Engine and generator performance are dependent upon 70 hours of break in.

• Polyethylene, single wall fuel tank o 100 gal. (378.5 L) capacity o 42.9 hr. run time – full load o Fuel tank built into skid of generator set o 120% Containment

• Cooling system capable of operating at 120°F (49°C) ambient

• Radiator and oil drains plumbed to exterior

• Rubber vibration dampers isolate engine/generator from frame

• Disposable air filter - paper element

• Air cleaner restriction indicator

• 60 Hz engine/generator

• Electronic isochronous governing

• Idle switch

GENERATOR

• Marathon Electric® SUPERSTART™ o Brushless o 4 pole o Class H insulation

• Voltage regulation +/- 0.5% with Magnum PM600 Voltage Regulator

SYSTEM OUTPUTS

• 3 position selector switch o Single phase – 120 / 240V Zig Zag o Three phase – 120 / 208V Low Wye o Three phase – 277 / 480V High Wye

• 22 kW / 22 kVA – standby, single phase

• 20 kW / 20 kVA – prime, single phase

• 23 kW / 29 kVA – standby, three phase

• 21 kW / 26 kVA – prime, three phase

SPECIFICATIONS

MOBILE DIESEL GENERATOR

MMG25IF4 MOBILE DIESEL GENERATOR

SYSTEM CONTROLS

• Power Zone® controller and display o Backlit, 800 x 480 pixel resolution color display o -40°F to 185°F (-40°C to 85°C) operating temperature range o Automatic coarse voltage adjustment o Integrated fine voltage adjustment o PLC functionality

• Push buttons for easy operation o Manual or Auto Start o Engine Start o Engine Stop/Reset o Alarm Mute o Operator Screens

Home Engine Generator Voltage Adjust o Scrolling Arrows for Diagnostic Information Engine diagnostic display

• Oil pressure

• Engine temperature

• Fuel level

• Battery

• After treatment inlet/outlet temperature

• Ash/soot levels

Generator diagnostic display

• System kW output display

• Line output & frequency display

Alarms

• Warning

• Shutdown

• Electrical Trip

• Engine

Alarm list – warnings / shutdowns; 250 event history log – date/time stamp

• Fuel level: warning – 15%; shutdown – 5%

• Over speed protection: shutdown – 115%

• Oil pressure: warning – 25 psi; shutdown – 20 psi

• Coolant temperature: warning – 220°F (104°C); shutdown – 230°F (110°C)

• Battery voltage: over – 15VDC; under – 11VDC

• Generator over voltage: warning – 110%; electrical trip – 111%

• Generator under voltage: warning – 87%; electrical trip – 86%

• Generator over frequency: warning – 105%; electrical trip – 110%

• Generator under frequency: warning – 95%; electrical trip – 90%

MMG25IF4 MOBILE DIESEL GENERATOR

SYSTEM CONTROLS (continued) Inputs/Outputs Auto Schedule Status

• Configuration of controller, firmware and connections

ELECTRICAL CONTROLS

• Remote start / stop contacts located in lug box

• Lockable control box door with diagnostics window

• Lockable lug box with safety switch o Trips main breaker when door is opened o Disables voltage regulator

• Output ground connection lug inside lug box

• 125A main breaker with shunt trip

• Convenience receptacles with individual breakers (restricted use in high wye mode) o (2) 120V 20 Amp GFCI duplex outlets – (NEMA 5-20R type) o (3) 125 / 250V 50 Amp, 3 pole, 4 wire Twistlock (Non-NEMA 6369)

• Voltage adjustment integrated into Power Zone controller, +/- 10%

• 720 CCA wet cell battery

• Battery disconnect

• Panel lighting for breakers, lugs, and selector switch

ENCLOSURE

• Aluminum, sound attenuated enclosure o UV & fade resistant, high temperature cured, white polyester powder paint o Insulated and baffled o 66 dB(A) @ 23 ft. (7 m) – prime power

• Fully lockable enclosure including doors and fuel fill

• Emergency stop switch located on outside of enclosure

• Central lifting point

• Multi-lingual operating/safety decals

• Document holder with operating manual including AC/DC wiring diagrams

• Interior Cabinet lighting

TRAILER

• DOT approved tail, side, brake, and directional lights - LED

• Transportation tie downs

• Safety chains with spring loaded safety hooks

• 2 in. (50.8 mm) ball hitch

• 5000 lb. (2268 kg) axle

• 2000 lb. (907 kg) tongue jack with footplate

• P225/75 R15 tubeless tires – 6 ply

MMG25IF4 MOBILE DIESEL GENERATOR

WEIGHT & DIMENSIONS

• Skid mounted o Dry weight: 2430 lbs (1102 kg) o Operating weight: 3160 lbs (1433 kg) o 95 x 39 x 65 in (2.41 x 0.99 x 1.65 m)

• Trailer mounted o Dry weight: 2950 lbs (1338 kg) o Operating weight: 3680 lbs (1669 kg) o 152 x 58 x 83 in (3.81 x 1.45 x 2.11 m)

WARRANTY

2 Years / 2000 Hours

CERTIFICATIONS

CSA Certified