DOTD Specification 196-035 Rev. 9-10-2009.pdf
PDF 16 KB Posted
- Attached to
- DOTD PVC, Duct & Couplings(S45)
- Solicitation number
- 3000026952
- Issued by
- East Baton Rouge Parish, Louisiana
About this file
This is a Louisiana Department of Transportation and Development (DOTD) specification document for polyvinyl chloride (PVC) conduit and fittings for electrical wiring installations. The specification details requirements for three sizes of Schedule 80 PVC conduit (1 inch, 2 inch, and 3 inch) along with associated fittings and components. The document establishes material standards requiring virgin polyvinyl chloride construction, compliance with UL and NEMA standards, 90°C cable rating capability, and sunlight resistance. The specification includes precise dimensional requirements for each conduit size, including outer diameter and minimum wall thickness specifications. Additionally, the document lists 15 SAP material master numbers corresponding to specific products from approved manufacturers such as Cantex and Carlon, with acceptable equivalent alternatives permitted.
The specification mandates that all conduit and fittings be capable of direct burial or encasement in concrete without requiring selective backfill or experiencing negative performance effects. Installation applications must protect both the conduit integrity and its contents. The document provides detailed product specifications including 1-inch, 2-inch, and 3-inch conduit sections in ten-foot lengths with bell ends, pipe end caps, 90-degree and 45-degree elbows with specified radius measurements, couplings, molded end bells, and PVC cement glue. The specification was revised on September 10, 2009, and serves as a procurement reference for standardized materials used in DOTD electrical infrastructure projects.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Louisiana Preference-2019.pdf | ||
| US Preference-2019.pdf | ||
| DOTD Specification 196-034 Rev. 1-4-2016.pdf | ||
| 3000026952.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sap Material Master Numbers DOTD Spec. 196-035 See Below Rev. 9/10/2009 2 Pages
LOUISIANA
DEPARTMENT OF TRANSPORTATION AND DEVELOPMENT
SPECIFICATIONS
CONDUIT AND FITTINGS, PVC,
FOR ELECTRICAL WIRING
DESCRIPTION:
The conduit shall be manufactured of virgin polyvinyl chloride. The conduit and fittings shall meet the latest standards of UL and NEMA and shall be rated for 90° C cable.
Conduit and fittings shall be sunlight resistant.
DIMENSIONS:
The dimensions of the conduit shall be as follows:
Size OD Min. Wall Thickness 1 Inch, Schedule 80 1.315 Inch 0.179 Inch 2 Inch, Schedule 80 2.375 Inch 0.218 Inch 3 Inch, Schedule 80 3.500 Inch 0.300 Inch
INSTALLATION:
Conduit and fittings shall be capable of being direct buried or encased in concrete with no special consideration to using selective backfill. No negative effects on performance or to the contents shall be experienced in either of these applications.
Conduit and conduit fitting as shown below:
SAP MATERIAL MASTER NUMBERS
10677 (12-50-0005) 1 inch PVC conduit, Schedule 80, bell end, ten foot length, Cantex
No. A53BA12, or equal
10678 (12-50-0010) 2 inch PVC conduit, Schedule 80, bell end, ten foot length, Cantex
No. A53CA12, or equal
10679 (12-50-0015) 3 inch PVC conduit, Schedule 80, bell end, ten foot length, Cantex
No. A53DA12, or equal
10680 (12-50-0017) 2 inch PVC pipe end cap, Carlon No. E958J, or equal
10681 (12-50-0018) 3 inch PVC pipe end cap, Carlon No. E958L, or equal
10682 (12-50-0020) 1 inch Schedule 80, standard radius 90° elbow, radius 5 ¾ inch, plain end, Cantex No. 5121055, or equal
10683 (12-50-0025) 2 inch Schedule 80, standard radius 90° elbow, radius
9 1/2 inch, plain end, Cantex No. 5121058, or equal
10684 (12-50-0030) 3 inch Schedule 80, standard radius 90° elbow, radius 13 inch, plain end, Cantex No. 5121060, or equal
10685 (12-50-0035) 1 inch Schedule 80, standard radius 45° elbow, radius 5 3/4 inch, plain end, Cantex No. 5121005, or equal
10686 (12-50-0040) 2 inch Schedule 80, standard radius 45° elbow, radius
9 1/2 inch, plain end, Cantex No. 5121008, Carlon No. UB7AJ, or equal
10687 (12-50-0045) 3 inch Schedule 80, standard radius 45° elbow, radius
13 inch, plain end, Cantex No. 5121010, Carlon No. UB7AL, 10688 (12-50-0050) 1 inch couplings, Cantex No. 6141625, Carlon No. E940F, 10689 (12-50-0055) 2 inch couplings, Cantex No. 6141628, or equal
10690 (12-50-0060) 3 inch couplings, Cantex No. 6141630, Carlon No. E940L, or equal
10691 (12-50-0065) 1 inch molded end bell, length 1 1/4 inch, Cantex No. 5144005, Carlon No. E997F-CAR, or equal
10692 (12-50-0070) 2 inch molded end bell, length 1 7/8 inch, Cantex No. 5144008, Carlon No. E997J-CAR, or equal
10693 (12-50-0075) 3 inch Schedule 80, molded end bell, length 2 1/4 inch, Cantex No.
5144010, Carlon No. E997L-CAR, or equal
10694 (12-50-0080) Cement glue for PVC connections, 1 pint, Cantex No. 7210412, Carlon No. VC9983, or equal
| Min. Wall Thickness |
| OD |
| Size |