Question and Answers Osmosis Water Purification Replace
RFQ DJA-22-ALAD-PR-0173
# Question (Q) Answer (A) 1 Is the intent to replace the entire Reverse Osmosis system? Yes – replace the entire system, equipment, and monitoring. Additional pictures attached.
2 Desired amount of water needed per day? 450GPD of 17 megaohm or better.
3 What the desired flow rate is needed (gpm)?
2 loops each 20GPM.
4 What water pressure is needed for use? 70psi.
5 Do you need DI Polishing at the end of the RO System? Yes.
6 Do you need UV lights for the water as well so there is no bacteria that can influence results?
Yes.
7 Is there a water softener in front of the RO System? Yes, considered part of the replacement.
8 Is there any iron in the incoming water? Yes.