DHHS CFP FCA Report 2026 BR.pdf
PDF 4 MB Posted
- Solicitation number
- RFP 171 270000000352 1
- Issued by
- Michigan
About this file
This is a Facility Condition Assessment Report prepared by the Michigan Department of Health and Human Services (DHHS) for the Center for Forensics Psychiatric Hospital located at 8303 Platt Road, Saline, Michigan 48176. The report documents a comprehensive roof inspection identifying multiple deficiencies requiring repair or replacement. Key issues documented include deteriorated EPDM membrane seams requiring re-sealing, minor EPDM bubbling, loose eyebrow steel roofing, rusted screws with dry rotted sealing washers, leaking ridge cap screws due to improper installation, damaged boot flashing around multiple settled vent stacks, lifting and loose steel roof sections, split EPDM membrane, and compromised sealant around transition flashing and parapet walls. The assessment indicates systemic structural failures including pulled or missed screws in the roof framing, a four-inch gap in roof sections, and ballooning EPDM on parapet walls.
The document serves as a facility condition report documenting the current state of the roof system at this state-owned psychiatric hospital. No specific pricing, timeline, or procurement information is provided in this assessment document. The report appears to be an internal facility evaluation used to establish the scope and urgency of required roof repairs or replacement work, which would inform future capital improvement planning and potential contract solicitations for remedial construction services.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Access and Touring_CFP_SS_008F.doc | DOC document | |
| Project Statement 26587.pdf | ||
| Billable Rate 26587.pdf | ||
| Prebid meeting location CFP.pdf | ||
| SAMPLE Billable Rate Contract (Rev 04-25).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Center For Forensics Psychiatric Hospital
8303 Platt Rd, Saline MI 48176
Center For Forensics Psychiatric Hospital – Roof Photo’s
EPDM Boiler plant some areas need seams re-sealed Minor EPDM bubbling
Screw and backer laying under EPDM All eyebrow steel roofing is loose
All screws are rusting sealing washers are dry rotted and deteriorating
Ridge cap screws are leaking from being screwed to adjacent sheet, open hole around the screws.
Bad seams and patches on parapet walls
Screws pulled out of the roof structure entire roof is loose 4inch gap
Screws missed/pulled out of roof framing
Several vent stacks settled causing damage to boot
Loose and lifting steel roof damage to boot damage to boot Split EPDM
Bad sealant around most transtion flashing
Bad sealant around most transtion flashing
Parapet walls EPDM balloning Bad sealant around most transtion flashing