This spreadsheet details underground storage tank (UST) sump and spill bucket inspection results for multiple facilities along with the related federal contract solicitation. Brockton facilities have eight sumps, with one requiring repair and retesting, and seven of eight spill buckets passing. Jamaica Plain facilities have two sumps, with one needing repairs to secure test boots and address corrosion before retesting, and split pass/fail results for spill buckets. West Roxbury facilities have four sumps with one passing and four spill buckets all passing. Solicitation number 36C24123Q1038 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1 seeks underground storage tank sump and hydrostatic repair and testing services.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| LOS Certification.pdf | ||
| 36C24123Q1038.pdf | ||
| SCA Wage Determination 2015-4047 Rev 24 6.30.2023.pdf | ||
| Past Performance Worksheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Brockton USTs Solicitation # 36C24123Q0628 - UST Sump Repair & Hydro Testing
| Brockton USTs | Bldg. 40 #2 Fuel Oil 30,000 gal. Unit 1 Tank | Bldg. 40 #2 Fuel Oil 30,000 gal. Unit 2 Tank | Bldg. 51 4000 gal. Diesel Tank | Bldg. 51 3000 gal. Gasoline Tank | Bldg. 67 4000 gal. Ultra-Low Sulfur Diesel Tank | Bldg. 68 2,500 gal. Ultra-Low Sulfur Diesel Tank | Bldg. 69 2,500 gal. Ultra-Low Sulfur Diesel Tank | Bldg. 70 2,500 gal. Ultra-Low Sulfur Diesel Tank |
| Sump | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| Spill Bucket | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Pass
Fail; requires hydrostatic retest
| Brockton - 8 sumps / 4 passed |
| 8 spill buckets. 1 needs repaired and retested. 7 of the 8 spill buckets passed |
Jamaica Plain USTs Solicitation # 36C24123Q0628 - UST Sump Repair & Hydro Testing
| Jamaica Plain USTs | Bldg. 5 Boiler Plant Low Ultra-Low Sulfur Diesel Tank 10,000 gal. Tank | Bldg. 1A Research Ultra-Low Sulfur Diesel 4,000 gal. Tank |
| Sump | 1 | 1 |
| Spill Bucket | 1 | 1 |
| Pass |
| Failed; required hydrostatic retest | |
| Jamaica Plain - 2 sumps and 2 spill buckets. Bldg. 1A diesel sump by the parking garage is missing 3 clamps to secure test boots, junction box is corroded and needs repairs and retesting. Bldg. 5 Sump needs no repairs but needs testing. |
West Roxbury USTs Solicitation # 36C24123Q0628 - UST Sump Repair & Hydro Testing
| West Roxbury USTs | Bldg. 8 Boiler Plant #2 Fuel Oil 25,000 gal. Tank #1 | Bldg. 8 Boiler Plant #2 Fuel Oil 25,000 gal. Tank #2 | Bldg. 2 #2 Fuel Oil 4,000 gal. Tank | Bldg. 1 #2 Fuel Oil 3,000 gal. Tank |
| Sump | 1 | 1 | 1 | 1 |
| Spill Bucket | 1 | 1 | 1 | 1 |
| Pass |
| Failed; required hydrostatic retest | ||
| W. Roxbury - 4 sumps / 1 passed | ||
| 4 spill buckets/4 passed |
File details come from the government source that posted it. Updated .