Commercial Pool Heat Pump Spacifications.xlsx

XLSX spreadsheet 13 KB Posted

Attached to
19PK3323Q1156– Supply of Commercial Pool Heat Pump
Solicitation number
19PK3323Q1156
Issued by

About this file

This document contains specifications for commercial pool heat pump modules to be supplied under Solicitation 19PK3323Q1156 from the Department of State. The specifications include performance details for inverter-based reversible heat pump modules at different air and water temperatures. Each modular unit would contain two inverter-powered compressors and a titanium tube heat exchanger. Key specifications cover heating capacity, power consumption, coefficient of performance, condenser fan type, compressor type, refrigerant, water flow rate requirements, and module dimensions. The solicitation is for the supply of commercial pool heat pumps meeting these specifications.

View the file

Other files

File Type Posted
RFQ_19PK3323Q1156_Supply of Commercial Pool Heat Pump.pdf PDF
Swimming pool data.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table 1

COMMERCIAL POOL HEAT PUMP SPECIFICATIONS

Inverter Based Reversible Type (with environment friendly refrigerant) Modular Type Vertical AircooledModules4
Aproximate pool volumem3580
Total Performance of the Module at Air 28°C, Water 29°C, Humidity 70%
Turbo Heating capacitykW128
Smart Heating capacitykW108
Power consumptionkW23-6
C.O.P. in Turbo Mode5.6
C.O.P. at 50% capacity10
Module Performance at Air 15°C, Water 26°C, Humidity 70%
Turbo Heating capacitykW98
Smart Heating capacitykW73
Power consumptionkW23-6
C.O.P. in TURBO Mode4.5
C.O.P. at 50% capacity7.5
Module General data
Condensor FanTypeVFD driven - 02 per module
Power inputkW800*2
Fan speedRPM500-750
Noise level(10m)dB(A)≦45
CompressorInverter powered compressor
Each2
(dual circuit will be preferred)
380~415V / 50Hz /3PH
Refrigerant TypeR410 A
Rated currentA33-36
Minimum fuseA50-55
Advised water fluxUS GPM230-270
Water pressure dropPSI6 (max)
Heat exchanger typeTitanium tube heat exchanger

(dual coil is preffered)

Water connectionØ 3.5"
Module - Dimensions
Net weightkg600 (Max)
Gross weightkg700 (Max)
Net dimension (HxWxB)mm2000*1800*1000

File details come from the government source that posted it. Updated .