This document contains specifications for commercial pool heat pump modules to be supplied under Solicitation 19PK3323Q1156 from the Department of State. The specifications include performance details for inverter-based reversible heat pump modules at different air and water temperatures. Each modular unit would contain two inverter-powered compressors and a titanium tube heat exchanger. Key specifications cover heating capacity, power consumption, coefficient of performance, condenser fan type, compressor type, refrigerant, water flow rate requirements, and module dimensions. The solicitation is for the supply of commercial pool heat pumps meeting these specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ_19PK3323Q1156_Supply of Commercial Pool Heat Pump.pdf | ||
| Swimming pool data.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Table 1
COMMERCIAL POOL HEAT PUMP SPECIFICATIONS
| Inverter Based Reversible Type (with environment friendly refrigerant) Modular Type Vertical Aircooled | Modules | 4 | |
| Aproximate pool volume | m3 | 580 | |
| Total Performance of the Module at Air 28°C, Water 29°C, Humidity 70% | |||
| Turbo Heating capacity | kW | 128 | |
| Smart Heating capacity | kW | 108 | |
| Power consumption | kW | 23-6 | |
| C.O.P. in Turbo Mode | 5.6 | ||
| C.O.P. at 50% capacity | 10 | ||
| Module Performance at Air 15°C, Water 26°C, Humidity 70% | |||
| Turbo Heating capacity | kW | 98 | |
| Smart Heating capacity | kW | 73 | |
| Power consumption | kW | 23-6 | |
| C.O.P. in TURBO Mode | 4.5 | ||
| C.O.P. at 50% capacity | 7.5 | ||
| Module General data | |||
| Condensor Fan | Type | VFD driven - 02 per module | |
| Power input | kW | 800*2 | |
| Fan speed | RPM | 500-750 | |
| Noise level(10m) | dB(A) | ≦45 | |
| Compressor | Inverter powered compressor | ||
| Each | 2 | ||
| (dual circuit will be preferred) | |||
| 380~415V / 50Hz /3PH | |||
| Refrigerant Type | R410 A | ||
| Rated current | A | 33-36 | |
| Minimum fuse | A | 50-55 | |
| Advised water flux | US GPM | 230-270 | |
| Water pressure drop | PSI | 6 (max) | |
| Heat exchanger type | Titanium tube heat exchanger |
(dual coil is preffered)
| Water connection | Ø 3.5" | |
| Module - Dimensions | ||
| Net weight | kg | 600 (Max) |
| Gross weight | kg | 700 (Max) |
| Net dimension (HxWxB) | mm | 2000*1800*1000 |