This document is a Statement of Work (SOW) for a Water Distribution and Storage Material Supply project at the Hellgate Campground in Canyon Ferry Reservoir, Montana, issued by the Bureau of Reclamation's Missouri Basin Regional Office. The project involves procuring materials for underground potable water piping, including 3" and 1.5" DR-11 HDPE pipes, various fittings, valves, hydrants, and accessories for a water distribution system expansion.
The SOW specifies detailed requirements for pipe materials, fittings, and components, which must meet specific standards including AWWA, ASTM, and NSF certifications. The supplier is responsible for delivering buried pipe components within 75 days of Notice to Proceed, with specific quantities outlined in the price schedule: 5,000 linear feet of 3" pipe, 1,000 linear feet of 1.5" pipe, multiple bends and tees, curb stops, hydrants, and related accessories. The materials will be delivered to the Hellgate Campground site, with the government providing a location for stockpiling and off-loading delivered items. Detailed technical specifications include requirements for pipe materials, tracing wire, warning tape, and frost-free hydrants.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140R6025Q0049.pdf | ||
| _Q0049_-_Combined_Synopsis.pdf | ||
| _Q0049_-_P_Cs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BOR-SOW
Water Distribution and Storage Material Supply
Statement of Work
Water Distribution and Storage Material Supply
Underground Piping
Bureau of Reclamation
CANYON FERRY RESERVOIR, MT
1.0 Background
The Bureau of Reclamation�s Missouri Basin Regional Office (MBRO) anticipates the award of a purchase order for the supply and delivery of the following to an area on the Hellgate Campground at
Canyon Ferry Reservoir:
A. Potable water buried pipe and fittings.
Government forces will construct the project. This Statement of Work is for procurement of materials to build the project. Measurement and Payment sections of these specifications are in reference to this
Supply Contract.
2.0 Scope
The Supplier shall provide all labor, equipment, tools, materials, transportation, expertise, supervision, start-up services on specialty valves and pumps, and other items and incidental services necessary to supply and deliver the specified materials needed for the construction of the project as shown in the project Plans and Specifications. Supplier is responsible for reviewing and understanding the Plans in order to assure reasonable material supply.
3.0 Objectives
The project will consist of the supply and delivery of the specified materials on site. The Contract includes all pipe, fittings, plumbing and appurtenances to construct the project Plans following the
Specifications.
4.0 Reference Standards
Reference Standards are defined in applicable Specifications.
5.0 Tasks
The Supplier shall provide all labor, equipment, tools, materials, transportation, expertise, supervision, start-up services on specialty valves and pumps, and other items and incidental services necessary to supply and deliver the specified materials needed for the construction of the project. The following
Exhibits are incorporated into this Contract:
A. The Bid Schedule is included in Exhibit A as Section B � Supplies and Prices.
B. The project Plans and Specifications are included in Exhibit B:
6.0 Delivery
The contractor shall furnish everything (equipment, materials, supplies, incidentals, etc.) required to successfully complete the tasks identified in the purchase order.
Supplier of the Utility building shall provide equipment and personnel to pick and set the building in its final place.
Delivery Dates:
Buried pipe components shall be delivered within 75 days of Notice to Proceed.
Supplier shall notify Onsite Delivery Contact at least 3 days in advance of delivery.
Onsite Delivery Contact:
Dustin Ramoie
Office: (406) 475-3922
Cell: (406) 217-2560
7.0 Site Conditions
The Government will provide a suitable location for the Supplier to stockpile delivered materials. The
Government will provide equipment and personnel to off-load delivered items with the exception of the
Utility Building.
8.0 Place of Performance
Work will be performed at the following location:
Department of the Interior
Bureau of Reclamation
Hellgate Campground
Canyon Ferry Reservoir
Lewis and Clark County, MT
Approximate GPS Coordinates: 46.612637° N, -111.649702° W
9.0 Definitions
A. Days: Calendar days.
B. Required Submittal Number (RSN): Identifies items to be submitted together as a complete submittal.
C. CO indicates Contracting Officer.
10.0 Submittals
RSN Submittal Submittal Required Due date or Delivery
Time
Submit to
33 26 60-1 Approval Data
Manufacturers Pipe, Fittings, Valves, Fixtures, and Accessory Data
Minimum of 14 days prior to Ordering
CO
33 26 60-2 Qualifications Manufacturer Certifications Minimum of 14 days prior to Ordering
CO
Hellgate Campground Water Distribution System Expansion � Underground Piping
Price Schedule B - 1
SECTION B � SUPPLIES OR SERVICES AND PRICES
HELLGATE CAMPGROUND WATER DISTRIBUTION SYSTEM EXPANSION
UNDERGROUND PIPING
CANYON FERRY RESERVOIR
Canyon Ferry, Montana
B.1 PRICE SCHEDULE
(a) Offers will be considered for award on the following Price Schedule, but no offer will be considered for award on only a part of the Price Schedule.
(b) Offers are subject to the terms and conditions of this solicitation.
(c) Quantities in the Price Schedule are estimated quantities for comparison of offers only.
Except as provided in the contract clause at FAR 52.211-18, Variation in Estimated Quantity, no claim shall be made against the Government for overruns or underruns. The contract clause at FAR 52.211-18, Variation in Estimated Quantity does not apply to lump sum items.
(d) Definitions:
(1) CLIN � Contract Line Item Number
PRICE SCHEDULE
CLIN Section Supplies or Services Quantity and Unit
Unit Price
Amount
1 33 26 60 3� DR-11 HDPE 5,000 lin ft $ $
2 33 26 60 1 ½� DR-11 HDPE 1,000 lin ft $ $
3 33 26 60 3� DR-11 90˚ Butt End Bend
5 ea $ $
4 33 26 60 3" SDR-11 HDPE PE4710
Butt End Tee
9 ea $ $
5 33 26 60 3� x1 ½� SDR-11 Butt End Reducer
10 ea $ $
Price Schedule B - 2
PRICE SCHEDULE
CLIN Section Supplies or Services Quantity and Unit
Unit Price
Amount
6 33 26 60 3� Curb Stop and Box (or 3� Flanged Gate Valve with Box)
8 ea $ $
7 33 26 60 1 ½� FIP Ball Curb Stop and Box
9 ea $ $
8 33 26 60 Self Closing Sanitary Yard Hydrant
8 ea $ $
9 33 26 60 Draining Frost-Free Sanitary Yard Hydrant
2 ea $ $
10 33 26 60 Adapter 3� DR-11 HDPE To Curb Stop
16 ea $ $
11 33 26 60 Adapter 1 ½� DR-11 HDPE To Curb Stop
18 ea $ $
12 33 26 60 Adapter 1 ½� DR-11 HDPE To Yard Hydrant
10 ea $ $
13 33 26 60 Tracer Wire 6000 lin ft $ $
14 33 26 60 Warning Burial Tape 6000 lin ft $ $
TOTAL FOR PRICE SCHEDULE $_________________
END OF SUPPLIES OR SERVICES AND PRICES
Table of Contents
00 01 10 - 1
SECTION C - DESCRIPTION / SPECIFICATIONS
TABLE OF CONTENTS
DIVISION 33 - UTILITIES
33 26 60 Water Distribution
DIVISION 52 - DRAWINGS
52 00 00 Drawings
END OF CONTENTS
Table of Contents
00 01 10 - 2
This page intentionally left blank.
Water Distribution
33 26 60 - 1
SECTION 33 26 60
WATER DISTRIBUTION
PART 1 GENERAL
1.01 MEASUREMENT AND PAYMENT
A. Pipe and Tubing:
1. Measurement: All pipe and tube delivered to the site will be measured by the lineal foot of pipe delivered for each type and diameter. Price includes cost of
Pipe Accessories-Buried for buried pipe.
2. Payment: Unit Price offered in the Price Schedule.
B. Fittings:
1. Measurement: Each fitting delivered to the for each type and diameter. Fittings that require transitions or appurtenances will be measured as one fitting.
2. Payment: Unit Price offered in the Price Schedule
C. Buried Valves with Valve Boxes:
1. Measurement: Each buried valve with valve box, such as curb stop with curb box, delivered to the site for each type and diameter. Valves that require transitions or appurtenances will be measured as one buried valve.
2. Payment: Unit Price offered in the Price Schedule
D. Frost-Free Hydrants
1. Measurement: Each frost-free hydrant delivered to the site for each type.
Measurement includes transitions and appurtenances.
2. Payment: Unit Price offered in the Price Schedule
1.02 DEFINITIONS
Not Used
1.03 REFERENCE STANDARDS
A. ASTM International (ASTM)
1. ASTM B16.18-21 Cast Copper Alloy Solder Joint Pressure Fittings
2. ASTM B16.24-21 Cast Copper Alloy Pipe Flanges, Flanged Fittings, and Valves: Classes 150, 300, 600, 900, 1500, and
Water Distribution
33 26 60 - 2
3. ASTM B32-00 Standard Specification for Solder Metal
4. ASTM B88-22 Standard Specification for Seamless Copper Water
Tube
5. ASTM B813-16 Standard Specification for Liquid and Paste Fluxes for Joining by Soldering of Copper and Copper
Alloy Tube.
6. ASTM D1785-21 Standard Specification for Poly(Vinyl
Chloride)(PVC) Plastic Pipe, Schedules 40, 80, and
7. ASTM D2564-20 Standard Specification for Solvent Cements for
Poly(Vinyl Chloride)(PVC) Plastic Piping Systems
8. ASTM D2665-20 Standard Specification for Poly(Vinyl
Chloride)(PVC) Plastic Drain, Waste, and Vent
Pipe and Fittings
9. ASTM D2729-20 Standard Specification for Poly(Vinyl
Chloride)(PVC) Sewer Pipe and Fittings
10. ASTM D2855-20 Standard Practice for the Two-Step (Primer and
Solvent Cement) Method of joining Poly(Vinyl
Chloride)(CPVC) Pipe and Piping Components with Tapered Sockets.
11. ASTM F626-21 Standard Specification for Primers for Use in
Solvent Cement Joints of Poly(Vinyl
Chloride)(PVC) Plastic Pipe and Fittings.
B. American Water Works Association (AWWA)
1. AWWA C800 Underground Service Line Valves and Fittings
2. AWWA C901-22 Polyethene (PE) Pressure Pipe and Tubing, 3/4 in.
(19 mm) Through 3 in. (76 mm), for Water Service
3. AWWA C651-14 Disinfecting Water Mains
C. American National Standards Institute (ANSI) / National Science Foundation (NSF)
1. ANSI/NSF 61-17 Drinking Water System Components-Health Effects
2. ANSI/NSF 372-22 Drinking Water System Components-Lead Content
D. International Organization for Standardization (ISO)
1. ISO:9001-15 Quality Management Systems Requirements
E. Manufacturers Standardization Society (MSS)
1. MSS SP-123 Non-Ferrous Threaded and Solder-Joint Unions for Use With Copper Water Tube
Water Distribution
33 26 60 - 3
F. Montana Public Works Standard Specification (MPWSS)
1. MPWSS-22 Montana Public Works Standard Specifications-
Current Edition.
1.04 SUBMITTALS
A. Submit the following to design Engineer of Record for review prior to purchase or testing.
B. RSN 33 26 60-1, Approval Data:
1. Submit manufacturer�s data on pipe materials, fittings, valves, fixtures, and accessories.
C. RSN 33 26 60-2, Qualifications:
1. Certification of line pipe and fitting manufacturers.
2. Certification of NSF 61 compliance of line pipe materials.
1.05 DELIVERY, STORAGE, AND HANDLING-By Supplier
A. Prevent damage to pipe and fittings during loading, transporting, unloading, storing, and laying.
B. Support and store pipe above ground surface.
C. Government will inspect pipe once it is delivered.
D. Replace or repair, as approved by COR, any pipe that is damaged during shipment at
Supplier�s expense. Include linings and coatings.
1.06 QUALIFICATIONS
A. Pipe manufacturers shall be certified in accordance with ISO:9001 or similar nationally certified program approved by CO.
B. Line pipe and fitting manufacturers:
1. 10-years successful experience producing products as specified.
2. Provide references for at least 3 completed projects with similar pipe diameters and pressures.
1.07 REPAIR KITS
A. Furnish one (1) repair kit for each material type and size of pipe used.
B. Repair kit shall include:
1. 20 feet of pipe and 2 couplings.
Water Distribution
33 26 60 - 4
2. At highest loading and pressure rating for each material type and nominal size of pipe provided.
PART 2 PRODUCTS
2.01 PIPE � BURIED
A. Pipe: PE 4710 DR 11 (I.P.S.), AWWA C901, ANSI/NSF-61.
B. Curb Stop Valve and Box: per MPWSS and AWWA C800 with mechanical joints.
C. Gate Valve and Box: per MPWSS and AWWA C509.
D. Materials and chemicals that may come in contact with drinking water shall be certified by NSF 61.
2.02 FITTINGS - BURIED
A. Fittings: Brass Compression or Brass FIPT with Compression-MIPT transition couplings per MPWSS and AWWA C800.
1. PE 4710 DR 11 (I.P.S.), AWWA C901, ANSI/NSF-61, 14 welded.
B. Resist same loading conditions as adjacent pipe.
2.03 PIPE ACCESSORIES - BURIED
A. Warning Tape:
1. Polyethylene tape.
2. Thickness: 4 mils.
3. Magnetically detectable.
4. Width, minimum: 6-inches.
5. Color: Blue with silver lettering.
6. Legend repeated at least every 3-feet: �CAUTION: WATERLINE BURIED
BELOW.�
B. Tracer Wire for Non-Metallic Pipe:
1. Type: High strength solid copper clad steel.
2. Size: 12 AWG, minimum.
3. Insulation:
a. High density, high molecular weight, polyethylene (HDPE).
b. Jacket Color: Blue.
c. Rated for direct burial.
Water Distribution
33 26 60 - 5
C. Tracer Wire Terminal Post:
1. Designed and manufactured for specific application.
2. Temperature and ultraviolet light stable.
3. Color: Blue.
4. Terminals: Two, minimum, per post.
5. Provide terminal jumpers to interconnect lengths of trace wire as needed.
6. Space as recommended by manufacturer.
2.04 FROST FREE HYDRANTS
A. Accessible Hydrant: Frost free hydrant Model S4H Backflow Protected Automatic
Draining Freezeless, Self Closing Sanitary Yard Hydrant � Certified Lead Free, manufactured by Woodford Manufacturing Company, 2121 Waynoka Road, Colorado
Springs, Colorado 80915, or approved equal with the following essential characteristics:
1. NSF/ANSI 372 Approved for potable water;
2. Bury Depth 3.0 feet;
3. 1 inch National Pipe Thread (NPT) female inlet;
4. 3/4 inch male hose thread outlet;
5. Diverter Spout;
6. Stainless steel canister;
7. Two check valves;
8. Fully Contained;
9. Sanitary � Prevents cross contamination;
10. ADA Compliant Self Closing.
B. Host Site Hydrant: Frost free hydrant Model S3 Backflow Protected Automatic Draining
Freezeless Sanitary Yard Hydrant � Certified Lead Free Manufactured by Woodford
Manufacturing Company, 2121 Waynoka Road, Colorado Springs, Colorado 80915, or approved equal with the following essential characteristics:
1. NSF/ANSI 372 Approved for potable water;
2. Bury Depth 3.0 feet;
3. 1 inch NPT female inlet;
4. 3/4 inch male hose thread outlet;
5. Diverter Spout;
6. Stainless steel canister;
7. Two check valves;
8. Fully Contained;
Water Distribution
33 26 60 - 6
9. Sanitary � Prevents cross contamination.
PART 3 EXECUTION
Not Used
END OF SECTION
Drawings
52 00 00 - 1
SECTION 52 00 00
DRAWINGS
PART 1 GENERAL
1.01 DISCREPANCIES, ERRORS, OR OMISSIONS
A. Promptly inform the CO of discrepancies discovered on the drawings and specifications.
The CO will make a determination in writing.
B. In case of discrepancies, written specifications take precedence over drawings unless otherwise specified. Anything mentioned in the written specifications and not shown on the drawings, or shown on the drawings and not mentioned in the written specifications, shall be of like effect as if shown or mentioned in both. In case of differences between drawings and written specifications, the written specifications shall govern.
1.02 PROJECT CONDITIONS
A. Where there are differences as determined by the CO between Details and dimensions shown on drawings and Details and dimensions of existing features at jobsite, use Details and dimensions of existing features at jobsite.
1.03 SPECIFICATION DRAWINGS
A. Reference drawings referred to on specification drawings and not considered necessary for contract purposes are not included in specifications.
B. Parts of work for which dimensions are not shown have been drawn to scale as nearly to final dimensions as possible before purchase of machinery or equipment and development of final general and detailed designs.
1.04 STANDARD DRAWINGS
A. Standard drawings may show Details which are not a part of work under this contract.
Disregard Details shown on these drawings which are not applicable to work under this contract.
1.05 LIST OF DRAWINGS
A. Drawings listed in Table 52 00 00A - List of Drawings, are made a part of Section C -
Description/Specifications.
PART 2 PRODUCTS
Drawings
52 00 00 - 2
PART 3 EXECUTION
Drawings
52 00 00 - 3
Table 52 00 00A - List of Drawings
Sheet
No.
Drawing No. Title
1 296-600-60157 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Site Plan and Notes
2 296-600-60166 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Plan
3 296-600-60158 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Plan and Profile Sta. 0+00 To 13+02
4 296-600-60159 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Plan and Profile Sta. 13+02 To 26+04
5 296-600-60160 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Plan and Profile Sta. 26+04 To 39+06
6 296-600-60161 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Plan and Profile Sta. 39+06 To 49+00
7 296-600-60162 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Group Use Area Plan
8 296-600-60163 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Water Storage Building Plan
9 296-600-60165 Canyon Ferry Reservoir � Recreation Area � Hellgate
Campground � Water Distribution System Expansion �
Accessible Water Hydrant
END OF SECTION
Drawings
52 00 00 - 4
This page intentionally left blank.
| SOW Piping #33488 |
| 00 00 50 - Section B |
| 00 01 10 - Table of Contents |
| 33 26 60 - Water Distribution |
| 52 00 00 - Drawings |
File details come from the government source that posted it. Updated .