Collector_Specifications.pdf

PDF 823 KB Posted

Attached to
Fire Station 14 Solar Water Heater Replacement
Solicitation number
252743WG
Issued by
Sarasota County, Siesta Key CDP, Florida

About this file

This file contains technical specifications for solar water heating equipment required for the Fire Station 14 Solar Water Heater Replacement project in Sarasota County, Florida. The procurement involves removal and replacement of a hurricane-damaged Alternate Energy Technologies AE-32 solar thermal collector with either an identical unit or an approved equivalent model. The AE-32 collector measures 97.1875 inches in length and 47.1875 inches in width with a gross area of 31.85 square feet and transparent area of 29.9 square feet, featuring a 100% copper absorber plate, low-iron tempered glass glazing with 90% solar energy transmission, and polyisocyanurate insulation. The system includes an American Water Heaters residential electric direct solar water heater storage tank available in three capacities: 65, 80, or 119 gallons, each equipped with a 4500-watt heating element, glasslined steel tank with 2-inch non-CFC foam insulation, and aluminum anode rod protection. The quote submission deadline is December 22, 2025, with a maximum quote amount of $150,000.00 per project plus up to 10 percent contingency allowable with County approval.

Contractors must possess an active Certified Plumbing Contractor license and provide two references demonstrating solar water heater collector repair, replacement, and installation experience within the past seven years. Insurance requirements include Workers' Compensation with $500,000.00 employers liability limits, Commercial General Liability of $1,000,000.00 per occurrence and $2,000,000.00 aggregate, and Business Automobile Liability of $1,000,000.00 combined single limit. The contract is funded through disaster recovery grants from the Federal Emergency Management Agency (FEMA) and the Florida Division of Emergency Management, with no specific set-asides for disadvantaged enterprises and no local or American business preferences due to grant funding requirements. All work and materials will be warranted for one year or the standard manufacturer warranty, whichever is greater, with the contract term extending for the duration of the project. Award will be made to the responsive and responsible offeror submitting the lowest total bid price.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Alternate Energy Technologies LLC

COLLECTOR SPECIFICATIONS

Collector: AE-32 Length: 97.1875 in. Width: 47.1875 in.

Height: 3.137 in. Gross Area: 31.85 ft² Transparent Area: 29.9 ft²

Header Size: 1” Header Length: 50” Fluid Capacity: 1.05 gals.

Dry Weight: 113 lbs. Max. Oper. Temp. : 350°F Test Pressure: 160 psig

Rec. Flow Rate: 1.25 gpm Warranty: 10 Years Design Life: 30 Years

Collector Frame and Battens:

Type 6063-T6 extruded aluminum frame and battens with bronze powder-coat finish.

Absorber Coating:

Exclusively by Thermafin™ Manufacturing Selective Crystal Clear Coating

0.96 0.08

Backsheet:

Type 3105-h14, 0.019” stucco embossed aluminum sheet riveted to aluminum frame.

Glazing:

Low-Iron Tempered Glass “High-T” with a total solar energy transmission of 90%.

Corner Bracket:

Architectural aluminum angles inside with aircraft-grade pin grip rivets.

Gaskets & Grommets:

A UV durable EPDM, continuous U-channel gasket with molded corners. Extruded Silicone Grommet, 1-1/8” Bore.

Insulation:

Polyisocyanurate closed cell insulation. Foil-faced, glass fiber-reinforced, rigid board.

Fasteners:

Batten screws are 18-8 SS, 10-24 x 3/8”, hex head screws, black oxide coated.

Absorber Plate:

Manufactured by Thermafin™ Mfg., a 100% copper absorber plate, high-frequency forge welded to create a homogeneous connection between the fin and riser tube.

Mounting Hardware:

The “Quick Lock” mounting design reduces mounting time. All mounting hardware integrates with frame extrusion and is tested to allowable loads of 51 PSF.

No exceptions taken.

AJR - Stewart Engineering Consultants, Inc.

June 9, 2015

Copyright© by American® Water Heaters 2008. All rights reserved.

No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system, without permission in writing from American Water Heaters.

Copyright© by American® Water Heaters 2012. All rights reserved.

American direct solar water heaters are designed for installation as a part of a direct (open loop) solar water heating system or for use with external heat exchangers in closed loop systems. Available in 65, 80 and 119-gallon capacities these models provide storage for the hot water produced by the solar collectors and a supplementary electric heating element that maintains consistent water temperature during periods when solar energy is not available.

6-Year Limited Tank/6-Year Limited Parts Warranty*

Residential Electric Direct Solar Water Heaters

Multiple Connection Options for Installation Flexibility

• Side and top connections for open loop systems or closed loop systems using an external heat exchanger

Electrical

• 4500 watt heating element - long lasting low-watt density design spreads wattage over larger surface area to prolong element life and maximize efficiency

• Pre-wired for surface mount temperature sensor (sensor supplied separately)

Tank Construction

• Glasslined Steel Tank – glasslining protects against corrosion to maximize tank life

• 2-inch thick “Environmentally-Friendly” Non-CFC Foam insulation (R16 Value) reduces standby heat loss

Anode Rod

• Aluminum anode rod with stainless steel core protects tank against corrosion

CSA Certified and ASME Rated T&P Relief Valve

Durable Tamper-Resistant Brass Drain Valve

Compliance

• Units are UL and cUL listed to UL 174 Standard for Household Electric Storage

Tank Water Heaters and CAN/CSA-C22.2 No. 110-M90; Complies with California legislation AB 1953 and Vermont legislation Act 193 that limits the lead content in plumbing fixtures that come into contact with drinking water to a maximum of 0.25%.

Standard 6-Year Limited Tank and Parts Warranty

• Optional 10-year extension on tank warranty when used in a residential application

• 3-year tank and 1-year parts warranty when installed in a commercial application

• For complete warranty information consult written warranty supplied with the product, online at www.americanwaterheater.com, or call American Water Heaters at 800.456.9805

NCESS00708 R January 2012

Eligible for a 30% federal tax credit when installed as part of a complete solar water heating system.

For more information visit www.americanwaterheater.com

No exceptions taken.

Order Entry and Sales 500 Princeton Road (FEDEX, UPS) Johnson City, TN 37601-2030 P.O. Box 4808 (Mailing) Johnson City, TN 37602-4808

(800) 937-1037

FAX (800) 581-7224

No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system, without permission in writing from American Water Heaters.

Distributed By:

Warranty and Service

500 Princeton Road (FEDEX, UPS) Johnson City, TN 37601-2030

P.O. Box 1597 (Mailing) Johnson City, TN 37605-1597

(800) 456-9805

FAX (800) 999-5210

Residential Electric Direct Solar Water Heaters

NCESS00708 R January 2012

*Limited warranty on tank and parts. See written warranty supplied with the water heater for complete details.

** All solar loop and domestic water connections are 3/4” NPT. Top solar loop and domestic water connections are male NPT with factory-installed dielectric pipe nipples. Side solar loop connections are female NPT and are plugged from the factory.

Specification

Furnish and install, where indicated, in accordance with manufacturer’s instructions and in compliance with all rules and regulations of authorities having jurisdiction.

Storage tank(s) shall be American® Model _______________________ as manufactured by American Water Heaters or equivalent. Storage tank(s) shall have a nominal storage capacity of __________ gallons, recovery of ___________ GPH at _______° F temperature rise and supplied with auxiliary heating elements rated at 4.5 KW, ________ volt. Storage tank(s) are hydrostatic tested at 300 PSI having a working pressure of 150 PSI and shall have a Fused Ceramic Shield internally lined tank applied under pressure and fired at 1600° F allowing for maximum protection. Storage tank(s) shall be equipped with an approved pressure and temperature relief valve. The outer jacketing shall have a baked enamel finish. The tank shall be foam insulated with an EPA-approved, non-CFC material 2” in thickness. Storage tank(s) shall have a 6-year limited warranty against corrosion as outlined in the written warranty.

HOT SUPPLY FROM

SOLAR COLLECTORS

COLD RETURN

TO SOLAR

COLLECTORS

DRAIN

VALVE

C

D

COLD RETURN

TO SOLAR

COLLECTORS

HOT SUPPLY FROM

SOLAR COLLECTORS

UPPER ACCESS

PANEL 4500 WATT

HEATING ELEMENT

FLOW

FLOW

LOWER ACCESS PANEL

TEMPERATURE SENSOR

MOUNTING STUD

ANODE

T&P

LOCATION

MODEL

NUMBER

GALLON

CAPACITY

NUMBER OF

HEATING

ELEMENTS

ELEMENT

WATTAGE

(240 VOLT)

RECOVERY

GALLONS

PER HOUR

(90°F RISE)

INSULATION

R

VALUE

HEIGHT

WATER

CONNECTION

JACKET

DIAMETER

A

HEIGHT

TOP OF

TANK

B

OPTIONAL

SOLAR

IN/DOWN

C

OPTIONAL

SOLAR

OUT/UP

D

APPROX.

SHIPPING

WEIGHT

SE62-65H-045S 65 1 4500 21 16 60-1/4 22 59-1/4 20-1/2 7-1/2 152

SE62-80H-045S 80 1 4500 21 16 60-1/4 24 59-1/4 20-1/2 7-1/2 191

SE62-119R-045S 119 1 4500 21 16 62 28 61-1/2 20-1/2 7-1/2 278

ALTERNATE ENERGY TECHNOLOGIES, LLC

• 1345 Energy Cove Ct. • Green Cove Springs, FL 32043 • 800-874-2190 • www.aetsolar.com

No exceptions taken.

ALTERNATE ENERGY TECHNOLOGIES, LLC

• 1345 Energy Cove Ct. • Green Cove Springs, FL 32043 • 800-874-2190 • www.aetsolar.com

File details come from the government source that posted it. Updated .