Closed Loop Fluid Cooler Schedule - Revised 11-21-22.pdf

PDF 52 KB Posted

Attached to
RFB FOR FLUID COOLER AND DELIVERY - Addendum
Solicitation number
RFB-025-2300000287-3
Issued by
Harrison County, Elkton City, Kentucky

About this file

This document is a Closed Loop Fluid Cooler Schedule for a state or local government contract opportunity. It provides detailed specifications and requirements for a closed loop fluid cooling system, including model numbers, fan data, performance data, electrical data, and various remarks and accessories. The schedule calls for the provision of 304 stainless steel construction for all wetted parts, excluding the coil, a variable frequency drive for each fan, an internal galvanized steel walkway, an ASME coil, a 304 stainless steel strainer and anti-vortexing hood at the unit outlet connection, a basin heater, and a BACnet interface card for integration into the building management system, among other requirements.

The document also specifies that the contractor must provide a minimum of one-year part and limited labor warranty, as well as a minimum of five-year warranty on the cold water basin, fans, fan motors, fan shafts, bearings, sheaves, and associated supports. The contractor must also provide a manufacturer's start-up and certified report for the engineer's review and approval.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BAC FXV 0806B-241D-L 10,900 7.5 8.5 21.0 38,980 1 15.0 74 1,575 95.0 78.0 100.0 90.0 325.0 5.4 480 / 3 31.0 57.0 ALL

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

MODEL

NOT USED.

UNIT SHALL BE PROVIDED WITH POSITIVE CLOSER DAMPER HOOD AND DAMPER ACTUATOR.

PROVIDE UNIT WITH AT MINIMUM ONE (1) YEAR PART AND LIMITED LABOR WARRANTY. PROVIDE UNIT WITH AT MINIMUM FIVE (5) YEAR WARRANTY ON COLD WATER BASIN, FANS, FAN MOTORS, FANS SHAFTS, BEARINGS, SHEAVES, AND ASSOCIATED SUPPRORTS.

PROVIDE UNIT WITH PVC FILL AND DRIFT ELIMINATORS. DRIFT ELIMINATORS SHALL HAVE AT MINIMUM THREE (3) CHANGES IN AIR DIRECTION.

PROVIDE UNIT IN 304 STAINLESS STEEL CONSTRUCTION FOR ALL WETTED PARTS, EXCLUDING COIL.

PROVIDE UNIT WITH VARIABLE FREQUENCY DRIVE FOR EACH FAN. VFD'S SHALL BE INSTALLED IN CONTROL PANEL.

PROVIDE UNIT WITH INTERNAL, GALVANIZED STEEL WALKWAY, WITH ANTI-SLIP DESIGN.

PROVIDE UNIT WITH ASME COIL.

NOISE PERFORMANCE IS BASED ON THE WEIGHTED AVERAGE SOUND DATA AT FIFTY (50) FEET FROM THE AIR INLET OF THE UNIT.

WIDTH OF UNIT MAY NOT EXCEED UNIT DIMENSIONS PROVIDED ABOVE.

HEIGHT OF UNIT MAY NOT BE LESS THAN UNIT DIMENSIONS PROVIDED ABOVE.

FC-1A/B

PROVIDE UNIT WITH 304 STAINLESS STEEL STRAINER AND ANTI-VORTEXING HOOD AT UNIT OUTLET CONNECTION.

PROVIDE UNIT WITH A BASIN HEATER. HEATER SHALL BE INTERLOCKED WITH PUMP CIRCUIT TO PREVENT HEATER OPERATION WHEN PUMP CIRCUIT IS ENERGIZED.

PROVIDE UNIT WITH MANUFACTURER'S START-UP AND CERTIFIED REPORT FOR ENGINEER'S REVIEW AND APPROVAL. INSTALLING CONTRACTOR START-UP IS NOT ACCEPTABLE.

PROVIDE UNIT WITH EXTENDED LUBRICATION LINES FOR EASY MAINTENANCE ACCESS.

PROVIDE UNIT WITH HEAVY DUTY, FRP, AXIAL FAN SUITABLE FOR LOW NOISE LEVELS.

PROVIDE UNIT WITH A MINIMUM OF TWO INDEPENDENT FAN ASSEMBLIES AND FAN MOTORS FOR REDUNDANCY.

PROVIDE HINGED ACCESS PANELS FOR ALL SERVICE POINTS.

PROVIDE UNIT WITH ELECTRIC WATER LEVEL CONTROL BY WAY OF SLOW-CLOSING SOLENOID VALVE. THE WATER LEVEL CONTROL SHALL PROVIDE HIGH AND LOW WATER LEVEL ALARMS.

PROVIDE UNIT WITH NEMA 3R CONTROL PANEL WITH NON-FUSED ELECTRICAL DISCONNECT WITH SINGLE-POINT ELECTRICAL CONNECTION TO THE PANEL CONTAINING VFD, EQUIPMENT, AND HEAT TRACE CONTROLS. THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL CONNECTIONS FROM PANEL TO FIELD MOUNTED EQUIPMENT AND

HEAT TRACE CONTROLS AS SPECIFIED. PANEL SHALL BE LOCKABLE. CONTROL PANEL WITH ALL COMPONENTS SHALL BE LISTED AND CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) IN ACCORDANCE WITH NFPA 70 - NATIONAL ELECTRICAL CODE 2014 LATEST EDITION. PROVIDE BACNET INTERFACE CARD FOR

FULL INTEGRATION INTO THE BUILDING MANAGEMENT SYSTEM (BMS).

PROVIDE UNIT WITH PREMIUM-EFFICIENT TEFC FAN MOTORS SUITABLE FOR VARIABLE FREQUENCY DRIVE OPERATION.

PROVIDE UNIT WITH VIBRATION CUTOFF SWITCHES.

PROVIDE UNIT WITH WELDED 304 STAINLESS STEEL BASIN.

REMARKS AND ACCESSORIES:

MOCP

(AMPS)

FC-1A/B

CLOSED LOOP FLUID COOLER SCHEDULE

MARK MFG. SIZE

EVAPORATOR FAN DATA PERFORMANCE DATA ELECTRICAL DATA

REMARKS AND

ACCESSORIES

MARK

APPROX. UNIT

OPERATING

WEIGHT

(LBS.)

VOLTAGE/

PHASE

UNIT

AIRFLOW

(CFM)

NUMBER OF

FANS

TOTAL FAN

POWER

(HP)

UNIT DIMENSIONS

LENGTH

(FT.)

WIDTH

(FT.)

HEIGHT

(FT.)

MCA

(AMPS)

dBA @ 50'

HEAT OF

REJ.

(MBH)

E.A.T.

(DEG Fdb)

E.A.T.

(DEG Fwb)

E.W.T.

(DEG F)

L.W.T.

(DEG F)

FLOW RATE

(GPM)

MAX PRESS.

DROP

(FT H2O)

File details come from the government source that posted it. Updated .