CCS Sewer RFP Packet Final.pdf
PDF 4 MB Posted
- Solicitation number
- 171-171-26-202
- Issued by
- Clay County, Biscoe Town, North Carolina
About this file
This Request for Proposals (RFP) package pertains to the construction of an off-site sewer force main extension project for Columbus County Schools in North Carolina, with involvement from the Town of Bolton and applicable regulatory agencies including the NC Department of Transportation and NC Department of Environmental Quality. Columbus County Schools solicits sealed proposals from qualified, licensed utility contractors to furnish all labor, materials, equipment, supervision, transportation, testing, restoration, and incidentals necessary to construct approximately 1,960 linear feet of 3-inch off-site sewer force main extending from East View School to the Town of Bolton's sewer collection station. The project scope includes installation of force main, excavation, trenching, pipe installation, connections, fittings, boring where required, backfill, restoration, erosion control, testing, and inspections. A mandatory site visit must be scheduled by contacting Timmy Ward, Maintenance Director, at 910-770-2303 or tward@columbus.k12.nc.us. Sealed proposals must be submitted to Timmy Ward at Columbus County Schools, 89 School Road, Hallsboro, NC 28442, in person or by email by September 3, 2026 at 1:00 PM. The last day for submitting questions is August 13, 2026, with responses due August 20, 2026. Bid opening is scheduled for September 3, 2026, with notice of award on September 9, 2026. The substantial completion date is December 31, 2026.
Qualified bidders must be licensed North Carolina contractors with utility experience, current insurance, OSHA compliance, and references for similar work. Proposals must include company information, license, insurance, price proposal, schedule, references, subcontractors list, and acknowledgment of addenda. The project involves multiple regulatory permits and approvals, including NCDOT utility encroachment permit E063-024-26-00040 for installation of 60 linear feet of 3-inch sewer force main under NC Highway 214 using the jack and bore method, and NC Department of Environmental Quality Permit No. WQ0047335 authorizing construction of approximately 1,823 linear feet of 3-inch force main. The project specifically specifies 3-inch SDR-21, 200 PSI PVC force main materials. The force main will serve the East View Pre K-8 School and tie into the Town of Bolton's existing sewer collection system, with wastewater treatment provided by the City of Whiteville's wastewater treatment facility. Engineering certification by a North Carolina-licensed Professional Engineer is required upon project completion prior to operation, along with as-built record drawings and supporting design calculations.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
East View School Off-Site Sewer Force Main Installation
REQUEST FOR PROPOSALS (RFP)
Off-Site Sewer Force Main Installation
Eastview School
Owner:
Columbus County Schools
Facility Services
89 School Road
Hallsboro, NC 28442
Attention: Timmy Ward, Maintenance Director
Project Name
East View School Off-Site Sewer Line Installation
Invitation
Columbus County Schools is soliciting sealed proposals from qualified, licensed utility contractors to furnish all labor, materials, equipment, supervision, transportation, testing, restoration, and incidentals necessary to construct approximately 1,960 linear feet of 3-inch off-site sewer force main extending from East View School to the Town of Bolton's sewer collection station.
Project Description
The project consists generally of the installation of approximately 1,960 linear feet of 3-inch sewer force main beginning at East View School and terminating at the Town of Bolton sewer collection station. The complete Scope of Work, plans, specifications, and special provisions are included in the attached documents and are incorporated into this RFP.
Scope of Work
Includes installation of force main, excavation, trenching, pipe installation, connections, fittings, boring where required, backfill, restoration, erosion control, testing, inspections, and all work shown in the attachments.
Contractor Qualifications
Licensed NC contractor with utility experience, insurance, OSHA compliance, and references for similar work.
Proposal Requirements
Include company information, license, insurance, price proposal, schedule, references, subcontractors, and acknowledgment of addenda.
Mandatory Site Visit Please contact Timmy Ward at 910-770-2303 or tward@columbus.k12.nc.us to schedule a site visit.
Submission
Deliver sealed proposals to Timmy Ward, Maintenance Director, Columbus County Schools, 89 School Road, Hallsboro, NC 28442. In person or by email tward@columbus.k12.nc.us by
September 3, 2026 at 1PM.
Attachments
Scope of Work, Plans, Specifications, Bid Form, Insurance Requirements, General
Conditions, Special Conditions, and Addenda.
Issue Date: July 20, 2026
Last Day for Questions: August 13, 2026
Last Day for Responses: August 20, 2026
Bid Opening Date: September 3, 2026
Notice of Award: September 9, 2026
Notice to Proceed: TBD
Substantial Completion Date: December 31, 2026 mailto:tward@columbus.k12.nc.us http://tward@columbus.k12.nc.us
06/11/2026
E063-024-26-00040
06/11/2026
For Division Engineer Wallace Jernigan Jr.
SADE
1 2 2 C I N E M A D R I V E , W I L M I N G T O N , N C 2 8 4 0 3 P H : ( 9 1 0 ) 7 9 1 - 6 7 0 7 F A X : ( 9 1 0 ) 7 9 1 - 6 7 6 0
June 5, 2026
NC Department of Transportation Division 6, District 3 1194 Prison Camp Rd.
Whiteville, NC 28472
Re: Columbus County Pre K-8 Sewer Encroachment Agreement Application Applicant: Columbus County Board of Education 2586 James B. White Hwy N., Whiteville, NC 28477
To Whom It May Concern, The applicant, Columbus County Board of Education, is requesting a utility encroachment agreement for installation of 60 LF of a 3” SDR-21 sanitary sewer force main inside 8” steel casing to be installed by Jack & Bore method under NC 214 Green Swamp Rd. S. Enclosed with this cover letter are the plans and encroachment agreement application.
The expected schedule for the proposed utility construction listed above is Fall 2026 through Early Winter 2026.
Thank you for your attention to this matter. Please feel free to contact our office if you have any questions or require additional information.
Sincerely, Rob Balland, PE
June 5, 2026
NC Department of Transportation Division 6, District 3 1194 Prison Camp Rd.
Whiteville, NC 28472
SUBJECT: Erosion and Sediment Control – a 3” Sewer Force Main – NC 214 (Green Swamp Rd. S.)
To Whom it may concern:
This letter is to acknowledge that the above-mentioned activity will disturb less than one acre. Therefore, an approved erosion and sediment control plan from NCDEQ is not required.
However, appropriate measures will be implemented during construction to prevent erosion and offsite sedimentation.
If there are further questions, please contact Jesse E. Beck, II (910-642-5168).
Very truly yours, Paramounte Engineering, Inc.
Andrew Richards, P.E.
AR
LOD LOD LOD LOD
LOD
LO
D
LO
D
LO
D
LO
DLOD
LOD
LOD
LOD
LOD
LB
GRASS
SOILGRAVEL
LBLB
LB
SO
IL
D R
IV
E
LBLB
" C
ED
AR
H
ED
G
ER
O W
ASPHALT
" O
AK
WIRE
FENCE
" S
YC
AM
O R
E
G R
AV
EL
D R
IV
E
SO
IL
D R
IV
EC
LF
SO
IL
D R
IV
E
" S
YC
AM
O R
E
" C
R
EP
E M
YR
TL
E C
LU
ST
ER
" H
O
LL
Y C
LU
ST
ER
SO
IL
D R
IV
E
SIG
N
SIG
N
SIG
N
S
G R
AV
EL
D R
IV
E
" S
YC
AM
O R
E
WM
C O
N C
R
ET
E D
R
IV
E
GRASS
" C
R
EP
E M
YR
TL
E C
LU
ST
ER
SOIL DRIVE
" O
AK
C
LU
ST
ER
" M
AP
LE
G R
AV
EL
D R
IV
E
SO
IL
D R
IV
E
ASPHALT
GRAVEL DRIVE
N/F
SPENCER L. NEWCOMER
Deed Book 1214 - Page 121
N/F
STEVEN FIORAVANTI
Deed Book 1141 - Page 818
N/F CECILE ETHERIDGE et al
Deed Book 1278 - Page 494
N/F
STEVEN FIORAVANTI
et al Deed Book 1266 -
N/F
NANCY H. BROWN
Deed Book 556 - Page 955
Plat Book 68 - Page 96
N/F
DARIUS K.
SIMMONS
Deed Book 668 -
N/F RONALD J. STUKES et ux
Deed Book 1038 - Page 390
N/F
CHARLES BRYANT SMITH
Deed Book 1098 - Page 399
N/F
AN PHAM
Deed Book 794 - Page 444
N/F
WILLIAM L. FORD
Deed Book 1296 - Page 88
N/F
NANCY H. BROWN
Deed Book 556 - Page 955
Plat Book 103 - Page 25
N/F
FRANK B. IRVING
Deed Book 1371 - Page 508
N/F
COLUMBUS COUNTY
BOARD OF EDUCATION
Deed Book 1359 - Page 974
Plat Book 106 - Page 79
N/F
ALLEN
WALTER
BROWN
Deed Book 1061
- Page 817
Plat Book 95
- Page 05
BENCHMARK "C"
(EXISTING NAIL)
TOP OF NAIL
ELEVATION = 60.94'
GW
FM
FM
FM
FM
FM
FM
FM
FM
N/F
ALLEN WALTER
BROWN
Deed Book 943
- Page 944
Property Line
Per Plat Book 122 - Page 31
FIELD
FIELD
GRASS
FIELD
HEDGEROW
D
ITC
H
DITCH
D
ITC
H
D
ITC
H
DITCH
D
IT
C H
D
ITC
H
DITCH
AS
PH
AL
T
DITCH
61'
12" RCP
NORTH INV. = 62.06'
SOUTH INV. = 62.05'12" RCP
NORTH INV. = 62.11'
SOUTH INV. = 61.86'
12" RCP
WEST INV. = 59.66'
EAST INV. = 59.65'
12" CPP
NORTH INV. = 58.50'
SOUTH INV. = 58.47'12" RCP
WEST INV. = 57.40'
EAST INV. = 57.34'
15" CMP
NORTH INV. = 58.00'
SOUTH INV. = 57.75'
15" RCP
NORTH INV. = 57.89'
DROP INLET
TOP = 59.79'
BOTTOM = 58.00'
15" RCP
SOUTH INV. = 57.95'
15" RCP
NORTH INV. = 58.23'
SOUTH INV. = 57.57'
24" RCP
WEST INV. = 56.58'
EAST INV. = 56.12'
24" RCP
NORTH INV. = 56.62'
SOUTH INV. = 55.41'
12" RCP
WEST INV. = 58.24'
EAST INV. = 58.11'
N/F
ALLEN WALTER
BROWN
Deed Book 943
- Page 944
N/F
ALLEN WALTER
BROWN
Deed Book 943
- Page 944
N/F
TOWN OF BOLTON
Deed Book 207 - Page 192 Plat Book 5 - Page 55
O
HE
O
HE
O
HE
O H
E O
H E
O H
E O
H E
O H
E O
H E
O H
E O
H E
OHE
OHE OHE OHE OHE OHE OHE OHE OHE
OHE
OHE
OHE
OHE
OHE
OHE
OHE
O H
E
OHE
O H
E O
H E
O H
E O
H E
O H
E O
H E
GW
GW
GW
GW
TELEPHONE
PED
TELEPHONE PED
TELEPHONE
PED
TELEPHONE PED
"ATMC" FOC BOX
"SOUTHERNBELL"
FOC NR
' P
U
BL
IC
R
/W P
ER
P
LA
T
BO
O
K
PA
G E
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
FM
FM
FIRST STREET
37' PUBLIC R/W
PER PB 59 - PG 11
C
ED
AR
STR
EET
PU
BLIC
R
/W W
ID
TH
VAR
IES
PER
PB 59 - PG
EX. 8" PVC
W
ATER
M
AIN
W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W W
W
W W
W W
W W
W W
W W
W
W W W W W W
W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W
W W
W W
W W
W
WW
EX
IS
TI
N
G H
YD
R
AN
T
WM
W
20' ALLEY
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
U T
M
AI
LB
O
X
C.O.
C.O.
C.O.
WM
WM
WM
MAILBOX
EX. AIR
RELEASE
VALVE
MAILBOXTELEPHONE
PED
EX. 4" SDR-21 PVC
FORCE MAIN
EX. 8" DR-18 PVC
FORCE MAIN
EX. 4" SDR-21 PVC
FORCE MAIN
EX. 8" DR-18 PVC
FORCE MAIN
EX. 4" SDR-21 PVC
FORCE MAIN
EX. 4" SDR-21 PVC
FORCE MAIN
EX. 8" DR-18 PVC
FORCE MAIN
59 60
58 5958 58 59
60 59
60 61
61 62 61 62
61 62
63 63
62 61
X
X X
X X
FM
FM
FM
FM
FM
FM
FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM FM
10+00 11+00
12+00 13+00
14+00 15+00 16+00 17+00 18+00 19+00 20+00 21+00 22+00 23+00 24+00 25+00
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LO
D
LOD
LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD
LOD
LODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLOD
LOD
LOD LOD
LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD
LOD
LODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLOD
LOD LOD LOD
10+00 11+00 12+00 13+00 14+00 15+00 16+00 17+00 18+00 19+00 20+00 21+00 22+00 23+00 24+00 25+00
.7
.4
.2
.3
.1
.4
.4 62
.0
.3
.9
.0
.1
.9
.1
.2
.0
.2
.0
.7
.5
.0
.9
.0
.0
.0
.0
.2
.6
.0
.0
.1
N
C H
W Y.
(S
AM
P O
TT
S
H W
Y.
EX
. E
D G
E O
F
PA
VE
M
EN
T
EX
. E
D G
E O
F
PA
VE
M
EN
T
R
IG
H T
O F
W
AY
R
IG
H T
O F
W
AY
1:1 TH
EO
R
ETIC
AL
SLO
PE
1:
TH
EO
R
ET
IC
AL
SL
O
PE
2.0'2.1'2.6'
TH
E
LI
N
E
SH
O W
N A
BO
VE
IS
E
XA
C
TL
Y
O N
E
IN
C H
L O
N G
A T
TH
IS
S H
EE
TS
O R
IG
IN
AL
P
AG
E
SI
ZE
LS
3P
P R
O
JE
C T:
ORIG
SUBMISSION:
SHEET NAME:
SHEET:
A
B
C
D
E
1 2 3 4 5 6
DATE DESCRIPTION∆
COPYRIGHT 2024 ALL RIGHTS RESERVED. PRINTED OR
ELECTRONIC DRAWINGS AND DOCUMENTATION MAY
NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN
PERMISSION FROM LS3P ASSOCIATES LTD.
/4
/2
3:
:2
PM
-2
Columbus County Schools
G re en S w am p R d.
H w y.
a nd
S am
P ot ts H w y
Bo lto n, N or th
C ar ol in a
C ol um bu s C ou nt y Sc ho ol s
PK
-8
PERMIT APPLICATION
WWW.LS3P.COM
101 NORTH THIRD STREET, SUITE 500
WILMINGTON, NORTH CAROLINA 28401
TEL. 910.790.9901 FAX. 910.790.3111
122 Cinema Drive Wilmington, North Carolina 28403
(910) 791-6707 (O) (910) 791-6760 (F) NC License #: C-2846 - SC License #: 003542
NORTH CAROLINA
PR
OFESSION
ENGI N EER
SEAL
AL
0 3 1 5 9 1
ROBERT P . BA LLA ND
06/08/2026
IS
SU
E D
F O
R
P R
E L
IM
IN
A R
Y P
E R
M
IT
T
IN
G B
ID
C
O N
ST
R
U C
T
IO
N
A 2025.09.24 FOR PERMIT / BIDDING
B 2025.10.17 ADDENDUM 01
C 2025.10.28 ADDENDUM 03
0 2026.01.15 PERMIT APPLICATION
1 2026.02.09 ASI#4-BYPASS DITCH REV
AND FORCE MAIN TIE-IN
2026.03.19 RFI#18 STORM MH2
CULVERT #2
2026.04.28 RFI#32 SEWER TIE-IN3
ELEVATIONS
2026.04.28 RFI#34 SEWER TIE-IN3
2026.06.03 RFI#46 STORM CONFLICT4
OFF-SITE
FORCE MAIN
PLAN & PROFILE
C-410
01/27/2026
OFF-SITE FORCE MAIN [STA. 10+00 - 25+00] - PROFILE VIEW
HORIZONTAL SCALE: 1" = 50'
VERTICAL SCALE: 1" = 5'
OFF-SITE FORCE MAIN [STA. 10+00 - 25+00] - PLAN VIEW
SCALE: 1" = 50'
0 25 50 100 200
SCALE: 1"=50'
GRAPHIC SCALE
NAD 83 (2011)
PROPOSED 3" SDR-21,
200 PSI, PVC FORCE MAIN
PROPOSED 3" SDR-21,
200 PSI, PVC FORCE MAIN
(1) 3"x3"x3" MJ TEE
(1) 3" MJ GATE VALVE
(1) 3" MJ PLUG
FOR PROPOSED
SCHOOL CONNECTION
(1) 3" MJ GATE VALVE
(1) 3" MJ PLUG
PROPOSED 60LF - 8"
STEEL BORE AND JACK
CASING PIPE, 0.188"
WALL THICKNESS
(2) 3" MJ 45°
BENDS
55' R/W
PROPOSED 10'
UTILITY EASEMENT
12.8' EOP TO FM
12.5' EOP TO FM
5.
1'
E O
P
TO
F M
7.
4'
E O
P
TO
F M
3.
4'
E O
P
TO
F M
7.
3'
E O
P
TO
F M
23'
EP-EP
25'
EP-EP
.5
EP
-E P
EP
-E
P
EP
-E
P
EP
-E
P
(1) 3" MJ PLUG
STA. 11+00
(1) 3" MJ GATE VALVE
STA. 11+03
(1) 3"x3"x3" MJ TEE
(1) 3" MJ GATE VALVE
(1) 3" MJ PLUG
STA. 11+07
PROPOSED SCHOOL
SITE CONNECTION
(1) 3" MJ 45°
HORIZONTAL BEND
STA. 13+20
(1) 3" MJ 45°
HORIZONTAL BEND
STA. 13+24
3" SDR-21, 200 PSI,
PVC SANITARY
SEWER FORCE MAIN
3' M
IN
3' M
IN
4'Ø AIR RELEASE
MANHOLE
STA. 20+32
SEE DETAIL
PROPOSED
10'x10'x5'
RECEIVING PIT
PROPOSED 50'x5'x4'
BORE PIT
5'
50'10'
6'
60LF - 8" STEEL
BORE AND JACK
CASING PIPE, MIN.
THICKNESS 0.188"
7' 8.5'
TOPOGRAPHIC/LOCATION NOTES:
* TOPOGRAPHIC AND LOCATION INFORMATION HEREON REPRESENTS
EXISTING CONDITIONS OF PROJECT SURVEY AREA UPON CLIENT REQUEST.
EXISTING MODEL BASED ON PUBLIC AND PRIVATE POINT CLOUDS WITH
INCLUDED SPOT ELEVATIONS TO ACCOMODATE FOR OBSERVED
IRREGULARITIES. PROJECT SURVEY AREA HAS BEEN FIELD SURVEYED.
* ALL ELEVATIONS ARE MEAN SEA LEVEL (NAVD 88) BASED UPON NATIONAL
GEODETIC SURVEY DESIGNATION "BOL" AS NOTED HEREON. [SEE
BENCHMARKS]
* SUBJECT SURVEY IS IN ZONE X (AN AREA DETERMINED TO BE OUTSIDE
THE 0.2% ANNUAL CHANCE FLOODPLAIN) PER FEMA NATIONAL FLOOD
INSURANCE PROGRAM.
* ALL PIPE SIZES HEREON ARE INSIDE DIAMETER.
* WATER LINES AND SANITARY SEWER FORCE MAIN INSERTED AND/OR
TRANSLATED PER COLUMBUS COUNTY GIS SHAPEFILES. MANHOLES,
HYDRANTS, GATE VALVES AND METERS BY FIELD SURVEY THIS DATE.
FORCE MAIN BEING 4" PVC AND 8" PVC PER PROJECT NO: 2-99-8315-4700 BY
McDAVID ASSOCIATES, INC. DATED AUGUST 31, 2006. SEE TOWN OF
BOLTON, N.C. UTILITIES DEPARTMENT FOR VERIFICATION.
* FIBEROPTIC CABLE IS LOCATED WITHIN THE RIGHT-OF-WAY OF N.C. HWY.
214 AND N.C. HWY. 211.
* PUBLIC/PRIVATE GEOTECHNICAL/SUE MARKING/FLAGGING NOT PROVIDED
FOR PROJECT SURVEY AREA.
* THE UNDERGROUND UTILITIES SHOWN HAVE BEEN LOCATED FROM FIELD
SURVEY INFORMATION AND EXISTING DRAWINGS. THE SURVEYOR MAKES
NO GUARANTEE THAT THE UNDERGROUND UTILITIES SHOWN COMPRISE
ALL SUCH UTILITIES IN THE AREA, EITHER IN SERVICE OR ABANDONED. THE
SURVEYOR FURTHER DOES NOT WARRANT THAT THE UNDERGROUND
UTILITIES SHOWN ARE IN THE EXACT LOCATION INDICATED, ALTHOUGH HE
DOES CERTIFY THAT THEY ARE LOCATED AS ACCURATELY AS POSSIBLE
FROM INFORMATION AVAILABLE. THE SURVEYOR HAS NOT PHYSICALLY
LOCATED THE UNDERGROUND UTILITIES. IN ADDITION, NO RESPONSIBILITY
OF ANY NATURE IS ASSUMED BY THE SURVEYOR FOR ANY CONDITIONS
WHICH MAY PRESENTLY EXIST BUT ARE UNKNOWN, SUCH AS TOXIC OR
HAZARDOUS WASTE MATERIALS, CEMETERIES, WETLANDS, ETC.
BOUNDARY NOTES:
* ALL COORDINATES AND BEARINGS HEREON ARE N.C. GRID, NAD83(2011)
REFERENCE, ESTABLISHED USING GNSS (GLOBAL NAVIGATION SATELLITE
SYSTEM) WITH NORTH CAROLINA VRS CORRECTIONS.
* ALL DISTANCES HEREON ARE HORIZONTAL GROUND UNLESS OTHERWISE
NOTED..
* THIS PROPERTY IS SUBJECT TO ANY AND ALL EASEMENTS,
RIGHTS-OF-WAY OR OTHER MATTERS OF RECORD.
* LAND OWNERS, AS SHOWN HEREON, TAKEN FROM COLUMBUS COUNTY
TAX RECORDS. CURRENT OWNERSHIP OR ADDITIONAL LAND OWNERS
SUBJECT TO TITLE RECORDS SEARCH.
ELECTRONIC NOTE:
I HEREBY CERTIFY THIS DOCUMENT ORIGINALLY ISSUED AND
SEALED BY JASON S. WALKER, L-5147, ON JULY 01, 2025.
THIS MEDIA SHALL NOT BE CONSIDERED A CERTIFIED DOCUMENT.
SE
E
SH
EE
T C
-4
5.
5'5.
8'
TYPICAL FORCE MAIN PRESSURE
SEWER TRENCH DETAIL #2
STA. 13+20 TO 18+00
NOT TO SCALE
TYPICAL FORCE MAIN PRESSURE
SEWER TRENCH DETAIL #3
STA. 18+00 TO 25+55
NOT TO SCALE
EX. 4" PVC
PRESSURE
SEWER
EX. 8" PVC
FORCE MAIN
6"
3' M
IN
3.
5'
M
IN
7" MIN.
18" TYPICAL
6"
EX. 4" PVC
PRESSURE
SEWER
18" TYPICAL
3' M
IN
3' M
IN
7" MIN.
18" MIN.
18" MIN.
EX. 4" PVC
PRESSURE
SEWER
EX. 8" PVC
FORCE MAIN
6"
3' M
IN
3.
5'
M
IN
7" MIN.
18" +/-3'
3' M
IN
7" MIN.
18" MIN.
PROPOSED
3" PVC
FORCE MAIN
PROPOSED
3" PVC
FORCE MAIN
TYPICAL FORCE MAIN PRESSURE
SEWER TRENCH DETAIL #1
STA. 10+00 TO 13+20
NOT TO SCALE
EX. 4" PVC
PRESSURE
SEWER
EX. 8" PVC
FORCE MAIN
6"
3' M
IN
3.
5'
M
IN
7" MIN.
18" +/-5.9'
3' M
IN
7" MIN.
18" MIN.
PROPOSED
3" PVC
FORCE MAIN
EXISTING GRADE EXISTING GRADE EXISTING GRADE
LEGEND:
PROPOSED SANITARY FORCE MAIN
EXISTING SANITARY FORCE MAIN
EXISTING WATER MAIN
EXISTING STORM SEWER CULVERT
EXISTING CONTOUR
EXISTING OVERHEAD POWER
EXISTING UNDERGROUND TELEPHONE
EXISTING POWER POLE
EXISTING PEDESTAL
EXISTING MAILBOX
EXISTING ELECTRIC TRANSFORMER
EXISTING SANITARY MANHOLE
OHE
W W
UT UT
TR
PROPOSED 10' PUBLIC
UTILITY EASEMENT
EXISTING
GRADE
PROPOSED OPEN CUT OF
EXISTING ASPHALT TO INSTALL
PROPOSED 3" FORCE MAIN.
(SEE DETAIL)
' W
ID
E
O
PE
N C
U T
TRAFFIC CONTROL:
CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL FOR ANY WORK
IMPEDING THE FLOW OF VEHICULAR OR PEDESTRIAN TRAFFIC IN NCDOT
OR PRIVATE RIGHT OF WAY PER NCDOT STANDARD DRAWINGS.
EXISTING VEGETATION:
CONTRACTOR SHALL REMOVE ANY EXISTING VEGETATION IN THE RIGHT
OF WAY THAT SHALL INTERFERE WITH THE INSTALLATION OF THE
PROPOSED UTILITY. CONTRACTOR SHALL NOT REMOVE ANY EXISTING
VEGETATION ON PRIVATE PROPERTY WITHOUT THE WRITTEN PERMISSION
FROM SAID PROPERTY OWNER.
PROPOSED AIR
RELEASE MANHOLE
STA. 20+32
(SEE DETAIL)
EX. 12" RCP STORM
SEWER CROSSING
STA. 18+32
INV.=59.66EX. 12" RCP STORM
SEWER CROSSING
STA. 16+35
INV.=57.40
M
IN
M
IN
EX. 24" RCP STORM
SEWER CROSSING
STA. 11+40
INV.=55.43
M
IN
PROPOSED 10'x10'x6'
RECEIVING PIT
PROPOSED
50'x5'x5' BORE PIT
6.2' 3.
0'
PROPOSED SILT FENCE 5'
OUTSIDE OF PROPOSED
FORCE MAIN
PROPOSED SILT FENCE 5'
OUTSIDE OF PROPOSED
FORCE MAIN PROPOSED SILT FENCE 5'
OUTSIDE OF PROPOSED
FORCE MAIN
EXISTING LIMITS OF
DISTURBANCE
PROPOSED LIMITS
OF DISTURBANCE
1,615SF (0.04 AC)
PROPOSED LIMITS
OF DISTURBANCE
4,065SF (0.09 AC)
PROPOSED LIMITS
OF DISTURBANCE
14,420SF (0.33 AC)
PROPOSED LIMITS
OF DISTURBANCE
555SF (0.01 AC)
EXISTING
UNDERGROUND
TELEPHONE
EX. 4" Ø FM
EX. 8" Ø
WATER
10LF - 8" STEEL
BORE AND JACK
CASING PIPE, MIN.
THICKNESS 0.188"
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text
NC HWY. 214 (SAM POTTS HWY.)
AutoCAD SHX Text S
POWER BOX
ON SLAB
EX. BOLTON
PUMP
STATION SITE
GRASS
SOILGRAVEL
ASPHALT
SITE CONTROL CORNER
BURIED IRON PIPE IN FIELD
NAD 83(2011) POSITION
N: 209,572.53 sFT
E: 2,181,814.65 sFT
FIELD
N/F
CITY OF WHITEVILLE
Deed Book 1145 - Page 904
N/F
SPENCER L. NEWCOMER
Deed Book 1214 - Page 121
FIELD
HEDGEROW
D
ITC
H
DITCH
15" RCP
WEST INV. = 60.05'
EAST INV. = 60.12'
ARV
ASSEMBLY MANHOLE
TOP OF LID = 62.45'
BOTTOM MANHOLE = 58.69'
FM FM FM FM
FM
FM
FM
FM
FM
FM FM
FM FM FM FM
FM
FM
FM
FM
FM
FM
FM FM FM FM FM
FM
FM
FM
FM
FM
W W W W W
W
W
62 61
X X
X X
XXX
X X
X X
X X X
TR
59 60 61 596062 61
N/F
CHARLES BRYANT SMITH
Deed Book 1098 - Page 399
FM FM FM FM FM
FM
FM
FM
FM
FM
FM
25+00 26+00
27+00 28+0028+23
LOD LOD LOD LOD LOD LOD
LOD
LOD
LOD
LO
D
LO
D LOD
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LO
D
LOD LOD LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
DLODLODLODLODLODLODLODLODLODLOD
25+00 26+00 27+00 28+00 29+00
.1
.0
.0
.0
.0
.0
.3
EX
. S
SM
H
ST
A
+2
R
IM
2.
IN
V
O U
T
.3
TH
E
LI
N
E
SH
O W
N A
BO
VE
IS
E
XA
C
TL
Y
O N
E
IN
C H
L O
N G
A T
TH
IS
S H
EE
TS
O R
IG
IN
AL
P
AG
E
SI
ZE
LS
3P
P R
O
JE
C T:
ORIG
SUBMISSION:
SHEET NAME:
SHEET:
A
B
C
D
E
1 2 3 4 5 6
DATE DESCRIPTION∆
COPYRIGHT 2024 ALL RIGHTS RESERVED. PRINTED OR
ELECTRONIC DRAWINGS AND DOCUMENTATION MAY
NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN
PERMISSION FROM LS3P ASSOCIATES LTD.
/4
/2
3:
:2
PM
-2
Columbus County Schools
G re en S w am p R d.
H w y.
a nd
S am
P ot ts H w y
Bo lto n, N or th
C ar ol in a
C ol um bu s C ou nt y Sc ho ol s
PK
-8
PERMIT APPLICATION
WWW.LS3P.COM
101 NORTH THIRD STREET, SUITE 500
WILMINGTON, NORTH CAROLINA 28401
TEL. 910.790.9901 FAX. 910.790.3111
122 Cinema Drive Wilmington, North Carolina 28403
(910) 791-6707 (O) (910) 791-6760 (F) NC License #: C-2846 - SC License #: 003542
NORTH CAROLINA
PR
OFESSION
ENGI N EER
SEAL
AL
0 3 1 5 9 1
ROBERT P . BA LLA ND
03/26/2026
IS
SU
E D
F O
R
P R
E L
IM
IN
A R
Y P
E R
M
IT
T
IN
G B
ID
C
O N
ST
R
U C
T
IO
N
A 2025.09.24 FOR PERMIT / BIDDING
B 2025.10.17 ADDENDUM 01
C 2025.10.28 ADDENDUM 03
0 2026.01.15 PERMIT APPLICATION
1 2026.02.09 ASI#4-BYPASS DITCH REV
AND FORCE MAIN TIE-IN
2026.03.19 RFI#18 STORM MH2
CULVERT #2
OFF-SITE
FORCE MAIN
PLAN & PROFILE
C-411
01/27/2026
OFF-SITE FORCE MAIN [STA. 25+00 - END] - PROFILE VIEW
HORIZONTAL SCALE: 1" = 50'
VERTICAL SCALE: 1" = 5'
OFF-SITE FORCE MAIN [STA. 25+00 - END] - PLAN VIEW
SCALE: 1" = 50'
SE
E
SH
EE
T C
-4
0 25 50 100 200
SCALE: 1"=50'
GRAPHIC SCALE
PROPOSED 3" SDR-21,
200 PSI, PVC FORCE MAIN
(2) 3" MJ 45°
BENDS
6.
7'
E O
S
TO
F M
(1) 3" MJ 45°
HORIZONTAL BEND
STA. 25+96
(1) 3" MJ 45°
HORIZONTAL BEND
STA. 26+55
3" SDR-21, 200PSI,
PVC SANITARY
SEWER FORCE MAIN
3' M
IN
CONTRACTOR SHALL CORE DRILL EX.
SSMH TO ACCEPT A 3" LINE AND
INSTALL NEOPRENE BOOT
(2) 3" MJ 45°
BENDS
CONTRACTOR SHALL CORE DRILL EX.
SSMH TO ACCEPT A 3" LINE AND
INSTALL NEOPRENE BOOT
+/-15' FROM FM TO FENCE
7.8' FROM EOP TO FM
TYPICAL FORCE MAIN PRESSURE
SEWER TRENCH DETAIL #4
STA. 25+55 TO 26+25
NOT TO SCALE
EX. 8" PVC
FORCE MAIN
3.
5'
M
IN
7" MIN.
+/-3'
3' M
IN
7" MIN.
18" MIN.
PROPOSED
3" PVC
FORCE MAIN
EXISTING GRADE
TYPICAL FORCE MAIN PRESSURE
SEWER TRENCH DETAIL #5
STA. 26+25 TO 28+20
NOT TO SCALE
7" MIN.
3' M
IN
7" MIN.
18" MIN.
PROPOSED
3" PVC
FORCE MAIN
EXISTING GRADE
STAINLESS STEEL
DOUBLE STRAP
SERVICE SADDLE
2" BRASS NPT ISOLATION
BALL VALVE
1 FULL JOINT PVC SDR-21
PIPE CENTERED AT VALVE.
INSTALL PIPE A MINIMUM
OF 6 INCHES OFF THE
MANHOLE BOTTOM.
SE
WER
MANHOLE COVER
CONCRETE GRADE RING
12" (MIN.) NO. 57 OR NO. 5
STONE UNDER MANHOLE
A R V
PVC SDR-21
PIPE
DESCRIPTION
1. PVC SDR-21 FORCE MAIN
2. - x 2" IP SADDLE
3. 2" BRASS NIPPLE
4. 2" BRASS BALL VALVE WITH HANDLE
5. 2" x 3/4" BRASS TEE
6. ARV - AIR RELEASE VACUUM VALVE
7. 3/4" BRASS NIPPLE
8. 3/4" BRASS BALL VALVE
9. 3/4" FIP x FEMALE QUICK CONNECT
#075D
PVC OUTLET TO
DIRECT LIQUID TO
GROUND.
60" DIAMETER (MIN.)
MANHOLE
TRACER WIRE MIN. 12 GAUGE, SINGLE
STRAND COATED COPPER WIRE. SPLICES
SHALL BE AS APPROVED BY UTILITY OWNER
PROJECT COORDINATOR. LOOP A MINIMUM
OF 6' OF TRACER WIRE IN MANHOLE.
NOTES:
1. COMBINATION AIR RELEASE VALVES SHALL BE OF THE
SINGLE HOUSING STYLE THAT COMBINES THE OPERATING
FEATURES OF BOTH AN AIR VACUUM AND AIR RELEASE
VALVE.
2. THE COMBINATION AIR RELEASE VALVE SHALL HAVE 2" NPT
INLET AND 1" NPT OUTLET CONNECTIONS AND A 3/16 INCH
DIAMETER ORIFICE FOR A MAX. 200PSI WORKING PRESSURE.
3. ALL MATERIALS SHALL MEET THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF WHITEVILLE.
4. MANHOLE, FRAME, AND COVER SHALL BE IN ACCORDANCE
WITH CITY OF WHITEVILLE STANDARD DETAILS.
5. 2" TAPPING SADDLE SHALL BE DUCTILE IRON WITH
STAINLESS STEEL STRAPS, BOLTS, NUTS, AND WASHERS.
6. SADDLES FOR PIPE SIZES 8" THRU 24" SHALL BE DOUBLE
STRAP.
7. ALL INTERNAL PARTS SHALL BE 316 STAINLESS STEEL.
8. THE COMBINATION AIR RELEASE VALVE SHALL HAVE A
SINGLE FLOAT DESIGN.
9. ALL COMBINATION AIR RELEASE VALVES SHALL BE
INSTALLED IN ACCORDANCE WITH MANUFACTURER
RECOMMENDATIONS.
10. ALL COMBINATION AIR RELEASE VALVES SHALL BE CRISPIN
MODEL UX20, ARI D-020, H-TEC 986, OR APPROVED EQUAL.
11. COMBINATION AIR RELEASE VALVE SHALL BE OFFSET 12"
FROM CENTER OF MANHOLE. OFFSET THE RING AND COVER
TO ALLOW ACCESS.
12. TOP OF FORCE MAIN SHALL BE A MIN. 4' DEEP AT AIR
RELEASE VALVE, UNLESS OTHERWISE REQUIRED DUE TO
FORCE MAIN AND/OR COMBINATION AIR RELEASE VALVE
SIZE.
13. COMBINATION AIR RELEASE VALVE BODIES SHALL BE MADE
OF STAINLESS STEEL OR REINFORCED NYLON.
14. THE MANHOLE SHALL BE CAST WITH AN ANTI-MICROBIAL
ADDITIVE (CON-SHIELD OR APPROVED EQUAL).
COMBINATION AIR RELEASE
VACUUM VALVE 2" NPT INLET
AND 1" NPT OUTLET OFFSET
12" FROM CENTER OF
MANHOLE.
12" MIN.
FLAT TOP
MANHOLE
COMBINATION AIR RELEASE
VACUUM VALVE
NOT TO SCALE
NOTE:
PIPE SUPPORT TO BE PLACED TO PROVIDE PROPER SUPPORT, ALIGNMENT, AND
GRADE AS SPECIFIED. CONTINUOUS SUPPORTS MAY BE USED AS ALTERNATIVE. OIL,
GREASE, OR PETROLEUM PRODUCT MAY NOT BE USED AS LUBRICANT.
A
TYPE 1 OR 2
FINAL BACKFILL
PIPE
NOTES:
1. BACKFILL SHALL BE SUITABLE MATERIAL THAT IS FREE FROM HEAVY CLAY, GUMBOS, DEBRIS, ORGANICS
AND LITTLE TO NO EXCESSIVE MOISTURE.
2. SELECT BACKFILL MAY BE SUBSTITUTED OR REQUIRED BY ENGINEER TO ACHIEVE COMPACTION, (I.E.
#57, ABC, CRUSHED LIMESTONE, CLEAN SAND, FLOWABLE FILL, ETC).
3. 8-INCH OF ABC BASE MATERIAL SHALL BE USED ON TOWN STREETS.
4. BACKFILL AND BASE MATERIALS SHALL BE COMPACTED 12” MINIMUM LIFTS
5. SOIL SHALL BE COMPACTED BY A MECHANIZED TAMPER (I.E JUMPING JACK), HOWEVER, VIBRATORY
ROLLERS > 18” WIDTH MAY BE USED FOR LARGER EXCAVATIONS. THE PLATE TAMP METHOD SHALL NOT
BE USED.
6. ALL APPROVED CASTINGS SHALL BE SET FLUSH TO GRADE AND SUPPORTED IF APPLICABLE.
ABC BASE AND SUBBASE COMPACTED TO 98% AND BACKFILL AND EMBEDMENT COMPACTED TO 90% AS
DETERMINED BY THE MODIFIED PROCTOR AASHTO METHOD T-99.
8. 1-FOOT CUTBACKS OF ASPHALT SHALL BE PREPARED ON UNDISTURBED SOIL. MINIMUM ASPHALT
DENSITY IS 90%.
8" ABC BASE
12" SUBBASE
BACKFILL
EMBEDMENT
TYPICAL BORING/ JACKING DETAIL
NOT TO SCALE
CL 50 DUCTILE IRON
DR 18 PVC
PIPE TRENCH DETAIL
NOT TO SCALE
PAVEMENT REPAIR WHERE PIPE INSTALLED
(FOR PRIVATE ROADS AND PAVED AREAS;
CONTRACTOR TO MEET MIN. REQUIREMENTS AS DEFINED BY
RIGHT-OF-WAY OWNER FOR PUBLIC ROAD REPAIRS)
NOT TO SCALE
PIPE CASING SUPPORT DETAIL
NOT TO SCALE
PIPE BEDDING
SLOPE WALLS TO ANGLE OF
REPOSE OR SHORING, AS
APPROVED BY ENGINEER
CLEAN SQUARE
CUT W/ TACK
MATCH EXISTING ASPHALT
OR 2" MIN SUPERPAVE S-9.5B
IN LIFTS
EXISTING
PAVEMENT
1'-0"
CUTBACK
1'-0"
CUTBACK
PI
PE
6"
VA
R
8" M
IN
SLOPE WALLS TO
ANGLE OF REPOSE OF
SOIL OR AS
APPROVED BY
ENGINEER
D
3" M
IN
6" M
IN
90°
O .D
6" MIN.6" MIN.
O.D.
FINAL GRADE
STABLE
FOUNDATION
MATERIAL
BEDDING, PER
SPECIFICATIONS
CLASS 1, 2 OR 3
PIPE SIZE, AS
INDICATED ON
THE PLANS
PAVEMENT WIDTH AND LOCATION
IN R/W VARIES. SEE PLAN
FOR INDIVIDUAL LOCATION.
1' 1'
MIN. 1:1 SLOPE
FROM EDGE OF
PAVEMENT
MIN. 1:1 SLOPE
FROM EDGE OF
PAVEMENT
3' M
IN
CRUSHED STONE
BASE
STEEL ENCASEMENT PIPE SEAL EACH END
A
SUPPORT SPACING VARIES
PER MANUFACTURER.
DESIGN ENGINEER SHALL
APPROVE/DETERMINE SPACING.
SEAL END OF CASING PIPE
AFTER TESTING WITH
BRICK BULKHEAD
POLYMER SKID
STEEL CASING PIPE
STAINLESS STEEL SUPPORTS
SECTION A-A
NOT TO SCALE
STAINLESS STEEL BAND
STAINLESS STEEL LEG
POLYMER SKID
STEEL CASING PIPE
CARRIER PIPE
NOTES:
1. CASING WILL BE INSTALLED AT LINE AND GRADE SHOWN ON INDIVIDUAL PROFILE FOR EACH
CROSSING. BORING/JACKING TO LINE AND GRADE IS REQUIRED.
2. TRACER WIRE SHALL BE TAPED AT 12' INTERVALS THROUGHOUT THE CASING.
3. PRESSURE AND NON-PRESSURE PIPING THROUGH CASING SHALL BE RESTRAINED JOINT.
4. SEE PIPE CASING SUPPORT DETAILS.
SKID SPACING AND LEG SIZE VARIES
BY PIPE SIZE AND PER
MANUFACTURER. DESIGN ENGINEER
SHALL APPROVE/DETERMINE SPACING.
CASING INSULATORS TO BE
WITHIN 2'-0" OF EACH END OF
CASING (TO KEEP PIPE
CENTERED IN CASING AT ENDS)
M
IN
EX. 15" RCP STORM
SEWER CROSSING
STA. 25+51
INV.=60.06
(2) 3" MJ 45°
HORIZONTAL BENDS
STA. 27+96
STA. 28+03
NAD 83 (2011)
PROPOSED SILT FENCE 5'
OUTSIDE OF PROPOSED
FORCE MAIN
PROPOSED SILT FENCE 5'
OUTSIDE OF PROPOSED
FORCE MAIN
PROPOSED LIMITS
OF DISTURBANCE
14,420SF (0.33 AC)
AutoCAD SHX Text S
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text S
AutoCAD SHX Text
7. ABC BASE AND SUBBASE COMPACTED TO 98% AND BACKFILL AND EMBEDMENT COMPACTED TO 90% AS
June 5, 2026
North Carolina Department of Transportation
Division 6, District 3
1194 Prison Camp Road
Whiteville, North Carolina 28472
Re: Utility Encroachment Permit – Force Main
Columbus Co. Schools PK-8
NC Hwy 214 (Sam Potts Hwy.)
Dear Sirs:
Construction work included in the above referenced encroachment permit number will be included in the contract for construction of Columbus Co. Schools PK-8. Payment for this work and release of the contractor’s bond will not be made until the work is complete, and the design engineer and
NCDOT agree that the work meets or exceeds the NCDOT standards.
Sincerely, Jesse E. Beck II
Superintendent, Columbus County Board of Education
JOSH STEIN
Governor
D. REID WILSON
Secretary
RICHARD E . ROGERS, JR.
Director
Division of Water Resources – Wilmington Regional Office
127 Cardinal Drive Extension, Wilmington, North Carolina 28405 Phone: 910-796-7215\ Internet: www.deq.nc.gov
May 8, 2026
Shawn Maynor, Mayor Town of Bolton 221 South 9th Street Bolton, NC 28423
Subject: Permit No. WQ0047335
Town of Bolton East View Pre K - 8 School Force Main Extension Sewer Wastewater Collection System Extension Columbus County
Dear Mr. Maynor:
In accordance with your application received March 27, 2026 we are forwarding herewith Permit No.
WQ0047335 dated May 8, 2026 to Town of Bolton (Permittee) for the construction and operation upon certification of the subject wastewater collection system extension. This permit shall be effective from the date of issuance until rescinded and shall be subject to the conditions and limitations as specified therein. This cover letter shall be considered a part of this permit and is therefore incorporated therein by reference.
Please pay particular attention to the following conditions contained within this permit:
Special Conditions:
Condition I.1: This permit shall become voidable unless the agreement between the TOWN OF BOLTON and the City of Whiteville for the collection and final treatment of wastewater is in full force and effect. [15A NCAC 02T.0304(h)]
Standard Conditions:
Condition II.1: This permit shall not be automatically transferable; a request must be made and approved.
Condition II.4: Requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2T .0403 or any individual system-wide collection system permit issued to the Permittee.
Condition II.7: Upon completion of construction and prior to operation of these permitted facilities, the completed Engineering Certification form with checklist attached to this permit shall be submitted with the required supporting documents to the address provided on the form.
Docusign Envelope ID: F81EC722-437F-41C2-96A3-1F49867A494C http://www.deq.nc.gov/
Permit No. WQ0047335 May 8, 2026 Page 2 of 9
Permit modifications are required for any changes resulting in non-compliance with this permit, regulations, or the Minimum Design Criteria. [15A NCAC 02T.0116]
Condition II.13: If the Permittee/Applicant holds a system-side collection system operation, maintenance and management permit (WQCS-prefix) from the Division, then the following applies: For all newly constructed, modified and rehabilitated pump stations, all equipment and components shall be sealed within a corrosion-resistant coating or encasement to the extent practicable and equivalent to the minimum design criteria unless the permittee can demonstrate it is not practicable or another form of corrosion resistance is employed. [15A NCAC 02T .0108 (b)]
It shall be responsibility of the Permittee to ensure that the as-constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina-licensed Professional Engineer to the licensing board.
If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding.
If you need additional information concerning this matter, please contact Tyler Benson at (910) 796-7215 or via e-mail at Tyler.Benson@deq.nc.gov.
Sincerely, Chad Coburn, Assistant Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ
Cc: Rob Balland, Paramounte Engineering (Laserfiche info via email)
City of Whiteville (Laserfiche info via email or mail)
Upload to Laserfiche
Permit No. WQ0047335 May 8, 2026 Page 3 of 9
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the
TOWN OF BOLTON
COLUMBUS COUNTY
for the construction and operation upon certification of approximately 1,823 linear feet of 3-inch force main to serve the East View Pre K-8 Private Sewer (Permit No. WQ47336) as part of the East View Pre K - 8 School Force Main Extension Sewer project, with no additional discharge of collected wastewater into the City of Whiteville’s existing sewerage system, pursuant to the application received March 27, 2026 and in conformity with 15A NCAC 2T; the Division’s Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division’s Minimum Design Criteria for the Fast-Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting data subsequently filed and approved by the Department of Environmental Quality and considered a part of this permit.
This permit shall be effective from the date of issuance until rescinded and shall be subject to the specified conditions and limitations contained therein.
Permit Number: WQ0047335
Issued Today: May 8, 2026
Chad Coburn, Assistant Regional Supervisor Wilmington Regional Office Water Quality Regional Operations Section Division of Water Resources, NCDEQ By Authority of the Director and The Environmental Management Commission
Permit No. WQ0047335 May 8, 2026 Page 4 of 9
SUPPLEMENT TO PERMIT COVER SHEET
TOWN OF BOLTON is hereby authorized to:
Construct, and then operate upon certification the aforementioned wastewater collection extension. The sewage and wastewater collected by this system shall be treated in the Whiteville Wastewater Treatment Facility in accordance with Permit Number NC0021920.
Permitting of this project does not constitute an acceptance of any part of the project that does not meet 15A NCAC 2T; the Division of Water Resources’ (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; and the Division’s Minimum Design Criteria for the Fast-Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by a North Carolina-licensed Professional Engineer in the application. It shall be the Permittee’s responsibility to ensure that the as-constructed project meets the appropriate design criteria and rules.
Construction and operation is contingent upon compliance with the Standard Conditions and any Special Conditions identified below.
I. SPECIAL CONDITIONS
1. This permit shall become voidable unless the agreement between the TOWN OF BOLTON and the City of Whiteville for the collection and final treatment of wastewater is in full force and effect. [15A NCAC 02T.0304(h)]
II. STANDARD CONDITIONS
1. This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request shall be considered on its merits and may or may not be approved. [15A NCAC 02T.0104; G.S 143-215.1(d3)]
2. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance with the conditions of this permit; 15A NCAC 2T; the Division’s Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division’s Minimum Design Criteria for the Fast-Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials unless specifically mentioned herein. [15A NCAC 02T.0110]
3. This permit shall be effective only with respect to the nature and volume of wastes described in the application and other supporting data. [15A NCAC 02T .0110]
4. The wastewater collection facilities shall be properly maintained and operated at all times. The Permittee shall maintain compliance with an individual system-wide collection system permit for the operation and maintenance of these facilities as required by 15A NCAC 2T .0403. If an individual permit is not required, the following performance criteria shall be met: [15A NCAC 02T .0108(b)]
Permit No. WQ0047335 May 8, 2026 Page 5 of 9
a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters, and to prevent any contravention of groundwater standards or surface water standards.
b. A map of the sewer system shall be developed and shall be actively maintained.
c. An operation and maintenance plan including pump station inspection frequency, preventative maintenance schedule, spare parts inventory and overflow response has been developed and implemented.
d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365 days per year). Pump stations that are connected to a telemetry system shall be inspected at least once per week.
e. High-priority sewer lines shall be inspected at least once per every six-months and inspections are documented.
f. A general observation of the entire sewer system shall be conducted at least once per year.
g. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina General Statute §143-215.1C.
h. A Grease Control Program is in place as follows:
1. For public owned collection systems, the Grease Control Program shall include at least biannual distribution of educational materials for both commercial and residential users and the legal means to require grease interceptors at existing establishments. The plan shall also include legal means for inspections of the grease interceptors, enforcement for violators and the legal means to control grease entering the system from other public and private satellite sewer systems.
2. For privately owned collection systems, the Grease Control Program shall include at least bi-annual distribution of grease education materials to users of the collection system by the permittee or its representative.
3. Grease education materials shall be distributed more often than required in Parts (1) and (2) of this Subparagraph if necessary to prevent grease-related sanitary sewer overflows.
i. Right-of-ways and easements shall be maintained in the full easement width for personnel and equipment accessibility.
j. Documentation shall be kept for Subparagraphs (a) through (i) of this Rule for a minimum of three years with exception of the map, which shall be maintained for the life of the system.
5. Noncompliance Notification:
The Permittee shall report by telephone to a water resources staff member at the Wilmington Regional Office, telephone number (910) 796-7215, as soon as possible, but in no case more than 24 hours or on the next working day, following the occurrence or first knowledge of the occurrence of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or
b. Any SSO and/or spill over 1,000 gallons; or
c. Any SSO and/or spill, regardless of volume, that reaches surface water
Permit No. WQ0047335 May 8, 2026 Page 6 of 9
Voice mail messages or faxed information is permissible, but this shall not be considered as the initial verbal report. Overflows and spills occurring outside normal business hours may also be reported to the Division of Emergency Management at telephone number (800) 858-0368 or (919) 733-3300.
Persons reporting any of the above occurrences shall file a spill report by completing and submitting Part I of Form CS-SSO (or the most current Division approved form) within five days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not recur. Part II of Form CS-SSO (or the most current Division approved form) can also be completed to show that the SSO was beyond control. [G.S. 143-215.1C(a1)]
6. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. [15A NCAC 02T.0108(b)]
7. Upon completion of construction and prior to operation of these permitted facilities, the completed Engineering Certification form with checklist attached to this permit shall be submitted with the required supporting documents to the address provided on the form. A complete certification is one where the form is fully executed and the supporting documents are provided as applicable. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions.
If the permit is issued to a private entity with an Operational Agreement, then a copy of the Articles of Incorporation, Declarations/Covenants/Restrictions, and Bylaws that have been appropriately filed with the applicable County’s Register of Deeds office shall be submitted with the certification.
A complete certification is one where the form is fully executed and the supporting documents are provided as applicable. Supporting documentation shall include the following:
a. One copy of the project construction record drawings (plan & profile views of sewer lines & force mains) of the wastewater collection system extension. Final record drawings should be clear on the plans or in accepted electronic format and are defined as the design drawings that are marked up or annotated with after construction information and show required buffers, separation distances, material changes, etc.
b. One copy of the supporting applicable design calculations including pipe and pump sizing, velocity, pump cycle times, and level control settings, pump station buoyancy, wet well storage, surge protection, detention time in the wet well, and force main, ability to flush low points in force mains with a pump cycle, and downstream sewer capacity analysis. If a portable power source or pump is dedicated to multiple stations, an evaluation of all the pump stations’ storage capacities and the rotation schedule of the portable power source or pump, include travel timeframes, shall be provided.
c. Changes to the project that do not result in non-compliance with this permit, regulations, or the Minimum Design Criteria should be clearly identified on the record drawings, on the certification in the space provided, or in written summary form.
Prior to Certification (Final or Partial): Permit modifications are required for any changes resulting in non-compliance with this permit (including pipe length changes of 10% or greater by type & size, increased flow, pump station design capacity design increases of 5% or greater, and increases in the number/type of connections), regulations, or the Minimum Design Criteria. Requested modifications or variances to the Minimum Design Criteria will be reviewed on a case-by-case basis and each on its own merit. Please note that variances to the Minimum Design Criteria should be requested and approved during the permitting process prior to construction. After-construction requests are
Permit No. WQ0047335 May 8, 2026 Page 7 of 9 discouraged by the Division and may not be approved, thus requiring replacement or repair prior to certification & activation. [15A NCAC 02T .0116]
8. Gravity sewers installed greater than ten percent below the minimum required slope per the Division’s
Gravity Sewer Minimum Design Criteria shall not be acceptable and shall not be certified until corrected. If there is an unforeseen obstacle in the field where all viable solutions have been examined, a slope variance can be requested from the Division with firm supporting documentation.
This shall be done through a permit modification with fee. Such variance requests will be evaluated on a case-by-case basis. Resolution of such request shall be evident prior to completing and submitting the construction certification. [ 15A NCAC 02T.0105(n)]
9. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. [15A NCAC 02T .0116]
10. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2T; the Division’s Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division’s Minimum Design Criteria for the Fast-Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an enforcement action by the Division, in accordance with North Carolina General Statutes §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina-licensed Professional Engineer to the licensing board. [15A NCAC 02T .0104; 15A NCAC 02T .0108(b-c)]
11. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement facilities.
[15A NCAC 02T .0110; 15A NCAC 02T .0108(b)]
12. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances that may be imposed by the Division any other Federal, State, or Local government agencies which have jurisdiction or obtaining other permits which may be required by the Division or any other Federal, State, of Local government agencies. [G.S. 143-215.1(b)]
13. If the Permittee/Applicant holds a system-side collection system operation, maintenance and management permit (WQCS-prefix) from the Division, then the following applies: For all newly constructed, modified and rehabilitated pump stations, all equipment and components shall be sealed within a corrosion-resistant coating or encasement to the extent practicable and equivalent to the minimum design criteria unless the permittee can demonstrate it is not practicable or another form of corrosion resistance is employed. [15A NCAC 02T .0108 (b)]
FAST TRACK SEWER ENGINEERING CERTIFICATION
NC DWR – Water Quality Regional Operations Section 127 Cardinal Drive Extension Wilmington, NC 28405 Wilmington Regional Office Phone: 910-796-7215 FAX: 910-350-2004
PERMITTEE: Town of Bolton
PERMIT #: WQ0047335
PROJECT: East View Pre K - 8 School Force Main Extension Sewer ISSUE DATE: May 8, 2026 COUNTY: Columbus
This project shall not be considered complete nor allowed to operate in accordance with Condition 7 of this permit until the Division has received this Certification and all required supporting documentation. Consequently, it should be submitted in a manner that documents the Division’s receipt. Send the required documentation to the Wilmington Regional Supervisor, Water Quality Section at the address at the bottom.
The Permittee is responsible for tracking all partial certifications up until a final certification is received. Certifications shall include Phase/Section covered, line size & lengths installed, and listing of lots/connections to be served and pump station design, if applicable. A Final Certification shall be a complete set of record drawings and design calculations regardless of whether partials have been submitted.
PERMITTEE’S CERTIFICATION
I, the undersigned agent for the Permittee, hereby state that this project has been constructed pursuant to the applicable standards & requirements, the Professional Engineer below has provided applicable design/construction information to the Permittee, and the Permittee is prepared to operate & maintain the wastewater collection system permitted herein or portions thereof.
Printed Name, Title Signature Date
ENGINEER'S CERTIFICATION
I, ___________________, as a duly registered Professional Engineer in the State of North Carolina, having been authorized to ( periodically, weekly, full time) observe the construction of the project name and location as referenced above for the above Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the following construction:
approximately 1,823 linear feet of 3-inch force main to serve the East View Pre K-8 Private Sewer (Permit No. WQ47336) as part of the East View Pre K - 8 School Force Main Extension Sewer project, with no additional discharge of collected wastewater;
such that the construction was observed to be built in compliance of this permit; 15A NCAC 2T; the Division of Water Resources’ (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division’s Minimum Design Criteria for the Fast-Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials.
North Carolina Professional Engineer’s Seal w/signature & date
Final Partial (include description)
Certification Comments/Qualifiers (attach if necessary):
SEWER ENGINEERING CERTIFICATION CHECKLIST
To be completed by the certifying engineer prior to operation of the permitted sewers, per 15A NCAC 02T.0116.
Certifying Engineer: _______________________________________________________
Certification Review Date: __________________________________________________
Project Name: ____________________________________________________________
WQ00______________ Project County: _______________________________________
1) Has permittee information changed since the permit was issued (or last modified): change of mailing address, change of ownership, transfer from developer to HOA/POA, etc. Yes No
• If yes, please provide either a change of ownership form or new contact information. Note that transfer of permits from the developer to the HOA/POA must occur with the first certification.
2) Have the as-built drawings have been signed, sealed, and dated by an N.C. PE? Yes No
3) Final Engineering certification? Yes No
• If Partial Engineering certification, provide detailed narrative including what is being certified in the current phase, what was previously certified (if applicable), and what is left to be certified.
4) Adequate information related to sewer lines: Yes No N/A
• Three feet minimum cover has been provided for all sewers unless ferrous pipe was installed.
• Minimum diameters for gravity sewers are 8-inches for public lines and 6-inches for private lines.
• Manholes have been installed: At the end of each line, at all changes in grade, size, or alignment, at all intersections, and at distances not greater than 425 feet; minimum diameter shall be 4 feet (48-inches).
5) Adequate information related to pump stations: Yes No N/A
• Ensure power reliability option was selected per 15A NCAC 02T.0305(h).
6) Was project construction completed in accordance with all of the following: Yes No N/A
• 15A NCAC 02T, Minimum Design Criteria (MDC) for the permitting of Gravity Sewers (latest version), and MDC for the Permitting of Pump Stations and Force Mains (latest version)?
If not, a variance approval is required in accordance with 15A NCAC 02T.0105(b), prior to certification and operation.
• Contact the Central Office to discuss the variance to determine a course of action.
• Applicant must submit two copies of the variance request form, plans, specifications, calculations, and any other pertinent information to the Central Office (one hard copy, one digital copy).
• The central office will review the variance request, and if approvable, specific language regarding the variance will be incorporated into the permit, either via a special condition or a supplementary letter. A copy of the reissued permit with variance language or the variance letter must be maintained with the original documents.
7) Does the project contains high priority lines (15A NCAC 02T .0402(2))? Yes No
• If yes, ensure that the permit already contains the necessary condition related to high priority lines 15A NCAC 02T.0403 (a)(5).
This is the start of the file's text. The full file is on GovTribe.