This is a technical specification document detailing requirements for cable and splice kit supplies for the Bureau of Reclamation's Grand Coulee facility in Washington state. The specification calls for two line items: (1) 600 feet of copper cable, medium-voltage power, 3-conductor (2/0), compact stranded, 15kV Type MV105, to be furnished on one continuous reel without splices (Okoguard Okoseal No. 115233806 or approved equal), and (2) 9 inline, heat-shrinkable, shielded power cable splice kits (Raychem/TE Connectivity No. HVS1521S or approved equal).
The cable must meet specific requirements including 15kV UL listing, 2/0 AWG conductor size, minimum 220 mil EPR insulation, 133% minimum insulation level, and be rated for 105 degrees C in wet or dry applications with direct burial capability. The splice kits must include solderless grounding components, accommodate 15kV conductor size #2-4/0, handle maximum jacket OD of 1.25", and have minimum installed length of 27". All items are to be delivered to the Bureau of Reclamation's Grand Coulee facility in Washington state.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140R1725Q0027.pdf | ||
| 140R1725Q0027_Solicitation_and_Clauses.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Cable & Splice Kits Specifications Line Item 0010:
600 feet Copper Cable, Medium‐Voltage Power, 3‐Conductor (2/0), Compact Stranded, 15kV Type MV‐105, furnish on one (1) 600‐foot continuous reel – NO splices, Okoguard Okoseal No. 115‐23‐3806, or Approved Equal.
Salient Characteristics:
· 15kV UL Listed Type MV‐105
· 2/0 AWG Conductor Size
· Minimum 220 Mil Ethylene‐Propylene Rubber (EPR) Insulation
· Minimum 133% Insulation Level (underground system)
· EPR/Uncoated Copper Shield w/ Overall PVC Jacket (flame‐retardant, oil, moisture, and
· sunlight resistant)
· 1 Bare Stranded Copper Grounding Conductor
· Rated at Minimum 105 Degrees C
· For Wet or Dry Applications
· Direct Burial
Line Item 0020:
9 each in‐line, heat‐shrinkable, shielded power cable splice kits, raychem (TE Connectivity) No. HVS‐1521S, or approved equal.
Salient Characteristics:
· Kit Consists of: Solderless Grounding Kit, Ground Clamp, Ground Braid and Shielding Mesh
· Must Accommodate 15kV Conductor Size #2‐4/0
· Maximum Jacket OD of 1.25”
· Maximum Connection Dimensions of .90” (W) x 4.25” (L)
· Minimum Kit Installed Length of 27”
To be delivered to:
Bureau of Reclamation-PN-GCPO Grand Coulee - Receiving Hwy 155 - Warehouse B - Door 6 Industrial Area Grand Coulee WA, 99133