_C24645016.Project_Manual.pdf
PDF 6 MB Posted
- Solicitation number
- 0000034594
- Issued by
- Shasta County, Shasta CDP, Shasta Lake City, Mount Shasta City, California
About this file
This is a comprehensive project manual and set of engineering documents for a septic system improvement project at McArthur Burney Falls Memorial State Park in Shasta County, California, prepared by the California Department of Parks and Recreation. The project involves replacing the existing septic system at the park, with work scheduled to commence after September 8, 2025. The scope includes installing an 8,000-gallon fiberglass septic tank, a 3,000-gallon concrete dosing chamber, pressure-dosed sand beds with Eljen B43 modules, new electrical service, and associated infrastructure. The project will require ground disturbance monitoring by a representative of the Pit River Tribe, and all construction work is to be performed Monday through Friday between 7:00 AM and 5:00 PM.
The project is funded through the California State Parks department and will be completed using specific manufacturer components, including Custom Fiberglass Works tanks, Zoeller pumps, and Eljen treatment modules. The electrical infrastructure will be connected to an existing panel, with new conduits and conductors being installed. Total project electrical load is calculated at approximately 14,788 VA at 240V. The project includes specific environmental and archaeological protection measures, such as monitoring for ground disturbance, preserving sensitive areas, and implementing storm water and soil loss prevention strategies. Contractors will be required to submit detailed submittals, follow strict installation guidelines, and adhere to California building, electrical, and environmental codes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| _C24645016.Burney_Septic._IFB_Advertisement.pdf | ||
| _C24645016_BID_Package.pdf | ||
| _C24645016._Sample_Documents.pdf | ||
| _C24645016.Invitation_for_Bids.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATE OF CALIFORNIA THE RESOURCES AGENCY CALIFORNIA STATE PARKS
Exhibit D, Attachment 1
Project Manual Septic Improvements - Comfort Station 1
McArthur Burney Falls Memorial State Park Shasta County, CA 96013
Contract Number
C24645016
California Department of Parks and Recreation Northern Buttes District
400 Glen Drive Oroville, CA 95966
(530) 538-2200
C24645016 Septic Improvements -Comfort Station 1
McArthur Burney Falls MSP
Project Manual
Table of Contents
Project Manual – Exhibit D, Attachment 1 Number Of Pages
Section 00804 – Disposal of Refuse
Section 01300 – Submittals
Section 02102 – Clearing and Grubbing
Section 02219 – Structure Excavation and Backfill
Section 02221 – Trenching, Backfilling, and Compaction
Section 02232 – Aggregate Base
Section 02574 – Utility Trench Resurfacing
Section 02603 – Sewage Treatment System
Section 16000 – Electrical
Section 311232 – Storm Water Soil Loss Prevention Plan
Special Provisions
Site Plans
SECTION 00804
DISPOSAL OF REFUSE
Part 1 - GENERAL
1.01 DESCRIPTION
A. Dispose of waste, refuse, debris, and rubbish resulting from the construction of the project.
B. If excess excavation spoils cannot be suitably disposed of on State property, as directed by the State Representative, it shall be hauled away at the Contractor’s expense.
1.02 PAYMENT
Payment for all work to be done under this section will be considered as included in bid price of other items as shown on page 2 of the Bid Form. No other compensation will be allowed by the State.
Part 2 - PRODUCTS (not used)
Part 3 - EXECUTION
3.01 REQUIREMENTS
A. Remove waste materials, debris, and rubbish from site and legally dispose of at public or private dumping areas off State property.
B. Conduct cleaning and disposal operations to comply with local ordinances and anti-pollution laws.
1. Do not burn or bury rubbish and waste materials on project site.
2. Do not dispose of volatile wastes such as mineral spirits, oil, or paint thinner in storm or sanitary drains.
3. Do not dispose of wastes into streams or waterways.
END OF SECTION
C:\BASESPEC\00XXX\00804.DOC
08/13/97 2:37 PM
SECTION 01300
SUBMITTALS
Part 1 - GENERAL
1.01 WORK REQUIREMENTS INCLUDE
A. To ensure that specified products and/or trade items are furnished and installed in accordance with design intent, procedures have been established for advance submittal of design data and for its review by the State’s Representative.
B. The following items constitute Complete Submittals. Submit these to the State’s Representative for review, in strict accordance with provisions of this section, but not limited to the following:
1. Provide transmittal letter with General Contractor’s signature for each submittal.
2. Shop drawings and/or other required record drawings.
3. Product data/material lists. Contractor to complete Form (DPR 815) columns C&D (sample attached).
4. Samples.
5. Required statements and information necessary when requesting substitutions.
1.02 SUBMITTALS AND SHOP DRAWINGS
A. Wherever submittals and shop drawings are called for, they shall be submitted within 10 days after the date of Notice to Proceed. The General Contractor is solely responsible for all project product and/or trade item coordination, required signatures, shop drawing, samples and/or other required submittal materials; including submittal dates, numbers of copies, and delivery to the State’s Representative’s for review.
1. No work shall proceed without reviewed copies of required submittals and shop drawings being kept on the job site.
2. No materials or equipment, requiring review of submittals and shop drawings, shall be delivered to the job site or installed without such review by the State’s Representative.
3. Delay in work occasioned by late Complete Submittals, and/or doing work from rejected submittals or shop drawings, or from the necessity of product resubmittal shall not affect the contract terms of payment or time.
Section 01300 - Page 2 Submittals
1.03 QUALITY ASSURANCE
A. Required COORDINATION of and for Complete Submittals.
1. Prior to each submittal, carefully review and coordinate all aspects of each product and/or trade item being submitted.
2. Verify that each product and/or trade item and the submittal for it conform in all aspects with the construction documents (plans and drawings, specified requirements, include all addenda, approved alternates, and change orders).
3. Contractor’s signature is required on each transmittal letter of submittal to certify that his/her required coordination has been performed.
B. Contractor’s signature is required on each transmittal letter of submittal in order for the State’s Representative to review.
Part 2 - PRODUCTS
2.01 PRODUCT DATA/MATERIAL LISTS
A. Manufacturer’s Standard Schematic Drawings:
1. Modify drawings in a neat and orderly fashion to delete information which is not applicable to project.
2. Supplement standard information to provide additional information applicable to project.
B. Manufacturer’s catalog sheets, brochures, diagrams, schedules, performance charts, illustrations, and other standard descriptive data;
require 3 copies each.
1. Clearly mark each copy to identify pertinent materials, products, or models.
2. Make note of dimensions and clearances required.
3. Make note of performance characteristics and capacities.
4. Make note of wiring diagrams and controls.
Section 01300 - Page 3
2.02 PATTERNS AND COLORS
Unless the exact pattern and color of a product are indicated in the contract documents whenever a choice of pattern or color is available for a product, submit accurate color charts and pattern charts to the State’s Representative for his/her review and selection.
2.03 SAMPLES
A. Physical examples to illustrate materials, equipment or workmanship, and to establish standards by which completed work is judged.
B. Office samples should be sufficient size and quantity (minimum of 3) to clearly illustrate functional characteristics of product or material, with integrally related parts and attachment devices.
1. Sizes: Provide following sizes unless other specified.
a. Flat or Sheet Products: Minimum 12-inch x 12-inch square, maximum 24 inch x 24 inch.
b. Linear Products: Minimum 12 inches, maximum 24-inches long.
c. Bulk Products: Minimum 1 pint, maximum 1 gallon.
2. Full-size samples may be used in the work upon approval, only.
Section 01300 - Page 4
C. Field Samples and Mock-Ups:
1. Erect at project site at location acceptable to State’s Representative.
2. Construct each sample or mock-up complete, including work of all trades required in finished work.
2.04 SUBSTITUTIONS
A. State’s Representative’s Review and Acceptance Required:
1. Contract is based solely on materials, equipment, and construction industry standards listed or described in the bid documents (including addenda, accepted alternates, and change orders), and does not contemplate any substitutions.
B. “Or Equal”:
1. Where the phrase “or equal”, or “or equal as reviewed by the State’s Representative”, occurs in the contract documents, do not assume that the materials, equipment, or methods will be approved as equal unless the item has been specifically so reviewed for this work by the State’s Representative.
2. The decision of the State’s Representative shall be final.
C. In making request for substitution, Bidder/Contractor represents and shall submit the following:
1. He/she has personally investigated proposed product or method, and determined that it is equal or superior in all respects to that specified, including size and/or color requirements.
2. He/she will provide the same warranty for substitution as for product or method specified.
3. He/she will coordinate installation of accepted substitution into work, making such changes as may be required for work to be complete in all respects.
4. He/she waives all claims for additional costs related to substitution which consequently becomes apparent.
5. Cost data is complete and includes all related costs under his/her contract.
6. Shall submit detail itemized cost statement showing labor, material installation, overhead and profit for each substitution.
Section 01300 - Page 5
D. Substitutions will not be considered if:
1. They are indicated or implied on shop drawings or project data submittals without formal request submitted in accordance with this section.
2. Acceptance will require substantial revision of contract documents by the State’s Representative.
3. The cost of additional submittal services for architectural review or redesign exceeds the anticipated savings of the proposed substitution, unless original specified products or methods are unavailable.
E. Reimbursement of State’s Representative’s Costs:
1. Should the services of the State’s Representative or consulting engineer be required as a result of any proposed substitution, beyond the normal submittal review, as determined by the State’s Representative, the cost of these additional services shall be considered in the review and approval process.
2.05 RECORD DRAWINGS
A. At time of installation, installed locations of all underground or concealed work, including plumbing and electrical, shall be recorded on prints by the General Contractor and shall be reviewed by the On-Site State’s Representative, on a daily basis. Label each document “AS-BUILT PROJECT RECORD” in large, neat, printed letters.
B. Record the following kinds of information on black-line or blue-line prints:
1. Changes by change orders and other modifications described in these specifications or GENERAL CONDITIONS.
2. Locations of work buried under and outside the building, such as plumbing and electrical lines and conduits.
3. Locations of significant work concealed inside the building whose general locations have been changed from those shown on the contract documents.
4. Locations of items, not necessarily concealed, which have been changed with the State’s Representative prior acceptance, from the location shown on the contract documents.
5. In addition to the previously specified requirements for record drawings:
Section 01300 - Page 6
a. Locate main runs of piping, conduit, ductwork, and similar items by dimensions.
b. Locate other items either by dimensions or in relation to spaces within the building.
c. Keep up to date during the entire progress of work, and make available to the inspector and State’s Representative at any time.
d. Furnish additional drawings as necessary for clarification of relocated work by Contractor.
e. Record deviations from the sizes, locations, and other features of installation shown in the contract documents.
Establish locations of underground work by dimension to column lines or walls, locating turns, and by referenced centerline and invert elevations and rates of fall.
f. Give sufficient information to locate work concealed in the building.
C. All information entered on prints shall be neat, legible, and emphasized by drawing “balloons” around changed items. Format of changed items on drawings shall be acceptable to State’s Representative.
D. Locate and dimension all work including stubs for future connections, with reference to permanent landmarks or buildings and indicate approximate depth below finish grade.
E. All symbols and designations used in preparing record drawings shall match those used in contract drawings.
Section 01300 - Page 7
Part 3 - EXECUTION
3.01 SUBMISSION REQUIREMENTS FOR COMPLETE SUBMITTAL
A. All submittals shall be delivered to and accompanied by letter of transmittal addressed to the State’s Representative. Each submittal/transmittal letter shall include the following to be considered and accepted as complete for Initial Review:
1. Have the State’s Representative project number at the top. Shall include General Contractor’s signature at bottom to certify his/her required coordination of Complete Submittal. Refer to Part 1.03, A., 3., above.
2. Be consecutively numbered.
3. Indicate original submittal number if resubmitted.
4. Indicate specification section number. (Separate submittals are required for each section specification involved.) Refer to Part 1.02, B., for shop drawings.
5. Include proper number of copies. Each Complete Submittal shall include 3 required complete copies for review and distribution.
Refer to Part 1.02, B., for shop drawings requirements.
6. Contain index of items submitted, properly identified with architectural document drawing numbers, etc.
7. Identify substitution requests and reasons for request.
B. State’s Representative shall review submittals for conformance with design concepts of project and review by State’s Representative covers only such conformance. Effort will be made by State’s Representative to discover any errors, but responsibility for accuracy of coordination and correctness of all submittals shall remain with the General Contractor.
Refer to Parts 1.02 and 1.03 listed above.
C. Review of submittals will be general and shall not relieve the General Contractor from complete project product/trade coordination responsibility and/or for proper installation or fitting and construction of work, nor from furnishing materials and work required by the contract documents which may not be indicated on submittals when reviewed. Refer to Parts 1.02 and 1.03 listed above.
Section 01300 - Page 8
D. No portion of work requiring submittals shall be commenced until submittal has been reviewed by State’s Representative. All portions of work shall be in accordance with contract documents and when required, the General Contractor’s submittals as reviewed by the State’s Representative.
END OF SECTION
A:\Specs\01300-SUBMITTALS.doc
7/22/00 4:01 PM
STATE OF CALIFORNIA
Department of Parks and Recreation
Contractor’s List of Materials
Section 01300 Project Title:
Designer: Contractor’s Name:
(A) Spec. (B) (C) (D) (E) (F)
Item Section Description Manufacturer Model or Type of Submittal Required DPR Action No. No. Catalog No.
Certif.
Shop Product To O&M Dwgs. Data Sample Rep. Manual None Date Date Date Date
1 0263 Fiberglass Septic Tank X X X
2 0263 Concrete Dosing Tanks X X X
3 0263 Complete Pump
System & Accessories
X X X X
4 0263 Treatment Modules X X X
5 0263 Geotextile Fabric X X
6 0263 Auto Distribution Valve X X
7 0263 Piping, valves, boxes X
8 16000 Electrical Accessories X
9 02232 Aggregate Base
10 02574 Asphalt Concrete
11 plans Sand Bedding &
Backfill
DPR 815
MCN - Make Corrections Noted; NET - No Exception Taken; R - Rejected; R&R - Revise & Resubmit; NSR - No Submittal Received
Section 01300 - Page 9
SECTION 02102
CLEARING AND GRUBBING
Part 1 - GENERAL
1.01 DESCRIPTION
A. Clearing and grubbing consists of removing all trees, vegetation and other objectionable material from within the areas of new construction as shown on the plans.
B. Unless shown to be removed or altered, existing improvements and facilities, adjacent property, trees and plants are not to be removed and shall be protected from injury or damage.
1.02 PAYMENT
Payment for all work called for in this section will be considered as included in other items as shown on the Bid Form. No separate compensation will be allowed by the State.
Part 2 - PRODUCTS (not used)
Part 3 - EXECUTION
3.01 CLEARING AND GRUBBING
Clear all identified trees, vegetable matter and man-made structures from the construction site as shown on the plans.
A. Limit clearing to 2 feet beyond planned structures and embankments.
B. Grub roots and buried vegetable matter within proposed excavation.
C. Remove man-made structures deep enough to prevent interference with new construction.
D. Clearing for utility trenches shall be limited:
1. Only remove trees marked by the State’s Representative.
Section 02102 - Page 2 Clearing and Grubbing
2. Only remove enough roots to place the utility.
3. Only remove enough shrubs to allow trenching equipment to operate.
3.02 TRIMMING
A. Clearance:
1. Provide 20-foot vertical clearance above new roads and parking areas.
2. Provide 8-foot vertical clearance above new walks.
3. Provide 6-foot vertical clearance above new buildings.
B. Technique: When a woody limb must be shortened or removed, the piece is always pruned just above a junction with another growing part (e.g., main stem, larger branch, equal-sized branch, smaller branch, twig, or bud).
Removing or shortening a woody limb that is larger than 2 inches in diameter is a 3 step process. For limbs smaller than 2 inches in diameter, the Contractor may skip to Step 3, Final Cut.
Step 1, Undercut: The undercut is necessary to prevent the bark from peeling and to assist in directional felling. Cut into the bottom of the limb at a point 1 to 2 feet beyond the junction with another growing part (stem, branch, twig, bud). Cut the limb 1/3 of the way through or until the saw begins to bind. When removing a vertical stem, make the undercut on the side that you wish the stem to fall.
Step 2, Precut (Jumpcut): The precut (jumpcut) is done to remove most of the limb weight. The precut is made on the top of the branch at a point 1 to 2 inches beyond the undercut (or on the opposite side of a vertical stem 1 to 2 inches above the undercut). The precut (jumpcut) is made all the way through the limb until it breaks off.
Step 3, Final Cut: The final cut is made to facilitate wound healing. The final cut is not a flush cut; the final cut shall not injure the branch bark ridge or the branch collar (see definitions).
1. When the smaller limb at a junction is to be removed, then the final cut is made perpendicular to the branch being cut. The final cut shall be close to, but not injuring the branch collar.
Section 02102 - Page 3 Clearing and Grubbing
2. When the larger or equal-sized limb at a junction is to be removed, then the final cut shall be made close to and parallel to, but not injuring the branch bark ridge.
The Contractor shall not apply any material onto the final cut surface of a limb.
C. Definition of Terms:
1. The Branch Collar, when visible, is a swelling of the limb at its point of attachment to a larger limb. This swelling usually encircles the smaller limb and connects with the Branch Bark Ridge.
2. The Branch Bark Ridge, when visible, are areas, rings, or line of bulging bark that may be rough and darker in color than the surrounding bark. The Branch Bark Ridge occurs at the junction of 2 limbs, between the 2 limbs.
END OF SECTION
C:\BASESPEC\02XXX\02102.DOC
06/09/97 11:31 AM
SECTION 02219
STRUCTURE EXCAVATION AND BACKFILL
Part 1 - GENERAL
1.01 DESCRIPTION
A. Excavate and backfill for structures as called for on the project plans and as set forth herein.
B. All references to the Standard Specifications are based on the most current issue.
1.02 PAYMENT
Payment for all work to be done under this section will be considered as included in the lump sum bid price as shown on the Bid Form. No other compensation will be allowed by the State.
Part 2 - PRODUCTS
2.01 STRUCTURE BACKFILL
Structure backfill material shall conform to the requirements of Section 19-3.06 of the CalTrans Standard Specifications.
Section 02219 - Page 2 Structure Excavation and Backfill
3.01 STRUCTURE EXCAVATION
Structure excavation shall be conducted as shown on the project plans and in accordance with the provisions of Section 19-3.01 through 19-3.05 of the Caltrans Standard Specifications.
3.02 STRUCTURE BACKFILL
Structure backfill shall be placed and compacted in accordance with the project plans and Section 19-3.06 of the Caltrans Standard Specifications.
END OF SECTION
C:\BASESPEC\02XXX\02219.DOC
06/10/97 2:17 PM
SECTION 02221
TRENCHING, BACKFILLING, AND COMPACTION
Part 1 - GENERAL
1.01 DESCRIPTION
This section applies to excavating and backfilling for all underground utilities and their accessories.
1.02 GUARANTEE
Any backfill placed under this contract which subsides or settles below adjacent ground level during the guarantee period shall be brought to grade by the Contractor by adding compacted backfill or additional paving in paved areas.
1.03 PAYMENT
Payment for all work to be done under this section will be considered as included in the lump sum bid price as shown on the Bid Form. No other compensation will be allowed by the State.
Part 2 - PRODUCTS
2.01 BACKFILL
A. Select backfill shall be imported, clean sand that does not exceed 3/4 inches in any dimension, and be free from vegetable matter and debris.
B. Native backfill shall be either from the excavation or an approved source, free from rocks or clods larger than 6 inches, vegetable matter, and debris.
C. Select backfill for utility lines placed less than 18” deep shall be 2 sack cement-sand slurry with minimum a thickness of 4”.
Part 3 - EXECUTION
3.01 EXISTING FACILITIES
A. When existing facilities are shown on the drawings, their locations are approximate. The Contractor shall be responsible to verify the exact locations of existing facilities before beginning trenching operations.
B. The Contractor shall notify the State’s Representative 24 hours before anticipated interruptions to existing facilities are to occur.
Section 02221 - Page 2 Trenching, Backfilling, and Compaction
3.02 EXCAVATION
A. Trenching near pipelines, services, buildings, or structures shall be done using methods that will not result in damage to the pipelines, services, buildings, or structures. Damage caused by Contractor shall be repaired or replaced by the Contractor at Contractor’s expense and to the satisfaction of the State, including the disinfection of any damaged potable waterline.
B. In planted areas, care should be exercised to avoid unnecessary damage to ground cover or foliage. Any unnecessarily injured vegetation shall be re-established with like kind upon completion of backfill operations as directed by the State’s Representative.
C. Excavations adjacent to existing trees shall be made with all possible care to avoid injury to the trees and tree roots. Underground utility or waterlines which are to be sited far from a tree, at a distance greater than 5 times the diameter of that tree measured at breast height (4.5 feet above ground level), may be dug by trenching.
Where an underground utility or waterline to be sited in close proximity to a tree, at a distance less than 5 times the diameter of that tree measured at breast height (4.5 feet above ground level), all excavations shall be accomplished either by power auger tunneling between open trenches at a depth of 3 feet below ground level, or hand digging around roots.
All damaged roots in open trenches that exceed 1 inch in diameter shall be cut back to uninjured tissue. All open trenches beneath driplines shall be kept moist until backfilled.
All underground utility lines sited under existing roads may be excavated by trenching unless specified within the contract.
This section does not apply to palm trees.
D. The Contractor shall excavate only so far in advance of pipe laying as
State’s Representative shall permit.
E. The Contractor shall remove any water that may be found or accumulates in the trenches, and shall do all work required to keep clear of water while the utility is being installed and until final tests are completed.
F. There may be archeologically sensitive sites located within the trenching alignment. The State reserves the right to halt the Contractor’s trenching operation for up to 48 hours in order to investigate such sites should they be discovered. The Contractor shall give the State’s Representative
Section 02221 - Page 3 Trenching, Backfilling, and Compaction
72 hours advance notice prior to trenching through known archeologically sensitive areas, and shall complete trenching operations with due diligence to avoid excess exposure of any sites.
3.03 BACKFILL
A. Time intervals between excavation or trenching and backfilling operations shall be kept minimal; however, backfill shall not be placed until the work has been inspected, tested, and/or approved by the State’s Representative.
B. Backfill of trenches beneath the dripline of trees shall not be compacted, except as a road bed. Backfill shall be added in 8-inch layers and each layer shall be thoroughly saturated with water. This will stimulate new tree root growth into backfilled area.
C. After underground utility lines are in place, and testing has been approved, place and compact select material over the utility.
D. Compaction of the fill shall be made by tamping backfill in 8-inch layers or by other approved methods to obtain a relative compaction of at least 90 percent, determined by California Compaction Test Method No. 216 or 231.
C:\BASESPEC\02XXX\02221.DOC
06/10/97 3:00 PM
SECTION 02232
AGGREGATE BASE
Part 1 - GENERAL
1.01 DESCRIPTION
This work consists of furnishing, spreading, and compacting aggregate base in accordance with Section 26 of the Caltrans Standard Specifications with the following modifications.
1.02 PAYMENT
Payment for all work to be done under this section shall be considered as included in the lump sum bid items as shown on the Bid Form. No separate compensation will be allowed by the State.
Part 2 - PRODUCTS
2.01 AGGREGATE BASE
A. Class 2, 3/4-inch maximum.
B. Submit certificate of compliance from aggregate base supplier or other approved proof of compliance with contract requirements for aggregate base material to State’s Representative.
Part 3 - EXECUTION
3.01 AGGREGATE BASE
A. Spread the aggregate uniformly in conformance with Section 26-1.04 of the Caltrans Standard Specifications.
B. Compaction of aggregate base shall be in conformance with Section 26-
1.05 of the Caltrans Standard Specifications.
END OF SECTION
C:\BASESPEC\02XXX\02232.DOC
07/21/97 3:48 PM
SECTION 02574
UTILITY TRENCH RESURFACING
Part 1 - GENERAL
1.01 DESCRIPTION
Paving repair and resurfacing for utility trenches shall generally consist of placing asphalt concrete over compacted aggregate base on utility trench backfill as specified and to dimensions shown on plans as Class A1 Backfill.
1.02 PAYMENT
Payment for all work to be done under this section will be considered as included in the lump sum bid price as shown on the Bid Form. No other compensation will be allowed by the State.
Part 2 - PRODUCTS
2.01 TACK COAT
The tack coat shall be SS-1, SS-1h, CSS-1, or CSS-1h asphalt emulsion diluted with an equal part of water.
2.02 ASPHALT CONCRETE
A. Produce the asphalt concrete at a central plant.
B. Aggregate shall conform to the 1/2-inch maximum, grading, Type A or Type B as specified in Section 39-2.02, Caltrans Standard Specifications.
C. Asphalt binder shall be PG64-10, or equivalent, steam-refined asphalt conforming to Section 92 o fthe Caltrans Standard Specifications.
D. The amount of binder shall be 5 to 7 percent by weight of the dry aggregate as determined by the State’s Representative.
2.03 EQUIPMENT
Roller, pneumatic tampers or vibra-plate compactors.
Section 02574 - Page 2 Utility Trench Resurfacing (2-Inch AC Over Cement/Sand Slurry)
3.01 EXCAVATION
The asphalt concrete to be removed for the trench shall be saw cut. All AC edges to be trimmed neat and in straight lines. The edges of the remaining AC surfacing shall be clean and nearly vertical to receive a tack coat. Any AC broken during trenching or backfill will be removed so the resulting edges are again clean and nearly vertical.
3.02 PATCHING
A. All patches shall receive a tack coat around the perimeter of excavation.
The tack coat shall be very thin and uniformly cover the entire perimeter surface.
B. The mixture shall be deposited with a minimum of segregation and be free of lumps and pockets of segregated material. The asphalt concrete may be spread by any means to obtain the specified results.
C. Rake material to center of trench.
D. Place enough asphalt to leave the compacted surface 1/8-inch above the existing surface.
3.03 COMPACTING
A. The initial compaction shall be completed before the temperature of the asphalt concrete drops below 200 degrees F.
B. Compact perimeter of patch first.
C. Compaction shall be performed so that cracking, shoving, or displacement will be avoided.
D. Produce a finished surface free from ruts, bumps, depressions, or irregularities.
E. Three complete coverages by the roller or as specified by compaction equipment manufacturer.
C:\BASESPEC\02XXX\02574.DOC
08/01/97 1:51 PM
SECTION 02603
SEWAGE TREATMENT SYSTEM
Part 1 - GENERAL
1.01 DESCRIPTION
A. Work included in this section consists of furnishing and installing all components necessary for the complete treatment system included within these plans and specifications.
B. Qualification Certifications
a. Contractor must receive certification for the installation of engineered treatment systems as required by the manufacturer.
1.02 SUBMITTALS
Conform to Section 01300 of these specifications for all equipment and materials specified on the plans and specifications herein.
1.03 QUALITY ASSURANCE
The completed system shall be given an operational test of the entire system at completion to check for any deficiencies and for correct operation of the automatic control system and all auxiliary equipment.
1.04 PAYMENT
Payment for all work to be done under this section will be considered as included in the lump sum bid price as shown on the Bid Form. No other compensation will be allowed by the State.
Part 2 - PRODUCTS
A. TANKS
1. General:
The manufacturer shall provide the structural design and certification to the engineer for review. The design shall be in accordance with accepted engineering practice. Tanks shall have been designed by a registered engineer and approved by state or local regulatory agencies, or authorities.
a. Loading Criteria:
Section 02603 - Page 2 Sewage Treatment System
• There shall be 140 pcf for minimum weight of saturated backfill, or 127 pcf for unsaturated backfill (500 psf minimum).
• Minimum lateral loading shall be 62.4 pcf. Lateral loading shall be determined from ground surface.
• The tank shall also support a concentrated wheel load of 2500 lbs. or H-20 traffic loading (AASHTO)
b. Tanks requiring deep burial (>48") or subject to truck or heavy traffic loading require special consideration. (A minimum soil cover of 12 inches shall be used, unless specified otherwise by manufacturer.)
c. All tanks shall be structurally sound and watertight and shall be guaranteed in writing by the tank manufacturer for a period of one year from the date of final acceptance. Manufacturer’s signed guarantee shall accompany bids. The tank guarantee/warranty shall be furnished at the time of submittal. The tank shall be capable of withstanding long-term hydrostatic loading, in addition to the soil loading, due to a water table maintained at ground surface.
d. Tanks shall be manufactured and furnished with two access openings.
A minimum of 24 inches in diameter for general tank access and minimum 30 inches diameter for pump equipment access with the configuration shown on the manufacturer’s drawings. Modification of completed tanks will not be permitted.
e. Inlet plumbing shall include an inlet tee which penetrates 18 inches into the liquid from the inlet flow line. (The depth may vary depending on the tank’s height; in all cases, though, the inlet should extend to a level below the bottom of the maximum scum depth.) The inlet plumbing shall allow for natural ventilation back through the building sewer and vent stack. An effluent filter shall be installed on the effluent (outlet) side of the septic tank.
f. Tanks shall be capable of successfully withstanding an aboveground static hydraulic test and shall be individually tested.
g. Tanks shall be installed in strict accordance with all specifications noted on the plans and the manufacturer’s recommended installation instructions.
Fiberglass Septic Tank:
Fiberglass Septic tank shall have a capacity of 8,000 gallons with dimensions and specifications shown on plans, as manufactured by Custom Fiberglass Works, Fiber Enterprises Model FES-80, or engineered approved equal. All installation and underground anchoring
Section 02603 - Page 3 required shall be installed in accordance with manufactured as specified on plans and as required by engineering design. Tank shall include 24” min diameter access risers with covers for H20 traffic loading. Outlet tee designed to accommodate two (2) effluent filters, Zoeller WW4, or equal.
Concrete Dosing Chamber Tank:
Concrete Dosing Chamber tank shall be 3,000 gallon capacity with dimensions and specifications shown on plans, as manufactured by Cook Concrete, or equal. All installation and underground anchoring required shall be installed in accordance with manufactured as specified on plans and as required by engineering design. Tank shall include one (1) 24” min diameter access risers with covers for H20 traffic loading and one (1) 30” min access riser with covers for H20 traffic loading for equipment end (outlet).
Walls, bottom and top of reinforced concrete tanks shall be designed across the shortest dimension using one-way slab analysis. Stresses in each face of monolithically constructed tanks may be determined by analyzing the tank cross-section as a continuous fixed frame.
a. The walls and bottom slab shall be poured monolithically
b. Reinforcing steel shall be ASTM A-615 Grade 60, FY = 60,000 psi.
Details and placement shall be in accordance with ACI 315 and ACI 318.
c. Concrete shall be ready-mix with cement conforming to ASTM CI50, Type II. It shall have a cement content of not less than six (6) sacks per cubic yard and maximum aggregate size of 3/4-inch.
Water/cement ratio shall be kept low (0.35±), and concrete shall achieve a minimum compressive strength of 4000 psi in 28 days. The contractor shall submit a concrete mix design to the engineer for review and approval. Three (3) concrete sample cylinders shall be taken and tested until the manufacturer and engineer are satisfied that the minimum compression strength is being obtained. To ensure compliance, the manufacturer shall then make and set three (3) sample cylinders for a minimum of 20% of the remaining tanks at the discretion of the engineer. If the minimum compressive strength is not being obtained, the manufacturer shall be required to make the test sample cylinders for each tank manufactured. Calcium chloride will not be allowed in the mix design. The cost of testing cylinders shall be the tank manufacturer’s responsibility. The tank manufacturer may supply a Swiss hammer for compressive testing in the field in lieu of sample cylinders.
Section 02603 - Page 4
d. Form release used on tank molds shall be Nox Crete™ or equal.
Diesel or other petroleum products are not acceptable.
e. Tanks shall not be moved from the manufacturing site to the job site until the tank has cured for seven (7) days or has reached two-thirds of the design strength.
f. Tanks shall be manufactured and furnished with access openings of the size and configuration necessary to accommodate individual packaged pump systems.
g. The tank and the top slab shall be sealed with a preformed flexible plastic gasket. The flexible plastic gasket shall be equal to the flexible butyl resin sealant ConSeal™ CS-102 or CS-202 as manufactured by Concrete Sealants, Inc. of New Carlisle, Ohio, and shall conform to federal specification SS-S-00210(2iOA) and AASHTO M-198.
h. In order to demonstrate water tightness, tanks shall be tested at the site prior to acceptance. Inlets to the septic tank will be watertight pipe seal Cast-A-Seal™ (manufactured by Press-Seal Gasket Corporation) or approved equal. After installation is completed and before backfilling, each tank shall be filled with water to a point 2" above the top of the tank and the water loss measured after a 24-hour period.
After it has been determined that there is no leakage, test the access riser seam. Backfill to a minimum depth of 2" above the riser seam to prevent damage from hydrostatic uplift. Fill the tank to a point 2" above the riser seam (the field test period may be reduced to not less than two (2) hours). No tank will be accepted if there is any leakage over the two (2) hour period.
B. DOSING AND PUMPING SYSTEM EQUIPMENT:
All pumping systems shall be supplied by a reputable manufacturer with at least five years of experience in supplying equipment for effluent sewers. References must be available on request from the engineer. Systems shall be Zoeller Pumps Co, or engineer-approved equal, composed of:
1. Effluent Pumps:
Zoeller Pump Co., Model 163 series or engineer-approved equal, duplex ½ Hp, 115 VAC, single phase, 60 Hz, motor, with 10 foot long extra heavy duty (SO) electrical cord with ground. Pump shall be UL and CSA listed as an effluent pump. Includes Z-rail mounting system, effluent filter, discharge assembly and all appurtenances shown on plans and included in the manufacturer’s recommended pump system assembly.
2. Floats:
Zoeller Pump Co, four mechanical switch floats for the dose tank mounted per design plans. The floats must be adjustable and must be removable.
Section 02603 - Page 5
The variable float designations and levels shall be preset as shown in the engineer’s plans. Each float lead shall be secured with a nylon strain relief bushing at the splice box. The floats shall be UL or CSA listed.
3. Electrical Splice Box:
Splice box for pump lead splices and for float lead splices. Internal splice boxes or engineer-approved equal, UL approved for wet locations, equipped with up to six (6) electrical cord grips and a 1-inch outlet fitting. Also included shall be UL listed waterproof wire nuts. The use of a UL-Approved Conduit Seal Kit shall be required to prevent the passage of gases, vapors, or flames through the conduit.
4. Pressure Dosed Geotextile Sand Filter System Complete system components shall be shown and as specified on plans.
Modules shall be model B43 manufactured by Eljen Corporation, or equal Modules shall be 48” x 36” x 7” and installed per plans and specification with geotextile fabric designed and supplied by same manufacturer as part of the complete filter system. 4-way Distribution valve as shown and specified on plans shall be a 4-way mechanically driven distribution valve, Zoeller Automatic Multizone Valvemodel no. 6400 for 4-zone operation Contractor shall obtain all required certification from the manufacturer and provide proof to the State prior to installation of all Treatment System products
5. Plastic PVC force main piping, if necessary, shall be PVC schedule 80 or as otherwise specified on plans. All gravity sewer inlet sections and drains connections to tanks shall be PVC. SDR 35, manufactured by Certainteed Corporation, or equal or as otherwise specified on plans.
All other piping, valves, fittings, boxes and other accessories necessary for a complete treatment system shall be as specified on plans and Section 15010.
6. Controls and Alarms:
Controls and alarms shall be listed per UL 508. Panels shall be repairable in the field without the use of soldering irons or substantial disassembly.
Control Panel, mechanical floats and alarm accessories shall be “E PAK Control Panel” as specified on plans, or equal, or recommended for the pumps per manufacturer’s specifications, Zoeller Pump Co., or engineer-approved equal. System shall include the necessary manufacturer’s cable necessary to connect float system to panel and alarm lights per manufacturer and as shown and specified on plans.
Section 02603 - Page 6
3.01 INSTALLATION
Install the package lift station as per the manufacturer’s instructions and the contract plans and specifications.
SECTION 16000
ELECTRICAL
Part 1 - GENERAL
1.01 WORK INCLUDED
A. Provide all necessary work for electrical supply to new facility including control panel installation and connection to existing system, cable feeders conduits, wiring devices, and connections to other electrical equipment as shown and specified on plans.
B. Perform all site work, including trenching, excavating, and backfilling for conduits or other structures that are part of electrical work.
1.02 CODE RULES AND SAFETY REGULATIONS
Work installed or material used must comply with the latest rules of:
A. California Administrative Code, Title 24, Part 3, “Basic Electrical Regulations”, State Building Standards Electrical Code.
B. Underwriter’s Laboratories, Incorporated (UL) Standards.
C. National Electric Code.
1.03 INSPECTION AND TESTS
State will monitor any tests required and inspect the work as considered necessary during the course of construction and at completion of work. The Contractor shall furnish all necessary test equipment, facilities, and personnel required to perform tests as required by the State’s Representative.
1.04 SITE CONDITIONS
Make minor deviations found necessary during progress of construction to conform to actual locations. Existing electrical lines shown on the contract drawing have been taken from original plans and may have been installed differently, or may have been altered since the original construction work. In any case, the Contractor shall determine the routing of existing conduit runs and shall install the new wiring as required by existing conditions.
1.05 SEPARATION FROM OTHER UTILITIES
Unless otherwise indicated on the plans, separate wire and conduit runs not less than 12 inches from gas, water, or other utility lines. All conduits shall be run neatly and separately. No conduits shall be installed in the same trench as sewer lines.
Section 16000 - Page 2 Electrical
1.06 SUBMITTALS
Contractor shall submit copies of descriptive data for all equipment furnished and installed. Conform to Section 01300 of the General Requirements.
1.07 PAYMENT
Payment for all work to be done under this section will be considered as included in the lump sum bid price as shown on the Bid Form. No other compensation will be allowed by the State.
Part 2 - PRODUCTS
2.01 RIGID STEEL CONDUIT AND FITTINGS
Rigid steel conduit and coated rigid steel conduit shall be threaded, hot-dipped galvanized inside and outside.
Wrap steel conduit in concrete and at soil surface interface with Scotchrap, Permacel, or equal using 1/2 lap for double thickness.
2.02 PLASTIC CONDUIT, SWEEPS, AND FITTINGS
PVC Conduit: Schedule 80 rigid polyvinyl chloride electrical conduit, listing by UL for direct underground burial.
Couplings and bends shall conform to same requirements as rigid steel conduit.
Use solvent cement for all PVC joints, as recommended by conduit manufacturer.
2.03 FLEXIBLE STEEL CONDUIT AND FITTINGS
Weatherproof flexible steel conduit shall be galvanized steel core with a copper bonding conductor between the spiral segments and with an extruded synthetic jacket over all to insure a watertight conduit. The conduit shall be American Brass Company “Sealtite” Type UA, Electri-Flex Company “Liquadite” Type LA, or equivalent, with grounding-type fittings approved for this type of flexible conduit.
Section 16000 - Page 3
2.04 BREAKERS
A. Main Breaker to be installed into existing subpanel to service new treatment system control panel shall be of same manufacturer and model series as existing breakers previously installed. Breaker size shall be 230V – 40 Amp.
2.05 PRECAST CONCRETE BOXES
Precast concrete boxes shall be Brooks Products, Incorporated, Christy, or equivalent, of the sizes shown. Depth of boxes shall be as required to provide specified cover over conduits. Covers shall be traffic type.
Not less than 1 cubic foot of gravel shall be provided under box for drainage.
2.06 For Ordinary Dry and Wet Locations: All wire shall be copper, marked per UL and bearing their label.
A. Insulated conductors shall be copper, Type 90° RHW-2, THHW, RHH, or
XHHW insulation.
B. Ground Wire: Bare copper or Type TW with green color insulation copper
(for use as equipment ground).
2.07 WIRING MATERIALS
A. Connectors for Copper Conductors #10 AWG and Smaller:
1. Preinsulated Spring Pressure Type: Scotchlok Types Y, R, G, and B; Ideal “Wing Nut”, T and B Series PT, or equal.
2. Splice Cap Type: Uninsulated metal cap applied with proper indenter tool which provides deformation of cap in 2 directions at right angles to each other, Buchanan, or equal.
B. Connectors and Lugs for Copper Conductors #8 AWG and Larger:
Pressure or compression type, Burndy, Dossert, T and B, or equal.
C. Lugs for Parallel Conductors: Provide multiple lugs where parallel conductors are used.
E. Electrical Tapes:
1. Friction Tape: Per ASTM D69.
2. Rubber Tape: 0.030-inch thick, per ASTM D119.
Section 16000 - Page 4
3. Plastic Tape: 0.007-inch thick, minimum, 3M Company “Scotch” #33, Johns-Manville “Dutch Brand” #120, Plymouth “Slipknot” 3472, or equal.
F. Wire Markers: Self-adhesive, wrap around, cloth Type E-Z Code, Brady
“Perma Code”, or equal.
G. Color Code:
1. Color code all secondary branch circuit and feeder conductors as follows:
a. Two Wire Grounded System: One black, 1 white (neutral).
b. Three Wire, Single Phase, Grounded System: One black, 1 red, 1 white (neutral).
c. Three Wire, 3 Phase, Ungrounded Delta System: One black, 1 red, 1 blue.
d. Four Wire, 3 Phase Grounded Wye or Delta System: One black, 1 red, 1 blue, 1 white (neutral). For delta system, color highest voltage to neutral leg orange.
2. Use green color for any conductor intended solely for equipment grounding, unless it is bare.
3. Use self-adhesive wrap around, cloth type markers of solid colors to color code conductors.
4. Marking: In addition to color coding, identify circuits with premarked, self-adhesive, wrap around cloth type markers, as follows:
a. Where 2 or more branch circuits or control wires of same color pass through or terminate in same accessible location (panel board, junction box, outlet box, gutter, pull box, etc.), mark each appropriately to distinguish it from other others of same color. If wires are branch circuit conductors, then 1 white (neutral) conductor is present, mark each with all related circuit numbers.
Even if completely identified by color coding, mark all signal and control wires at all termination points in accordance with State approved schedules or wiring diagrams.
b. Permanently label all circuits in main panel with engraved phenolic labels. Install with bolts and nuts or rivets in a permanent manner. Gluing not acceptable.
Section 16000 - Page 5
2.08 GROUNDING
A. Ground clamps shall be of a type specifically designed for grounding purposes. Where ground conductor is in conduit, use ground clamp which grounds both conductor and conduit. Strap metal is not acceptable for grounding or bonding.
B. Ground rods shall be copper clad steel, 3/4-inch diameter by 10-feet long, unless otherwise shown.
3.01 GENERAL
A. Any exposed conduit shall be run parallel with, or at right angles to, framing members.
B. Good workmanship shall be evidenced in the installation of all electrical materials and equipment. Equipment shall be level, plumb, and true with the structure and other equipment. All materials shall be firmly secured in place and adequately supported and permanent.
3.02 BACKFILLING AND REPAIRS
A. Trenching and backfilling for electrical work shall be as specified under
Section 02221 and this section.
B. Do not place backfill until electrical work has been inspected and approved by State.
C. Cover non-metallic conduit not encased in concrete with a 3-inch layer of sand or other suitable material with 3/8-inch maximum rocks or clods.
D. Compact sand backfill by flooding or jetting. Do not place additional backfill until free water has dissipated.
Section 16000 - Page 6
E. Except where sand or select fill is required as specified above and except under paved areas, walks, or roads, use backfill of suitable excavated material with 2-inch maximum rocks or clods. If excavated material is unsuitable or inadequate for the backfill as specified, furnish and import from other than State sources additional suitable material to complete the project.
Compact the fill by adding backfill material in 8-inch maximum layers and tamping by hand or machine. Backfilling shall be done when the State’s Representative is present.
If required by the State’s Representative, the Contractor is responsible for providing certification of compaction by an Independent Certified Testing Laboratory.
F. Backfill for excavations under existing or proposed pavements, walks, roads, or similar surfaces shall be made with selected material placed in 8-inch maximum layers and compacted to obtain relative compaction of 90 percent minimum, as determined by Test Method California No. 216 of the California State Department of Transportation. Backfill material under pavements, walks, and roads shall be specified in Section 02221.
G. Remove shoring as backfill is placed. Remove from State property surplus material remaining after backfilling or place as directed by State.
H. In planted areas, replace or replant all shrubs or ground cover plants in kind.
I. Replace existing roads, walks, paving, or similar surfaces to match existing work, except material used shall not be of lesser quality than required for the same material in General Work Specifications, if such work is specified therein.
J. Bring to grade any subsidence occurring during the guarantee period by adding surfacing materials of like kind.
3.03 CUTTING, FRAMING, PATCHING
Cutting and patching of construction is to be done under this section of specifications.
Section 16000 - Page 7
3.04 CONDUIT SYSTEMS
A. General Requirements:
1. Install an accessible conduit system for connection of all junction boxes, etc.
2. For PVC conduits, maintain continuity of conduit system ground by installing copper grounding wire inside PVC conduit, per Title 24, CAC; ground this wire at each accessible location (manhole, pull box, cabinet, outlet, and junction box, etc.) and at each termination.
3. Route conduits to clear all access openings.
4. Where conduits pass through exterior concrete or masonry walls below grade, or through floor slab on fill below grade, make entrance watertight. Install pipe sleeves in concrete with 1/2-inch minimum clearance around conduit and caulk with oakum and mastic, or use gland type conduit entrance seal.
5. Underground conduits, which terminate inside building below grade, or which slope so that water might flow into building, shall be sealed at termination after installation of conductors. Install plugs or caps in spare (empty) conduits.
B. Bending:
1. Bends greater than 30 degrees for PVC conduit systems shall be factory made conduit bends.
2. Whenever possible, make bends for exposed stub-ups completely below the surface. Make stubs vertical and arrange neatly.
Field bending not…
This is the start of the file's text. The full file is on GovTribe.