C15D6 Stationary Generator Diesel Product data.pdf

PDF 297 KB Posted

Attached to
Cummins Generators Federal contract opportunity
Solicitation number
F3T3CE2126AW01
Issued by
Department of the Air Force Air Combat Command

About this file

This document contains a product specification sheet for Cummins diesel generator sets and an associated federal contract opportunity notice. The specification sheet provides technical details on Cummins C10D6 and C15D6 diesel generator sets including standby and prime ratings, cooling system specifications, enclosure designs, fuel tank options, control systems, and engine, alternator and electrical specifications. The related federal contract opportunity is seeking quotes for the acquisition of Cummins C20D6 and C15D6 diesel generator sets, as well as a Cummins transfer switch, to be awarded by the Department of the Air Force Air Combat Command. The solicitation number is provided along with requirement details and agency information.

View the file

Other files for this federal contract opportunity

Other files attached to Cummins Generators, newest first.
File Type Posted
Cummins Generators Sources Sought FY22.pdf PDF
OTECA70 Switch transfer Product Sheet Features.pdf PDF
OTECA70 Switch transfer Product Sheet.pdf PDF
C20D6 Stationary Generator Diesel Product data.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

power.cummins.com ©2017 Cummins Inc. | NAS-5871-EN (10/17)

Specification sheet

Diesel generator set

10 kW - 15 kW

EPA emissions stationary Standby

Description

Cummins generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary Standby applications.

Cooling system - Standard cooling package provides reliable running at up to 50 °C (122 °F) ambient temperature.

Enclosures - The aesthetically appealing enclosure incorporates special designs that deliver one of the quietest generators of its kind.

Aluminum material plus durable powder coat paint provides the best anti-corrosion performance. The generator set enclosure has been evaluated to withstand 180 MPH wind loads in accordance with ASCE7-10. The intelligent design has removable panels and service doors to provide easy access for service and maintenance.

Fuel tanks - Two dual wall sub-base fuel tank series are offered as optional features, providing economical and flexible solutions to meet extensive code requirements on diesel fuel tanks.

NFPA - The generator set accepts full rated load in a single step in accordance with NFPA 110 for Level 1 systems.

Warranty and service - Backed by a comprehensive warranty and worldwide distributor network.

Features

Kubota heavy-duty engine - Rugged 4-cycle, liquid-cooled, industrial diesel engine delivers reliable power, low emissions and fast response to load changes.

Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.

Control system - The PowerCommand 1.1 electronic control is standard equipment and provides total generator set system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance.

Model

Standby rating 60 Hz

Prime rating 60 Hz

Data sheets 60 Hz kW kVA kW kVA

C10 D6 10.0 12.5 9.1 11.4 NAD-5857

C15 D6 15.0 18.8 13.6 17.0 NAD-5858

Generator set specifications

Governor regulation class ISO8528 Part 1 Class G3

Voltage regulation, no load to full load ± 1.0%

Random voltage variation ± 1.0%

Frequency regulation Isochronous

Random frequency variation ± 0.25%

Radio frequency emissions compliance FCC code Title 47 Part 15 Class B

Engine specifications

Bore 87.0 mm (3.43 in.)

Stroke 92.4 mm (3.64 in.)

Displacement 1.65 litres (100.5 in

Configuration Cast iron, in-line, 3 cylinder

Battery capacity 550 amps at ambient temperature of 0 °F to 32 °F (-18 °C to 0 °C)

Battery charging alternator 40 amps

Starting voltage 12 volt, negative ground

Fuel system Indirect injection: low or ultra-low sulfur, number 2 diesel fuel

Fuel filter Single element, spin-on fuel filter with water separator

Air cleaner type Dry replaceable element

Lube oil filter type(s) Spin-on, full flow paper filter (cartridge type)

Standard cooling system 50 °C (122 °F) ambient cooling system

Alternator specifications

Design Brushless, 4 pole, drip proof, revolving field

Stator 2/3 pitch

Rotor Direct coupled, flexible disc

Insulation system Class H per NEMA MG1-1.65

Standard temperature rise 120 ºC (248 °F) Standby

Exciter type Torque match (shunt) with EBS as option

Alternator cooling Direct drive centrifugal blower

AC waveform Total Harmonic Distortion (THDV) < 5% no load to full linear load, < 3% for any single harmonic

Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43

Telephone Harmonic Factor (THF) 0.03

Available voltages

Single phase 3 phase

120/240 120/208 120/240 delta 277/480 347/600

Note: Consult factory for other voltages.

Generator set options Fuel system

Basic fuel tanks

Regional fuel tanks

Engine

Engine air cleaner – heavy duty

Shut down – low oil pressure

Extension – oil drain

Alternator

120 °C (248 °F) temperature rise alternator

105 °C (221 °F) temperature rise alternator

Excitation Boost System (EBS)

Alternator heater, 120 V

Control

AC output analog meters (bargraph)

Stop switch – emergency

Auxiliary output relays (2)

Auxiliary configurable signal inputs (8) and relay outputs (8)

Electrical

Single circuit breaker

Dual circuit breakers

80% rated circuit breakers

100% rated circuit breakers

Enclosure

Aluminum enclosure sound level 1 or level 2, with muffler installed, sandstone or green color

Open set

Cooling system

Shutdown – low coolant level

Warning – low coolant level

Extension – coolant drain

Cold weather options:

- <4 °C (40 °F) – cold weather

- <-17 °C (0 °F) – extreme cold weather

Exhaust system

Exhaust connector NPT

Open set with muffler mounted

Generator set application

Battery rack, larger battery

Radiator outlet duct adapter

Generator set options (continued) Warranty

Base warranty – 2 year, 1000 hour, Standby

Standby, 3 year, 1500 hour, parts

Standby, 5 year, 2500 hour, parts

Standby, 3 year, 1500 hour, parts and labor

Standby, 5 year, 2500 hour, parts and labor

Standby, 3 year, 1500 hour, parts, labor and travel

Standby, 5 year, 2500 hour, parts, labor and travel

Generator set accessories Extreme cold weather kit

Battery rack, larger battery

Battery heater kit

HMI211RS in-home display, including pre-configured 12” harness

HMI211 remote display, including pre-configured 12” harness

HMI220 remote display

Auxiliary output relays (2)

Auxiliary configurable signal inputs (8) and relay outputs (8)

Annunciator – RS485

Remote monitoring device – PowerCommand 500

Battery charger – stand-alone, 12 V

Circuit breakers

Enclosure Sound Level 1 to Sound Level 2 upgrade kit

Enclosure paint touch up kit

Mufflers – industrial, residential or critical

Alternator Excitation Boost System (EBS)

Alternator heater

Maintenance and service kit

Engine lift kit

Various fuel tanks and accessories

Control system PowerCommand 1.1

AC protection

Over current warning and shutdown

Over and under voltage shutdown

Over and under frequency shutdown

Over excitation (loss of sensing) fault

Field overload

Engine protection

Overspeed shutdown

Low oil pressure warning and shutdown

High coolant temperature warning and shutdown

Low coolant level warning or shutdown

Low coolant temperature warning

High, low and weak battery voltage warning

Fail to start (overcrank) shutdown

Fail to crank shutdown

Redundant start disconnect

Cranking lockout

Sensor failure indication

Low fuel level warning or shutdown

Alternator data

Line-to-Line and Line-to-Neutral AC volts

3-phase AC current

Frequency

Total kVa

Engine data

DC voltage

Lube oil pressure

Coolant temperature

Engine speed

PowerCommand control is an integrated generator set control system providing voltage regulation, engine protection, operator interface and isochronous governing (optional). Major features include:

Battery monitoring and testing features and smart starting control system.

Standard PCCNet interface to devices such as remote annunciator for NFPA 110 applications.

Control boards potted for environmental protection.

Control suitable for operation in ambient temperatures from - 40 °C to +70 °C (-40 °F to +158 °F) and altitudes to 5000 meters (13,000 feet).

Prototype tested; UL, CSA, and CE compliant.

InPower™ PC-based service tool available for detailed diagnostics.

Operator/display panel

Manual off switch

Alpha-numeric display with pushbutton access for viewing engine and alternator data and providing setup, controls and adjustments (English or international symbols)

LED lamps indicating generator set running, not in auto, common warning, common shutdown, manual run mode and remote start

Suitable for operation in ambient temperatures from -40 °C to +70 °C

Bargraph display (optional)

Other data

Generator set model data

Start attempts, starts, running hours

Fault history

RS485 Modbus interface

Data logging and fault simulation (requires InPower service tool)

Digital governing (optional)

Integrated digital electronic isochronous governor

Temperature dynamic governing

Digital voltage regulation

Integrated digital electronic voltage regulator

2-phase Line-to-Line sensing

Configurable torque matching

Control functions

Time delay start and cooldown

Cycle cranking

PCCNet interface

(2) Configurable inputs

(2) Configurable outputs

Remote emergency stop

Automatic Transfer Switch (ATS) control

Generator set exercise, field adjustable

Options

Auxiliary output relays (2)

Remote annunciator with (3) configurable inputs and

(4) configurable outputs

PMG alternator excitation

PowerCommand 500/550 for remote monitoring and alarm notification (accessory)

Auxiliary, configurable signal inputs (8) and configurable relay outputs (8)

Digital governing

AC output analog meters (bargraph)

- Color-coded graphical display of:

- 3-phase AC voltage

- 3-phase current

- Frequency

- kVa

Remote operator panel

Ratings definitions

Emergency Standby Power (ESP):

Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and

BS 5514.

Limited-Time Running Power (LTP):

Applicable for supplying power to a constant electrical load for limited hours. Limited-Time Running Power (LTP) is in accordance with ISO 8528.

Prime Power (PRP):

Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

Base Load (Continuous) Power (COP):

Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.

This outline drawing is for reference only. See respective model data sheet for specific model outline drawing number.

Do not use for installation design

For more information contact your local Cummins distributor or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.

NAS-5871-EN (10/17)

Model

Dim “A” mm (in.)

Dim “B” mm (in.)

Dim “C” mm (in.)

Set weight* dry kg (lbs)

Set weight* wet kg (lbs)

Open set

C10 D6 1670 (65.74) 864 (34) 1121 (44.13) 369 (816) 383 (847)

C15 D6 1670 (65.74) 864 (34) 1121 (44.13) 415 (918) 429 (949)

Sound attenuated enclosure Level 1

C10 D6 1830 (72) 864 (34) 1156 (45.5) 421 (931) 435 (962)

C15 D6 1830 (72) 864 (34) 1156 (45.5) 467 (1033) 481 (1064)

Sound attenuated enclosure Level 2

C10 D6 2075 (81.69) 864 (34) 1156 (45.5) 426 (942) 440 (973)

C15 D6 2075 (81.69) 864 (34) 1156 (45.5) 472 (1044) 486 (1075)

* Weights represent a set with standard features. See outline drawings for weights of other configurations.

Codes and standards Codes or standards compliance may not be available with all model configurations – consult factory for availability.

This generator set is designed in facilities certified to ISO 9001 and manufactured in facilities certified to ISO 9001 or

ISO 9002.

The generator set is available Listed to UL 2200, Stationary Engine Generator Assemblies.

The Prototype Test Support (PTS) program verifies the performance integrity of the generator set design. Cummins products bearing the PTS symbol meet the prototype test requirements of NFPA 110 for Level 1 systems.

U.S. EPA

Engine certified to U.S. EPA SI Stationary Emission Regulation 40 CFR, Part 60.

All low voltage models are CSA certified to product class 4215-01.

International Building Code

The generator set is certified for seismic application in accordance with International Building Code (IBC) 2012.

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device or after building main switch is open.

http://power.cummins.com/

File details come from the government source that posted it. Updated .