C04_Attachment 1_Salient Characteristics_1232SA26Q0552.docx

DOCX document 38 KB Posted

Attached to
Liebert Mini-Mate
Solicitation number
1232SA26Q0552
Issued by

About this file

This file is an attachment defining the salient characteristics and technical specifications for HVAC units required under a Request for Quotation (RFQ) issued by the Department of Agriculture Agricultural Research Service. The procurement (Solicitation Number 1232SA26Q0552) is for two Liebert MMD18A-PJE740AJN mini-mate units and one Liebert MMD36ENYJED40AE7 mini-mate unit with a PFH037A-YLN Prop Air Cooled Condensing Unit, classified as a supply purchase with no installation required. This is a small business set-aside acquisition under NAICS code 333415, with a small business size standard of 1,250 employees, and is a brand name or equal acquisition.

The two MMD18A-PJE740AJN units (1.5 tonnage each) must operate at 208/230 volts, 1 phase, 60 Hz with self-contained air-cooled systems featuring scroll compressors, hot gas bypass, two-speed blower assemblies, microprocessor controls, canister humidifiers (2.5 lbs/hr capacity), electric reheat, and compatibility with Liebert thermostat controls via the IS-UNITY-DP BMS monitoring solution. The single MMD36ENYJED40AE7 unit (3 tonnage) is a split system evaporator with MERV 8 box filter, two-speed blower, 4.3 lbs/hr canister humidifier, electric reheat, and the same Liebert control compatibility. The outdoor PFH037A-YLN condensing unit (3 tonnage) requires 208/230 volts, 3 phase, 60 Hz operation with a scroll compressor, hot gas bypass, and capability to operate in temperatures as low as -30°F. All units must maintain identical footprints to existing equipment, connect to existing ductwork and electrical points, and include freight and handling charges prepaid. Warranties must include a five-year compressor warranty and one-year entire unit parts warranty.

View the file

Other files

File Type Posted
C04_Sol_1232SA26Q0552.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 1 - Salient Characteristics

· New unit shall be documentable and a pre-approved equivalent to the following Liebert Units:

· MMD18A-PJE740AJN (Qty: 2)

· MMD36ENYJED40AE7 (Qty: 1) with PFH037A-YLN Prop Air Cooled Condensing Unit (Qty: 1)

· Units shall be shipped to site.

· Freight and handling charges shall be included in the estimate and be pre-paid.

· Unit footprint shall be the same size as the existing units. Units must connect at the same locations to existing duct work and electrical connections as specified in minimum technical specifications.

· Units shall interface with existing Liebert Thermostat Controls.

· Warranties shall include:

· Five-year compressor only warranty

· One-year entire unit parts warranty

The following are salient characteristics required for the units:

MMD18A-PJE740AJN

· Quantity: 2

· Tonnage: 1.5

· Input voltage of 208/230 Volts, 1 Phase, 60 Hz

· 208/30V, I/C Blower

· Self-contained air-cooled system with evaporator coil, compressor, filter drier, thermal expansion valve, R-407C refrigerant unit charge, high head pressure switch, hot gas bypass, two-speed blower assembly, and microprocessor control with audible and visual alarms

· Scroll Compressor

· Hot Gas Bypass

· Condenser Inlet duct connection for self-contained air cooled unit 425mm by 355mm.

· Electric Reheat

· Evaporator return (ducted only) 368mm by 457mm.

· Evaporator supply (ducted only) 279mm by 381mm.

· Total unit dimensions: 1422mm long, 686mm wide, 508mm tall.

· Canister Humidifier with a capacity of 2.5 lbs/hr

· Compliance with ASME A112.1.2 section 2.4.2 (backsiphonage testing)

· Remote Humidifier Contact

· Non-Locking Disconnect Switch

· Filter Clog Indicator

· High Temperature Sensor

· Must be compatible with Leibert thermostat controls via factory-installed IS-UNITY-DP BMS Monitoring Solution.

MMD36ENYJED40AE7 with PFH037A-YLN Prop Air Cooled Condensing Unit (see below)

· Quantity: 1

· Tonnage: 3 Ton

· Box Filter MERV 8 2/3T MM Evap

· PFH Condensing Unit

· Split System Evaporator

· Includes evaporator coil, filter drier, thermal expansion valve, two-speed direct drive internal blower, and microprocessor control with audible and visual alarms.

· Unit designed for R-407C and shall be field-charged

· Electric Reheat

· Canister Humidifier with a capacity of 4.3 lbs/hr

· Compliance with ASME A112.1.2 section 2.4.2 (backsiphonage testing)

· Remote Humidifier Contact

· Non-Locking Disconnect Switch

· Filter Clog Indicator

· High Temperature Sensor

· Must be compatible with Leibert thermostat controls via factory-installed IS-UNITY-DP BMS Monitoring Solution.

PFH037A-YLN Prop Air Cooled Condensing Unit

· Quantity: 1

· Tonnage: 3 Ton

· 208/230 Volts, 3 Phase, 60 Hz

· Outdoor Prop Fan Condensing Unit

· Scroll Compressor with Hot Gas Bypass Capacity Control

· High head pressure switch for system protection

· Starts & Operates at low outdoor temperatures down to -30°F

· Nitrogen holding charge (System is field-charged, with field-supplied R-407C refrigerant)

File details come from the government source that posted it. Updated .