Burn Bldg Addendum #1.pdf
PDF 3 MB Posted
- Solicitation number
- 75-12102024
- Issued by
- Alamance County, North Carolina
About this file
This document is an addendum for the ACC PSTC Burn Building project in Burlington, North Carolina, which is being managed by Alamance Community College. The addendum includes revisions to the site drainage plans, clarification on testing and inspection requirements, and coordination details for the upcoming site visit. The key modifications are the addition of a 3-foot wide concrete drainage channel around the structure, confirmation that the general contractor should perform fire training structure testing per the specifications, and details on the site visit scheduled for December 3, 2024 from 1pm-3pm.
The bid form includes unit pricing for unsuitable soil removal and replacement, as well as unit price allowances as described in the specifications. Bidders should review the revised civil drawings and specifications carefully. All construction must comply with applicable local, state, and OSHA standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ACC PSTC Burn Building Notice To Bidders.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM NO. 1
DATE OF ISSUE – November 22, 2024
ACC PSTC BURN BUILDING
ALAMANCE COMMUNITY COLLEGE
BURLINGTON, NORTH CAROLINA
PROJECT MANUAL
SCO ID# 19-21198-01C
Architect’s Project Number: 600646.1
Prepared by
MOSELEY ARCHITECTS
911 N. WEST STREET
SUITE #205
RALEIGH, NORTH CAROLINA 27603
ACC PSTC – BURN BUILDING ADDENDUM #1
212 STONE QUARRY ROAD, BURLINGTON NC 27258
November 22, 2024 ADDENDUM NO. 01 Page 1 of 1
GENERAL:
Planholders are requested to insert this Addendum in the front of their Project Manual. Inform all concerned that the Bidding Documents are modified by this Addendum.
The following modifications and clarifications are hereby made a part of the Bidding Documents and supersede or otherwise modify the provisions of the published Project Manual and Drawings, dated October 4, 2024; with Addendum No. 01, dated November 22, 2024.
Refer to the Drawings, Specification Sections, or other Documents, if any, attached to this Addendum, which are hereby made a part of this Addendum.
MODIFICATIONS TO Drawings ADDENDUM NO. 1:
Drawing Revisions:
1. Replace drawing C2.0 with the attached. Due to minimal slopes on asphalt drainage around structure, the drainage path is being revised to show as 3-ft wide shallow concrete drainage channel.
2. Replace Drawing C3.0 with the attached. The concrete detail has been updated to show a cross section for the proposed concrete drainage channel. Note: This does not change the alternate 1 request to pave all the areas with heavy duty concrete in lieu of the asphalt paving and shallow concrete channel.
Responses to Questions:
1. Spec 14000 - 1.08A notes that the Owner is carrying the testing for Special inspections and Section 312000 - 1.7C notes that the Owner is carrying sitework testing. Please confirm if the GC should include third party testing and labelling of the fire training structure per 133421 1.4H.
Response: GC should perform testing as described in 133421 1.4H
2. Please confirm if the bid form unit price for unsuitable soils should assume removal offsite or disposal on site and any replacement.
Response: Yes, please review section 012200 – Unit prices which describes this as removal off-site and replacement with off-site CABC stone.
3. 312000 – 1.10D.1 notes there are unit price allowances. Please clarify.
Response: Please review section 012200 unit prices and 012100 Allowances. Your allowance times your unit cost should be included in your bid.
4. Please confirm how to coordinate site visits.
Response: The site will be open to visitors Tuesday December 3, 2024 from 1pm-3pm. Parking is available at the training complex. Check in at the administration building.
GND
572.27'
W
W
W
W
W
W
W
W
W
W
W
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
W
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W W W W
W
W
W
W
W
W
W
W
W
W
W
W
W
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
UGT
UG
T
UG
T
UG
T
UG
T
UG
T
UG
T
W
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
UG
T
UG
T
UG
T
UG
T
UG
T
UGT
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W W W W
W
W
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
U G P
UG
P
U G P
U G P
UG
P
2.
N
9°
'1 2"
E
N61° 45' 50"E 181.34'
S79° 57' 19"E 62.00'
S1 0°
2'
1"
W
6.
BURLINGTON LAND
HOLDINGS, LLC
DB. 2998 P. 773
77.38 ACRES+-(BY
COORDINATES) 0.12+-
SQUARE MILES
CITY OF BURLINGTON
DB. 274 P. 333
EX. ASPHALT
PAVEMENT
EX. TRAINING
BUILDING
EX. CONCRETE
EX
. C
O N
C R
ET
E EX
. 8 " D
U C
TI
LE
IR
O
N
EX. E
DGE O
F
ASPHALT
EX. UNDERGROUND
TRAINING VAULTS
(NOT ACTIVE UTILITIES)
EX
. A
SP
HA
LT
D
RI
VE
EX. UNDERGROUND
TELEPHONE
EX.GRAVEL
TOP DITCH
BOTTOM
DITCH
EX. TRAINING
TOWER
EX
. F
EN
CE
EX
.S
AN
IT
AR
Y
SE
W
ER
EX. E
DGE O
F
ASPHALT
EX. LAWN
EX. LAWN
EX. LAWN
EX. WATER
VAULT
EX
. E
D G
E O
F
AS
PH
AL
T
EX
. E
D G
E O
F
AS
PH
AL
T
EX. E
DGE O
F
ASPHALT
EX. CONCRETE
EX.
CONC.
EX. UNDERGROUND
POWER
EX. TRAINING
BUILDING
EX. TELEPHONE
BOX
EX
. W
AT
ER
L
IN
E
EX
AC
T
SI
ZE
M
AT
ER
IA
L
UN
KN
OW
N
EX. WATER LINE EXACT SIZE &MATERIAL UNKNOWN
EX. LAWN
EX. WATER
METER
EX
.U
N D
ER
G
R O
U N
D P
R
IM
AR
Y
EX. HYDRANT
EX. GATE
VALVE
EX. PIPE AND
CONCRETE VAULT
EX. TRANSFORMER
BENCHMARK
N:853763.83 E:1887707.98
EX
. 8
" D U
C
TI
LE
IR
O N
EX
. 8
" D U
C
TI
LE
IR
O N
EX. GATE VALVE
EX. GATE VALVE
EX. HYDRANT
BURN TOWER
LEASE LOT
EX. TREE LINE
EX. TREE LINE
C O
N
ST
R U
C
TI
O N
L
IM
IT
S
C O
N
ST
R U
C
TI
O N
L
IM
IT
S
C O
N
ST
R U
C
TI
O N
L
IM
IT
S
CONSTR
UCTI
ON LI
MIT
S
EX
. E
D G
E O
F C
O N
C R
ET
E
EX.GRAVEL
EX. WATERLINE
(SIZE & MATERIAL
UNKNOWN)
N79° 57' 19"W 62.00'
N
° 0 2'
1"
E
6.
N:853849.62 E:1887867.73
FIRE TRAINING
TOWER
(SEE ARCH)
FFE=576.92
SIDE 'A'
SI
D
E 'B
SIDE 'C'
SI
D
E 'D
" D
IP
(C
HP
576.80'
EX. GND
575.45'
PROVIDE POSITIVE
DRAINAGE AROUND
STRUCTURE
PROVIDE POSITIVE
DRAINAGE AROUND
STRUCTURE
PROVIDE POSITIVE
DRAINAGE IN DITCH
PROVIDE POSITIVE
DRAINAGE IN DITCH
HP
575.04'
GND
574.65'
C3.0
C3.0
C3.0
C3.0
C3.0
ALT #1: PROVIDE
HEAVY DUTY
CONCRETE IN LIEU
OF ASPHALT
C3.0
C3.0
ALT #1: PROVIDE
HEAVY DUTY
CONCRETE IN LIEU
OF ASPHALT
C3.0
A
HYDRANT IMPROVEMENTS
UNDER SEPARATE
CONTRACT. COORDINATE
INSTALL PRIOR TO PAVING
B
C
PROVIDE 95%
COMPACTED
SUBGRADE
AROUND PIPE
C
-2.37%
-3.36%
-4 .4
4%
-3.42%
-4.17%
-3 .4
1%
-4.17%
-1 .7
1%
2' SHOULDER
AT 2%
1.5' SHOULDER
AT 2%
2' SHOULDER
AT 2%
A
A
A
ADJUST EXISTING MANHOLE LID AND
FRAME SO LID IS FLUSH IN PAVEMENT.
PROVIDE NON-SHRINK GROUT SO
THAT VAULT IS WATERTIGHT.
A
PROVIDE STAIRS
PER SPECIFICATION
SECTION 133421
D
D
D
D
D
C3.0
C3.0
C3.0
C3.0
PVMT
575.10'
PVMT
576.16'
PVMT
575.33'
PVMT
576.00'
ALT #1: PROVIDE
HEAVY DUTY
CONCRETE IN LIEU
OF ASPHALT
COORDINATE LAYDOWN AND
STORAGE AREAS WITH
OWNER AND SITE USERS
LP
573.60'
PVMT
575.15'
PVMT
575.05'
PVMT
574.75'
PVMT
574.85'
PROVIDE TOP OF
RIP RAP AT
FINISHED GRADE
(KEYED IN)
C3.0
C3.0
C3.0
3'
3'
CONCRETE FLUME
CONCRETE FLUME
CONCRETE FLUME
1. ALL CONSTRUCTION SHALL COMPLY WITH ALL APPLICABLE ALAMANCE
COUNTY, NCDOT AND OSHA STANDARDS AND SPECIFICATIONS.
2. ALL DIMENSIONS ARE TO FACE OF CURB, EDGE OF PAVEMENT, BUILDING
WALL FACE OR PROPERTY LINE, UNLESS OTHERWISE NOTED.
3. ALL RADII ARE DIMENSIONED FROM BACK OF CURB. IF NOT STATED, RADII
DIMENSION IS 5'.
4. FIELD VERIFY ALL DIMENSIONS, UTILITIES AND GRADES PRIOR TO
CONSTRUCTION. NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO
COMMENCING ANY RELATED CONSTRUCTION.
5. BE RESPONSIBLE WITH OFF-SITE DISPOSAL OF ALL WASTE MATERIALS
GENERATED DURING CONSTRUCTION AND FOR OBTAINING ALL
APPLICABLE PERMITS FOR OFF-SITE STOCKPILES AND/OR WASTE AREAS.
6. REPLACE ANY DAMAGED STRUCTURES, PAVING, UTILITIES, OR
LANDSCAPING DURING CONSTRUCTION. REPLACEMENT SHALL BE MADE
AT NO EXPENSE TO THE OWNER. REPAIRS MAY BE PERFORMED PER
ARCHITECT'S WRITTEN APPROVAL.
7. AT LEAST 72 HOURS PRIOR TO CONSTRUCTION OR EXCAVATION, NOTIFY
"NORTH CAROLINA ONE CALL" (811) OR (1-800-632-4949) TO HAVE EXISTING
UTILITIES LOCATED. ALL PRIVATE UTILITIES SHALL BE LOCATED AS
NEEDED BY A PRIVATE UTILITY LOCATE COMPANY AT NOT ADDITIONAL
COST TO OWNER.
8. ALL CURB AND GUTTER OFFSITE SHALL BE 24" WIDE UNLESS NOTED .
OTHERWISE
9. ALL DISTURBED CURB & GUTTER AND ASPHALT SHALL BE REPLACED PER
PROJECT DETAILS AND NCDOT STANDARDS AND SPECIFICATIONS.
10. RAISE ALL STRUCTURES AT NO ADDITIONAL COST TO THE OWNER SO
THAT THE TOP OF THE STRUCTURE EQUALS THE FINISH GRADE OF THE
FINISHED PAVEMENT.
11. COORDINATE THE PROJECT SCHEDULE WITH THE CIVIL ARCHITECT AND
OWNER IN ACCORDANCE WITH THE OWNER'S ONGOING ONSITE
OPERATIONS. ANY UTILITY INTERRUPTIONS SHALL BE COORDINATED
WITH THE OWNER AT LEAST 72 HOURS PRIOR TO THE INTERRUPTION.
12. PROVIDE A SMOOTH TRANSITION BETWEEN NEW ASPHALT AND EXISTING
ASPHALT SURFACES.
13. ALL SIDEWALKS ARE TO HAVE NO MORE THAN A 1:20 (5.0%) SLOPE FOR
THE LENGTH OF THE SIDEWALK AND NO MORE THAN A 1:50 (2.0%) SLOPE
FOR THE WIDTH OF THE SIDEWALK. NOTIFY ARCHITECT IF THIS CANNOT
BE ACHIEVED.
1. ALL CONSTRUCTION SHALL COMPLY WITH ALL APPLICABLE CITY OF
BURLINGTON , NCDOT AND OSHA STANDARDS AND SPECIFICATIONS.
2. COORDINATE THE PROJECT SCHEDULE WITH THE OWNER, AND
ADJACENT USERS OF THE PROPERTY. MAINTAIN TRAFFIC FLOW AND DO
NOT INTERRUPT UTILITIES AROUND THE SITE. DO NO DISTURB
OPERATIONS OF ADJACENT SITES AND FACILITIES AND/OR THEIR
OWNER'S ONGOING OPERATIONS.
3. ALL EXISTING VAULTS, MANHOLES, STORM DRAIN STRUCTURES, VALVE
BOXES, CLEANOUTS, AND ALL OTHER UTILITY STRUCTURES SHALL BE
ADJUSTED AS NEEDED TO MATCH FINISHED GRADE.
4. ALL BACKFILL, COMPACTION, AND ALL OTHER SOILS TESTING REQUIRED
TO VERIFY COMPLIANCE WITH THE CONSTRUCTION DRAWINGS SHALL BE
PERFORMED BY THE OWNER'S INDEPENDENT TESTING LABORATORY.
5. ALL SPOT ELEVATIONS INDICATED ARE AT TOP OF CURB UNLESS NOTED
OTHERWISE.
6. SPOT GRADE ABBREVIATIONS:
6.1. HP: HIGH POINT
6.2. LP: LOW POINT
6.3. FFE: FINISHED FLOOR ELEVATION
6.4. GND: FINISHED GROUND ELEVATION
6.5. PVMT: FINISHED PAVEMENT ELEVATION
6.6 EX. GND.: EXISTING GROUND
7. SPOT ELEVATIONS ARE GIVEN AT THE MAJORITY OF THE MAJOR BREAK
POINTS BUT IT SHOULD NOT BE ASSUMED THAT ALL NECESSARY SPOT
ELEVATIONS ARE SHOWN. DUE TO SPACE LIMITATIONS, THERE MAY BE
OTHER CRITICAL SPOTS NOT LABELED THAT SHOULD BE TAKEN INTO
CONSIDERATION. REVIEW THE GRADING PLAN IN DETAIL AND ENSURE
ALL CRITICAL GRADE POINTS ARE STAKED AND FOLLOWED TO PROVIDE
POSITIVE DRAINAGE. NOTIFY ARCHITECT IF ADDITIONAL POINTS ARE
NEEDED.
8. ALL ELEVATIONS ARE BASED ON NC GRID NORTH (NAD 83 2011).
9. CALL NC ONE CALL (811) TO LOCATE ALL UNDERGROUND UTILITIES.
PRIVATE UTILITIES SHALL BE LOCATED BY A PRIVATE LOCATE SERVICE
AT NO ADDITIONAL EXPENSE TO THE OWNER.
10. INSTALL ALL STORM SEWERS TO PROVIDE REQUIRED CLEARANCES TO
CROSSING UTILITIES AS INDICATED IN THE DRAWINGS AND
SPECIFICATIONS.
11. JOINT FILL AND CAULK EACH CONCRETE EXPANSION JOINT AND WHERE
CONCRETE PAVEMENT ABUTS OTHER PAVEMENTS, SIDEWALKS, OR HARD
SURFACES.
12. MAINTAIN ALL EROSION CONTROL DEVICES AFTER EACH RAINFALL
EVENT IN ACCORDANCE WITH NCDEQ LAND QUALITY REQUIREMENTS
AND AS DIRECTED BY THE NCDEQ AND CIVIL ARCHITECT.
13. FLUSH ALL SEDIMENT OUT OF STORM DRAINAGE PIPES AND
STRUCTURES FOLLOWING SITE STABILIZATION AND AT THE END OF
CONSTRUCTION. FLUSH OUT PIPES AS NEEDED THROUGHOUT
CONSTRUCTION TO MAINTAIN PROPER FUNCTIONING OF THE DRAINAGE
SYSTEM.
14. ALL SIDEWALKS ARE TO HAVE NO MORE THAN A 1:20 (5.0%) SLOPE FOR
THE LENGTH OF THE SIDEWALK AND NO MORE THAN A 1:50 (2.0%) SLOPE
FOR THE WIDTH OF THE SIDEWALK.
15. IF ANY DISCREPANCIES OF THE SLOPE REQUIREMENTS ABOVE ARE
FOUND, NOTIFY ARCHITECT PRIOR TO POURING ANY CONCRETE.
SITE LAYOUT NOTES
GRADING & DRAINAGE NOTES
ASPHALT PAVEMENT
HEAVY DUTY CONCRETE (BASE BID: CONCRETE
FLUME; ALT #1; ALL PAVING IN LIEU OF ASPHALT)
COORDINATE EXP. CONTROL JOINTS
STANDARD DUTY CONCRETE
GRADING & DRAINAGE KEY NOTES
TIE PAVEMENTS FLUSH WITH EXISTING
C3.0
C3.0
A
C3.0
TOWER FOUNDATION. SEE SPECIFICATION
SECTION 133421
B
PROVIDE CLASS A RIP RAP 12" THICK OVER
8-OUNCE NON-WOVEN WEED BARRIER
C
PROVIDE TALL FESCUE GRASS SEED IN
ALL DISTURBED AREAS
D
EROSION CONTROL WATTLE4
C3.0
STORM PIPE TABLE
PIPE #
PIPE 1
DIA
12"
FROM - TO
1 - 2
UPSTREAM
INVERT
373.60
DOWNSTREAM
INVERT
373.40
SLOPE
1.22%
LENGTH
16.40 LF
DESCRIPTION
12" DIP (C50)
N
AD
SCALE 1"=10'
20'10'
SITE, GRADING, &
PHASE 2 EROSION
CONTROL PLAN
C2.0
M O
SE
LE
YA
R
C H
IT
EC
TS
.C
O M
PROJECT NO:
DATE:
PH
O
N E
(9
) 8
-0
N
. W
ES
T
ST
R
EE
T, S
U
IT
E
R
AL
EI
G H
, N O
R
TH
C
AR
O
LI
N A
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
7/ 1/
:4
9:
A M
AL
AM
AN
CE
C
OM
MU
NI
TY
C
OL
LE
GE
AC
C P
ST
C -
BU
RN
BU
ILD
ING
2 S
TO
NE
Q
UA
RR
Y
RO
AD
, B
UR
LIN
GT
ON
, N C
-21
8-0
1C
600646.1
OCTOBER 4, 2024
REVISIONS
DATE DESCRIPTION
120 MOSAIC BLVD; SUITE 200-21
PITTSBORO, NC 27312
PHONE:(919)698-6883 | LICENSE: C-5114
WWW.FRANKLANDDESIGN.COM
11/22/2024 ADDENDUM 1
VICINITY MAP |1"=2000'
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text P
AutoCAD SHX Text W
AutoCAD SHX Text P
TYPICAL CONSTRUCTION JOINT
CONC SLAB THICKNESS = 7"
CABC THICKNESS = 6"
REINFORCEMENT = 6x6 - W2.9xW2.9
TYPICAL THICKENED EDGE
(ALL EDGES OF CONCRETE)
12" 6"
MIN
6"
CONCRETE PAVEMENT DIMENSIONS
1/4"
2"
8"
7" 6"
TYPICAL CONTROL JOINT
1/4"
JOINT
2"
4"
TYPICAL EXPANSION
JOINT
1/2"
JOINT
FULL
DEPTH
8"
DOWEL RODS = 18" #5 SMOOTH BARS
GREASED BOTH SIDES
NOTES:
1. ALL CONCRETE PAVEMENT SHALL HAVE A 28-DAY COMPRESSIVE STRENGTH OF 4,000 PSI MIN. (ASTM C39).
2. CONTROL JOINTS SHALL BE SPACED AT 8' O.C.E.W. MAX. OR AS INDICATED ON THE PLAN.
3. EXPANSION JOINTS SHALL BE SPACED AT 20' O.C.E.W. MAX. OR AS INDICATED ON THE PLAN AND WHERE
CONCRETE PAVEMENT ABUTS ANY RIGID OBJECT. CAULK ALL EXPANSION JOINTS WITH SELF LEVELING
CAULK.
4. INSTALL THICKENED EDGES ALONG ALL EDGES / SIDES OF CONCRETE PAVEMENT.
5. O.C.E.W. REFERS TO "ON CENTER EACH WAY".
6. HEAVY DUTY CONCRETE PAVEMENT: THE THICKENED EDGE SHOWN IN CONCRETE PAVEMENT DETAIL IS
REQUIRED WHERE THE CONCRETE MEETS THE ASPHALT, GRAVEL, CONCRETE MOW STRIPS, AND
UNBOUND EDGES. THE 6X6 - W2.9XW2.9 REINFORCEMENT SHOWN CAN BE OMITTED EXCEPT FOR
ODD-SHAPED SLABS AND SLABS CONTAINING STRUCTURES (LIGHTS, BOLLARDS, OR OTHER
STRUCTURES.). THE REINFORCEMENT IS TO MITIGATE CRACKING DUE TO STRUCTURES. #5 SMOOTH BARS
ARE TO BE USED AT THE CONSTRUCTION JOINTS AS NOTED IN THE DETAIL.
CONCRETE PAVEMENT SLAB
COMPACTED AGGREGATE BASE COURSE (CABC)
(SEE NCDOT SPECIFICATIONS)
COMPACTED SUBGRADE
1/4" WIDE x 2" DEEP
JOINT W/ 1/8" RADII
DOWEL ROD: 18" #5 SMOOTH BAR
18" O.C. GREASED BOTH SIDES.
1/4" WIDE x 2" DEEP
JOINT W/ 1/8" RADII.
SEAL WITH
PAVEMENT CAULK TO
1/8" BELOW
PAVEMENT ELEV
INSERT FABRIC JOINT
FILLER FULL DEPTH
PRIME COAT
ON STONE
(ADJACENT OTHER
HARD SURFACES
ONLY)
TACK
COAT
BETWEEN
LIFTS
SEE SITE PLAN
4"
1/4" PER FT CROSS SLOPE
1/4" WIDE x 1" DEEP
GROOVED JOINT
W/ 1/8" RADII
1/2" WIDE FULL-
DEPTH JOINT W/
1/8" RADII
JOINT FILLER
TO 1/4" FROM
SIDEWALK
SURFACE
TYPICAL CONTROL JOINT
NTS
TYPICAL EXPANSION JOINT
NTS
RIGID OBJECT
EXPANSION JOIINT
TYPICAL SIDEWALK SECTION
NTS
GENERAL NOTES:
1. PROVIDE GROOVE CONTROL JOINT 1-IN DEEP WITH 1/8-IN RADII IN SIDEWALK AT 5' INTERVALS UNLESS INDICATED
OTHERWISE.
2. PROVIDE 1/2-IN EXPANSION JOINT AT 50' INTERVALS.
3. PROVIDE 1/2-IN EXPANSION JOINT WHERE THE SIDEWALK ABUTS ANY RIGID STRUCTURE.
4. SEE SPECIFICATIONS FOR ADDITIONAL JOINT SPACING REQUIREMENTS.
5. ALL CONCRETE SHALL BE 3,000 P.S.I. WITH BROOM FINISH.
6. ALL CONCRETE SHALL HAVE 2% OR LESS CROSS SLOPE.
7. ALL CONCRETE SHALL HAVE 5% OR LESS LONGITUDINAL SLOPE.
8. ALL CONCRETE SHALL SLOPE AWAY FROM BUILDINGS OR STRUCTURES
COMPACTED SUBGRADE
4-IN STONE ABC SUBGRADE
PROFILE VIEW
FILTER FABRIC
OR DITCH LINER DITCHLINE
WOODEN STAKE WITH WATTLE
ANCHORED TO THE TOP
FLOW
DITCHLINE
FILTER FABRIC
OR DITCH LINER
WOODEN STAKE
8" FABRIC STAPLE
12" DIAMETER STRAW FILLED WATTLE
FASTENED TO WOODEN STAKE BY NAIL OR
STAPLE
18" 18"
6" COVER
12" DIAMETER STRAW FILLED WATTLE
NOTES:
1. WATTLES SHALL BE FILLED WITH STRAW OR OTHER APPROVED MATERIAL.
2. SPACING FOR WATTLES SHALL BE AS SHOWN ON EROSION CONTROL PLAN.
3. STAKE IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS.
4. THE SOCK SHALL BE PRODUCED FROM A 5 MIL THICK CONTINUOUS POLYPROPYLENE, WOVEN INTO A TUBULAR
MESH NETTING MATERIAL, WITH OPENINGS IN THE KNITTED MESH OF 1/8"TO 3/8" OPENINGS.
5. HARDWOOD 2"x2" STAKES SHALL BE DRIVEN THROUGH CENTER OF COMPOST SOCK AT 4' O.C. MAXIMUM
SPACING ANGLED UP SLOPE.
MAINTENANCE NOTES:
1. INSPECT COMPOST SOCKS WEEKLY AND AFTER EACH SIGNIFICANT RAINFALL EVENT (1/2 INCH OR GREATER).
2. REMOVE ACCUMULATED SEDIMENT AND ANY DEBRIS. THE COMPOST SOCK MUST BE REPLACED IF CLOGGED OR
TORN.
3. IF PONDING BECOMES EXCESSIVE, THE SOCK MAY NEED TO BE REPLACED WITH A LARGER DIAMETER OR A
DIFFERENT MEASURE.
4. THE SOCK NEEDS TO BE REINSTALLED IF UNDERMINED OR DISLODGED.
5. THE COMPOST SOCK SHALL BE INSPECTED UNTIL LAND DISTURBANCE IS COMPLETE AND THE AREA ABOVE THE
MEASURE HAS BEEN PERMANENTLY STABILIZED.
CROSS SECTION
N.T.S.2 HEAVY DUTY CONCRETE PAVINGASPHALT PAVEMENT N.T.S.1
NCDOT CABC STONE
INTERMEDIATE COURSE
TYPE I-19.0C (2018)
NOTES:
1. AS NEEDED, INSTALL INTERMEDIATE COURSES OF PAVEMENT TO STABILIZE THE SITE DURING
CONSTRUCTION. PROVIDED ADEQUATE THICKNESS PER NCDOT SPECIFICATIONS FOR INTERMEDIATE PAVING. ADDITIONAL INTERMEDIATE COURSE USED TO STABILIZE THE SITE SHALL BE PROVIDED AT
NO ADDITIONAL COST.
2. PROTECT PAVEMENT DURING ALL PHASES OF WORK. THE FINAL SURFACE OF PAVEMENT SHALL BE
FREE OF ALL DEFECTS OR DAMAGE. REPLACE ANY DAMAGED PAVEMENT AS DIRECTED BY
ARCHITECT.
4. ALL BACKFILL, COMPACTION, PAVEMENT DENSITY AND ALL OTHER SOILS OR MATERIAL TESTING REQUIRED TO VERIFY COMPLIANCE WITH THE CONSTRUCTION DRAWINGS SHALL BE PERFORMED BY THE OWNER'S INDEPENDENT TESTING AGENT. PROVIDE ADDITIONAL QC TESTING, PROOF ROLL, AND
REQUIREMENTS NOTED IN SPECIFICATIONS AT OWN DISCRETION.
5. OWNER WILL ACQUIRE 3RD PARTY QC TESTING SERVICES FOR SOILS AND PAVEMENTS.
6. REFER TO SPECIFICATION SECTION 321216 & 311000 FOR ADDITIONAL INFORMATION.
COMPACTION NOTES:
SUBGRADE AND ABC STONE
1. COMPACT TO MAXIMUM DRY DENSITY PER ASTM D698 STANDARD PROCTOR AND WITHIN 3%
MAXIMUM MOISTURE CONTENT.
2. COMPACT SUBGRADE SOIL TO 95%
3. COMPACT ABC STONE TO 100%.
4. REFER TO SPECIFICATION SECTION 31 10 00 FOR ADDITIONAL INFORMATION.
ASPHALT
1. COMPACT ASPHALT TO 92% MAXIMUM SPECIFIC GRAVITY.
2. REFER TO SPECIFICATION SECTION 32 12 16 FOR ADDITIONAL INFORMATION.
ASPHALT
PAVEMENT
4"
8"
CLASSIFICATION
PATTERN
KEYNOTE C8.0
SURFACE COURSE
TYPE S-9.5B (2018) 2"
GEOGRID (SEE ALLOWANCE)
COMPACTED SUBGRADE
N.T.S.4 EROSION CONTROL WATTLESSTANDARD DUTY CONCRETE N.T.S.3
CONCRETE FLUME
2" DEEP. CENTERLINE
GRADE PER PLANS
13"
12"
7"
3' OR AS SHOWN ON PLANS
ADJACENT PAVEMENTS
2% OR MATCH
ADJACENT
2% OR MATCH
ADJACENT
SITE DETAILS
C3.0
M O
SE
LE
YA
R
C H
IT
EC
TS
.C
O M
PROJECT NO:
DATE:
PH
O
N E
(9
) 8
-0
N
. W
ES
T
ST
R
EE
T, S
U
IT
E
R
AL
EI
G H
, N O
R
TH
C
AR
O
LI
N A
A
B
C
D
E
1 2 4 53 6 7 8 9 10
F
G
H
I
J
7/ 1/
:4
9:
A M
AL
AM
AN
CE
C
OM
MU
NI
TY
C
OL
LE
GE
AC
C P
ST
C -
BU
RN
BU
ILD
ING
2 S
TO
NE
Q
UA
RR
Y
RO
AD
, B
UR
LIN
GT
ON
, N C
-21
8-0
1C
600646.1
OCTOBER 4, 2024
REVISIONS
DATE DESCRIPTION
120 MOSAIC BLVD; SUITE 200-21
PITTSBORO, NC 27312
PHONE:(919)698-6883 | LICENSE: C-5114
WWW.FRANKLANDDESIGN.COM
11/22/2024 ADDENDUM 1
| ADD COVER |
| 600646.1 ADD01 |
| ACC Burn_Revised C2.0 |
| ACC Burn_Revised C3.0 |
File details come from the government source that posted it. Updated .