BROMFIELD ERV AC .pdf
PDF 2 MB Posted
- Attached to
- HVAC replacement
- Solicitation number
- BD-22-1623-HPS-CO-79759
- Issued by
- Worcester County, Massachusetts
About this file
This document is a set of drawings and technical specifications for the addition of an Energy Recovery Ventilator (ERV) HVAC system to the Science Classrooms at Bromfield High School in Harvard, Massachusetts. The project involves the installation of new mechanical, electrical, and controls equipment, including an air-cooled condensing unit, air handling unit, and associated ductwork, piping, and controls. The project drawings and specifications provide detailed information on the equipment, layout, and installation requirements.
The related state and local contract opportunity is for the replacement of two existing Heat Recovery Units (HRU-1 and HRU-2) at an unspecified location in Worcester County, Massachusetts. The successful bidder will be responsible for all subcontracted work related to roofing, electrical, and plumbing. No additional details are provided regarding pricing terms, set-asides, incumbent contractors, funding sources, or contract duration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Prevailing wage 9-21-2021.pdf | ||
| BROMFIELD ERV AC ~1.pdf | ||
| RFP HRU UPGRADE.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCIENCE CLASSROOM ERV AC ADDITION
HARVARD PUBLIC SCHOOLS
14 MASSACHUSETTS AVENUE
HARVARD, MASSACHUSETTS
01451
DRAWING LIST:
BROMFIELD HIGH SCHOOL
14 MASSACHUSETTS AVENUE
HARVARD, MASSACHUSETTS
01451
M1.0 Mechanical Roof New Work Plan
E0.1 Electrical Notes & Legend E1.0 Electrical Roof New Work Plan
T0.1 Title Sheet
M0.1 Mechanical Legend, Notes, & Abbreviations M0.2 Mechanical Schedules, Details, & Sequences
C
TITLE
AP
PR
. B Y
SH
T.
R
EF
DRAWING NO.
PROJECT
SI
ZE
CLIENT
CH'KD.
BY
APPR'D.
BY
BY
DRAWN
NAME
R
EV
. N o.
DESCRIPTION
DATE
C H
K.
B
Y
BLW Engineers, Inc.
e: info@blwengineers.com
311 Great Road, PO Box 1551 Littleton, Massachusetts 01460 t: 978.486.4301 f: 978.428.0067
DATE
3.
Harvard Public Schools 14 Mass Ave.
Harvard, MA 01451
Science Classroom ERV AC Bromfield High School
14 Massachusetts Ave, Harvard, MA
03.19.21
03.19.21
03.19.21
100%CD
TITLE SHEET
T0.1
KRB
KRB
DLC
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text F
AutoCAD SHX Text G
AutoCAD SHX Text H
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text HVAC * Electrical * Plumbing * Fire Protection
C
TITLE
AP
PR
. B Y
SH
T.
R
EF
DRAWING NO.
PROJECT
SI
ZE
CLIENT
CH'KD.
BY
APPR'D.
BY
BY
DRAWN
NAME
R
EV
. N o.
DESCRIPTION
DATE
C H
K.
B
Y
BLW Engineers, Inc.
e: info@blwengineers.com
311 Great Road, PO Box 1551 Littleton, Massachusetts 01460 t: 978.486.4301 f: 978.428.0067
DATE
3.
Harvard Public Schools 14 Mass Ave.
Harvard, MA 01451
Science Classroom ERV AC Bromfield High School
14 Massachusetts Ave, Harvard, MA
03.19.21
03.19.21
03.19.21
100%CD
MECHANICAL
LEGENDS, NOTES,
& ABBREVIATIONS
M0.1
KRB
KRB
DLC
AutoCAD SHX Text
CONTROL SCHEMATIC LEGEND
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text
TEMPERATURE SENSOR
AutoCAD SHX Text
HUMIDITY SENSOR
AutoCAD SHX Text
TIME CLOCK CONTROLLER
AutoCAD SHX Text
SWITCH CONTROLLER
AutoCAD SHX Text
HEAT/COOL THERMOSTAT
AutoCAD SHX Text
CONTROL LINE
AutoCAD SHX Text
PIPING LEGEND
AutoCAD SHX Text
TS
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text
REVERSE ACTING THERMOSTAT
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text
PIPE DOWN
AutoCAD SHX Text
PIPE UP
AutoCAD SHX Text
RUN-OUT OFF BOTTOM
AutoCAD SHX Text
RUN-OUT OFF TOP
AutoCAD SHX Text
PIPE OFF TOP
AutoCAD SHX Text
PIPE OFF BOTTOM
AutoCAD SHX Text
PIPE BREAK
AutoCAD SHX Text
RL
AutoCAD SHX Text
RL
AutoCAD SHX Text
REFRIGERANT LIQUID
AutoCAD SHX Text
RS
AutoCAD SHX Text
RS
AutoCAD SHX Text
REFRIGERANT SUCTION
AutoCAD SHX Text
DSD
AutoCAD SHX Text E1
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
AIR FLOW MEASURING STATION
AutoCAD SHX Text
ENTHALPY CONTROL
AutoCAD SHX Text F
AutoCAD SHX Text
FLOW RATE SENSOR
AutoCAD SHX Text
VFD
AutoCAD SHX Text
TS1
AutoCAD SHX Text
TEMPERATURE SENSOR
AutoCAD SHX Text
%%UAFS-
AutoCAD SHX Text
HS1
AutoCAD SHX Text
HUMIDITY SENSOR
AutoCAD SHX Text
FZ
AutoCAD SHX Text
FREEZESTAT
AutoCAD SHX Text
CO SENSOR
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO2
AutoCAD SHX Text
CO2 SENSOR
AutoCAD SHX Text
FLOW SWITCH
AutoCAD SHX Text
FS1
AutoCAD SHX Text
HIGH LIMIT THERMOSTAT
AutoCAD SHX Text
HLT
AutoCAD SHX Text
STATIC PRESSURE SENSOR
AutoCAD SHX Text
SP1
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
DPS
AutoCAD SHX Text
DIFFERENTIAL PRESSURE SENSOR
AutoCAD SHX Text
PRESSURE SENSOR
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISION CLOUD
AutoCAD SHX Text
DRAWING REVISION NOTE
AutoCAD SHX Text
DRAWING WORK NOTE
AutoCAD SHX Text
EXISTING SUPPLY/RETURN/EXHAUST/TRANSFER REGISTER
AutoCAD SHX Text
SRX, RRX, ERX, TRX
AutoCAD SHX Text
DRAWING NOTES
AutoCAD SHX Text
QUANTITY
AutoCAD SHX Text
NECK SIZE OR LENGTH IF LINEAR DIFFUSER
AutoCAD SHX Text
AIR VOLUME (CFM)
AutoCAD SHX Text 10"%%C, 12"x12" SG-A, RG-A or EG-A
AutoCAD SHX Text
200 CFM
AutoCAD SHX Text
(TYP. OF 3)
AutoCAD SHX Text
SUPPLY/RETURN/EXHAUST REGISTER OR GRILLE
AutoCAD SHX Text
QUANTITY
AutoCAD SHX Text
NECK SIZE OR LENGTH IF LINEAR DIFFUSER
AutoCAD SHX Text
AIR VOLUME (CFM)
AutoCAD SHX Text 12"x12", SD
AutoCAD SHX Text
200 CFM
AutoCAD SHX Text
(TYP. OF 3)
AutoCAD SHX Text
SUPPLY DIFFUSER DESIGNATION
AutoCAD SHX Text
EXPANSION TANK
AutoCAD SHX Text
EXHAUST AIR REGISTER
AutoCAD SHX Text
ER
AutoCAD SHX Text
ET
AutoCAD SHX Text
ELECTRIC UNIT HEATER
AutoCAD SHX Text
EUH
AutoCAD SHX Text
FINS PER INCH
AutoCAD SHX Text
FPI
AutoCAD SHX Text
FULL LOAD AMPS
AutoCAD SHX Text
FLA
AutoCAD SHX Text
FA
AutoCAD SHX Text
EXH
AutoCAD SHX Text
EXHAUST
AutoCAD SHX Text
FREE AREA
AutoCAD SHX Text
HOOD EXHAUST
AutoCAD SHX Text
GALLONS PER MINUTE
AutoCAD SHX Text
GENERAL EXHAUST
AutoCAD SHX Text
GENERAL CONTRACTOR
AutoCAD SHX Text
GC
AutoCAD SHX Text
GE
AutoCAD SHX Text
HE
AutoCAD SHX Text
GPM
AutoCAD SHX Text
HP
AutoCAD SHX Text
HORSE POWER
AutoCAD SHX Text
KILOWATTS
AutoCAD SHX Text
KW
AutoCAD SHX Text
ID
AutoCAD SHX Text
KE
AutoCAD SHX Text
IN
AutoCAD SHX Text
HVAC
AutoCAD SHX Text
HEATING, VENTILATION AND AIR CONDITIONING
AutoCAD SHX Text
INCHES
AutoCAD SHX Text
INSIDE DIAMETER
AutoCAD SHX Text
KITCHEN EXHAUST
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
MECH
AutoCAD SHX Text
LD
AutoCAD SHX Text
MBH
AutoCAD SHX Text
LWT
AutoCAD SHX Text
LAT
AutoCAD SHX Text
LEAVING AIR TEMPERATURE
AutoCAD SHX Text
LEAVING WATER TEMPERATURE
AutoCAD SHX Text
LOUVERED DOOR
AutoCAD SHX Text
THOUSANDS OF BRITISH THERMAL UNITS PER HOUR
AutoCAD SHX Text
FEET
AutoCAD SHX Text
COMBINATION FIRE AND SMOKE DAMPER
AutoCAD SHX Text
FEET PER MINUTE
AutoCAD SHX Text
FPM
AutoCAD SHX Text
FT
AutoCAD SHX Text
FSD
AutoCAD SHX Text
GAL
AutoCAD SHX Text
GALLONS
AutoCAD SHX Text
PRESSURE DROP
AutoCAD SHX Text
PD
AutoCAD SHX Text
PLUMBING CONTRACTOR
AutoCAD SHX Text
OUTSIDE DIAMETER
AutoCAD SHX Text
OPPOSED BLADE DAMPER
AutoCAD SHX Text
OBD
AutoCAD SHX Text
OD
AutoCAD SHX Text
PC
AutoCAD SHX Text
NC
AutoCAD SHX Text
NORMALLY CLOSED
AutoCAD SHX Text
OUTSIDE AIR TEMPERATURE
AutoCAD SHX Text
OAT
AutoCAD SHX Text
NTS
AutoCAD SHX Text
OA
AutoCAD SHX Text
NO
AutoCAD SHX Text
NIC
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text
NORMALLY OPEN
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
OUTSIDE AIR
AutoCAD SHX Text
EACH
AutoCAD SHX Text
EA.
AutoCAD SHX Text
DRAWING
AutoCAD SHX Text
DWG
AutoCAD SHX Text
ENERGY MANAGEMENT SYSTEM
AutoCAD SHX Text
EXHAUST AIR GRILLE
AutoCAD SHX Text
EG
AutoCAD SHX Text
EMS
AutoCAD SHX Text
ENTERING AIR TEMPERATURE
AutoCAD SHX Text
EXHAUST AIR
AutoCAD SHX Text
EA
AutoCAD SHX Text
EAT
AutoCAD SHX Text
DIGITAL OUTPUT
AutoCAD SHX Text
DO
AutoCAD SHX Text
DIA.
AutoCAD SHX Text
DN
AutoCAD SHX Text
DDC
AutoCAD SHX Text
DB
AutoCAD SHX Text
DRY BULB TEMPERATURE (%%DF)
AutoCAD SHX Text
DIRECT DIGITAL CONTROL
AutoCAD SHX Text
DIAMETER
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
COMBUSTION AIR
AutoCAD SHX Text
CA
AutoCAD SHX Text
CONTROL VALVE
AutoCAD SHX Text
CURRENT TRANSFORMER
AutoCAD SHX Text
CT
AutoCAD SHX Text
CV
AutoCAD SHX Text
CONTR
AutoCAD SHX Text
CONTRACTOR
AutoCAD SHX Text
CONNECT
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
CUBIC FEET PER MINUTE
AutoCAD SHX Text
CEILING DIFFUSER
AutoCAD SHX Text
CD
AutoCAD SHX Text
CFM
AutoCAD SHX Text
CONN.
AutoCAD SHX Text
CO
AutoCAD SHX Text
CAP
AutoCAD SHX Text
CAS
AutoCAD SHX Text
CAR
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
COMBUSTION AIR RELIEF
AutoCAD SHX Text
COMBUSTION AIR SUPPLY
AutoCAD SHX Text
BRITISH THERMAL UNIT PER HOUR
AutoCAD SHX Text
BRITISH THERMAL UNIT
AutoCAD SHX Text
BOTTOM OF DUCT
AutoCAD SHX Text
BOD
AutoCAD SHX Text
BTUH
AutoCAD SHX Text
BTU
AutoCAD SHX Text C
AutoCAD SHX Text
CLOSED
AutoCAD SHX Text
AUTOMATIC TEMPERATURE CONTROL
AutoCAD SHX Text
ATC
AutoCAD SHX Text
AP
AutoCAD SHX Text
ARCH.
AutoCAD SHX Text
AFF
AutoCAD SHX Text
AD
AutoCAD SHX Text
ACCESS DOOR
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
ACCESS PANEL
AutoCAD SHX Text
ARCHITECT
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
DRAIN
AutoCAD SHX Text
DR
AutoCAD SHX Text
FLOOR DRAIN
AutoCAD SHX Text
FLD
AutoCAD SHX Text
FRESH AIR INTAKE
AutoCAD SHX Text
FAI
AutoCAD SHX Text
COOLING COIL
AutoCAD SHX Text
CC
AutoCAD SHX Text
CONTROL PANEL
AutoCAD SHX Text
CP
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
EC
AutoCAD SHX Text
EXHAUST ROOF VENT
AutoCAD SHX Text
ERV
AutoCAD SHX Text
EXTERNAL STATIC PRESSURE
AutoCAD SHX Text
ESP
AutoCAD SHX Text
ENTERING WATER TEMPERATURE
AutoCAD SHX Text
EWT
AutoCAD SHX Text
HEATING COIL
AutoCAD SHX Text
HC
AutoCAD SHX Text
HOOD EXHAUST FAN
AutoCAD SHX Text
HEF
AutoCAD SHX Text
HOOD SUPPLY FAN
AutoCAD SHX Text
HSF
AutoCAD SHX Text
INTAKE HOOD
AutoCAD SHX Text
IH
AutoCAD SHX Text
VI
AutoCAD SHX Text
VIBRATION ISOLATION
AutoCAD SHX Text
HRU
AutoCAD SHX Text
HEAT RECOVERY UNIT
AutoCAD SHX Text
EQUIPMENT TAGS
AutoCAD SHX Text
STATIC PRESSURE
AutoCAD SHX Text
STAND ALONE DIGITAL CONTROLLER
AutoCAD SHX Text
SDC
AutoCAD SHX Text
SP
AutoCAD SHX Text
SPD
AutoCAD SHX Text
SPEED
AutoCAD SHX Text
SS
AutoCAD SHX Text
SR
AutoCAD SHX Text
SUPPLY AIR REGISTER
AutoCAD SHX Text
STAINLESS STEEL
AutoCAD SHX Text
SAT
AutoCAD SHX Text
SUPPLY AIR TEMPERATURE
AutoCAD SHX Text
SQUARE FEET
AutoCAD SHX Text
SF
AutoCAD SHX Text
TOILET EXHAUST
AutoCAD SHX Text
TE
AutoCAD SHX Text
TA
AutoCAD SHX Text
TD
AutoCAD SHX Text
SST
AutoCAD SHX Text
SATURATED SUCTION TEMPERATURE
AutoCAD SHX Text
TRANSFER AIR
AutoCAD SHX Text
TRANSFER AIR DUCT
AutoCAD SHX Text
TRANSFER AIR GRILLE
AutoCAD SHX Text
TG
AutoCAD SHX Text
TOILET EXHAUST FAN
AutoCAD SHX Text
TEF
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
VFD
AutoCAD SHX Text
WB
AutoCAD SHX Text
WET BULB TEMPERATURE (%%DF)
AutoCAD SHX Text
VB
AutoCAD SHX Text
VACUUM BREAKER
AutoCAD SHX Text
UC
AutoCAD SHX Text
UNDERCUT DOOR
AutoCAD SHX Text
WMS
AutoCAD SHX Text
WIRE MESH SCREEN
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
TYP
AutoCAD SHX Text
TSTAT
AutoCAD SHX Text
SUPPLY AIR
AutoCAD SHX Text
SA
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
1. MECHANICAL WORK INDICATED IS DIAGRAMMATIC. EXACT LOCATIONS OF ALL COMPONENTS ARE TO BE MECHANICAL WORK INDICATED IS DIAGRAMMATIC. EXACT LOCATIONS OF ALL COMPONENTS ARE TO BE DETERMINED IN THE FIELD (SPACING SUBJECT TO ARCHITECT'S REVIEW AND APPROVAL) TO AVOID CONFLICT WITH OTHER TRADES AND EXISTING SITE CONDITIONS. 2. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THE SITE TO IDENTIFY EXISTING CONDITIONS THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THE SITE TO IDENTIFY EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE WORK OF THIS SECTION. REPORT IN WRITING TO THE ARCHITECT CONDITIONS WHICH MIGHT ADVERSELY AFFECT WORK. NO EXTRA PAYMENT WILL BE CONDITIONS WHICH MIGHT ADVERSELY AFFECT WORK. NO EXTRA PAYMENT WILL BE PROVIDED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY AN EXPERIENCED OBSERVER. EXPERIENCED OBSERVER. 3. WORK REQUIRING INTERRUPTION OF BUILDING SERVICES SHALL BE CAREFULLY REVIEWED AND WORK REQUIRING INTERRUPTION OF BUILDING SERVICES SHALL BE CAREFULLY REVIEWED AND COORDINATED WITH THE OWNER TO MINIMIZE FREQUENCY AND DURATION OF SERVICE INTERRUPTIONS. 4. ALL INSTALLATIONS SHALL PERMIT AND PROVIDE ACCESSIBILITY FOR SERVICE AND REPLACEMENT OF ALL INSTALLATIONS SHALL PERMIT AND PROVIDE ACCESSIBILITY FOR SERVICE AND REPLACEMENT OF ALL NEW EQUIPMENT AND EXISTING EQUIPMENT IMPACTED BY THIS WORK. 5. COORDINATE ALL OPENINGS IN FLOORS WITH STRUCTURAL DRAWINGS AND GENERAL CONTRACTOR. COORDINATE ALL OPENINGS IN FLOORS WITH STRUCTURAL DRAWINGS AND GENERAL CONTRACTOR. 6. COORDINATE ALL ROOF OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER. COORDINATE ALL ROOF OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER. 7. REFER TO STRUCTURAL FRAMING PLANS FOR EXACT LOCATION OF ALL ROOF MOUNTED EQUIPMENT. REFER TO STRUCTURAL FRAMING PLANS FOR EXACT LOCATION OF ALL ROOF MOUNTED EQUIPMENT. 8. ALL MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF GOVERNING LOCAL, STATE, AND FEDERAL SEISMIC CODES. PARTICULAR ATTENTION SHALL BE MADE TO VIBRATION ISOLATION, ANCHORING, AND BALANCING REQUIREMENTS. 9. PROVIDE SMOKE DETECTORS AND SMOKE DAMPERS WHERE SHOWN ON THE MECHANICAL DRAWINGS. PROVIDE SMOKE DETECTORS AND SMOKE DAMPERS WHERE SHOWN ON THE MECHANICAL DRAWINGS. COORDINATE THE QUANTITY AND EXACT LOCATION WITH ACTUAL SHEET METAL SHOP DRAWINGS, TO BE PRODUCED BY MECHANICAL CONTRACTOR, AND APPROVED BY ENGINEER. PROVIDE SMOKE DETECTORS AND SMOKE DAMPERS IN BOTH SUPPLY AND RETURN DUCTS ON ALL AIR HANDLERS AS SHOWN IN MECHANICAL DRAWINGS. 10. ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH CODES AND STANDARDS SET FORTH IN ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH CODES AND STANDARDS SET FORTH IN NFPA, SMACNA, AND ASHRAE FOR MEDIUM AND LOW PRESSURE DUCTWORK SYSTEMS. 11. ALL DUCTS, PIPES, AND EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM THE BUILDING ALL DUCTS, PIPES, AND EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE WITH PROPER ALLOWANCES FOR CONTRACTION, EXPANSION, AND VIBRATION ELIMINATION. 12. PROVIDE COPPER 1" RUN-OUTS TO HOT WATER REHEAT COILS, CABINET HEATERS AND UNIT PROVIDE COPPER 1" RUN-OUTS TO HOT WATER REHEAT COILS, CABINET HEATERS AND UNIT HEATERS UNLESS NOTED OTHERWISE. 13. ROOM THERMOSTATS SHALL BE MOUNTED 4'-6" ABOVE FINISHED FLOOR UNLESS OTHERWISE SHOWN ROOM THERMOSTATS SHALL BE MOUNTED 4'-6" ABOVE FINISHED FLOOR UNLESS OTHERWISE SHOWN OR DIRECTED. 14. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR FREE AREA REQUIRED. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR FREE AREA REQUIRED. 15. ALL PIPING IS TO BE SLOPED A MINIMUM OF 1/4" PER HUNDRED FEET IN THE DIRECTION OF ALL PIPING IS TO BE SLOPED A MINIMUM OF 1/4" PER HUNDRED FEET IN THE DIRECTION OF DRAINAGE. 16. NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED ON THIS PROJECT. NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED ON THIS PROJECT. 17. COORDINATE ENTIRE INSTALLATION WITH THE WORK OF ALL OTHER TRADES PRIOR TO ANY COORDINATE ENTIRE INSTALLATION WITH THE WORK OF ALL OTHER TRADES PRIOR TO ANY FABRICATION OR INSTALLATIONS. 18. OBTAIN ALL REQUIRED PERMITS AND PAY ALL FEES RELATED TO SAME. OBTAIN ALL REQUIRED PERMITS AND PAY ALL FEES RELATED TO SAME. 19. ALL PIPING AND DUCTWORK SHOWN IS DIAGRAMMATIC ONLY. DETERMINE THE EXACT LOCATION IN ALL PIPING AND DUCTWORK SHOWN IS DIAGRAMMATIC ONLY. DETERMINE THE EXACT LOCATION IN THE FIELD. 20. REVIEW ALL ARCHITECTURAL, STRUCTURAL, PLUMBING, ELECTRICAL, FIRE PROTECTION AND SITE REVIEW ALL ARCHITECTURAL, STRUCTURAL, PLUMBING, ELECTRICAL, FIRE PROTECTION AND SITE DRAWINGS BEFORE STARTING ANY WORK TO BECOME FAMILIAR WITH THE DETAILS OF STARTING ANY WORK TO BECOME FAMILIAR WITH THE DETAILS OF CONSTRUCTION, AND COORDINATE WITH OTHER TRADES. 21. PROVIDE ALL NECESSARY PIPING, EQUIPMENT AND SUPPORTS AS WELL AS ANY ADDITIONAL PROVIDE ALL NECESSARY PIPING, EQUIPMENT AND SUPPORTS AS WELL AS ANY ADDITIONAL EQUIPMENT, ETC. NOT SHOWN ON THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS BUT NECESSARY TO PROVIDE COMPLETE AND WORKABLE SYSTEMS. 22. PROVIDE ACCESS TO ALL EQUIPMENT REQUIRING PERIODIC SERVICE AND MAINTENANCE. PROVIDE ACCESS TO ALL EQUIPMENT REQUIRING PERIODIC SERVICE AND MAINTENANCE. 23. DO NOT SCALE THESE DRAWINGS. TAKE ALL MEASUREMENTS IN THE FIELD IN COORDINATION WITH DO NOT SCALE THESE DRAWINGS. TAKE ALL MEASUREMENTS IN THE FIELD IN COORDINATION WITH ALL EQUIPMENT AS APPROVED AND WITH ALL OTHER TRADES. 24. FOR EQUIPMENT SCHEDULES, SEE M002. FOR EQUIPMENT SCHEDULES, SEE M002. 25. ALL ROTATING EQUIPMENT SHALL HAVE FLEXIBLE PIPE ON DUCT CONNECTIONS AND APPROVED ALL ROTATING EQUIPMENT SHALL HAVE FLEXIBLE PIPE ON DUCT CONNECTIONS AND APPROVED VIBRATION ISOLATORS. 26. DETAILS SHOWN ON DRAWING M003 & M004 ARE APPLICABLE TO ALL EQUIPMENT, EXCEPT WHERE DETAILS SHOWN ON DRAWING M003 & M004 ARE APPLICABLE TO ALL EQUIPMENT, EXCEPT WHERE INDICATED. 27. PROVIDE AIRTIGHT ACCESS DOOR FOR INSPECTION OF FIRE DAMPERS, FILTERS, AND COILS. PROVIDE AIRTIGHT ACCESS DOOR FOR INSPECTION OF FIRE DAMPERS, FILTERS, AND COILS. 28. CONTRACTOR SHALL VERIFY DUCT, PIPING AND EQUIPMENT LOCATIONS FOR INTERFERENCES BEFORE CONTRACTOR SHALL VERIFY DUCT, PIPING AND EQUIPMENT LOCATIONS FOR INTERFERENCES BEFORE INSTALLATION. 29. REFERENCE DRAWING M005 FOR SEQUENCE OF OPERATION OF NEW EQUIPMENT. REFERENCE DRAWING M005 FOR SEQUENCE OF OPERATION OF NEW EQUIPMENT. 30. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S WRITTEN ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.
AutoCAD SHX Text
EQUIPMENT DESIGNATION
AutoCAD SHX Text
%%UUH-1
AutoCAD SHX Text
EXISTING EQUIPMENT DESIGNATION
AutoCAD SHX Text
%%UUH-X
AutoCAD SHX Text
POUNDS PER SQUARE INCH
AutoCAD SHX Text
PSI
AutoCAD SHX Text
RA
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
RM
AutoCAD SHX Text
RH
AutoCAD SHX Text
RELIEF HOOD
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
ROOF EXHAUST FAN
AutoCAD SHX Text
REF
AutoCAD SHX Text
RETURN FAN
AutoCAD SHX Text
RF
AutoCAD SHX Text
RETURN AIR REGISTER
AutoCAD SHX Text
RR
AutoCAD SHX Text
AIR COOLED CONDENSING UNIT
AutoCAD SHX Text
ACCU
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text F
AutoCAD SHX Text G
AutoCAD SHX Text H
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AP
PR
. B Y
SH
T.
R
EF
DRAWING NO.
PROJECT
SI
ZE
CLIENT
CH'KD.
BY
APPR'D.
BY
BY
DRAWN
NAME
R
EV
. N o.
DESCRIPTION
DATE
C H
K.
B
Y
BLW Engineers, Inc.
e: info@blwengineers.com
311 Great Road, PO Box 1551 Littleton, Massachusetts 01460 t: 978.486.4301 f: 978.428.0067
DATE
3.
Harvard Public Schools 14 Mass Ave.
Harvard, MA 01451
Science Classroom ERV AC Bromfield High School
14 Massachusetts Ave, Harvard, MA
03.19.21
03.19.21
03.19.21
100%CD
MECHANICAL
SCHEDULES, DETAILS,
AND SEQUENCES
M0.2
KRB
KRB
DLC
AutoCAD SHX Text
HVAC SCHEDULES
AutoCAD SHX Text
HVAC SEQUENCES OF OPERATION
AutoCAD SHX Text
HVAC DETAILS
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
COMPRESSOR MTR
AutoCAD SHX Text
RLA / LRA
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
OPERATING
AutoCAD SHX Text
# / HP
AutoCAD SHX Text
VOLTS
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
CFM
AutoCAD SHX Text
PHASE
AutoCAD SHX Text SCT(%%dF)
AutoCAD SHX Text SST(%%dF)
AutoCAD SHX Text EAT(%%dF)
AutoCAD SHX Text
CONDENSER FAN
AutoCAD SHX Text
ELECTRICAL DATA
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
(AS STANDARD)
AutoCAD SHX Text MODEL No.
AutoCAD SHX Text
COOLING DATA
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
(AS STANDARD)
AutoCAD SHX Text
SERVED
AutoCAD SHX Text
LOCATION(S)
AutoCAD SHX Text TAG No.
AutoCAD SHX Text
COOLING
AutoCAD SHX Text
AIR COOLED CONDENSING UNIT SCHEDULE
AutoCAD SHX Text
MBH
AutoCAD SHX Text
ACCU-4
AutoCAD SHX Text
HRU-4
AutoCAD SHX Text
TECHNICAL
AutoCAD SHX Text
20A0LS13-1
AutoCAD SHX Text
AIR COOLED
AutoCAD SHX Text 139.2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HZ
AutoCAD SHX Text
AutoCAD SHX Text
MCA
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
EER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 10.88
AutoCAD SHX Text PROVIDE DISCONNECT SWITCH, LOW AMBIENT OPERATION, & EQUIPMENT STAND W/VIBRATION ISOLATION;
AutoCAD SHX Text
SIZE REFRIGERANT PIPE PER MANUFACTURER'S INSTALLATION INSTRUCTIONS
AutoCAD SHX Text
ACCU-5
AutoCAD SHX Text
HRU-5
AutoCAD SHX Text
20A0LS15-1
AutoCAD SHX Text
AIR COOLED
AutoCAD SHX Text 169.2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 11.11
AutoCAD SHX Text PROVIDE DISCONNECT SWITCH, LOW AMBIENT OPERATION, & EQUIPMENT STAND W/VIBRATION ISOLATION;
AutoCAD SHX Text
SIZE REFRIGERANT PIPE PER MANUFACTURER'S INSTALLATION INSTRUCTIONS
AutoCAD SHX Text
ABOVE GROUND
AutoCAD SHX Text
PIPE MATERIAL TABLE
AutoCAD SHX Text
REFRIGERANT PIPING RL & RS
AutoCAD SHX Text
COPPER - ARC
AutoCAD SHX Text
COPPER, NO LEAD
AutoCAD SHX Text
BRAZED
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
PIPING
AutoCAD SHX Text
FITTINGS
AutoCAD SHX Text
JOINTS
AutoCAD SHX Text
PIPE INSULATION TABLE
AutoCAD SHX Text
FOR PIPE DIA. (INCHES)
AutoCAD SHX Text 1-1/2"< %%C <4"
AutoCAD SHX Text
INSULATION WALL THICKNESS (INCHES)
AutoCAD SHX Text %%C < 1"
AutoCAD SHX Text %%C < 1-1/2"
AutoCAD SHX Text %%C > 4"
AutoCAD SHX Text
SERVICE/LOCATION
AutoCAD SHX Text
INSULATION TYPE
AutoCAD SHX Text
FITTING INSULATION TYPE
AutoCAD SHX Text
REFRIGERANT PIPING (COOLING ONLY)
AutoCAD SHX Text
ELASTOMERIC
AutoCAD SHX Text
ELASTOMERIC
AutoCAD SHX Text 1"
AutoCAD SHX Text 1"
AutoCAD SHX Text 1/2"
AutoCAD SHX Text 1/2"
AutoCAD SHX Text
AutoCAD SHX Text
OUTDOOR
AutoCAD SHX Text
AIR
AutoCAD SHX Text
ES
AutoCAD SHX Text
TS
AutoCAD SHX Text
AIR
AutoCAD SHX Text
EXHAUST
AutoCAD SHX Text
TS
AutoCAD SHX Text
APPLICATION
AutoCAD SHX Text
TO EMS
AutoCAD SHX Text
CONTROLLER
AutoCAD SHX Text
DM
AutoCAD SHX Text
FILTER
AutoCAD SHX Text
VFD
AutoCAD SHX Text
TS
AutoCAD SHX Text
AIR
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
SD
AutoCAD SHX Text
TS
AutoCAD SHX Text
ES
AutoCAD SHX Text
RETURN
AutoCAD SHX Text
AIR
AutoCAD SHX Text
SPECIFIC
AutoCAD SHX Text H
AutoCAD SHX Text
DX
AutoCAD SHX Text
LL
AutoCAD SHX Text
VFD
AutoCAD SHX Text
CO2
AutoCAD SHX Text T
AutoCAD SHX Text
SPACE SENSOR
AutoCAD SHX Text
CONSTANT VOLUME HEAT RECOVERY UNIT
AutoCAD SHX Text
APPLICATION TABLE
AutoCAD SHX Text
HRU-4/5 & ACCU-4/5
AutoCAD SHX Text HRU-4&5 ARE EXISTING AND WERE INSTALLED WITH SPLIT DX COOLING COILS. THE BELOW SEQUENCE IS TO ADD CONTROL OF THE NEW SPLIT CONDENSING UNITS DURING COOLING OPERAITON. THE HEAT RECOVERY UNIT SHALL BE CONTROLLED THROUGH THE EMS SYSTEM. THE SEQUENCE LISTED BELOW IS REVERSIBLE UNLESS NOTED OTHERWISE. OCCUPIED HOURS: : THE HEAT RECOVERY UNIT SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE HEAT RECOVERY UNIT SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE HEAT RECOVERY UNIT SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE RECOVERY UNIT SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE RECOVERY UNIT SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE UNIT SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE UNIT SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE SUPPLY FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE CONTINUOUSLY; THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE THE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE UNIT'S EXHAUST FAN SHALL BE ENERGIZED AND OPERATE EXHAUST FAN SHALL BE ENERGIZED AND OPERATE EXHAUST FAN SHALL BE ENERGIZED AND OPERATE FAN SHALL BE ENERGIZED AND OPERATE FAN SHALL BE ENERGIZED AND OPERATE SHALL BE ENERGIZED AND OPERATE SHALL BE ENERGIZED AND OPERATE BE ENERGIZED AND OPERATE BE ENERGIZED AND OPERATE ENERGIZED AND OPERATE ENERGIZED AND OPERATE AND OPERATE AND OPERATE OPERATE OPERATE CONTINUOUSLY; THE UNIT'S HEAT RECOVERY WHEEL SHALL BE ENERGIZED AND OPERATE CONTINOUSLY. THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SUPPLY AIR TEMPERATURE SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS AIR TEMPERATURE SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS AIR TEMPERATURE SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS TEMPERATURE SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS TEMPERATURE SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SETPOINT SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SHALL BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS BE RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS RESET FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS FROM ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS ITS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS MINIMUM SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SETPOINT, 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS 55°F (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS (ADJUSTABLE) TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS TO ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS ITS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS MAXIMUM SETPOINT, 95°F (ADJUSTABLE), AS SETPOINT, 95°F (ADJUSTABLE), AS SETPOINT, 95°F (ADJUSTABLE), AS 95°F (ADJUSTABLE), AS 95°F (ADJUSTABLE), AS (ADJUSTABLE), AS (ADJUSTABLE), AS AS AS REQUIRED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT, 75 F (ADJUSTABLE) IN COOLING MODE AND 68 F (ADJUSTABLE) IN HEATING MODE. IF HEATING IS REQUIRED, THE HEATING TWO WAY CONTROL VALVE SHALL MODULATE OPEN AS REQUIRED TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF COOLING IS REQUIRED AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR COOLING IS REQUIRED AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR COOLING IS REQUIRED AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR IS REQUIRED AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR IS REQUIRED AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR REQUIRED AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR REQUIRED AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR AND THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THE EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR EXHAUST AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR AIR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR ENTHALPY IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR IS HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR HIGHER THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THAN THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THE OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR OUTDOOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR TEMPERATURE, THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR THE HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR HEAT RECOVER WHEEL SHALL BE DEENERGIZED FOR RECOVER WHEEL SHALL BE DEENERGIZED FOR RECOVER WHEEL SHALL BE DEENERGIZED FOR WHEEL SHALL BE DEENERGIZED FOR WHEEL SHALL BE DEENERGIZED FOR SHALL BE DEENERGIZED FOR SHALL BE DEENERGIZED FOR BE DEENERGIZED FOR BE DEENERGIZED FOR DEENERGIZED FOR DEENERGIZED FOR FOR FOR ECONOMIZER OPERATION. IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF OPERATION. IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF OPERATION. IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF FURTHER COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF COOLING IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF IS REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF REQUIRED, THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF THE STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF STAGES OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF OF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF DX COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF COOLING SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. IF THE SUPPLY AIR TEMPERATURE SETPOINT. IF THE SUPPLY AIR TEMPERATURE SETPOINT. IF SUPPLY AIR TEMPERATURE SETPOINT. IF SUPPLY AIR TEMPERATURE SETPOINT. IF AIR TEMPERATURE SETPOINT. IF AIR TEMPERATURE SETPOINT. IF TEMPERATURE SETPOINT. IF TEMPERATURE SETPOINT. IF SETPOINT. IF SETPOINT. IF IF IF IF THE EXHAUST AIR ENTHALPY IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL EXHAUST AIR ENTHALPY IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL EXHAUST AIR ENTHALPY IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL AIR ENTHALPY IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL AIR ENTHALPY IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL ENTHALPY IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL ENTHALPY IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL IS LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL LOWER THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL THAN THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL THE OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL OUTDOOR AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL AIR ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL ENTHALPY, THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL THE HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL HEAT RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL RECOVERY WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL WHEEL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL WILL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL BE ENERGIZED AND THE STAGES OF DX COOLING SHALL ENERGIZED AND THE STAGES OF DX COOLING SHALL ENERGIZED AND THE STAGES OF DX COOLING SHALL AND THE STAGES OF DX COOLING SHALL AND THE STAGES OF DX COOLING SHALL THE STAGES OF DX COOLING SHALL THE STAGES OF DX COOLING SHALL STAGES OF DX COOLING SHALL STAGES OF DX COOLING SHALL OF DX COOLING SHALL OF DX COOLING SHALL DX COOLING SHALL DX COOLING SHALL COOLING SHALL COOLING SHALL SHALL SHALL OPERATE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT. DEFROST CONTROL SHALL BE PROVIDED THROUGH THE UNIT'S PACKAGED CONTROLS. UNOCCUPIED HOURS: THE HEAT RECOVERY UNIT SUPPLY AND RETURN FANS SHALL BE DEENERGIZED; THE TWO WAY CONTROL VALVE SHALL BE OPEN; THE OUTDOOR AIR, RETURN AIR, AND EXHAUST AIR DAMPERS SHALL BE IN THE 100 PERCENT RETURN POSITION. HEATING AND COOLING SHALL BE LOCKED OUT DURING UNOCCUPIED HOURS. WHEN A FREEZESTAT SENSES A LOW TEMPERATURE CONDITION AND/OR A SMOKE DETECTOR SENSES A SMOKE CONDITION, THE UNIT SUPPLY AND RETURN FANS SHALL BE DEENERGIZED; THE TWO WAY CONTROL VALVE SHALL BE OPEN; AND THE APPROPRIATE ALARM SIGNAL SHALL BE TRANSMITTED TO THE EMS.
AutoCAD SHX Text
CONSTANT VOLUME HEAT RECOVERY UNIT SEQUENCE OF OPERATION
AutoCAD SHX Text
%%UACCU
AutoCAD SHX Text
ACCU-4
AutoCAD SHX Text
FROM UNIT(S)
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
REF LIQUID
AutoCAD SHX Text
REFRIGERANT PIPE SIZE TABLE
AutoCAD SHX Text
TO UNIT(S)
AutoCAD SHX Text
HRU-4
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
CONDENSATE DRAIN
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
REF SUCTION
AutoCAD SHX Text
1. CONTRACTOR SHALL PROVIDE REFRIGERANT PIPE FROM AIR COOLED CONDENSING UNITS TO EXISTING HRU'S. CONTRACTOR SHALL PROVIDE REFRIGERANT PIPE FROM AIR COOLED CONDENSING UNITS TO EXISTING HRU'S. 2. CONTRACTOR SHALL VERIFY REFRIGERANT PIPE SIZE WITH MANUFACTURER PRIOR TO INSTALLATION.CONTRACTOR SHALL VERIFY REFRIGERANT PIPE SIZE WITH MANUFACTURER PRIOR TO INSTALLATION.
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text 1-3/8"
AutoCAD SHX Text 7/8"
AutoCAD SHX Text
AutoCAD SHX Text 1-3/8"
AutoCAD SHX Text 7/8"
AutoCAD SHX Text
AutoCAD SHX Text
HRU-5
AutoCAD SHX Text
ACCU-5
AutoCAD SHX Text
TYPICAL REFRIGERANT PIPING INSULATION DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
ONE-PIECE CLOSED CELL, ELASTOMERIC
AutoCAD SHX Text
OR PVC PIPE INSULATION
AutoCAD SHX Text
PROVIDE WITH UV RESISTANT
AutoCAD SHX Text
JACKET OR PIPE GUARD WHERE
AutoCAD SHX Text
REFRIGERANT PIPE
AutoCAD SHX Text
REFRIGERANT PIPE
AutoCAD SHX Text
(OVERLAP ALL JOINTS, AND SEAL
AutoCAD SHX Text
PER INSULATION MANUFACTURER'S
AutoCAD SHX Text
INSTRUCTIONS)
AutoCAD SHX Text
EXPOSED TO ATMOSPHERE
AutoCAD SHX Text
(OVERLAP AND SEAL ALL JOINTS)
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
COIL
AutoCAD SHX Text
(OUTDOOR UNIT)
AutoCAD SHX Text
ACCU
AutoCAD SHX Text
TO ROOF
AutoCAD SHX Text
A.C. CONDENSATE DRAIN
AutoCAD SHX Text
SEE NOTE 5
AutoCAD SHX Text
(TYP.)
AutoCAD SHX Text
CONN.
AutoCAD SHX Text
FLEX.
AutoCAD SHX Text
POWER WIRING TO HP BY E.C. SEE NOTE 5.
AutoCAD SHX Text
A. %%USINGLE FEED SYSTEM
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
PREFAB. EQUIPMENT
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
EVAPORATOR
AutoCAD SHX Text
RS
AutoCAD SHX Text
RL
AutoCAD SHX Text
THERMAL EXPANSION
AutoCAD SHX Text
VALVE AND DISTRIBUTOR
AutoCAD SHX Text
BY COIL MANUFACTURER
AutoCAD SHX Text
REFRIGERANT
AutoCAD SHX Text
VALVE (TYPICAL)
AutoCAD SHX Text
FILTER/DRIER
AutoCAD SHX Text
SIGHT GLASS-
AutoCAD SHX Text
MOISTURE INDICATOR.
AutoCAD SHX Text THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR POWER WIRING TO THE ACCU UNIT, FUSED DISCONNECT AND WIRING TO THE ACCU. THE LOW OR LINE VOLTAGE CONTROL/FAN POWER WIRING BETWEEN THE ACCU AND THE GF UNIT SHALL BE PROVIDED BY THE ATC CONTRACTOR.
AutoCAD SHX Text
1. SIZE PIPING PER EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. 2. ALL INTERIOR PIPING SHALL BE CONCEALED IN CEILINGS AND WALLS. 3. FURNISH AND INSTALL ALL REFRIGERANT VALVES AND SPECIALTIES REQUIRED BY MANUFACTURER. 4. PROVIDE WEATHERTIGHT SEAL AT ALL PIPING PENETRATIONS. COORDINATE PENETRATIONS WITH G.C. AND ALL ASSOCIATED TRADES AS REQUIRED. 5. SPLIT SYSTEM MANUFACTURERS UTILIZE DIFFERENT WIRING CONFIGURATIONS. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE THE WIRING REQUIREMENTS OF THE SHOP DRAWING APPROVED EQUIPMENT WITH THE ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
SPLIT SYSTEM PIPING DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
(PROVIDED FOR HRU)
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
PREFAB. EQUIPMENT
AutoCAD SHX Text
10" MIN.
AutoCAD SHX Text
18" MIN.
AutoCAD SHX Text
ROOF
AutoCAD SHX Text
CHANNEL
AutoCAD SHX Text
GALVANIZED
AutoCAD SHX Text
SUPPORT REFER TO DETAIL
AutoCAD SHX Text
PREFABRICATED EQUIPMENT
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
FOR PIPE EXPANSION.
AutoCAD SHX Text
1" SPACE EACH SIDE
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text 1/2 SECTION x 10"L
AutoCAD SHX Text
LOAD BEARING. INSULATE PER
AutoCAD SHX Text
SPECIFICATION (TYPICAL)
AutoCAD SHX Text 120%%d, 14 GA, 8"L
AutoCAD SHX Text
SHEETMETAL. SADDLE
AutoCAD SHX Text
LOCK NUT
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
LOCK NUT
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
FREE TO SLIDE
AutoCAD SHX Text
ON ROD
AutoCAD SHX Text
BARRIER (TYPICAL)
AutoCAD SHX Text
CONTINUOUS VAPOR
AutoCAD SHX Text 7/8"%%c RODS (TYPICAL)
AutoCAD SHX Text
INSULATE PER SPECIFICATION
AutoCAD SHX Text
PIPE GUIDE
AutoCAD SHX Text
(TYPICAL)
AutoCAD SHX Text
ROOF PIPE SUPPORT
AutoCAD SHX Text
SYSTEMS
AutoCAD SHX Text
TECHNICAL
AutoCAD SHX Text
SYSTEMS
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text F
AutoCAD SHX Text G
AutoCAD SHX Text H
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AP
PR
. B Y
SH
T.
R
EF
DRAWING NO.
PROJECT
SI
ZE
CLIENT
CH'KD.
BY
APPR'D.
BY
BY
DRAWN
NAME
R
EV
. N o.
DESCRIPTION
DATE
C H
K.
B
Y
BLW Engineers, Inc.
e: info@blwengineers.com
311 Great Road, PO Box 1551 Littleton, Massachusetts 01460 t: 978.486.4301 f: 978.428.0067
DATE
3.
Harvard Public Schools 14 Mass Ave.
Harvard, MA 01451
Science Classroom ERV AC Bromfield High School
14 Massachusetts Ave, Harvard, MA
03.19.21
03.19.21
03.19.21
100%CD
MECHANICAL
ROOF
NEW WORK PLAN
M1.0
KRB
KRB
DLC
SCALE: 3/32"= 1'-0"
MECHANICAL - ROOF NEW WORK PLAN1
AutoCAD SHX Text HRU-4 (EXISTING) (EXISTING) 119"x64"x70"H 2358 LBS
AutoCAD SHX Text HRU-5 (EXISTING) (EXISTING) 117"x75"x71"H 2661 LBS
AutoCAD SHX Text HRU-7 (EXISTING) (EXISTING) 108"x54"x55"H 1933 LBS
AutoCAD SHX Text HRU-6 (EXISTING) (EXISTING) 108"x54"x55"H 1933 LBS
AutoCAD SHX Text ACCU-5 120"x34"x46"H 1164 LBS
AutoCAD SHX Text ACCU-4 120"x34"x46"H 1040 LBS
AutoCAD SHX Text PROVIDE RS&RL FROM ACCU-5 TO EXISTING HRU-5 UNIT; SIZE PER MANUFACTURERS INSTALLATION INSTRUCTIONS
AutoCAD SHX Text PROVIDE RS&RL FROM ACCU-4 TO EXISTING HRU-4 UNIT; SIZE PER MANUFACTURERS INSTALLATION INSTRUCTIONS
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text F
AutoCAD SHX Text G
AutoCAD SHX Text H
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
A P
P R
B
Y
S H
T
R
E F
DRAWING NO.
PROJECT
S I Z
E
CLIENT
CH'KD.
BY
APPR'D.
BY
BY
DRAWN
NAME
R E
V
N o
DESCRIPTION
DATE
C H
K
B
Y
BLW Engineers, Inc.
e: info@blwengineers.com
311 Great Road, PO Box 1551 Littleton, Massachusetts 01460 t: 978.486.4301 f: 978.428.0067
DATE
Harvard Public Schools
14 Mass Ave.
Harvard, MA 01451
Science Classroom ERV AC
Bromfield High School
14 Massachusetts Ave, Harvard, MA
03.19.21
03.19.21
03.19.21
100%CD
ELECTRICAL
LEGENDS, NOTES,
& ABBREVIATIONS
E0.1
KRB
KRB
DLC
AutoCAD SHX Text 1.5
AutoCAD SHX Text
20AT
AutoCAD SHX Text
%%U30AF
AutoCAD SHX Text 3R
AutoCAD SHX Text
%%UGENERAL SPECIFICATIONS
AutoCAD SHX Text
1. CONDITIONS OF THE CONTRACT AND DIVISION 1, GENERAL REQUIREMENTS APPLY TO WORK SHOWN ON THESE DRAWINGS. CONDITIONS OF THE CONTRACT AND DIVISION 1, GENERAL REQUIREMENTS APPLY TO WORK SHOWN ON THESE DRAWINGS. EXAMINE DRAWINGS AND OTHER SPECIFICATIONS FOR REQUIREMENTS THAT AFFECT WORK SHOWN ON THESE DRAWINGS. 2. PROVIDE ITEMS REFERRED TO IN SINGULAR NUMBER IN CONTRACT DOCUMENTS IN QUANTITIES NECESSARY TO COMPLETE PROVIDE ITEMS REFERRED TO IN SINGULAR NUMBER IN CONTRACT DOCUMENTS IN QUANTITIES NECESSARY TO COMPLETE WORK. 3. VISIT SITE AND EXAMINE CONDITIONS UNDER WHICH WORK MUST BE PERFORMED. REPORT ADVERSE CONDITIONS IN WRITING VISIT SITE AND EXAMINE CONDITIONS UNDER WHICH WORK MUST BE PERFORMED. REPORT ADVERSE CONDITIONS IN WRITING TO ARCHITECT. COMMENCEMENT OF WORK SHALL BE CONSTRUED AS COMPLETE ACCEPTANCE OF EXISTING CONDITIONS INCLUDING PREPARATORY WORK DONE BY OTHERS. 4. PERFORM WORK AND PROVIDE MATERIALS AND EQUIPMENT AS SHOWN ON DRAWINGS. COORDINATE ELECTRICAL WORK WITH PERFORM WORK AND PROVIDE MATERIALS AND EQUIPMENT AS SHOWN ON DRAWINGS. COORDINATE ELECTRICAL WORK WITH WORK SHOWN ON THESE DRAWINGS. 5. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION. 6. PERFORM WORK AS REQUIRED BY CODES, REGULATIONS AND LAWS OF LOCAL, STATE AND FEDERAL GOVERNMENTS AND PERFORM WORK AS REQUIRED BY CODES, REGULATIONS AND LAWS OF LOCAL, STATE AND FEDERAL GOVERNMENTS AND OTHER AUTHORITIES WITH LAWFUL JURISDICTION. 7. MATERIAL AND EQUIPMENT SHALL BE UL, NEMA, ANSI, IEEE, ADA & CBM APPROVED FOR INTENDED SERVICE. MATERIAL MATERIAL AND EQUIPMENT SHALL BE UL, NEMA, ANSI, IEEE, ADA & CBM APPROVED FOR INTENDED SERVICE. MATERIAL AND INSTALLATION SHALL MEET REQUIREMENTS OF NATIONAL AND STATE ELECTRICAL CODE. 8. MAINTAIN RECORD DRAWINGS ON SITE. RECORD SET MUST BE COMPLETE, CURRENT AND AVAILABLE FOR INSPECTION MAINTAIN RECORD DRAWINGS ON SITE. RECORD SET MUST BE COMPLETE, CURRENT AND AVAILABLE FOR INSPECTION WHEN REQUISITIONS FOR PAYMENT ARE SUBMITTED. 9. GUARANTEE WORK IN WRITING FOR ONE (1) YEAR FROM DATE OF FINAL ACCEPTANCE. REPAIR OR REPLACE DEFECTIVE GUARANTEE WORK IN WRITING FOR ONE (1) YEAR FROM DATE OF FINAL ACCEPTANCE. REPAIR OR REPLACE DEFECTIVE MATERIALS OR INSTALLATION AT NO COST TO OWNER. CORRECT DAMAGE CAUSED IN MAKING NECESSARY REPAIRS AND REPLACEMENTS UNDER GUARANTEE AT NO COST TO OWNER. 10. SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT. STATEMENT OF GUARANTEE REQUIREMENTS SHALL NOT BE SUBMIT GUARANTEE TO ARCHITECT BEFORE FINAL PAYMENT. STATEMENT OF GUARANTEE REQUIREMENTS SHALL NOT BE INTERPRETED TO LIMIT OWNER'S RIGHTS UNDER LAW AND THIS CONTRACT. 11. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE INFORMATION AND DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE INFORMATION AND COMPONENTS SHOWN ON RISER DIAGRAMS BUT NOT SHOWN ON PLANS, AND VICE VERSA, AS IF EXPRESSLY REQUIRED ON BOTH. 12. UTILIZE MOLDED CASE CIRCUIT BREAKERS. MINIMUM INTERRUPTING CAPACITY SHALL BE 10,000 AMPS SYMMETRICAL AT UTILIZE MOLDED CASE CIRCUIT BREAKERS. MINIMUM INTERRUPTING CAPACITY SHALL BE 10,000 AMPS SYMMETRICAL AT 240 VOLTS, AND 14,000 AMPS SYMMETRICAL AT 480 VOLTS. 13. ADDRESS QUESTIONS REGARDING DRAWINGS TO ARCHITECT IN WRITING BEFORE AWARD OF CONTRACT. OTHERWISE, ADDRESS QUESTIONS REGARDING DRAWINGS TO ARCHITECT IN WRITING BEFORE AWARD OF CONTRACT. OTHERWISE, ARCHITECT INTERPRETATION OF MEANING AND INTENT OF DRAWINGS SHALL BE FINAL. 14. DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENT FOR THOSE DEVIATION FROM CONTRACT DOCUMENTS, OR PROPOSED SUBSTITUTION OF MATERIALS OR EQUIPMENT FOR THOSE SPECIFIED, SHALL BE REQUESTED IN SEPARATE LETTER, WHETHER DEVIATIONS ARE DUE TO FIELD CONDITIONS, STANDARD SHOP PRACTICE, OR OTHER CAUSE. 15. ALL WIRING SHALL BE RUN CONCEALED UNLESS SPECIFIED OTHERWISE. ALL WIRING SHALL BE RUN CONCEALED UNLESS SPECIFIED OTHERWISE. 16. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER, RECTILINEAR TO BUILDING STRUCTURE. ALL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER, RECTILINEAR TO BUILDING STRUCTURE. 17. LOCATION OF MECHANICAL EQUIPMENT THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON THE MECHANICAL LOCATION OF MECHANICAL EQUIPMENT THAT REQUIRE ELECTRICAL CONNECTIONS ARE SHOWN ON THE MECHANICAL DRAWINGS. 18. ALL RACEWAY RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH EXPANSION FITTINGS. ALL RACEWAY RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH EXPANSION FITTINGS. 19. CONDUIT HOMERUNS SHOWN ON THE DRAWING WITH MORE THAN THREE (3) CURRENT CARRYING CONDUCTORS ARE SHOWN CONDUIT HOMERUNS SHOWN ON THE DRAWING WITH MORE THAN THREE (3) CURRENT CARRYING CONDUCTORS ARE SHOWN DIAGRAMMATICALLY. THE CONTRACTOR SHALL NOT INSTALL MORE THAN THREE (3) CURRENT CARRYING CONDUCTORS IN A RACEWAY UNLESS DONE SO STRICTLY BY THE NATIONAL ELECTRICAL CODE AS AMENDED BY THE STATE. 20.
This is the start of the file's text. The full file is on GovTribe.