This document is a technical data sheet for the Acousti-Seal Legacy Electric (933E) operable partition system manufactured by Modernfold, Inc. The Acousti-Seal Legacy Electric is an electrically operated, continuously hinged operable partition with features such as automatic floor seals, integrated safety components, and a choice of suspension systems and panel finishes. The document provides detailed specifications on the panel construction, operation, sound ratings, and available options. It also includes technical drawings and diagrams illustrating the system components and installation details. This technical data appears to be for informational purposes and does not appear to be directly related to a federal contract opportunity.
The related federal contract opportunity is for the procurement of Modernfold room dividers for the Lebanon VA Medical Center. The solicitation number is 36C24424Q0799 and the contract is being issued by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 4. The required products appear to be Modernfold operable partitions and associated services for repair, maintenance, and replacement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 1
Acousti-Seal® Legacy® Electric (933E) Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
• Continuously Hinged Electric Partitions Provide Effortless Operation
• Extends and Stacks with the Activation of Push Button Switches
• Integrated Safety with Key-Activated Two-Button Operation
• Two Year Warranty on Partition System
• Lifetime Warranty on Standard Hinges
• Operable Bottom Floor Seal Sets Automatically when Partition is Fully Extended
• Used in Hotel Ballrooms, Civic/Convention Centers, Classrooms, Gymnasiums, Meeting Rooms, Conference Rooms, and Multipurpose Rooms
Modernfold Model Acousti-Seal® Legacy® Electric (933E) Electrically Operated, Continuously Hinged Partitions
This specification along with product information and model details can be downloaded from www.modernfold.com
SPECIFICATION - SECTION 10 22 26 (10650) OPERABLE PARTITIONS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Electrically operated, continuously hinged partitions.
B. Related Sections include the following:
1. Division 03 Sections for concrete tolerances required.
2. Division 05 Sections for primary structural support, including pre-punching of support members by structural steel supplier per operable partition supplier’s template.
3. Division 06 Sections for wood framing and supports, and all blocking at head and jambs as required.
4. Division 09 Sections for wall and ceiling framing at head and jambs.
1.3 QUALITY ASSURANCE
A. Installer Qualifications: An experienced installer who is certified in writing by the operable partition manufacturer, as qualified to install the manufacturer’s partition systems for work similar in material, design, and extent to that indicated for this Project.
B. Acoustical Performance: Test operable partitions in an independent acoustical laboratory in accordance with ASTM E90 test procedure and classified in accordance with ASTM E413 to attain no less than the STC rating specified. Provide a complete and unedited written test report by the testing laboratory upon request.
C. Preparation of the opening shall conform to the criteria set forth per ASTM E557 Standard Practice for Architectural Application and Installation of Operable Partitions.
D. The operable wall must be manufactured by a certified ISO-9001-2015 company or an equivalent quality control system.
1.4 REFERENCE STANDARDS
A. ASTM International
1. ASTM E557 Standard Practice for Architectural Application and Installation of Operable Partitions.
2. ASTM E90 - Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements.
3. ASTM C1036 - Standard Specification for Flat Glass.
4. ASTM C1048 - Heat-Treated Flat Glass—Kind HS, Kind FT Coated and Uncoated Glass.
5. ASTM E84 - Surface Burning Characteristics of Building Materials.
6. ASTM E413 - Classification for Rating Sound Insulation
B. Health Product Declaration Collaborative
1. Health Product Declaration Open Standard v2.1 C. International Standards Organization
1. ISO 14021 - Environmental Labels and Declarations - Self-Declared Environmental Claims (Type II Environmental Labeling).
2. ISO 14025:2011-10, Environmental Labels and Declarations - Type III Environmental Declarations - Principles and Procedures.
3. ISO 14040:2009-11, Environmental Management
- Life Cycle Assessment - Principles and Framework.
4. ISO 14044:2006-10, Environmental Management
- Life Cycle Assessment - Requirements and Guidelines.
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.2
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
5. ISO 21930 – Sustainability in Buildings and
Civil Engineering Works — Core Rules for Environmental Product Declarations of Construction Products and Services.
D. Other Standards
1. ADA – Americans with Disabilities Act.
2. UL 508A – Standard for Industrial Control Panels
3. NFPA 70 – National Electrical Code
4. ANSI Z97.1 - Safety Glazing Materials Used in
Buildings.
5. CPSC 16 CFR 1201 - Safety Standard for
Architectural Glazing Materials.
6. NEMA LD3 - High Pressure Decorative
Laminates.
1.5 SUBMITTALS
A. Product Data: Material descriptions, construction details, finishes, installation details, and operating instructions for each type of operable partition, component, and accessory specified.
B. Shop Drawings: Show location and extent of operable partitions. Include plans, elevations, sections, details, attachments to other construction, and accessories. Indicate dimensions, weights, conditions at openings, and at storage areas, and required installation, storage, and operating clearances. Indicate location and installation requirements for hardware and track, including floor tolerances required and direction of travel.
Indicate blocking to be provided by others.
C. Setting Drawings: Show imbedded items and cutouts required in other work, including support beam punching template.
D. Samples: Color samples demonstrating full range of finishes available by architect. Verification samples will be available in same thickness and material indicated for the work.
E. Reports: Provide a complete and unedited written sound test report indicating test specimen matches product as submitted.
F. Create spaces that are healthy for occupants.
1. Furnish products and materials with Health
Product Declaration (HPD), Manufacturer Inventory, or other material health disclosure documentation. Products without an HPD or other disclosure documentation are not acceptable.
G. Furnish materials that generate the least amount of pollution.
1. Furnish products and materials that have third party verified environmental product declarations (EPD’s). Consider products and materials that have optimized environmental performance (reduced life cycle impacts).
Products without an EPD or other disclosure documentation are not acceptable.
H. Buy American: Operable partition to be manufactured in the United States in compliance with applicable U.S. Federal Trade Commission (FTC) and U.S. Customs Service and Border Protections regulations and be labeled “Made in America”.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Clearly mark packages and panels with numbering systems used on Shop Drawings. Do not use permanent markings on panels.
B. Protect panels during delivery, storage, and handling to comply with manufacturer’s direction and as required to prevent damage.
1.7 WARRANTY
A. Provide written warranty by manufacturer of operable partitions agreeing to repair or replace any components with manufacturing defects.
B. Warranty period: Two (2) years.
PART 2 – PRODUCTS
2.1 MANUFACTURERS, PRODUCTS, AND OPERATION
A. Manufacturers: Subject to compliance with requirements, provide product by the following:
1. Modernfold, Inc.
B. Panels to be manufactured in the U.S.A.
C. Products: Subject to compliance with the requirements, provide the following product:
1. Acousti-Seal Legacy – Electric Partition (933E) electrically operated continuously hinged operable partition.
2.2 OPERATION
A. Acousti-Seal Legacy – Electric Partition (933E):
Series of continuously hinged flat panels, electrically operated, top supported with operable floor seals.
B. Final Closure (select one):
1. Side Jamb with overlapping trail panel.
2. Side Jamb with overlapping trail panel with
“Modernfold Presto Automation Package”. (For complete specification see Presto Package brochure Form #2514)
3. Side Seal with pocket door interface (Remote stack only).
C. Partition shall be operated by:
1. Two push button control stations wired in series and located on opposite sides and opposite ends of the partition. Control stations shall
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 3
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
be activated by key switch at stack end of partition.
2. Modernfold Presto ® Automation Package with Touch Screen Operator Control Station by Modernfold, Inc.
3. Motor unit shall be reversible, continuous duty, and class A insulated. Motor unit shall have NEMA MG 1 service factor, high starting torque, thermal overload protection, and open/drip proof enclosure. Motor assembly shall have wiring compliant with NFPA 70, 24-volt controls, compliant with UL 508A, and speed of 28 feet/ minute. The drive unit motor shall be equipped with outboard limit switches to prevent over-extension. A positive chain drive attached to the lead panel shall pull the partition across the opening. Cable, belt, or other friction type drives will not be accepted.
D. Electric motor shall be (select one):
1. 115-volt, 1-phase, 1 HP, 14.0 FLA
2. 208/230-volt, 1-phase, 1 HP, 7.0 FLA
3. 208/230-volt, 3-phase, 1 HP, 4.5 FLA
4. 460-volt, 3-phase, 1 HP, 2.0 FLA
5. 208/230-volt, 3-phase, 1-1/2 HP, 5.2 FLA
2.3 PANEL CONSTRUCTION
A. Nominal 3-inch (76 mm) thick panels in manufacturer’s standard 48-inch (1220 mm) widths.
All panel horizontal and vertical framing members fabricated from minimum 16-gage formed steel with overlapped and welded corners for rigidity.
Top channel is reinforced to support suspension system components. Frame is designed so that full vertical edges of panels are of formed steel and provide concealed protection of the edges of the panel skin.
B. Panel Skin Options (select one):
1. Roll-formed 21-gage steel wrapping around the panel edge. Panel skins shall be lock formed and welded directly to the frame for unitized construction. Acoustical ratings of panels with this construction (select one):
a. 28 STC
b. 50 STC
c. 52 STC
2. Roll-formed 21-gage Micro-perforated steel wrapping around panel edge provided on 50% of panel faces manufactured with sound absorptive backing. Panel skins shall be lock formed and welded directly to the frame for unitized construction. Acoustical ratings of panels with this construction shall be no less than:
a. 45 STC (net with NRC construction)
b. 0.65 NRC with wall covering and upholstery fabric or non-woven needle punch carpet covering
C. Hinges for Panels, Closure Panels, Pass Doors, and Pocket Doors shall be (select one):
1. Full leaf butt hinges, attached directly to panel frame with welded hinge anchor plates within panel to further support hinge mounting to frame. Lifetime warranty on hinges. Hinges mounted into panel edge or vertical astragal are not acceptable.
2. SOSS Invisible laminated hinge with antifriction segments mounted between each heat-treated link. Hinge to be attached directly to panel frame. Welded internal hinge bracket shall support the hinge and allow for adjustment of hinge plates. Concealed hinges mounted into edge or vertical astragal are not acceptable.
D. Panel Trim: No vertical trim required or allowed on edges of panels; minimal groove appearance at panel joints.
E. Panel Weights:
1. 28 STC - 6 lbs./square foot
2. 50 STC - 8 lbs./square foot
3. 52 STC - 11 lbs./square foot
2.4 PANEL FINISHES
A. Panel Face finish shall be (select as required):
1. Reinforced vinyl with woven backing weighing not less than 20 ounces (567 g) per lineal yard.
2. Reinforced heavy-duty vinyl with woven backing weighing not less than 30 ounces (850
g) per lineal yard.
3. Acoustical, non-woven needle punch carpet, with fused fibers to prevent unraveling or fray of material.
4. Wall covering and upholstery fabric with surface treatment to resist stains.
5. Customer’s own material (subject to factory approval).
6. Full height steel markerboard work surface.
7. Full height 1/4-inch (6.35 mm) natural cork tackboard with vinyl or fabric covering.
8. Uncovered for field finishing.
9. Primed for field finishing.
B. Panel Trim: Exposed panel trim of one consistent color from manufacturer’s standard offering (select one):
1. Dark Bronze
2. Smoke Gray
3. Natural Choice
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.4
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
2.5 SOUND SEALS
A. Vertical Interlocking Sound Seals between panels:
Roll-formed astragals, with reversible tongue and groove configuration in each panel edge, for universal panel operation. Rigid plastic astragals or astragals in only one panel edge are not acceptable.
B. Horizontal Top Seals: Continuous contact extruded vinyl bulb shape with pairs of non-contacting vinyl fingers to prevent distortion without the need for mechanically operated parts.
C. Horizontal Bottom Seals (select one):
1. A2 - Automatic operable seals providing nominal 2-inch (51 mm) operating clearance with an operating range of +1/2-inch (13 mm) to –1-1/2 inch (38 mm) which automatically drop as panels are positioned, without the need for tools or cranks.
2. Floating Bottom Seal. Floating operable seals provide nominal 3-1/2 inch (89 mm) operating clearance within operating range of +1/2-inch (15 mm) to –3-inch (76 mm) and shall provide continuous floor contact as panels are positioned with no need for tools or cranks.
a. Carpet glides (carpet flooring)
b. Swivel casters (hard surface flooring)
2.6 SUSPENSION SYSTEM (select one)
A. #14 Suspension System
1. Suspension Tracks: Minimum 7-gage, 0.18-inch (5 mm) roll-formed steel. Track shall be supported by adjustable steel hanger brackets connected to structural support by pairs of 1/2-inch (13 mm) diameter threaded rods. Brackets must support the load bearing surface of the track.
a. Exposed track soffit: Steel, removable for service and maintenance, attached to track bracket without exposed fasteners, and pre-painted off-white.
2. Carriers: All-steel trolleys with steel-tired ball bearing wheels.
3. Warranty period: Ten (10) years.
– OR –
B. #30 Suspension System
1. Suspension Tracks: Track shall be structural aluminum. Track shall be supported by adjustable steel hanger brackets connected to structural support by pairs of 3/8-inch (9.5 mm) diameter threaded rods.
a. Exposed track soffit: Track soffit to be integral to track shape and shall be powder-coated off white paint finish.
Track must accommodate termination of plenum sound barriers on both sides of track for maximum sound control.
2. Carriers: One trolley in alternating panels with 3-inch (76 mm) diameter glass reinforced nylon, all steel precision-ground ball-bearing wheels.
Steel wheeled or reinforced polymer trolleys on aluminum track not permitted. Trolleys shall attach to panels with 1/2-inch (13 mm) diameter pendent bolt mounted to welded steel mounting plate.
3. Warranty period: Two (2) years.
2.7 OPTIONS
A. Single Pass Door:
1. Matching pass door same thickness and appearance as panels. ADA compliant pass door to be trimless and equipped with friction latch and flush pulls for panic operation. No threshold will be permitted.
B. Hardware:
1. Hand pull with push plate.
2. Lever handles both sides of door
3. Automatic door closer.
4. Door viewer.
5. Self-Illuminated exit signs:
a. Chemical exit sign – recess mount C. Work Surfaces:
1. Markerboard: White enamel on steel, bonded to the face of the panel with horizontal trim without exposed fasteners. Trim is not acceptable on vertical edges to provide uninterrupted work surface.
2. Tackboard: Minimum 1/4-inch (6.35mm) natural cork, covered with vinyl or fabric, with horizontal trim without exposed fasteners. Trim is not acceptable on vertical edges.
D. “Presto” Safety Components:
1. Presto Safety Nose (wireless) – High sensitivity pressure leading edge requiring no more than
2.2 lb. of pressure to stop partition movement in case of obstruction. Lead sensors requiring hard wiring through partition system or requiring more than 2.2 lb. of pressure for activation are not acceptable. Sensing edge to be housed in fluid resistant housing and set in snap in channel for easy maintenance and be provided with 4-lead fail-safe wiring.
2. Presto Safety Mats – Located at panel storage area. Personnel sensing switch mat shall activate with the presence of a minimum 22
lb. obstruction in the stack area and prevent panels from stacking until the personnel/
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 5
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
ACOUSTI-SEAL® LEGACY®
ELECTRIC (933E) 28 STC 50 STC 52 STC
#14 Bracket Mounted Track 28’-4” (8636 mm)
26’-4” (8026 mm)
18’-4” (5588 mm)
#30 Bracket Mounted Track 12’-4” (3759 mm)
12’-4” (3759 mm)
12’-4” (3759 mm)
STC CONSTRUCTION ANDSTC CONSTRUCTION AND
TRACK SYSTEM HEIGHT LIMITATIONSTRACK SYSTEM HEIGHT LIMITATIONS
obstruction is removed. Mats shall be provided with 4-lead fail-safe wiring.
3. Presto Vision (PIR/Microwave Detector) – Wall or ceiling mounted motion sensors covering the travel area of the automated partition shall automatically stop the movement of the panels in the presence of unauthorized movement or obstruction. Detector can detect motion in an area up to 300 ft. (91M) long by
7.5 ft. (2.3M) wide and 10 ft. (3M) high and be equipped with anti-masking protection.
E. Available Accessories/Options:
1. Pocket Doors: Acousti-Seal Pocket Doors by
Modernfold, Inc., with same construction, finish, and appearance as the adjacent panels.
Equipped with electric interlock system.
2. Finished end caps.
3. Intersecting partition interface.
4. Window frame options:
a. Aluminum window frame, glazed or unglazed
b. Wood window frame, glazed or unglazed
5. Inset window glazing options:
a. 1/4-inch clear tempered glass – aluminum frame or wood frame
b. 1/4-inch low iron tempered glass – aluminum frame or wood frame
c. 1/4-inch Lexan – aluminum frame
d. 1/2-inch clear tempered glass – wood frame
e. 1/2-inch low iron tempered glass – wood frame
f. 1-inch insulated glass – wood frame
6. Resilient Padding – 1/2-inch (13mm) resilient material covered with heavy-duty vinyl.
PART 3 – EXECUTION
3.1 INSTALLATION
A. General: Comply with ASTM E557, operable partition manufacturer’s written installation instructions, Drawings and approved Shop Drawings.
B. Install operable partitions and accessories after other finishing operations, including painting have been completed.
C. Match operable partitions by installing panels from marked packages in numbered sequence indicated on Shop Drawings.
D. Broken, cracked, chipped, deformed or unmatched panels are not acceptable.
3.2 CLEANING AND PROTECTION
A. Clean partition surfaces upon completing installation of operable partitions to remove dust, dirt, adhesives, and other foreign materials according to manufacturer’s written instructions.
B. Provide final protection and maintain conditions in a manner acceptable to the manufacturer and Installer that ensure operable partitions are without damage or deterioration at time of Substantial Completion.
3.3 ADJUSTING
A. Adjust operable partitions to operate smoothly, easily, and quietly, free from binding, warp, excessive deflection, distortion, nonalignment, misplacement, disruption, or malfunction, throughout entire operational range. Lubricate hardware and other moving parts.
3.4 EXAMINATION
A. Examine flooring, structural support, and opening, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of operable partitions. Proceed with installation only after unsatisfactory conditions have been corrected.
3.5 DEMONSTRATION
A. Demonstrate proper operation and maintenance procedures to Owner’s representative.
B. Provide Operation and Maintenance Manual to
Owner’s representative.
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.6
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
STEEL SKIN PANEL CONSTRUCTION
Acousti-Seal® Legacy® Electric Panel Section Frame Details
Acousti-Seal® Legacy® Electric Standard Panel Joint
NON-DISTORTING
BULB-AND-FINGER
ACOUSTICAL SWEEP
FORMED STEEL SKIN
WITH NO SHARP
EDGES WELDED TO
FRAME
.75" (19mm)
SOLID STEEL
TROLLEY MOUNT
INSULATED BOTTOM
SEAL CAVITY WITH
DOUBLE ACOUSTICAL
SEALS
DUAL-DUROMETER
FLOOR SEAL WITH
CONTOUR MATCHING
OUTER SEALS
FLOOR
SELF-CONTAINED,
SERVICEABLE
BOTTOM SEALS
16 GA. FORMED
STEEL BOTTOM
FRAME CHANNEL
DOUBLE
16 GA. STEEL
TOP CHANNEL
WITH HEAVY
STEEL CORNER
REINFORCEMENTS
UNDERSIDE OF
TRACK/SOFFIT
PANEL DETAILS ARE NOT TO SCALE
NOMINAL 21 GA. STEEL
SKINS WITH ACOUSTICAL
BACKER
ROLL-FORMED EDGES
WRAPPED AROUND,
LOCKED AND WELDED
TO VERTICAL FRAME
STEEL DUAL
INTERLOCKING VERTICAL
ASTRAGAL WITH VINYL
ACOUSTICAL GASKET
ROLL-FORMED
STEEL VERTICAL
FRAME CHANNEL
WITH NO SHARP
EDGES
MINIMUM GROOVE
AT PANEL JOINT WITH
NO VERTICAL EDGE TRIM
16 GA. ROLL-FORMED
STEEL VERTICAL
FRAME CHANNEL
ACOUSTICAL
INSULATION
AS-41
Roll-formed skin wraps completely around the edge of vertical 16-gage steel channel and is locked in place, eliminating any sharp edges and creating a unitized panel. The finish material is secured under the steel astragal to prevent peeling.
Model Detail from Website
STEEL BUTT
HINGES ATTACH
DIRECTLY TO
HEAVY STEEL
BACKER PLATES
WELDED TO FRAME
FINISH MATERIAL WRAPPED
AROUND PANEL EDGE AND
CAPTURED BY VERTICAL
ASTRAGAL
16 GA. ROLL-FORMED
STEEL VERTICAL FRAME
CHANNEL WITH NO
SHARP EDGES
ROLL-FORMED EDGES
WRAPPED AROUND,
LOCKED AND WELDED
TO VERTICAL FRAME
AS-42R
Heavy steel hinges are mounted directly to the center of the vertical frame channel, not simply on the outside edge of the panel. Steel plates welded to the back of the channel prevent buckling or bending and provide the strongest hinged connection.
Model Detail from Website
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 7
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
SUSPENSION SYSTEM OPTIONS
(1 m m
M
IN
IM
U M
.75" (19 mm)
GUIDE
RAIL
10.25" (260 mm)
SOFFIT
VINYL TOP SEAL
CLG
LINE
FA
B
R
IC
AT
IO
N H
E
IG
H T
AUTOMATIC DROP SEAL
PROVIDES 2" (51 mm)
OPERATING CLEARANCE
(+ .50" TO 1.50") /
(+13 mm TO – 38 mm)
STRUCTURAL
SUPPORT NOT BY
MODERNFOLD
.50" (13 mm) DIA X 9" (229 mm)
LONG HANGER RODS
BY MODERNFOLD
ROLLER CHAIN
HANGER BRACKET
BY MODERNFOLD
STEEL BALLBEARING
TROLLEYS
OFF WHITE
BAKED ENAMEL
SOFFIT TRIM PAN
BY MODERNFOLD
7.50" (191 mm)
BRACKET
5" (127 mm)
GAGE
#14 Track System Bracket Mounted with Automatic Drop Seal
AS-143
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.8
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
SUSPENSION SYSTEM OPTIONS
#14 Track System Bracket Mounted with Floating Seal for Hard Floor
AS-144
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 9
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
SUSPENSION SYSTEM OPTIONS
#14 Track System Bracket Mounted with Floating Seal for Carpet Floor
AS-145
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.10
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
SUSPENSION SYSTEM OPTIONS
RECOMMENDED ACCESS
PANEL OPENING
36" (914 mm)10.53"
(267 mm)
1.88" (48 mm)
5" (127 mm)
30" (762 mm)
12" (305 mm)
TRACK
CENTERLINE
#14 Track System Bracket Mounted Top View
#14 Motor TV
Model Detail from Website
RECOMMENDED ACCESS
PANEL OPENING
36" (914 mm)
10.53" (267 mm)
TRACK
CENTERLINE
12" (305 mm)
12" (305 mm)
#14 Track System Bracket Mounted Horizontal View
#14 Motor
HV
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 11
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
SUSPENSION SYSTEM OPTIONS
FA
B
R
IC
AT
IO
N H
E
IG
H T
3.50" (89 mm)
2.50" (64 mm)
5.38" (137 mm)
TRACK
STRUCTURAL
SUPPORT NOT
BY MODERNFOLD
CLG
LINE
VINYL TOP SEAL
STEEL
BALLBEARING
TROLLEYS
ROLLER CHAIN
HANGER BRACKET
BY MODERNFOLD
RECOMMENDED
SOUND BAFFLE
NOT BY
MODERNFOLD
OR DISTRIBUTOR
GUIDE RAIL
.38" (10 mm) DIA X 9" (229 mm)
LONG HANGER RODS
BY MODERNFOLD
m m
M
IN
IM
U
M
GAGE
BRACKET
.75" (19 mm)
#30 Track System Standard Spacing
AS-119
Model Detail from Website
FA
B
R
IC
AT
IO
N H
E
IG
H T
STRUCTURAL
SUPPORT NOT
BY MODERNFOLD
RECOMMENDED
SOUND BAFFLE
NOT BY
MODERNFOLD
OR DISTRIBUTOR
CLG
LINE
VINYL
TOP SEAL
GUIDE RAIL
STEEL
BALLBEARING
TROLLEYS
ROLLER CHAIN
HANGER
BRACKET BY
MODERNFOLD
5.50" (140 mm)
4.50" (114 mm)
GAGE
5.38" (137 mm)
TRACK
.38" (10 mm) DIA × 9" (229 mm)
LONG HANGER
RODS BY
MODERNFOLD
m m
M
IN
IM
U
M
.75" (19 mm)
BRACKET
#30 Track System Optional Wider Spacing
AS-120
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.12
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
SUSPENSION SYSTEM OPTIONS
RECOMMENDED ACCESS
PANEL OPENING
1.88" (48 mm)
5.00" (127 mm)
30.00" (762 mm)
36.00" (914 mm)
10.56" (268 mm)
12.00" (305 mm)
TRACK
CENTERLINE
#30 Track System Motor Top View
#30 Motor TV
Model Detail from Website
RECOMMENDED ACCESS
PANEL OPENING
36.00" (914 mm)
10.56" (268 mm)
12.00" (305 mm)
12.00" (305 mm)
TRACK
CENTERLINE
#30 Track System Motor Horizontal View
#30 Motor
HV
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 13
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
PANEL, WORK SURFACE, AND PASS DOOR OPTIONS
SELF-LUMINOUS EXIT SIGNS
(RECESSED MOUNTED)
NO VERTICAL TRIM
ON PANEL (TYPICAL)
"H" TYPE PASS
DOOR
SELF-LUMINOUS
EXIT SIGN (OPTIONAL
LOCATION)
RECESSED HAND PULL WITH
FRICTION LATCH (ADA COMPLIANT)
RECESSED ERASER
HOLDER
6' -8 m m
O R
7' -0 m m
VA
RI
A
BL
E
'-0 m m
MARKERBOARD OR TACKBOARD
(NO VERTICAL TRIM REQUIRED)
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.14
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
PANEL, WORK SURFACE, AND PASS DOOR OPTIONS
FLOOR SEAL OPTIONS
FLOOR
2"
(51 mm)
AUTOMATIC DROP SEAL
PROVIDES 2" (51 mm)
OPERATING CLEARANCE
(+ .50" TO 1.50") /
(+13 mm TO – 38 mm)
2-inch Automatic Seal
AS-12C
Model Detail from Website
Floating Seal - Hard Floors
AS-15
Model Detail from Website
Floating Seal - Carpet
AS-17
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 15
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
POCKET ENCLOSURE AND STACKING OPTIONS
PANEL CROSS SECTIONS
STACK DEPTH
NO. OF PANELS
× 3.75" (95 mm) + 9.50" (241 mm)
/2
P A
N E
L W
ID
TH
P
LU
S
(1 m m
M
IN
/2
P A
N E
L W
ID
TH
P
LU
S
(1 m m
M
IN
OPTIONAL
SIDE R
SIDE L
FLOOR GUIDE
IN STACK
AREA ONLY
(SEE AS-40)
Legacy® Electric Standard Stack
FINISH SAME
AS PANELS
CAULKING BETWEEN
JAMB AND WALL
3" (76 mm)
1.25" (32 mm)
ALIGNMENT FORK
(AS REQUIRED)
BLOCKING
BY OTHERS
Nominal Fixed Jamb
AS-21C
Model Detail from Website
3" (76 mm)
4" (102 mm) TO 12" (305 mm)
ALIGNMENT FORK
(AS REQUIRED)
FINISH SAME
AS PANELS
CAULKING BETWEEN
JAMB AND WALL
BLOCKING
BY OTHERS
Variable Fixed Jamb
AS-22C
Model Detail from Website
STACK DEPTH
PLUS 6" (152 mm)
MIN.
INSTALLATION WIDTH
(TO FACE OF POCKET)
POCKET DOOR
INTERLOCK SWITCH
(2 REQ'D)
TYPE II
POCKET DOOR
SIDE R
SIDE L
10" (254 mm)
HOLD FLOOR
GUIDE IN STACK
AREA ONLY
(SEE AS-40B)
STACK DEPTH
NO. OF PANELS
× 3.75" (95 mm) + 8.50" (216 mm)
1/
PA
N
EL
W
ID
TH
PL
U
S 8" m m
M
IN
1/
PA
N
EL
W
ID
TH
PL
U
S 8" m m
M
IN
Legacy® Electric Remote Stack
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.16
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
FINISH SAME
AS PANELS
CAULKING
BETWEEN
JAMB AND WALL
SIDE SEAL
RETAINER
9" (229 mm)
JAMB
JAMB
REFERENCE
.2
(8 m m
Side Jamb Steel Skin
AS-38R
Model Detail from Website
VINYL SEAL AND
STEEL ASTRAGAL
VINYL BULB
SEAL
m m
R
E F
Bulb Seal and Intersection
AS-49
Model Detail from Website
Panel Splice Steel Skin
AS-19
Model Detail from
PANEL CROSS SECTIONS
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 17
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
VINYL SEAL
.2
(1 m m
END CAP
JAMB
REF.
ASSEMBLY SHIPS
LOOSE FOR FIELD
ATTACHMENT
FOOT BOLT
POCKET DOOR
Side Seal Remote Stack
AS-58RA
Model Detail from Website
2.38" (60 mm)
RECESS
1.19" (30 mm)
1.
(4 m m
R
EC
ES
S
.1 9"
(5 m m
1.5" (38 mm)
GROUT BY OTHERS
FINISHED FLOOR1"
(25 mm)
Remote Stack Floor Guide
AS-40B
Model Detail from Website
FLOOR TRACK
GROUT AS REQUIRED
#8 - 18 × 1.25
FLAT HEAD SCREW
BY MODERNFOLD
LEAD EXPANSION ANCHOR
BY MODERNFOLD
2" (5 m m
2" (51 mm)
Standard Floor Guide
AS-40
Model Detail from
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com.18
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
SOSS Hinged Panel Joint
AS-42RS
Model Detail from Website
ROLL-FORMED EDGES
WRAPPED AROUND,
LOCKED AND WELDED
TO VERTICAL FRAME
Steel Panel Construction
Please contact your local Modernfold distributor for further assistance, or visit our website at www.modernfold.com. 19
Technical Data 10 22 26 (10650) Operable Partitions
ACOUSTI-SEAL® LEGACY® SERIES TECHNICAL DATA
NON-STEEL SKIN PANEL CONSTRUCTION
Form No. 2555 1/22
215 West New Road Greenfield, IN 46140
Tel: 800.869.9685
Email: info@modernfold.com Website: www.modernfold.com
Acousti-Seal® Legacy® Electric (933E) Technical Data 10 22 26 (10650) Operable Partitions
Tek-Wall Ridge 002 Tonic 111873-679 x x
307" VERIFIED
x
CARPET TILE
(0.149")
16 7/8"
8"
8"
14 1/4"
11 7/8"
OVERLAY ON MOST CURRENT M101
ENTIRE SUPPORT STRUCTURE
WILL BE BELOW DUCTWORK
OLD 36X18 TO BE
REMOVED AND
REPLACED BY (2) 24X12
AS SHOWN ABOVE
NEW 24X12 DUCTS WILL
BE ROUTED ABOVE
SUPPORT STRUCTURE
(ON RIGHT): PHOTO IN LINE WITH DOOR
TRACK FACING SOUTH
(ABOVE): PHOTO IN LINE WITH DOOR
TRACK FACING NORTH
File details come from the government source that posted it. Updated .