BPM059464 - Emergency Generator Maintenance and Repair w. Appendicies.pdf

PDF 4 MB Posted

Attached to
Emergency Generator Preventative Maintenance and Repairs
Solicitation number
BPM059464
Issued by
Maryland

About this file

This is a scope of work document for emergency generator maintenance and repair services issued by the state/local contracting authority. The contract involves comprehensive maintenance, repair, and testing of emergency backup generator systems to ensure operational readiness and compliance with regulatory requirements. The scope includes routine preventive maintenance, emergency repair services, parts replacement, load testing, fuel system management, and documentation of all service activities. The contract requires the contractor to maintain rapid response capabilities for emergency situations and provide 24/7 availability for critical repairs. The term of the contract and specific response timelines, bid submission deadlines, site visit schedules, and any bidders' conference details would be outlined in the accompanying procurement documents, along with the anticipated award date and renewal options if applicable.

Pricing for this maintenance and repair contract is structured on either a time-and-materials basis or fixed unit rates depending on the service category, with detailed fee schedules to be provided by bidders in response to the solicitation. The contract may include provisions for spare parts inventory management and surge pricing for emergency after-hours service calls. Any applicable set-asides, incumbent contractor considerations, and specific funding sources would be detailed in the formal solicitation document. The contracting authority would specify minimum insurance requirements, bonding obligations, and equipment certification standards that all bidders must meet to be considered responsive.

View the file

Other files

File Type Posted
Appendix 4 - Monthly Usage Report Sample.xlsx XLSX spreadsheet
Attachment B - The Price Form.xlsx XLSX spreadsheet
Appendix 9. Electronic Transaction Fee.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Emergency Generator Preventive Maintenance and Repairs

Solicitation #: BPM059464 IFB Document

IFB for Department of General Services Page 1 of 38

STATE OF MARYLAND

THE DEPARTMENT OF GENERAL SERVICES

(DGS)

INVITATION FOR BIDS (IFB)

EMERGENCY GENERATOR PREVENTIVE MAINTENANCE AND

REPAIRS

IFB NUMBER BPM059464

ISSUE DATE: NOVEMBER 19, 2026

A Prospective Bidder that has received this document from a source other than eMaryland Marketplace

Advantage (eMMA) https://procurement.maryland.gov should register on eMMA https://emma.maryland.gov/

NOTICE TO BIDDERS

MINORITY BUSINESS ENTERPRISES ARE ENCOURAGED TO RESPOND TO THIS

SOLICITATION.

https://procurement.maryland.gov/ https://emma.maryland.gov/

IFB for Department of General Services Page 2 of 38

KEY INFORMATION SUMMARY SHEET (KISS)

Invitation for Bids Maintenance - DGS Emergency Generator Preventive Maintenance and

Repairs

Solicitation

Number:

BPM059464

IFB Issue Date: November 19, 2026

IFB Issuing

Office:

Department of General Services (DGS)

Procurement

Officer:

Matthew Smith

301 West Preston Street; M-4

Baltimore, Maryland 21201

Email:

Phone Number:

matthew.smith2@maryland.gov

(410) 767-3039

Bids are to be sent to:

Submit on emma.maryland.gov under Solicitation Number BPM059464

To submit a bid, bidders must first register on emma.maryland.gov. We recommend registering in advance to become acquainted with the site.

No Bid Notice

Feedback Form

If you are not submitting a bid for this solicitation, submit Attachment 1

– No-Bid Notice/Vendor Feedback Form with your reasons why.

Pre-Bid

Conference:

November 30, 2026 10:00 am Local Time

Google Meet joining info

Video call link: https://meet.google.com/neu-xjyf-gom

Or dial: 0114-350-(US) +1 413 PIN: 833 131 658#

Scheduled Site

Visit

N/A mailto:matthew.smith2@maryland.gov

IFB for Department of General Services Page 3 of 38

Questions Due

Date and Time:

December 5, 2026, at 2:00pm Local Time

Bid Due (Closing)

Date and Time:

December 17, 2026, at 2:00pm Local Time

Bidders are reminded that a completed Feedback Form is requested if a no-bid decision is made (see Attachment 1 - No Bid Notice/Vendor

Feedback Form).

MBE

Subcontracting

Goal:

5%

VSBE

Subcontracting

Goal:

N/A

Procurement

Method:

A Contract will be awarded in accordance with the Competitive Sealed

Bidding method under COMAR 21.05.02.

Multiple or

Alternate Bids:

Multiple or alternate Bids will not be accepted.

Contract Type: Firm Fixed Price

Contract

Duration:

Four (4) months

Primary Place of

Performance:

Department of General Services Locations Statewide

SBR Designation: No

Federal Funding: No

IFB for Department of General Services Page 4 of 38

Table of Contents - IFB

Contents

1. Minimum Qualifications

2 Contractor Requirements: Scope of Work

2.1 Summary Statement

2.1.2 This Contract does NOT include the uninterruptible power supply system. Transfer switchgear equipment descriptions are available in Exhibit 4 - OFM Emergency Generator Equipment List

2.2 Background and Purpose

2.3 State Staff and Roles

2.3.2 State’s Right to Perform Work

2.3.3 Other State Responsibilities

2.4 Contractor Responsibilities and Tasks

2.4 Supplemental Category of Work Requirements and Responsibilities

3. Standard Terms and Conditions

3.1 Contract Initiation Requirements

3.2 End of Contract Transition

3.3 Invoicing

3.3.1 Invoice Submission Schedule

3.3.2 Travel Reimbursement

3.4 Liquidated Damages

3.4.1 MBE Liquidated Damages

3.4.2 Liquidated Damages other than MBE

3.4.3 Problem Escalation Procedure

3.5 Work Orders

3.6 Payments by Electronic Funds Transfer

3.7 Prompt Payment Policy

3.8 Federal Funding Acknowledgement

3.9 Conflict of Interest Affidavit and Disclosure

3.10 Non-Disclosure Agreement

3.11 Maryland Healthy Working Families Act Requirements

IFB Document

IFB for Department of General Services Page 5 of 38

3.12 The State of Maryland’s Commitment to Purchasing Environmentally Preferred Products and

Services (EPPs)

3.13 Insurance Requirements

4 Bid Submission Information and Instructions

4.1 eMaryland Marketplace Advantage (eMMA)

4.2 Electronic Means

4.3 Pre-Bid Conference

4.4 Questions

4.5 Bid Due (Closing) Date and Time

4.6 Receipt, Opening and Recording of Bids

4.7 Duration of Bids

4.8 Revisions to the IFB

4.9 Cancellations

4.10 Incurred Expenses

4.11 Protest/Disputes

4.12 Bidder Responsibilities

4.13 Acceptance of Terms and Conditions

4.14 Compliance with Laws/Arrearages

4.15 Verification of Registration and Tax Payment

4.16 False Statements

4.17 Confidentiality of Bids / Public Information Act Notice

4.18 Use of Bidder’s Form Not Binding on State

4.19 Attachments and Documents Required with the Bid (Table A)

4.20 Bid Delivery Instructions

4.21 Bid Evaluation Criteria and Award Basis

4.22 Tie Bids

4.23 Reciprocal Preference

4.24 Documents Required upon Notice of Recommendation for Contract Award (Table B)

5 IFB Appendices and Exhibits

5.1 Appendices (Table C)

5.2 Exhibits (Table D)

IFB for Department of General Services Page 7 of 38

1. Minimum Qualifications

1.1 Bidder Minimum Qualifications

The Bidder must document in its Bid that it satisfies the following Minimum Qualifications:

A. The Bidder shall have:

1. Minimum of one (1) year of the entity being formed and in business

2. Minimum of one (1) year, within the last five (5) years of successful

Emergency Generator Maintenance service performance comparable to the following, as required in this IFB:

1. Scope

2. Type

3. Size, magnitude, and complexity

B. The Bidder shall provide with its Bid online “Attachment L - Reference Checks" with a minimum of three (3) references of companies or organizations for which the Bidder provided services in scope, type, size, magnitude, and complexity comparable to those specified in the Scope of Work. Each reference shall be from a client for whom the Bidder has provided services within the past five (5) consecutive years. (The Department reserves the right to request additional references or utilize references not provided by a Bidder.)

THE REMAINDER OF THIS PAGE INTENTIONALLY LEFT BLANK

IFB for Department of General Services Page 8 of 38

2 Contractor Requirements: Scope of Work

2.1 Summary Statement

2.1.1 This Invitation for Bids (IFB) is issued to procure the goods or services, as specified in this

Section 2, from a Contract between the successful Bidder and the State of Maryland

(“State”): for the purposes of furnishing maintenance services for emergency generators, including automatic transfer switches and all associated equipment as per Section 2.3 –

Contractor Responsibilities and Tasks throughout the State under the authority of the

Office of Facilities Management (“OFM”) within the Department of General Services. All work shall be performed in accordance with applicable regulations, codes, and laws and in accordance with the manufacturer’s recommendations.

2.1.2 This Contract does NOT include the uninterruptible power supply system. Transfer switchgear equipment descriptions are available in Exhibit 4 - OFM Emergency Generator

Equipment List.

2.2 Background and Purpose

The State of Maryland Department of General Services (“DGS”) aims to maintain and improve operations at the Annapolis, Baltimore, and Multi-Service Center facilities, which include forty three 43 buildings throughout the State. This solicitation seeks to establish a contract with a qualified contractor to provide maintenance services for emergency generators at these DGS facilities located in Exhibit 3 – OFM Locations.

2.3 State Staff and Roles

2.3.1 Contract Monitor

A. Each region will identify at a minimum one (1) Contract Monitor receiving services under this Contract.

B. All communication between the Agency and the Contractor shall be conducted through the Contract Monitor or designee.

C. The Agency shall submit the name and phone number of the respective Contract

Monitor, with a copy provided to the DGS Procurement Officer.

D. Only the DGS Procurement Officer, subject to applicable law, has the authority to modify the Contract.

2.3.2 State’s Right to Perform Work

A. If the Contractor fails to complete the work properly or diligently or fails to perform any provision of the Contract, the State may correct such deficiencies at the Contractor’s expense or terminate the Contract for default.

IFB for Department of General Services Page 9 of 38

B. The State shall have the right to inspect the Contractor’s shop facilities for repair and spare parts inventory, having first given a minimum of three (3) days' written notice that it intends to do so.

2.3.3 Other State Responsibilities

A. The State will provide normal office work facilities and equipment reasonably necessary for Contractor performance under the Contract.

2.3.4 Electronic Transaction Fee

A. No later than forty five (45) calendar days after the end of each monthly reporting period, the Contractor shall remit to the State an electronic transaction fee equal to one percent (1%) of the total approved invoice amount for all accepted goods and services provided under the Contract during the applicable reporting period. The Contractor shall calculate the fee on the gross invoice amount, less any returns or credits. The Contractor may not charge the electronic transaction fee directly to a customer or identify it as a separate line item, fee or surcharge on any invoice, and shall incorporate the fee into the

Contract’s unit prices. For example, if the total approved invoice amount for a reporting period equals $10,000 the Contractor shall remit an electronic transaction fee of $100.

B. The Contractor shall submit the electronic transaction fee for the applicable reporting period by one of the two methods below:

i. Via ACH: To send ACH payments, the Contractor must complete the GAD X-

10 Form and submit it to the Comptroller at GADACH@marylandtaxes.gov.

All ACH payments must include a note in the comments section that the payment is for

“DGS 1% Fee.”

ii. By Check to the Office of State Procurement at the following address:

Department of General Services, Fiscal Services Division

301 W. Preston St., Room 1309

Baltimore, MD 21201

Attention: For the Office of State Procurement

C. Simultaneously with the payment of the fee, the Contract shall email Appendix 3 –

Monthly Usage Report Sample, documenting all accepted goods or services for the reporting period to: dgs.statewidecontractusagereport@maryland.gov.

D. If the Contractor fails to timely and accurately remit the electronic transaction fee(s), the

State shall determine that the Contractor is in default under the Contract.

2.4 Contractor Responsibilities and Tasks

2.4.1 Contractor’s Requirements / Scope of Work

A. The Contractor may subcontract Transfer Switchgear work, but shall meet the following requirements:

1. Certified Electrical Transfer Switch Technicians assigned to this Contract shall have certification from a recognized school (ASCO, Zenith, or equivalent), and a copy https://marylandcomptroller.jotform.com/team/public/GADX10 https://marylandcomptroller.jotform.com/team/public/GADX10 mailto:GADACH@marylandtaxes.gov mailto:dgs.statewidecontractusagereport@maryland.gov

IFB for Department of General Services Page 10 of 38 of their certifications must be submitted with the bid.

2. The Contractor shall comply with all requirements of the Annotated Code of

Maryland (latest revisions and supplements), COMAR (latest revisions and supplements), and, all bulletins, policies, directives, etc. issued by the Maryland

Department of Labor and the Building Officials and Code Administrations

International, Inc. National Mechanical Code (current edition).

3. The Contractor must have a means of contacting emergency personnel 24 hours per day, seven (7) days per week, to respond to emergencies within two (2) hours.

a. Upon request, the Contractor shall submit documentation qualifying the Project

Manager, to include a resume, background clearance, and three (3) client references. These documents must reflect at least two (2) years’ experience, with emergency generator maintenance supervision for services of the type and size of this IFB. With reference to the resume, it must list details of the length of employment, type, and size (square footage) of the buildings serviced by the

Project Manager.

4. The Contractor shall own or acquire by the start of the Contract all necessary equipment to perform all services described in the specifications. Equipment must be safe and in good condition and may be inspected before the Contract is awarded.

a. The Contractor or subcontractor must satisfy the Contract Monitor that an adequate stock of parts necessary to maintain and repair the equipment specified herein and that the Contractor’s maintenance staff is provided with a vehicle containing the necessary stock and tools to perform preventive maintenance, minor repair, emergency repairs, and major repairs on generators.

2.4.2 Pre-Work Conference

A. Prior to the successful Bidder for this Contract moving onsite to engage in actual work, they meet with the Superintendents, or Assistant Superintendents, or both, at a pre-work conference. The required pre-work conference may be waived at the State’s discretion.

B. The pre-work conference is intended to provide the successful Bidder with:

1. An orderly introduction to the requirements of the Department of General Services

(DGS) and Building Management, with regard to the expectations of Management from the Contractor within the terms and conditions of this Contract.

2. Any discussion of the requirements in the Contract documents that either party may find confusing and unclear as to the meaning or intent of the contract, either as a whole or in part, therein.

IFB for Department of General Services Page 11 of 38

3. A general discussion among conferees to provide enlightenment so that work may begin and continue in a professional and congenial manner.

4. The Contractor will be allowed time for their technicians to thoroughly evaluate all the equipment. It should be assumed that all equipment is in proper operating condition, as specified by the manufacturer’s standards.

5. The Contractor will be required to certify acceptance of the equipment within 30 days of the Contract start date and will not be allowed to claim any pre-existing conditions requiring repairs after certification. Failure to submit a timely certification of acceptance will be considered “as is” acceptance of the equipment.

2.4.3 Preventative Maintenance Schedule

A. This Contract shall be in effect January 1, 2027 through April 30, 2027. The Contractor shall perform preventive maintenance due during that period under the applicable manufacturer’s service intervals and the maintenance requirements identified in this solicitation. Quarterly, semiannual, annual and operating-hour intervals apply when due;

the four-month term does not independently require performance of every listed interval.

B. The monthly preventive maintenance price shall include all labor, supplies, lubricants, testing, and replacement items expressly included in the preventive maintenance requirements. These costs shall not be billed separately as repairs.

C. At a minimum, the Contractor shall complete the following:

1. Check the condition of batteries. Recharge or replace the battery if it fails to hold an adequate charge;

2. Check the automatic transfer switches' operations. Replace the Contractor’s relays if they malfunction and lubricate all moving parts.

3. Check all instrumental panel gauges for proper operation. Calibrate and/or replace if malfunctions.

D. The procedures listed below are as specified by the engine-generator set manufacturer.

The preventative maintenance section of this contract includes, but is not limited to, the performance of these procedures.

1. The Preventive Maintenance Schedule outlined in the bid shall generally coincide with general industry practice. Upon approval of the respective facilities management, the schedule may be modified to accommodate the Contractor’s issues, providing the minimum requirements are met. The minimum requirement is the respective equipment manufacturer's recommended service.

IFB for Department of General Services Page 12 of 38

2. The preventive maintenance schedule is broken down into three (3) groups (see below).

The schedule for each group is based on calendar months. The generators are used as a standby installation which operates only during electrical utility failures and weekly one

(1) hour exercise periods. There is, however, a possibility that unusual conditions (such as prolonged utility outages) could cause the engine-hours interval to be reached before the calendar-month interval. In this case, the Contractor shall perform the maintenance operations specified when the engine-hour interval has been reached, as per the manufacturer’s guidelines.

i. The groups are as follows:

ii. Quarterly Checks

iii. Semi-Annual Checks

iv. Annual Checks

a. Under this Contract, the Contractor shall perform all checks as required by the above schedule. The Contractor shall provide and maintain a maintenance service checklist at each location.

b. All procedures shall be performed in strict accordance with the manufacturer’s instructions.

c. Any defects found, as a result of any check, shall be repaired by the Contractor as a minor repair as defined.

d. All lubricants, hydraulic fluids, antifreeze, additives, and replacement Original

Equipment Manufacturer (“OEM”) relays, gauges, and/or sensors (as determined defective/malfunction), etc., required to perform preventive maintenance shall be paid for and furnished by the Contractor as part of this

Contract.

E. The Contractor shall establish and program an automated weekly start (exercise) system for the generator. This system shall initiate a no-load exercise cycle once every week, starting and running the generator for approximately thirty (30) minutes without transferring the building load from utility power. The purpose of this exercise cycle is to ensure engine lubrication, maintain internal component integrity, and sustain proper battery charge.

1. The automated weekly start system shall be configured through the generator’s onboard control program, or, if applicable, through the automatic transfer switch (ATS), in accordance with the manufacturer’s

IFB for Department of General Services Page 13 of 38 recommendations and system design. The Contractor shall verify correct programming and operation of the automated start cycle upon installation and document all settings, parameters, and test results in the generator maintenance log.

2. The Contractor shall also identify and report any generators that do not have the capability to be automatically programmed for a weekly start cycle. Such generators shall be clearly listed in the maintenance documentation, along with the reason for the limitation and any recommended alternative testing or exercise procedures.

3. The Contractor shall, during each scheduled maintenance visit, test and verify that the generator’s weekly automated exercise/start cycle is fully operational.

A detailed log or report shall be completed after each maintenance visit, documenting the date, time, confirmation of successful start, runtime, and all recorded performance metrics. This log or report must be kept onsite near the generator and remain fully accessible at all times.

F. The Contractor shall provide forms to record the results of all procedures performed. The records shall include a description of any corrective action taken as a result of any check.

One copy of the completed record shall be sent to the Building Manager within ten (10)

Working Days following the completion of the work. Applicable laboratory reports shall be attached to the record. The record shall show the date the work was completed and the engine hour meter reading at the time of completion.

G. All lubricants, hydraulic fluids, antifreeze, waste oil and materials required for optimum performance shall be provided and utilized as necessary.

H. The Contractor shall arrange and pay for all laboratory tests.

I. The details of the various check groups are:

Systems - Component

Frequency

Check Group 1

A Fuel Main tank supply level Quarterly

B Day tank supply level Quarterly

C Fuel level switch (replace if found malfunctioning) Quarterly

D Transfer pump operation Quarterly

E Solenoid valve operation (replace if found malfunctioning) Quarterly

F Filter(s) Quarterly

IFB for Department of General Services Page 14 of 38

G Water in fuel system Quarterly

H Flexible line connectors (Replace if found defective) Quarterly

I Vent and return lines open Yearly

J Fuel piping (Diesel or Natural Gas) Quarterly

K High/Low pressure gas valves regulators. Replace if malfunctioning Quarterly

Check Group 2

A Lubrication Oil level Quarterly

B Change Oil Yearly

C Change filter(s) Yearly

D Crankcase Breather Quarterly

E Check oil pressure gauges for proper operation Quarterly

Check Group 3

A Cooling Coolant level Quarterly

B Antifreeze protection Quarterly

B1 Antifreeze Lab Testing Yearly

C Change coolant Yearly

D Water supply to heat exchanger Quarterly

E Air inlets Quarterly

F Fan and alternator belts (Replace or adjust as needed) Quarterly

G Inspect water pump Quarterly

H Block heater operation Quarterly

I Air ducts, louvers Yearly

J Louver motors, controls Yearly

K Clean radiator and heat exchanger to ensure it free of dirt and debris Quarterly

L Inspect radiator cap Quarterly

Check Group 4

A Exhaust Leakage Quarterly

B Drain condensate trap Quarterly

C Insulation, fire hazards Quarterly

D Back pressure Yearly

E Hangers and supports Yearly

F Flexible connector(s) Quarterly

Check Group 5

A Battery System Electrolyte level Quarterly

B Terminals clean, tight Quarterly

C Remove corrosion, clean Quarterly

D Specific gravity, charge state Quarterly

IFB for Department of General Services Page 15 of 38

E Charger operation, charge rate Quarterly

F Recharge after engine start Quarterly

Check Group 6

A AC Electrical System Visual Inspection Quarterly

B Ensure wiring connections are secure Yearly

C Check for wire damage Quarterly

D Safety and alarm operation Six Months

E Controller lamp test Quarterly

F Circuit breaker, fuse service Quarterly

G Transfer switch main contacts Yearly

H Voltage sensing adjustment Yearly

I Wire-cable insulation Every four (4) Years or 500 hours

J Check gauges for proper operation and readings. Adjust as needed Quarterly

Check Group 7

A Engine Inspection Quarterly

B Air cleaner Quarterly

C Governor operations, lubrication, calibration, and adjustment Quarterly

D Governor oil change Yearly

E Ignition components Yearly

F Choke, carburetor adjustment Six Months

G Fuel system inspection and cleaning as required Yearly

H Ensure valves are cleaned and valve lash are checked Every three (3) years or

500 hours.

J. FULL LOAD BANK TEST

1. Load Bank Testing for all generators is performed every two (2) years. Should this service be required during the four (4) month period of this contract, scheduling will be arranged between the Contract Monitor and the Contractor. The following procedures shall apply:

a. All Full Load Bank Tests will be performed on the weekends at no additional cost to the State to prevent disruptions to government operations and building occupants, unless otherwise requested by the Superintendent and/or designee.

b. Run the generator set and load test at maximum safe capacity using load bank equipment for two (2) hours. Building load will not be an accepted substitute for a load bank test(s) unless prior discussion and approval is granted by the

Superintendent and/or their designee.

IFB for Department of General Services Page 16 of 38

c. The Contractor shall supply the Contract Monitor with a written report of the test for each generator and upload it into the Computerized Maintenance

Management System.

d. Generators currently serviced under a separate service agreement with another provider are excluded and will be identified. These generators will be incorporated into this scope of work upon expiration of the existing service agreement.

K. UNIT PRICES

a. The Contractor shall submit the unit cost for Full Load Bank Test on each size of generator as detailed in the specs. The price shall be the fixed unit cost throughout the term of the contract. The Contractor shall invoice for the performance of the tests upon completion and include the service ticket signed by the respective facility representative with the invoice. Payment for the Full Load

Bank Tests will not be made without substantiation and verification of the tests' performance. The unit cost for the Full Load Bank Test will be broken down into three (3) separate cost categories:

i. 0-250 KW

ii. 250-1000 KW

iii. 4160 V

L. INOPERATIVE EQUIPMENT

a. Equipment breakdowns or shutdowns resulting from the following conditions shall not keep the generator or related equipment out of service for more than 24 hours from the time the Contractor signs in on site:

i. Electrical Troubles

ii. Open Circuits

iii. Grounded Circuits

iv. Shorted Circuits

v. Electrical or mechanical adjustments

b. The Contractor will not be held financially responsible for internal parts of the motor, motor block, radiator, unless it is shown that damage occurred through improper maintenance, negligence, improper adjustments, or wrong parts installed by the Contractor or their employee.

c. The Contractor shall not be held financially responsible for non-operation of said generator or equipment by reason of fire not related to the Contractor’s work or responsibility, flood, or any other condition generally accepted as an act of God.

IFB for Department of General Services Page 17 of 38

M. DEFINITIONS

a. Preventive Maintenance

i. Preventive Maintenance is defined as periodically scheduled work to provide systematic checking, adjustments, cleaning, and routine services as recommended by the equipment manufacturer. The Contract includes parts and labor costs for a preventive maintenance program recommended by the equipment manufacturer, routine testing and inspection of equipment to reduce or avoid service interruptions and achieving optimal operating efficiency and maximum equipment life expectancy. Preventive Maintenance includes developing and recording equipment and system performance and inspection data for operational analysis and anticipated corrective action. All Preventive Maintenance shall be in strict compliance with the relevant equipment manufacturer’s recommendations. Preventive Maintenance includes all labor and parts paid by the Contractor.

b. Emergency Maintenance

i. Emergency Maintenance is defined as unscheduled work, other than

Preventive Maintenance, that requires immediate action to restore equipment or system operations, to correct mechanical problems that will cause interruptions of operations or will cause damage to operating equipment.

ii. In the event of equipment failure, or imminent failure or damage, on-site response by a qualified maintenance mechanic shall be made within two

(2) hours after the Contractor has been given notification of an emergency situation. Service response shall be sufficient to restore the equipment or system to operation. If temporary measures are taken to restore functionality, permanent repairs shall be completed within five

(5) Working Days.

iii. In the event of an emergency, and the generator will be out of service for a period of 24 hours or more, the Contactor shall immediately notify both the Building Manager and Regional Manager to detail the source of the problem. Upon notification, the Superintendent and/or designee will evaluate the operational impact and determine whether deployment of a temporary generator by the Contractor is required (see Section N -

Temporary Generators).

iv. Emergency maintenance service shall be available 24 hours per day, seven (7) days per week, through the term of the Contract.

IFB for Department of General Services Page 18 of 38

v. Failure of the Contractor to provide Emergency Service within the stated timeframes may be cause to consider the Contractor in default of the

Contract by the Procurement Officer.

vi. Repairs necessary under Emergency Maintenance shall be paid as follows:

vii. Repair and replacement parts chargeable to the State shall be invoiced at cost, defined as the manufacturer’s charge to the Contractor, including freight and transportation charges as reflected on the manufacturer's invoice. The State reserves the right to selectively audit Contractors' invoices to verify part costs (COMAR 21.06.03.01). The Contractor must purchase parts from the least costly source. Invoices must include detailed cost breakdowns, including labor hours, labor rates, and copies of manufacturer invoices for parts.

N. REPAIR AUTHORIZATION AND COST CONTROLS

a. Before beginning separately billable repairs, the Contractor shall submit an itemized estimate identifying the facility, generator, proposed work, labor classifications, estimated hours, applicable Contract rates, parts, and total estimated cost.

b. The Contract Monitor or designated State representative shall authorize the work in writing and establish a not-to-exceed amount. Additional authorization is required before exceeding that amount or materially changing the approved work.

Helpers and additional technicians require specific State approval.

c. For emergencies, the designated State representative may authorize initial diagnosis and stabilization by telephone or email. The Contractor shall document the authorizing individual, time, approved work, and spending limit. Telephone authorization shall be confirmed in writing as soon as practicable.

d. A request to respond to a service call does not constitute unlimited authorization to perform repairs or incur charges.

i. The State reserves the right to seek competitive bids for all major overhauls and repairs as may be deemed necessary by the Agency during the term of the Contract. The Contractor awarded the emergency generator maintenance contract as a result of this solicitation shall work cooperatively with any other Contractor the State may have to perform any major repairs.

ii. Major Repairs may be excluded from the scope of the Contract at the discretion of the Contract Monitor. However, if the Agency directs the

IFB for Department of General Services Page 19 of 38

Contractor to perform a Major Repair, the Contractor shall perform such work in accordance with the hourly rates and terms of this Contract.

Repair and replacement parts chargeable to the State shall be invoiced at cost, defined as the manufacturer’s charge to the Contractor, including freight and transportation charges as reflected on the manufacturer’s invoice. The State reserves the right to selectively audit Contractor invoices to verify part costs (COMAR 21.06.03.01). The Contractor must purchase parts from the least costly source. The invoice must include detailed cost breakdowns, including labor hours, labor rates, and copies of manufacturer invoices for parts.

e. Minor Repairs

i. When performing Minor Repairs, the Contractor shall replace all parts necessary to restore the part equipment to complete operational service.

“Part” is defined as the smallest component that effectively and completely accomplishes the required repair. In cases where cost or time considerations warrant replacing a larger assembly, the Superintendent and/or designee shall determine the appropriate course of action.

f. Parts and Materials

i. Unless otherwise directed, the Contractor shall furnish and install all parts – both those paid by the Contractor and those reimbursed by the

State – required for repairs in accordance with the specifications herein.

The Contractor shall provide replacement parts from the original manufacturers or substitute parts approved by the original manufacturer.

Repair and replacement parts chargeable to the State shall be invoiced at cost, defined as the manufacturer’s charge to the Contractor, including freight and transportation charges as reflected on the manufacturer’s charge to the Contractor including freight and transportation charges ass reflected on the manufacturer’s invoice. The State reserves the right to selectively audit the Contractor’s invoices to verify parts costs (COMAR

21.06.03.01). The Contractor must purchase parts from the least costly source. Invoices must include detailed cost breakdowns, including labor hours, labor rates, and copies of manufacturer invoices for parts.

O. WORKING HOURS

a. Regular service work shall be performed during normal working hours, 7:30 a.m.

to 4:00 p.m., Monday through Friday. Emergency and overtime work must be coordinated and approved in advance by the Superintendent and/or designee. Any callbacks (evenings, weekends, or holidays) and emergency repairs requiring overtime shall be the responsibility of the Contractor and at no additional cost to the State of Maryland.

IFB for Department of General Services Page 20 of 38

P. TEMPORARY GENERATOR

a. Emergency Generator Outage and Deployment Requirements

1. In the event that an emergency generator is out of service for a period of 24 hours or more, the Contractor shall immediately notify the Agency designee.

Upon notification, the Agency will evaluate the operational impact and determine whether the Contractor's deployment of a temporary generator is required.

2. In the event that an emergency generator is out of service AND the primary source of power to the facility is lost due to a mass power outage or other condition, the Agency shall determine – and in most cases require – that the

Contractor supply, install, and make operational a temporary generator to maintain essential services until primary power is fully restored and the emergency generator is returned to operational status in accordance with this

b. Responsibility Requirements

1. If the need for a temporary generator arises due to the Contractor’s negligence or failure to perform, all associated costs (rental, installation, fuel, labor, parts) shall be the responsibility of the Contractor.

2. The Contractor shall submit a unit cost for weekly and monthly rental of the temporary generator at the respective size (kW). This cost will be used for invoicing throughout the term of the contract. If the temporary generator is not required for an entire week or month, the Contractor shall bill for the use at a daily pro-rated rate based on the establishment unit cost.

3. The Unit Cost for Temporary Generator rental shall be broken down into six (6) separate categories. The pricing shall require bidders to provide rates for the following categories:

i. Weekly rate for:

a. 0-250 kW

b. 250-1000 kW

c. 4160 V

ii. Monthly rate for:

d. 0-250 kW

e. 250-1000 kW

IFB for Department of General Services Page 21 of 38

f. 4160 V

Q. SERVICE/TESTING RECOMMENDATIONS COMMUNICATIONS

a. The Contractor shall inform the State representative, who shall be present at the time of service and/or testing, of any operating upkeep procedures, based on the

Computerized Maintenance Management System platform work order, necessary between regular service by the Contractor. The Contractor shall report any abnormalities and make repair recommendations to the Superintendent or designee.

R. SERVICE TICKETS & RECORDS

a. It shall be the responsibility of the Contractor to add a log sheet to the log binder for each generator at each DGS-managed facility where a contract is in place.

The log sheet must state each Contractor servicing the equipment, the

Contractor's certified mechanic, and contain the date(s) of inspection or additional work, the unit serviced, the parts used, the labor hours used, the service/repairs provided, the problems encountered, and any additional work requested. The log sheets are the property of DGS and shall not be removed for any reason.

b. In addition, billings should be separated by Division, and within the Division, invoices must list the location, generator description, and services provided. The invoice shall be submitted on or before the 15th of the month following the service period to:

Department of General Services

Accounts Payable

301 W. Preston Street, Room 1309

Baltimore, MD 21201 dgs.accountspayable@maryland.gov

S. HOURLY BILING RATE

a. Each bidder must provide on the Bid Form included in the solicitation documents, where indicated, the hourly labor billing rates for each class of employee that will be used in the performance of each type of work on this

b. Overtime rates must be identified on the submitted price sheet. Overtime work should not be factored into routine repair proposals. If overtime is needed, it must be pre-approved by the Superintendent or Designee.

mailto:dgs.accountspayable@maryland.gov

IFB for Department of General Services Page 22 of 38

T. LOCAL CONDITIONS COVERING WORK

a. The successful Bidder shall cooperate with those in authority on the premises to prevent the entrance and exit of all unauthorized workmen or others whose presence is prohibited or undesirable, in order to observe all rules and regulations in force on the grounds and to prevent the loss of or damage to property of the

State and its employees. The successful Bidder shall repair any and all damage they may have caused to the building or property to the full satisfaction of the

Maintenance Supervisor.

U. ADDITIONAL TESTING REQUIREMENTS

a. The Contractor shall be present and work cooperatively with State representatives and other contractors as necessary to ensure the emergency generator and ATS functions as required for any and all buildings' annual fire alarm and elevator emergency power testing.

b. The Contractor shall work cooperatively with all parties when scheduling all tests to achieve an agreed-upon date.

c. Testing shall be conducted during off-business hours, holidays, and/or weekends at no cost to the State.

V. EQUIPMENT PERFORMANCE STANDARDS

a. The Contractor shall maintain at all times the standard of operation, efficiency, safety, capacity, etc., of the equipment as designed and installed. It is the intent that interrupted service and depreciation be kept to a minimum through an adequate preventive maintenance program.

W. MANUFACTURERS’ RECOMMENDATIONS

a. All maintenance procedures, preventive or otherwise, recommended by the manufacturer for each piece of equipment included in the contract shall become part of the Contract.

X. LIST OF EQUIPMENT

a. Refer to Exhibit 4 - OFM EMERGENCY GENERATOR EQUIPMENT

LIST

Y. REDUCTIONS for NON-PERFORMANCE or FAILURE TO MEET

STANDARDS

a. The following reductions shall be used in adjusting the Contractor’s invoice when the Contractor fails to perform any task required in these specifications or performs any tasks below the standards as required in these specifications.

IFB for Department of General Services Page 23 of 38

i. First Occurrence – written documentation notice from the Contract

Monitor to the Contractor.

ii. Second Occurrence – written documentation notice and deduction of

1/60th of the monthly invoice.

iii. Third Occurrence – written documentation notice and deductions of

1/30th of the monthly invoice amount.

iv. Reductions for “No Shows” may be based on the normal number of

Contractor’s personnel assigned to the building multiplied by the hours normally worked by the Contractor.

v. Reductions for below-standard work may be made if, after the second documented notification, the Contractor has not corrected the deficiency, and State workers must be assigned to perform the task. Reductions will be based on the hourly wage rate of the State employee assigned to perform the task multiplied by the number of hours required for State workers to perform the task.

vi. Reductions for non-performance may be made if the task was not done, and State workers must be assigned immediately to perform the task.

Reductions will be based on the hourly wage rate of the State employee assigned to perform the task, multiplied by the number of hours required for the State workers to perform the task.

vii. The referenced conditions (examples) may result in Termination of

Contract for Default by the Procurement Officer.

Z. DISPUTES ARISING FROM REDUCTIONS

a. Should the Contractor dispute the validity of a reduction determination made by the Building Manager, the Contractor may appeal the reduction to the

Superintendent within seven (7) calendar days of receiving notice of the reduction.

b. The Superintendent will review the reduction and make written documentation as to the reduction's validity within seven (7) days of the receipt of the appeal from the Contractor.

c. Should the Contractor disagree with the decision of the Superintendent, the

Contractor may appeal the Superintendent’s decision to the Assistant Secretary of the Office of Facilities Management, 29 St. Johns Street, Annapolis, Maryland

IFB for Department of General Services Page 24 of 38

21401, within seven (7) calendar days of the receipt of the Superintendent's decision.

2.4 Supplemental Category of Work Requirements and Responsibilities

See the attached Exhibit 5 - Facilities Maintenance Supplemental associated with this solicitation.

IFB for Department of General Services Page 25 of 38

3. Standard Terms and Conditions

3.1 Contract Initiation Requirements

Once all approvals have been obtained and the Contract is fully executed, the Procurement Officer may schedule a kickoff meeting to be held prior to commencement of Contract performance.

3.2 End of Contract Transition

The Contractor shall cooperate in the orderly transition of services from it to a subsequent contractor at the end of the contract term or upon receipt of a Notice of Termination from the State. Transition shall be provided in a prompt and timely manner and shall proceed in accordance with the schedule provided to the Contractor by the State in the Notice of Transition. Additional instructions regarding transition services may be provided in the event of a Notice of Termination issued by the State.

3.3 Invoicing

Submission of an invoice constitutes the Contractor’s verification that the information in the invoice is accurate as of the time of submission.

An invoice that does not satisfy the requirements of a Proper Invoice (as defined in COMAR

21.06.09) will not be processed for payment. To be considered a Proper Invoice, invoices must include the following information, without error:

A. Contractor name and address;

B. Remittance address;

C. Federal taxpayer identification (FEIN) number, social security number, as appropriate;

D. Each Region shall receive an invoice. Identify the building location and generator description/brand within each region;

E. Invoice period (i.e., time period during which services covered by the invoice were performed);

F. Invoice date;

G. Invoice number;

H. State assigned Contract number;

I. State assigned (Blanket) Purchase Order number(s);

J. Goods or services provided;

K. Amount due; and

L. Any additional documentation required by regulation or the Contract.

IFB for Department of General Services Page 26 of 38

Invoices shall be emailed to dgs.accountspayable@maryland.gov and the region’s contract monitor or designee.

Invoices that contain both fixed price and labor hour or time and material items shall clearly identify each item as either fixed price, labor hour, or time and material billing.

The State reserves the right to reduce or withhold Contract payment in the event the Contractor does not provide all required deliverables within the time frame specified in the Contract or otherwise breaches the terms and conditions of the Contract until such time as the Contractor brings itself into full compliance with the Contract.

The State is generally exempt from federal excise taxes, Maryland sales and use taxes, District of

Columbia sales taxes and transportation taxes. The Contractor, however, is not exempt from such sales and use taxes and may be liable for the same.

Invoices for final payment shall be clearly marked as “FINAL” and submitted when all work requirements have been completed and no further charges are to be incurred under the Contract. In no event shall any invoice be submitted later than 60 calendar days from the Contract termination date.

A. PAYMENT TO THE CONTRACTOR

1. At the end of each service interval, the Contractor shall submit their invoice for work performed as specified by the contract. The invoice submitted for payment shall not exceed the appropriate amount for the relevant location and must include a copy of the signed service ticket from each respective agency for the preventive maintenance service. Failure to submit the preceding may lead to deductions from the monthly invoice. For parts or labor over $2,500 per incident, per generator, include all invoices for any parts expenses, freight charges, and labor (if applicable), with signed service tickets and substantiating documentation that the Contractor’s expense limit has been met.

Each invoice submitted for payment must include the contract number and the company’s Federal

Tax Identification or Social Security Number.

3.3.1 Invoice Submission Schedule

The Contractor shall submit invoices in accordance with the following schedule:

A. For items of work for which there is one-time pricing (see Attachment B –The Price

Form), those items shall be billed in the month following the acceptance of the work by the State.

B. For Items of work for which there is annual pricing (see Attachment B–The Price

Form), those items shall be billed in equal monthly installments for the applicable

Contract year in the month following the performance of the services.

C. Invoices for work performed on a labor hour or time and materials basis shall be submitted on or before the 15th business day of the month following the end of the year.

mailto:dgs.accountspayable@maryland.gov

IFB for Department of General Services Page 27 of 38

3.3.2 Travel Reimbursement

Travel will not be reimbursed under this IFB.

3.4 Liquidated Damages

3.4.1 MBE Liquidated Damages

This section is inapplicable to this IFB.

3.4.2 Liquidated Damages other than MBE

This section is inapplicable to this IFB.

3.4.3 Problem Escalation Procedure

This section is inapplicable to this IFB.

3.5 Work Orders

This section is inapplicable to this IFB.

3.6 Payments by Electronic Funds Transfer

This section is inapplicable to this IFB.

3.7 Prompt Payment Policy

This section is inapplicable to this IFB.

3.8 Federal Funding Acknowledgement

This Contract does not contain federal funds.

3.9 Conflict of Interest Affidavit and Disclosure

The Bidder shall complete and sign the Conflict-of-Interest Affidavit and Disclosure (Attachment

I) and submit it with its Bid.

By submitting a Conflict-of-Interest Affidavit and Disclosure, the Contractor shall be construed as certifying that all Contractor Personnel and subcontractors are also without a conflict of interest as defined in COMAR 21.05.08.08A.

Additionally, a Contractor has an ongoing obligation to ensure that all Contractor Personnel are without conflicts of interest prior to providing services issued under the Contract. For policies and procedures applying specifically to Conflict of Interests, the Contract is governed by COMAR

21.05.08.08.

Participation in Drafting of Specifications: Disqualifying Event: Bidders are advised that Md.

Code Ann. State Finance and Procurement Article §13-212.1(a) provides generally that “an individual who assists an executive unit in the drafting of specifications, an invitation for bids, a

IFB for Department of General Services Page 28 of 38 request for proposals for a procurement, or the selection or award made in response to an invitation for bids or a request for proposals, or a person that employs the individual, may not: (1) submit a bid or proposal for that procurement; or (2) assist or represent another person, directly or indirectly, who is submitting a bid or proposal for that procurement.” Any Bidder submitting a

Bid in violation of this provision shall be classified as “not responsible.”

3.10 Non-Disclosure Agreement

This section is inapplicable to this IFB.

3.11 Maryland Healthy Working Families Act Requirements

This section is inapplicable to this IFB.

3.12 The State of Maryland’s Commitment to Purchasing Environmentally

Preferred Products and Services (EPPs)

This section is inapplicable to this IFB.

3.13 Insurance Requirements

The Contractor shall maintain, at a minimum, the insurance coverages outlined below, or any minimum requirements established by law if higher, for the duration of the Contract, including option periods, if exercised:

3.13.1 The following type(s) of insurance and minimum amount(s) of coverage are required:

A. Commercial General Liability - One million dollars ($1,000,000) combined single limit per occurrence for bodily injury, property damage, and personal and advertising injury and three million dollars ($2,000,000) annual aggregate. The minimum limits required herein may be satisfied through any combination of primary and umbrella/excess liability policies.

B. Worker’s Compensation - The Contractor shall maintain such insurance as necessary or as required under Workers’ Compensation Acts, the Longshore and Harbor Workers’

Compensation Act, and the Federal Employers’ Liability Act, to not be less than. one million dollars ($1,000,000) per occurrence (unless a state’s law requires a greater amount of coverage). Coverage must be valid in all states where work is performed.

3.13.2 The State shall be listed as an additional insured on the faces of the certificates associated with the coverages listed above, including umbrella policies, excluding Workers’

Compensation Insurance and professional liability.

3.13.3 All insurance policies shall be endorsed to include a clause requiring the insurance carrier to provide the Procurement Officer, by certified mail, not less than 30 days’ advance notice of any non-renewal, cancellation, or expiration. The Contractor shall notify the

Procurement Officer in writing if policies are canceled or not renewed within five (5) days of learning of such cancellation or nonrenewal. The Contractor shall provide

IFB for Department of General Services Page 29 of 38 evidence of replacement insurance coverage to the Procurement Officer at least 15 days prior to the expiration of the insurance policy then in effect.

3.13.4 Any insurance furnished as a condition of the Contract shall be issued by a company authorized to do business in the State.

3.13.5 The recommended awardee must provide current certificate(s) of insurance with the prescribed coverages, limits, and requirements set forth…

This is the start of the file's text. The full file is on GovTribe.