Text version

Sheet3

BOILER NATURAL GAS COMBUSTION PERFORMANCE TEST DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER__________________________________ DATE_________________
Boiler No. ____ Boiler Make, Model, Type_______________________________________________ Burner Make, Model, Type____________________________________________
Clock Time for Test PointHour - Min
Firing RateControl Output0 - 100%
Fuel Flow Control Valve0 - 100%
Combustion Air Damper0 - 100%
Forced Draft Fan VFDHz
Flue Gas AnalysesO2 - Test Instrument%
CO - Test InstrumentPPM
NOX-Test InstrumentPPM
O2 - Plant Data System%
Flue Gas Temp.Boiler OutletDegrees F
Economizer OutletDegrees F
DraftWindbox / FurnaceIn WC
Boiler Outlet / Econ OutletIn WC
Fuel DataRegulator Press - InletPSI
Regulator Press - OutletPSI / In WC
Burner PressPSI / In WC
Flow RateSCFH
Energy InputBTU/HR
Flame Appearance
Boiler Steam OutputFlow RateLB/HR
Press - Boiler / HeaderPSI
Boiler Water Level% Glass
FeedwaterPress - Econ In / OutPSI
Press - Control Valve InletPSI
Temp - Econ In / OutDegrees F
Temp - Boiler InletDegrees F
Deaerator Steam PressPSI
Test Personnel: __________________________________________________________________________________________________________________________________________
Notes:
Reference - Test Methods: Refer to VA Master Spec for the boiler, Part 3, Inspections and Tests.
VACO 183A 1/19/07

Sheet4

BOILER NO. 2 FUEL OIL COMBUSTION PERFORMANCE TEST DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER__________________________________DATE_________________
Boiler No. ____ Boiler Make, Model, Type_______________________________________________ Burner Make, Model, Type____________________________________________
Clock Time for Test PointHour - Min
Firing RateSubmaster0 - 100%
Fuel Flow Control Valve0 - 100%
Comb. Air Damper0 - 100%
FD Fan VFDHz
Flue Gas AnalysesO2 - Test Instrument%
CO - Test InstrumentPPM
NOX-Test InstrumentPPM
O2 - Plant Data System%
Smoke
Flue Gas Temp.Boiler OutletDegrees F
Economizer OutletDegrees F
DraftWindbox / FurnaceIn WC
Outlet - Boiler / EconIn WC
Fuel DataPress - Header / Fuel TrainPSI
Burner Press - Oil / AtomPSI
Flow RateGPH
Energy InputBTU/HR
Flame Appearance
Boiler Steam OutputFlowLB/HR
Press - Boiler / HeaderPSI
Boiler Water Level% Glass
FeedwaterPress - Econ In / OutPSI
Press - Control Valve InletPSI
Temp - Econ In / OutDegrees F
Temp - Boiler InletDegrees F
Deaerator Steam Press.PSI
Test Personnel: __________________________________________________________________________________________________________________________________________
Notes:
Reference - Test Methods: Refer to VA Master Spec for the boiler, Part 3, Inspections and Tests.
VACO 183A 1/19/07