Boiler Cut Sheet.pdf
PDF 420 KB Posted
- Attached to
- Z2AA--Boiler replacement-VA Regional Office. Jackson, MS. Federal contract opportunity
- Solicitation number
- 36C10E22R0001
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| MS20200051.pdf | ||
| 36C10E22R0001 0003.docx | DOCX document | |
| 36C10E22R0001 0002.docx | DOCX document | |
| 36C10E22R0001 0001.docx | DOCX document | |
| Boiler Technical Data.pdf | ||
| WD Number MS20200052.pdf | ||
| 36C10E22R0001_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Data Sheet
Benchmark 750-6000 with Edge Controller High Efficiency Boilers The AERCO Benchmark® (BMK) Water Boiler is designed for condensing application in any closed loop hydronic system. It delivers unmatched burner modulation to match energy input directly to fluctuating system.
No other product packs as much capacity into such a small footprint that fits through a standard door and can be transported in a freight elevator.
Energy Efficient To minimize emissions, the BMK Series is fitted with a low NOx burner whose emissions will meet the most stringent NOx and CO requirements.
The fully modulating burner also maintains AERCO standards for energy efficiency, longevity, reliability and construction quality.
The BMK Series comes standard with AERCO’s Patent Pending, Oxygen Level (O2) monitoring system. This monitoring system, designed to display the O2 level directly on the unit in real time, can also be remotely monitored via Modbus giving the customer the ability to measure the emissions level and fuel economy of the boiler without traditional combustion calibration devices.
Application and Plant Design The BMK boilers can be used as an individual unit or in modular arrangements and offers selectable modes of operation. In addition to controlling the boiler according to a constant set point, indoor/outdoor reset schedule or 4-20mA signal, one or more units can be integrated via Modbus communications protocol. For boiler plants ranging from 2-16 boilers, the AERCO Edge® built-in Boiler Sequencing Technology (BST)* can be utilized. The Benchmark can be easily integrated with a facility-wide Energy Management or Building Automation System.
Features
• Natural gas, propane, or dual fuel (model dependent)
• 20:1 turndown ratio (5%) depending on capacity
• Integrated O2 monitoring and alert for critical conditions
• 439 stainless steel fire tube heat exchanger
• Capable of variable primary flow Installations
• NOx emissions capable of 9PPM or less @ all firing rates *depending on capacity
• Compact footprint, light weight, freight elevator friendly
• Ducted combustion air capable
• Easy open access for service
• Acceptable vent materials AL29-4C, Polypropylene, PVC, cPVC (model dependent)
• Reliable quiet operation
• Optional gas train with VPS (Value Proving
System) for BMK Platinum 4000/5000/6000
Edge [i]
• Precise temperature vontrol
• On-board Boiler Sequencing Technology (BST)
• Controls options: constant setpoint, indoor/ outdoor reset, remote setpoint, 4-20mA signal or ModBus
*See BST System technical data sheet for additional system details and capabilities
Manager On
On On Off Off Off
Specifications
BMK
750 1000 1500 2000 2500 3000 4000 5000N 50004 60004
Boiler Category ASME Sect.IV
Gas Connections (NPT) 1’’ 2’’ 3” 2 / 3’’
Max. Gas Pressure 14’’ 2psi/10”4
Min. Gas Pressure 1 4’’ 14 / 4”4
Max. Allowed Working Pressure 160 PSIG 80PSIG/150 PSIG
Optional
Electrical Req.
120V/1PH/60Hz 2 13 FLA 16 FLA N/A
Electrical Req.
208V/3PH/60Hz 2 N/A 10 FLA N/A 19 FLA
Electrical Req.
460V/3PH/60Hz 2 N/A 5 FLA 12 FLA 9 FLA
Electrical Req.
575V/3PH/60Hz 2 N/A N/A N/A 7 FLA
Water Connect. (Flanged) 3’’ 4’’ 6” 6’’
Min. Water Flow (GPM) 12 25 35 75
Max. Water Flow (GPM) 175 250 350 500 600
Water Volume Gallons 16.25 14.25 44 40 58 55 75 110
Water Pressure Drop 3.0 PSIG @100 GPM 3.0 PSIG @170 GPM 3.0 PSIG
@218 GPM
3.0 PSIG
@261 GPM 5.0 PSIG @475 GPM 4.0 PSIG @500 GPM
Turndown Ratio 15:1 (7%) 20:1 (5%) 20:1 (5%) 15:1 (7%) 15:1 (7%) 15:1 (7%) 20:1 (7%) 12:1 (8%) 15:1 (7%)
Vent/Air Intake Connections 6 Inch 8 Inch 12 Inch Vent/10 Inch Air
Intake 14 Inch Optional/
12 Inch Flue Venting
Vent Materials AL29-4C Polypro, CPVC, PVC AL29-4C Polypro
Type of Gas Natural Gas, Propane Natural Gas, Propane, Dual Fuel, Natural Gas, Natural Gas Natural Gas, Dual Fuel
NOx Emissions <9ppm Capability4 ✓ ✓ <13 ppm ✓ ✓
Temp. Control Range 50ºF to 190ºF
Ambient Temp. Range 0ºF to 130ºF
Standard Listings & Approvals UL, CUL, CSD-1, ASME
Gas Train Operations FM Compliant or Factory Installed DBB (IRI) FM Compliant or Factory Installed DBB (IRI), VPS (Value Proving System)
FM Compliant, VPS (Val-ue Proving System)
Sound Rating dbA 65 65 70 70 72 72 75 79
Weight (dry) Ibs. 669 700 1406 1500 2,000 2,170 2200 3,000
Shipping Weight Ibs. 862 900 1606 1700 2,200 2,300 2350 3,800
1. Values are for natural gas FM compliant gas trains only. See Benchmark Gas Components & Supply Design Guide GF-2030 for propane, DBB & dual fuel gas train minimum gas pressure requirements.
2. See Benchmark Electrical Power Guide GF-2060 for Service Disconnect Switch amperage requirements.
3. BMK5000/6000 operating at standard gas pressure (>14” W.C.) can achieve 9 ppm NOx.
4. BMK5000/6000 low gas pressure option is available as a different style number. It operates between 4” and 10” of gas pressure.
Ratings
1Max output dependent upon application – see efficiency curves
Dimensions 750-4000 Dim: Inches
BMK Min Input
MBH
Max Input
MBH
Max Output1 MBH Efficiency Range Thermal Efficiency
80º to 180ºF
750 50 750 653-720 87%-98% 95.6%
1000 50 1000 870-960 87%-98% 96.8%
1500 75 1500 1305-1440 87%-98% 94.6%
2000 100 2000 1740-1920 87%-98% 94.6%
2500 167 2500 2175-2400 87%-98% 93.5%
3000 200 3000 2610-2880 87%-98% 94.6%
4000 267 4000 3480-3840 87%-98% 94.1%
5000N 250 4990 4341-4790 87%-98% 93.8%
5000 400 5000 4350-4800 87%-98% 93.9%
6000 400 6000 5220-5760 87%-98% 94.5%
BMK Models (Width) A (Depth) B (Height) C D E F G H I J K L
750 28’’ 24.5’’ 78’’ 34’’ 10.2’’ 9.6’’ 53’’ 21’’ 17.1’’ 4.5’ 5.1’’ 51.5’’
1000 28’’ 25’’ 78’’ 34’’ 10.2’’ 9.6’’ 53’’ 21’’ 17.1’’ 4.5’’ 5.1’’ 51.5’’
1500 28’’ 43.6’’ 78’’ 58.4’’ 6.6’’ 11.5’’ 57.8’’ 18’’ 42’’ 8.9’’ 4.4’’ 19.1’’
2000 28’’ 43.6’’ 78’’ 58.4’’ 7’’ 11.5’’ 57.8’’ 18’’ 42’’ 8.9’’ 4.4’’ 19.1’’
2500 28’’ 56’’ 78’’ 68.4’’ 5.6’’ 11.5’’ 57.8’’ 18’’ 42’’ 6.4’’ 4.4’’’ 27.1’’
3000 28’’ 56’’ 78’’ 68.4’’ 5.6’’ 11.5’’ 57.8’’ 18’’ 42’’ 6.4’’ 4.4’’’ 27.1’’’
4000 34” 63.5” 78.2” 80.6” 6” 12.4” 56” 21.4” 44.4” 9” 5.5” 28.7”
5000N 34” 63.5” 78.2” 80.6” 6” 12.4” 56” 21.4” 44.4” 9” 5.5” 28.7”
© 2020 AERCO
AERCO International, Inc. • 100 Oritani Drive • Blauvelt, NY 10913
USA: T: (845) 580-8000 • Toll Free: (800) 526-0288 • AERCO.com
Heating and Hot Water Solutions
Dimensions 5000/6000 Dim: Inches
BMK Models (Width) A (Depth) B (Height) C
5000 35’’ 89.3’’ 79.8’’
6000 35’’ 89.3’’ 79.8’’
File details come from the government source that posted it. Updated .