This document is a Limited Asbestos Survey report for Building 2011 at Fort Bliss, Texas, conducted by AnE Consulting, Inc. on August 18, 2016, for Pride Industries. The survey identified asbestos-containing materials (ACMs) in the building's flooring, specifically 12" white vinyl floor tiles with black mastic. Laboratory analysis confirmed 6% chrysotile asbestos content in the floor tile and mastic, which was observed to be in good condition and classified as non-friable.
The report recommends that if planned renovation or demolition activities will disturb the identified ACM, the materials must be abated by a licensed/accredited abatement contractor in accordance with Federal, State, and Local regulations. A mandatory 10-day notification is required prior to abatement. The estimated quantity of material to be replaced is 450 square feet. The survey was conducted in compliance with national environmental and safety standards, including NESHAP, AHERA, and ASHARA, to ensure proper identification and handling of potential asbestos-containing materials.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Limited Asbestos Survey at Building 2011
Fort Bliss, Texas
Prepared for:
PRIDE INDUSTRIES
P. 0. Box 31310 El Paso, Texas 79931
Prepared by:
.. ca,islJLTIJ"6, IJolC, 912 Texas Ave. Suite C El Paso, Texas 79901
Jose Moriel, Asb s Building Inspector TDSHS #60-3220, Expires 03/05/2017
Date of Inspection
August 18, 2016
August 22, 2016
PRIDE INDUSTRIES
Attn: Victor Duenas P. 0. Box 31310 El Paso, Texas 79931
RE: Limited Asbestos Survey at Building 2011 Fort Bliss, Texas
Dear Mr. Duenas, On August 18, 2016, AnE Consulting, Inc., conducted a limited asbestos survey of the structure at the above-referenced facility. The inspection report is attached.
We appreciate the opportunity to be of service to you. Please contact us with questions or comments, or if we may be of further assistance.
Sincerely, AnE Consulting, Inc.
Asbestos Consulting Agency TDSHS License #10-0441, expires 02/01/2017
Asbestos ilding Inspector TDSHS License #60-3220, Expires 03/05/2017
Enclosures: Asbestos Survey Report Laboratory reports with chain of custody documentation Texas asbestos licenses
AnE Consulting, Inc. • 912 Texas, Suite C • El Paso, Texas • 79901 +1915 532-3788Voice • +1915 532-3789 Fax• aneconsulting@att.net
V COMSILTDI&. l'IC, Purpose
The structure is located at Building 2011, Fort Bliss, Texas. Mr. Victor Duenas, of Pride Industries, requested that AnE Consulting, Inc. (AnE) conduct a limited survey for asbestos containing materials (ACMs) associated with the unit floor. This survey is intended for the identification and locations of Asbestos Containing Materials and may be utilized for future renovation and demolition projects.
Subject Property Overview
It is unknown when the structure was built. The area inspected consists of vinyl floor tiles. The unit was occupied at the time of the survey.
Inspection
Field activities were conducted on August 18, 2016, by Mr. Jose Moriel, licensed by the Texas
Department of State Health Services (TDSHS) as an Asbestos Building Inspector (license number 60-3220) with AnE Consulting Inc.
The survey was performed in general accordance with the National Emission Standards for Hazardous Air Pollutants (NESHAP) issued by the U.S. Environmental Protection Agency ( 40
CFR 61, Subpart M - National Emission Standard for Asbestos), the Asbestos Hazard Emergency Response Act (AHERA, 40 CFR 763), and the Asbestos School Hazard Abatement Reauthorization Act of 1990 (ASHARA, 40 CFR 763, Appendix C to Subpart E). These regulations generally require that, prior to any construction, renovation, or demolition, the area(s) where the work is to be performed shall be inspected by a properly trained and licensed or certified individual for the presence of ACMs that potentially may be disturbed during the work.
AnE employed a sampling strategy which involved identifying homogeneous materials throughout the proposed areas of work, and collecting bulk samples of the suspect materials for laboratory analysis for asbestos content. The term "homogeneous," as defined by in AHERA, means any material having the same color and texture, and having been installed in the same general time period.
The unit contained one (1) homogeneous area that was identified during the course of this survey, from which three (3) bulk samples were collected. Accessible areas of the unit were visually inspected. Destructive sampling was not conducted for this survey. These identified homogenous materials are summarized in Table 1 that follows.
Page 1 • Building 2011, Fort Bliss, TX - Limited Asbestos Survey • July 18, 2106 • (()2013 AnE Consulting, Inc.
Table 1-Summary of Homogenous Materials
Suspect ACM Location(s)
12" X 12" White Vinyl Floor Tile with Black Mastic Throughout
(Triple Layer)
The homogeneous materials were then assessed in terms of friability, condition, and quantity.
The term "friable" means a material that when dry can be reduced to a powder using hand pressure (25 TAC§ 295.32 (45)). Prior to sampling, each suspect asbestos material was properly wetted, and then each bulk sample was carefully extracted and placed in its own self-sealing container. Each container was wiped, sealed, and labeled with a unique sample number.
Appropriate chain of custody paperwork was completed listing each sample collected.
Laboratm.y Analysis
All samples were shipped under standard chain of custody protocols to Micro Analytical Services, Inc. (MAS) in Houston Texas. This facility is accredited by the National Voluntary
Laboratory Accreditation Program (NVLAP) for asbestos analysis, and licensed by the TDSHS as an asbestos laboratory (license number 30-0341).
The bulk samples were analyzed by Polarized Light Microscopy (PLM) coupled with Dispersion Staining in accordance with EPA Method 600/M4-82-020. The laboratory report with chain of custody documentation is attached to this report.
An ACM is defined as any material or product that contains greater trum one percent (1%) asbestos (25 TAC § 295.32 (15). Based on the laboratory data, the identified homogenous material was found to contain asbestos greater than one percent.
Table 2 - Summary of Asbestos-Containing Materials
Material Description Asbestos Content Condition / Friability
12" X 12" White Vinyl Floor Tile with Black Mastic 6% Chrysotile Non-Friable
(Triple Layer)
Page 2 • Building 2011, Fort Bliss, TX- Limited Asbestos Survey • July 18, 2106 • ©2013 AnE Consulting, Inc.
Summary of Findings
The following is a summary of findings based on the field activities conducted and laboratory analyses performed.
• Asbestos-containing 12" white vinyl floor tile black mastic was identified throughout.
The material was observed to be in good condition and considered non-friable. The estimated quantity of the material to be replaced is 450 square feet.
• All quantities are estimates and contractor shall field verify.
Recommendations
Based on the findings, AnE recommends the following:
• H the planned renovation or demolition activities will disturb the identified ACM, then the materials must be abated by a licensed/accredited abatement contractor in accordance with applicable Federal, State, and Local Rules and Regulations.
• A mandatory 10-day notification must be submitted in accordance with NESHAP for the planned abatement of the asbestos-containing materials. Written notification must be postmarked at least 10 working days prior to the start of the abatement. Responsibility for proper notification is that of the building owner, which may be delegated to the asbestos abatement contractor or consultant by the owner.
• H during the renovation or demolition project other suspect asbestos-containing materials are encountered, then the work must be stopped and the suspect asbestos containing material(s) should be tested for asbestos content.
Qualifications and limitations The discussions, findings, and recommendations contained herein are based upon data collected on the day of our investigation, the laboratory analysis of the samples collected, and typical practices accepted by the asbestos consulting profession. The scope of our work was limited to the subject areas and services stated in this report. Those building materials not inspected shall be assumed to contain asbestos unless laboratory analysis indicates otherwise.
Page 3 • Building 2011, Fort Bliss, TX - Limited Asbestos Survey • July 18, 2106 • ©2013 AnE Consulting, Inc.
:A-f.icro jlna[ytica{ Services, Inc. 11301 Richmond Ave. Ste.KIOOB♦Houston♦Tx 77082♦Phone(281)497-4SOO♦FIU(281)497-4517
NVLAP Lab No. 200618-0 TDSHS License No. 30-0341
CLIENT:
PROJECT:
PLM BULK ASBESTOS ANALYSIS REPORT
AnE Consulting, Inc.
Bldg. 2011
MAS JOB NO.: 12735-00
REPORT DATE: August 19, 2016
IDENTIFICATION: Asbestos, Bulk Sample Analysis, Quantitation by Visual Area Estimation
TEST METHOD: Polarized Light Microscopy with Dispersion Staining EPA Test Method 600/M4-82-020; (40CFR Part 763 Appendix E to Subpart E) &
EPA 600/R-93/116
STATEMENT OF LABORATORY ACCREDITATION
These samples were analyzed at Micro Analytical Services, Inc. in the Asbestos Laboratory at 11301 Richmond Ave. Suite Kl00B, Houston, Texas, 77082. The Laboratory holds accreditation from the National Institute of Standards and Technology under the National Voluntary Laboratory Accreditation Program (NVLAP). This laboratory is also licensed and authorized to perform as an Asbestos Laboratory in the State of Texas within the purview of Texas Civil Statutes, Article 4477-3a, as amended, so long as this license is not suspended or revoked and is renewed according to the rules adopted by the Texas Board of Health.
The samples were analyzed in general accordance with the procedures outlined in the Method for the Determination of Asbestos in Bulk Building Materials, EPN600/M4-82-020(40CFR Part 763 Appendix E to Subpart E) & EPA 600/R- 93/116 or the U.S. Environmental Protection Agency method, under AHERA, for the analysis of asbestos in building materials by polarized light microscopy. The results of each bulk sample relate only to the material tested and the results shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Specific questions concerning bulk sample results shall be directed to the Asbestos Bulk Laboratory at Micro Analytical Services, Inc.
Analyst: Tony T. Dang
94..icro jl.na{ytica[ Services, Inc. 11301 Richmond Ave. Ste. KlOOB♦Holl8ton♦Texas 77082♦Phone(281)497-4500♦Fax(281) 497-4517
AnE Consulting, Inc.
912 Texas Ave. Suite B El Paso, Texas 79901
Field ID/ Layer# Lab ID
2011-01 1
MAS378133
2011-01 2
MAS378133
2011-01 3
MAS378133
2011-01 4
MAS378133
2011-01 5
MAS378133
2011-01 6
MAS378133
2011-01 7
MAS378133
2011-01 8
MAS378133
2011-02 1
MAS378134
2011-02 2
MAS378134
2011-02 3
MAS378134
2011-02 4
MAS378134
2011-02 5
MAS378134
2011-02 6
MAS378134
Polarized Light Microscopy Analysis
Project Name: Bldg. 2011 Sample Description Asbestos
Detected?
(Yes/No)
White non-fibrous floor tile No
Yellow non-fibrous mastic No
White non-fibrous floor tile No
Yellow non-fibrous mastic No
Beige non-fibrous floor tile No
Yellow non-fibrous mastic No
Beige fibrous floor tile Yes
Black fibrous mastic Yes
White non-fibrous floor tile No
Yellow non-fibrous mastic No
Purple non-fibrous floor tile No
Yellow non-fibrous mastic No
Beige non-fibrous floor tile No
Yellow non-fibrous mastic No
MAS Project#: 12735-00 Date Received: 08/19/2016 Date Analyzed: 08/19/2016
Asbestos Non-Asbestos Constituents Constituents
100% Other
100% Mastic
100% Other
100% Mastic
100% Other
100%Mastic
2% Chrysotile 98% Other
6% Chrysotile 94%Mastic l00%Other
100% Mastic
100% Other
100% Mastic
100%0ther
100% Mastic
Samples have been analyz.ed by the EPA Interim Method 600/M4-82-020(40CFR Part 763 Appendix E to Subpart E) & EPA 600/R-93/I 16. The test results herein relate only to the sample submitred and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NlST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method.
NVLAP Lab Code: 2000618 IDSHS License: 30--0341
Analyzed by: Tony Dang Approved NVLAP Signatory: Tony Dang Page 1 of2
:Micro jlna{ytica{ Services, Inc. 11301 Richmond Ave. Ste. KIO0B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Polarized Light Microscopy Analysis
AnE Consulting, Inc. MAS Project #: 12735-00 912 Texas Ave. Suite B Date Received: 08/19/2016 El Paso, Texas 79901 Date Analyzed: 08/19/2016
Project Name: Bldg. 2011 Field ID/ Layer# Sample Description Asbestos Asbestos Non-Asbestos Lab ID Detected? Constituents Constituents
(Yes/No) (%) (%) 2011-02 7 Beige fibrous floor tile Yes 2% Chrysotile 98%Other
MAS378134
2011-02 8 Black fibrous mastic Yes 6% Chrysotile 94%Mastic
MAS378134
2011-03 1 White non-fibrous floor tile No 100%Other
MAS378135
2011-03 2 Yellow non-fibrous mastic No 100%Mastic
MAS378135
2011-03 3 White non-fibrous floor tile No 100% Other
MAS378135
2011-03 4 Yellow non-fibrous mastic No 100% Mastic
MAS378135
2011-03 5 Beige non-fibrous floor tile No 100% Other
MAS378135
2011-03 6 Yellow non-fibrous mastic No 100% Mastic
MAS378135
2011-03 7 Beige fibrous floor tile No 3% Cellulose MAS378135 97% Other 2011-03 8 Black fibrous mastic Yes 6% Chrysotile 94% Mastic
MAS378135
Samples have been analyzed by the EPA lnterim Method 600/M4-82-020(40CFR Part 763 Appendix E to Subpart E) & EPA 600/R-93/116. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services {MAS). The above percentages ate visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval. oc endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method.
NVLAP Lab Code: 2000618 TDSHS License; 30-0341
Analyzed by: Tony Dang Approved NVLAP Signatory: Tony Dang Page 2 of2
9.1.icro Jlna{ytica[ Services, Inc. 11301 RichmondAve.SuitcKIOOB•Hous1on♦Texas 77082♦Phonc (:i:8l)497-4S00♦Flllt(281) 497-4517
Asbestos Bulle Sample Chain of Custody
Company: AnE Consultin2. Inc. Contact: Project Name:
Address: 912 Texas Ave. Ste.C Bill to: Nick Rodriwiez
Project#:
City: El Paso Email: a....ecr,nst>l4i~c:11¾-.nd State/Zip: Texas 79902 V, PO#:
Phone: (915)532-3788 I Fax: (915)532-3789 Date Collected: MAS Project#: J:::. ?~~" .
Tum around time (circle): Emergency 8 2-day 3-day 4-day 5-day
Field ID Lab ID Sample Description Sample Location Comments r71Jll-o I -~-iRJ_~< 12.1' 'F lcxv +·, le, tf.XJv ~\d..o. ?O\\ Y1 hl,·a.., Tx (J? '<hi:-1 -~ if \J\V),11 flee(+, \p_ fi.~ -~7R.t~~ Ill.+~ ~r.lL Mn,;+· t ...
j
Relinquished br-:::::!f·~: ...... - · ~--~,,..,...\ : :-t,t :;-·, ·_- _ ,. __ Date:._O~ ~~J -.·- -7~/~ _ __ Time:. __ /)-_'/Y"wL..--__ --
Received by=-~- -'d'>H. =--------~Date: ____ 4..,L~-- '/__1~_1b_~ __ Time:_ .... _4-__ • ..,.~'-"'"'-<;--J-~(--
Relinquished by:. __________ Date: ______ Time: ____ ___ _
Received by:. ___________ Date: ________ Time: _______ _
Page_of_ MAS.FlOJ
TEXAS DEPARTMENT OF STATE HEALTH SERVICES
ANE CONSULTING lNC is certifot! to perform a.s a
Asbestos ~onsultant Agency in the State of Texas within the purview of Texas Occupations Code, chapter 1954, so long as this license is not suspended or revoked and is 1·enewed according to the "'les adopted by the Texas Boa.rd of Health.
P~ /~//
DAVID LAKEY, M.D.
COMMISSIONER OF HEALTH
License Number: 10_0441 Expiration Date: 2/1/2011
Control Number: 96762 (Void After Expiration Date)
VOID IF ALTERED NON-TRANSFERABLE
~'t:. -~~~ ~b,__,._,,_.fJ.t,~ ,,,~I~,,;, - ;f..~*.l~ :.:., ,,t!' 11 ... ., • '•<\ -~·-•• :} f'-t' J . , ... , . \ \\.'" .
:I:~ . • ~/;-'-;P f,t,·•.',:Y1;' '\' ·:· . . ,.,- .\ .. ,i•-- • ...... .. --,~· ·- · ~ ~ ·:'"· • ·· .. ' , ,, ,,. J
\ ~~ •,i , • I ....,,, ~ ': 1~~-;J.f. .t
:i-. . .,,.;' --·
TEXAS n·EP J\RTMENT OF STATE HEAL TH. SERVICES
MICRO AN"ALYTICAL SERVICES INC
is certjfiei to perform as a
Asbestos· Laboratory
PCM,PLM .
in the State of Texas within the pttrview of Texas Occupations Code. chapter 1954. so long as· this license is not suspended or revoked and is renewed according to theintles adopted by the Te..'(as Board of Health.
. KlRK. COLE, INTERIM
COMMISSIONER OF HEALTH
License Number: 300341 Expiration·Date: 1/25/2018
Control Number: 96091 (Void After Expiration Date)