BL6 Work Order History Tulsa and Muskogee JANUARY 2109-DECEMBER 2019 (2).xlsx

XLSX spreadsheet 74 KB Posted

Attached to
FM Tulsa and O&M Muskogee Procurement
Solicitation number
47PH0220R0016
Issued by

View the file

Other files

File Type Posted
Solicitation Amendment 0002 47PH0220R0016.pdf PDF
Solicitation Amendment 0001 46PH0220R0016 .pdf PDF
1 Attachment 1a Addendum to OK Eastern IUOE Local 627 CBA 2018 01 02.pdf PDF
5 Changes to Solicitation 47PH0220R0016.pdf PDF
4 Questions and Answers to Solicitation 47PH0220R0016.pdf PDF
3 Solicitation 47PH0220R0016 Pre-Proposal Conference Agenda Tulsa and Muskogee.pptx PPTX presentation
2 REVISED Figure B 3 Pricing of Services 8 year.xlsx XLSX spreadsheet
FIGURE L1 Management Plan Baseline Worksheet .xlsx XLSX spreadsheet
Exhibit C7 PBS Waste Audits (1) (2).pdf PDF
Exhibit M8 - Misc Best Practices Shave Energy (3).pdf PDF
BL3 Building Location Information Tulsa OK OK0063ZZ (2).pdf PDF
Figure B 2 SCA DOL CBA COMBINATION WD .xlsx XLSX spreadsheet
Attachment 3 SCA Wage Determination Muskogee County June 30 2020 WD2015 5320 (1).pdf PDF
Exhibit C3 - Surveilence Form 1181-A (1).xls XLS spreadsheet
BL5 Roof Information for Tulsa Federal Building OK0063ZZ (1) (3).pdf PDF
Section J Documents.pdf PDF
Exhibit C5 - Erosion and Sediment Control (1) (2).pdf PDF
Attachment 1 CBA Tulsa and Muskogee Oklahoma (1).pdf PDF
Exhibit C1 Building Information Sheet Tulsa Federal Building OK0063ZZ (2).pdf PDF
Figure B 3 Pricing of Services 8 year.xlsx XLSX spreadsheet
Exhibit C4 Building Exterior and Hardscape Plan (2).pdf PDF
Exhibit M3 - Environmental Sustainable Products (1) (2).pdf PDF
BL7 Energy and Water Monthly Report Template.pdf PDF
Exhibit C1 Building Information sheet Muskogee (1) (2).pdf PDF
Exhibit M1 and C2 - FM Quality Assurance Surveillance Plan (1).pdf PDF
BL1 Fire Extinguisher Report Tulsa and Muskogee Buy (2) (2).pdf PDF
Exhibit M9 - 2018 GSA Preventative Maintenance Guide Tulsa and Muskogee Buy (1).pdf PDF
Exhibit C6 Recycle Solid Water Trash Report .pdf PDF
Exhibit M4 - Bldg Op Plan Template (1) (2).pdf PDF
Exhibit M5 - Smart Buildings (3).pdf PDF
Figure L 2 Past Performance Questionnaire.pdf PDF
BL5 Roof Information for Muskogee Federal Courthouse OK0041ZZ (1).pdf PDF
Exhibit M2 - Green Purchasing Report (1) (2).pdf PDF
BL8 PM Schedule Muskogee Federal Building (1) (1).pdf PDF
BL8 PM Schedule Tulsa Federal Building (1).pdf PDF
Muskogee O and M and Tulsa FM Solicitation Spec September 03 2020.pdf PDF
Attachment 4 Table of Deliverables Tulsa and Muskogee New Procurement.pdf PDF
Attachment 2 Form 98 From DOL Tulsa Muskogee New Buy (4).txt TXT text file
Attachment 3 SCA Wage Determination Tulsa County June 30 2020 WD2015 5318 (1).pdf PDF
BL2 Inventory List Muskogee Federal Building OK0041ZZ (2).pdf PDF
Exhibit M7 - Qualificaiton of Electrical Testing Technicians (1) (3).pdf PDF
FIGURE B 1 Staffing Declaration .xls XLS spreadsheet
BL3 Building Location Information Muskogee OK OK0041ZZ (2).pdf PDF
Exhibit M6 - Water Treatment (1) (3).pdf PDF
BL2 Inventory List Tulsa Federal Building OK0063ZZ (2).pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

List of Work Orders

Work OrderWORK ORDER HISTORY JANUARY 2019- DECEMBER 2019Work TypeWork Sub-TypeStatusLocation DescriptionAssetAsset TagEquipment IDTarget StartIs dynamicDynamic Job Plan appliedSiteLocation
18-38212543USMS 16 light bulbs outWRSERVCALLCLOSEOK0041ZZ-Floor 011/2/19 10:52 AMNO0762833
19-39031051Room 205 light outOMIINITIALCLOSEOK0041ZZ-Floor 021/17/19 11:36 AMNO0762834
19-39031064Room 210 light outOMIINITIALCLOSEOK0041ZZ-Floor 021/17/19 11:40 AMNO0762834
19-39031074Room 325 light outOMIINITIALCLOSEOK0041ZZ-Floor 031/17/19 11:45 AMNO0762835
19-39031084Room 430 light outOMIINITIALCLOSEOK0041ZZ-Floor 041/17/19 11:49 AMNO0762836
19-39154486Courtroom #1 lights outWRSERVCALLCLOSEOK0041ZZ-Floor 021/22/19 10:37 AMNO0762834
19-39335707Hang pictures in Judge West's ChambersWRUTILMISCCLOSEOK0041ZZ-Floor 041/28/19 9:00 AMNO0762836
19-39257152Room 527 missing electrical coverGSAINORMALCLOSEOK0041ZZ-Floor 051/29/19 11:04 AMNO0762837
19-39257502North Exit Sally Port magnetic lock on door is looseGSAINORMALCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE1/29/19 11:10 AMNO0761246
19-392578525th Floor Women's Restroom toilet seat looseGSAINORMALCLOSEOK0041ZZ-Floor 051/29/19 11:15 AMNO0762837
19-392580165th Floor Mechanical Room remove punch bag holderGSAINORMALCLOSEOK0041ZZ-Floor 051/29/19 11:19 AMNO0762837
19-392582195th Floor Hallway wall outside of 537 has a dent in it and needs repairedGSAINORMALCLOSEOK0041ZZ-Floor 051/29/19 11:22 AMNO0762837
19-392584714th Floor Stairwell light out on stairs going up to 5th FloorGSAINORMALCLOSEOK0041ZZ-Floor 041/29/19 11:26 AMNO0762836
19-392586764th Floor Men's Restroom handicap toilet is marked "out of order"GSAINORMALCLOSEOK0041ZZ-Floor 041/29/19 11:30 AMNO0762836
19-392591894th Floor Judge Shreder's 1 wrong ceiling tile and 2 stained ceiling tiles, the 2 stained need to check for leaks...written up continuouslyGSAINORMALCLOSEOK0041ZZ-Floor 041/29/19 11:39 AMNO0762836
19-392598114th Floor Judge Shreder's Conf Room has 6 lights outGSAINORMALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-12893911/29/19 11:46 AMNO0762836
19-39260464Judge West's Hallway missing ceiling tile and 2 stained in hallwayGSAINORMALCLOSEOK0041ZZ-Floor 041/29/19 11:53 AMNO0762836
19-39260645Judge West's Chambers light out in chandelierGSAINORMALCLOSEOK0041ZZ-Floor 041/29/19 11:57 AMNO0762836
19-39335553Probation has 2 stained ceiling tiles (1 in kitchen and 1 in Kyle's Office)/Repeat - Check for leaksGSAINORMALCLOSEOK0041ZZ-Floor 012/1/19 10:59 AMNO0762833
19-39342273Light bulb out by Room 422OMIINITIALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-12893912/1/19 3:07 PMNO0762836
19-39342290Light bulb out by Room 230OMIINITIALCLOSEOK0041ZZ-Floor 021289765OK0041F34A002OK0041ZZ-LGI-12897652/1/19 3:12 PMNO0762834
19-39342302Parking light bulb outOMIINITIALCLOSEOK0041ZZ-Parking1289828OK0041L04A001OK0041ZZ-LGE-12898282/1/19 3:15 PMNO0762838
19-393423082nd Floor Hallway stained ceiling tileOMIINITIALCLOSEOK0041ZZ-Floor 022/1/19 3:18 PMNO0762834
19-39368909USMS Men's Locker Room sink on the left has a continuous dripWRSERVCALLCLOSEOK0041ZZ-Basement2/4/19 10:34 AMNO0762830
19-39368923USMS Men's Locker Room toilet seat brokenWRSERVCALLCLOSEOK0041ZZ-Basement2/4/19 10:34 AMNO0762830
19-402162955th Floor light out in hallwayOMIINITIALCLOSEOK0041ZZ-Floor 051289392OK0041F34A005OK0041ZZ-LGI-12893922/11/19 3:22 PMNO0762837
19-402163094th Floor light out in stairwellOMIINITIALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-12893912/11/19 3:30 PMNO0762836
19-40216318Basement light out Men's Locker RoomOMIINITIALCLOSEOK0041ZZ-Basement1290427OK0041F34A006OK0041ZZ-LGI-12904272/11/19 3:34 PMNO0762830
19-40427635Condensate drain line was disconnected on Boiler #1GSAINORMALCLOSEOK0041ZZ-Basement-Boiler Mechanical Room954674OK0041B02F001OK0041ZZ-BLR-HW1-B02F0012/20/19 10:36 AMNO0788600
19-40427866Domestic hot water tank was leaking again/Needs completely re-piped from the domestic hot water boiler to the storage tankGSAINORMALCLOSEOK0041ZZ-Basement-Boiler Mechanical Room955078OK0041H03A001OK0041ZZ-WHT-02-H03A-12/20/19 10:53 AMNO0788600
19-40428894Wooden extension ladder needs removed in Sally PortGSAINORMALCLOSEOK0041ZZ-Parking2/20/19 11:05 AMNO0762838
19-40429327Several breaker panels were unlocked in the basementGSAINORMALCLOSEOK0041ZZ-Basement2/20/19 11:11 AMNO0762830
19-40429642There had been a chemical spill in the boiler plantGSAINORMALCLOSEOK0041ZZ-Basement-Boiler Mechanical Room2/20/19 11:16 AMNO0788600
19-40429862Chemical pump for the closed loop heating water needs correctly mounted/This should be secured to the wall or beam postGSAINORMALCLOSEOK0041ZZ-Basement-Boiler Mechanical Room2/20/19 11:19 AMNO0788600
19-40430234Tower chemical controller for the cooling tower had 5 alarms on it even though it wasn't running/These should be resetGSAINORMALCLOSEOK0041ZZ-Roof367274OK0041C09B001OK0041ZZ-CTR-C09B-12/20/19 11:25 AMNO0762840
19-40430773AHU 8 VFD display wasn't workingGSAINORMALCLOSEOK0041ZZ-Floor 04367253OK0041A11C001OK0041ZZ-AHU-01-A11C-12/20/19 11:34 AMNO0762836
19-40449766Remove pipes and conduit from USMS Fitness Room - 2 hrs UTWRUTILMISCCLOSEOK0041ZZ-Basement2/21/19 10:16 AMNO0762830
19-40454587Room 315 light outOMIINITIALCLOSEOK0041ZZ-Floor 031289383OK0041F34A003OK0041ZZ-LGI-12893832/22/19 11:37 AMNO0762835
19-404546035th Floor Hallway light outOMIINITIALCLOSEOK0041ZZ-Floor 051289392OK0041F34A005OK0041ZZ-LGI-12893922/22/19 11:42 AMNO0762837
19-40454621Basement Men's Restroom toilet seat looseOMIINITIALCLOSEOK0041ZZ-Basement2/22/19 11:49 AMNO0762830
19-40487941Recommend use of spill sock during coldest winter months to address potential for wet floor in basement confined space for boiler stackOMIINITIALCLOSEOK0041ZZ-Basement2/26/19 8:23 AMNO0762830
19-40605001Cell Block Interview Room 133C lights out (Attorney side and Prisoner side)WRSERVCALLCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-12898902/27/19 10:25 AMNO0762833
19-406071793rd Floor Jury Room Men's Restroom toilet runs continuouslyGSAINORMALCLOSEOK0041ZZ-Floor 032/27/19 2:13 PMNO0762835
19-406072063rd Floor Jury Room Women's Restroom door stickingGSAINORMALCLOSEOK0041ZZ-Floor 032/27/19 2:18 PMNO0762835
19-40607218Room 305 door handle is looseGSAINORMALCLOSEOK0041ZZ-Floor 032/27/19 2:21 PMNO0762835
19-40607233Exterior globe light out in back Parking LotGSAINORMALCLOSEOK0041ZZ-Parking-Parking Lot2/27/19 2:25 PMNO0788777
19-40607289AHU 8 is making loud noiseGSAINORMALCLOSEOK0041ZZ-Floor 04367253OK0041A11C001OK0041ZZ-AHU-01-A11C-12/27/19 2:28 PMNO0762836
19-406076873rd Floor Stairwell light outOMIINITIALCLOSEOK0041ZZ-Floor 032/27/19 2:36 PMNO0762835
19-40607697Remove tape and paint in front of Room 201OMIINITIALCLOSEOK0041ZZ-Floor 022/27/19 2:40 PMNO0762834
19-40607713Boiler Room light outOMIINITIALCLOSEOK0041ZZ-Basement-Boiler Mechanical Room1290427OK0041F34A006OK0041ZZ-LGI-12904272/27/19 2:44 PMNO0788600
19-40607722AHU 7 sweep floorOMIINITIALCLOSEOK0041ZZ-Floor 032/27/19 2:47 PMNO0762835
19-406077612nd Floor by Judge Payne's Office light outOMIINITIALCLOSEOK0041ZZ-Floor 021289765OK0041F34A002OK0041ZZ-LGI-12897652/27/19 2:51 PMNO0762834
19-40609017Main Entrance three lights outGSAINORMALCLOSEOK0041ZZ-Floor 012/28/19 8:00 AMNO0762833
19-40631703Hang 3 AED (1 in Basement, 1 Main Entrance 1st Fl, 1 on 3rd Fl) - 1 Hour UTWRUTILMISCCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE2/28/19 11:30 AMNO0761246
19-40766228Sweep AHU 8OMIINITIALCLOSEOK0041ZZ-Floor 043/6/19 8:00 AMNO0762836
19-40766237Replace all bulbs in stairwells all floorsOMIINITIALCLOSEOK0041ZZ-Entire Building3/6/19 8:00 AMNO0762831
19-40766242Bugs in light by Room 210OMIINITIALCLOSEOK0041ZZ-Floor 023/6/19 8:00 AMNO0762834
19-40766248Bugs in light by Room 315OMIINITIALCLOSEOK0041ZZ-Floor 033/6/19 8:00 AMNO0762835
19-40994425Surge protector remote monitor 4L1 in alarm - canceled alarm, but won't resetCMCORRECTCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE3/11/19 9:00 AMNO0761246
19-40794949Check all room temperatures on 4th FloorWRSERVCALLCLOSEOK0041ZZ-Floor 043/11/19 10:07 AMNO0762836
19-410969671st Floor Janitors Closet sink stopped upWRSERVCALLCLOSEOK0041ZZ-Floor 013/12/19 10:00 AMNO0762833
19-41096979North Sally Port overhead door not operatingGSAINORMALCLOSEOK0041ZZ-Parking3/12/19 11:00 AMNO0762838
19-41097029Moved clock 1 hour forward Courtroom 2CMCORRECTCLOSEOK0041ZZ-Floor 023/13/19 8:00 AMNO0762834
19-41097069Door closer by Sally Port broke where JCI park trucksWRSERVCALLCLOSEOK0041ZZ-Parking3/13/19 9:00 AMNO0762838
19-40991124Wet ceiling tile in Room 408WRSERVCALLCLOSEOK0041ZZ-Floor 043/13/19 9:12 AMNO0762836
19-40992426Two AC units not working in USMS Control RoomWRSERVCALLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE3/13/19 3:30 PMNO0761246
19-41860859Rooms 408 and 409 too coldGSAINORMALCLOSEOK0041ZZ-Floor 043/18/19 8:13 AMNO0762836
19-418778061st Floor Men's Restroom water leakGSAINORMALCLOSEOK0041ZZ-Floor 013/18/19 9:00 AMNO0762833
19-41877974Adjust timer for outside lightsOMIINITIALCLOSEOK0041ZZ-Exterior-Outside1289828OK0041L04A001OK0041ZZ-LGE-12898283/20/19 3:19 PMNO0788601
19-41877991Clean AHU 3 floorOMIINITIALCLOSEOK0041ZZ-Basement367228OK0041A11A003OK0041ZZ-AHU-01-A11A-33/20/19 3:24 PMNO0762830
19-41878000Clean AHU 9 floorOMIINITIALCLOSEOK0041ZZ-Floor 05-Room-529954688OK0041A11C002OK0041ZZ-AHU-01-A11C-23/20/19 3:27 PMNO0788770
19-42049254Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab.WRSERVCALLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE367272OK0041F15A001OK0041ZZ-ALM-07-F15A-14/1/19 8:00 AMNO0761246
19-42095202Room 212 light outOMIINITIALCLOSEOK0041ZZ-Floor 021289765OK0041F34A002OK0041ZZ-LGI-12897653/29/19 3:32 PMNO0762834
19-42095216Room 315 light outOMIINITIALCLOSEOK0041ZZ-Floor 031289383OK0041F34A003OK0041ZZ-LGI-12893833/29/19 3:36 PMNO0762835
19-420952214th Floor Men's Restroom toilet seat looseOMIINITIALCLOSEOK0041ZZ-Floor 043/29/19 3:39 PMNO0762836
19-422311395th Floor Server Room missing ceiling tileGSAINORMALCLOSEOK0041ZZ-Floor 054/3/19 2:59 PMNO0762837
19-42231155Probation stained ceiling tile in Jeff's OfficeGSAINORMALCLOSEOK0041ZZ-Floor 014/3/19 3:02 PMNO0762833
19-42231165Room 310 stained ceiling tile in Pat Keaney's OfficeGSAINORMALCLOSEOK0041ZZ-Floor 034/3/19 3:06 PMNO0762835
19-422311732nd Floor Men's Restroom low water pressureGSAINORMALCLOSEOK0041ZZ-Floor 024/3/19 3:09 PMNO0762834
19-42231194Basement Bathrooms both toilet seats are looseGSAINORMALCLOSEOK0041ZZ-Basement4/3/19 3:16 PMNO0762830
19-422459131st Floor light out in Marshals OfficeOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-12898904/4/19 9:00 AMNO0762833
19-422459311st Floor Men's Restroom sink leakingOMIINITIALCLOSEOK0041ZZ-Floor 014/4/19 9:00 AMNO0762833
19-42245396Install Courts SignageGSAINORMALCLOSEOK0041ZZ-Entire Building4/5/19 9:00 AMNO0762831
19-42292510Chain broke on drive thru gateOMIINITIALCLOSEOK0041ZZ-Parking-Parking Lot954745OK0041G03B002OK0041ZZ-FNG-G03B-24/11/19 10:00 AMNO0788777
19-422933461st Floor light out in LobbyOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-12898904/11/19 10:06 AMNO0762833
19-42293365Judge Payne's faucet brokeOMIINITIALCLOSEOK0041ZZ-Floor 024/11/19 10:11 AMNO0762834
19-427108241st Floor Lobby lights outOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-12898904/16/19 2:42 PMNO0762833
19-427108405th Floor Men's Restroom toilet not workingOMIINITIALCLOSEOK0041ZZ-Floor 054/16/19 2:45 PMNO0762837
19-42710929Caulk needs repaired by roof doorOMIINITIALCLOSEOK0041ZZ-Roof4/16/19 3:07 PMNO0762840
19-43309124Stained ceiling tile in Probation OfficeOMIINITIALCLOSEOK0041ZZ-Floor 014/24/19 8:00 AMNO0762833
19-43309135Light out in 1st Floor LobbyOMIINITIALCLOSEOK0041ZZ-Floor 014/24/19 8:00 AMNO0762833
19-433091462nd Floor Bankruptcy light dimmer switch not workingOMIINITIALCLOSEOK0041ZZ-Floor 024/24/19 8:00 AMNO0762834
19-43413051No AC in USMS Control RoomGSAINORMALCLOSEOK0041ZZ-Floor 01954683OK0041A13B002OK0041ZZ-ACU-A13B-24/30/19 8:53 AMNO0762833
19-43499001Stained ceiling in Judge White's OfficeOMIINITIALCLOSEOK0041ZZ-Floor 025/1/19 8:00 AMNO0762834
19-43499036Stained ceiling in Marshals OfficeOMIINITIALCLOSEOK0041ZZ-Floor 055/1/19 8:00 AMNO0762837
19-43494324Leaks on 4th Floor, entire west side of building from the south to the north. Under window seals throughoutGSAINORMALCLOSEOK0041ZZ-Floor 045/2/19 11:19 AMNO0762836
19-43495189Room 526 has a ceiling leakGSAINORMALCLOSEOK0041ZZ-Floor 055/2/19 11:29 AMNO0762837
19-43572953Room 210 toilet won't flushOMIINITIALCLOSEOK0041ZZ-Floor 025/8/19 8:00 AMNO0762834
19-43572992Basement Men's Restroom toilet won't flushOMIINITIALCLOSEOK0041ZZ-Basement5/8/19 8:00 AMNO0762830
19-43573942Basement Men's Restroom loose toiletGSAINORMALCLOSEOK0041ZZ-Basement5/9/19 10:59 AMNO0762830
19-43573960Basement Men's Restroom handicap rail is looseGSAINORMALCLOSEOK0041ZZ-Basement5/9/19 11:05 AMNO0762830
19-435739725th Floor US Attorney's Office too hotGSAINORMALCLOSEOK0041ZZ-Floor 055/9/19 11:08 AMNO0762837
19-444105602nd Floor Hallway lights outOMIINITIALCLOSEOK0041ZZ-Floor 021289765OK0041F34A002OK0041ZZ-LGI-12897655/20/19 8:00 AMNO0762834
19-444105974th Floor Hallway lights outOMIINITIALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-12893915/20/19 8:00 AMNO0762836
19-44531800Replace water level tube on green roof holding tankOMIINITIALCLOSEOK0041ZZ-Roof5/24/19 10:50 AMNO0762840
19-44531816Room 245 door frame dustyOMIINITIALCLOSEOK0041ZZ-Floor 025/24/19 10:56 AMNO0762834
19-44662512USMS Lloyd's Office window blind pulled to top and won't releaseWRSERVCALLCLOSEOK0041ZZ-Floor 015/30/19 3:26 PMNO0762833
19-447866033rd Floor Hallway light outOMIINITIALCLOSEOK0041ZZ-Floor 031289383OK0041F34A003OK0041ZZ-LGI-12893836/4/19 8:00 AMNO0762835
19-447866145th Floor Stairwell light outOMIINITIALCLOSEOK0041ZZ-Floor 051289392OK0041F34A005OK0041ZZ-LGI-12893926/4/19 8:00 AMNO0762837
19-44786625Replace Jace batteriesOMIINITIALCLOSEOK0041ZZ-Basement367264OK0041C04A002OK0041ZZ-BAS-01-C04A-26/4/19 8:00 AMNO0762830
19-44862357Basement Hallway hole in ceiling tile outside Marshals areaGSAINORMALCLOSEOK0041ZZ-Basement6/11/19 9:56 AMNO0762830
19-448644435th Floor Hallway stained ceiling tile outside Room 527, check for leaks and replace ceiling tileGSAINORMALCLOSEOK0041ZZ-Floor 056/11/19 10:03 AMNO0762837
19-45762876USMS wall in Interview Room A can now be prepared to be paintedWRSERVCALLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE6/24/19 9:31 AMNO0761246
19-45762900USMS door in Interview Room B has a mark that needs to be touched upWRSERVCALLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE6/24/19 9:38 AMNO0761246
19-45763003USMS 15 most wanted sign needs to be hung in the hallway where the old sign was locatedWRUTILMISCCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE6/24/19 9:44 AMNO0761246
19-45763124Hang new cork board in USMS Hallway leading to the kitchen areaWRUTILMISCCANOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE6/24/19 9:51 AMNO0761246
19-45763178Probation ceiling tile collapsed in back office (Nick's Office)GSAINORMALCLOSEOK0041ZZ-Floor 016/24/19 10:05 AMNO0762833
19-45763308Stained ceiling tile outside Room 528GSAINORMALCLOSEOK0041ZZ-Floor 056/24/19 10:35 AMNO0762837
19-457633455th Floor Hallway emergency exit light is dim when testedGSAINORMALCLOSEOK0041ZZ-Floor 056/24/19 10:42 AMNO0762837
19-457633874th Floor Small Men's Restroom door not closing properlyGSAINORMALCLOSEOK0041ZZ-Floor 046/24/19 10:55 AMNO0762836
19-45763514Exit light not testing correctly outside Room 411GSAINORMALCANOK0041ZZ-Floor 046/24/19 11:13 AMNO0762836
19-45764475Exit light not testing correctly outside Room 411GSAINORMALCLOSEOK0041ZZ-Floor 046/24/19 11:22 AMNO0762836
19-45764514Exit light not testing correctly at 3rd Floor South StairwellGSAINORMALCLOSEOK0041ZZ-Floor 036/24/19 11:30 AMNO0762835
19-45764578Exit light not testing correctly outside Room 327 and 317GSAINORMALCLOSEOK0041ZZ-Floor 036/24/19 11:46 AMNO0762835
19-457645962nd Floor Hallway water fountain on North end overshootsGSAINORMALCLOSEOK0041ZZ-Floor 021288104OK0041G26A001OK0041ZZ-EWC-12881046/24/19 11:51 AMNO0762834
19-45764615Stained ceiling tile outside Room 229GSAINORMALCLOSEOK0041ZZ-Floor 026/24/19 11:57 AMNO0762834
19-457646241st Floor Men's Restroom toilet seat looseGSAINORMALCLOSEOK0041ZZ-Floor 016/24/19 12:00 PMNO0762833
19-457646361st Floor Men's Restroom sink is leakingGSAINORMALCLOSEOK0041ZZ-Floor 016/24/19 12:05 PMNO0762833
19-45788914Judges Hallway lights outOMIINITIALCLOSEOK0041ZZ-Floor 031289383OK0041F34A003OK0041ZZ-LGI-12893836/25/19 8:51 AMNO0762835
19-45788928Room 321 stained ceiling tileOMIINITIALCLOSEOK0041ZZ-Floor 036/25/19 8:55 AMNO0762835
19-45905894Room 407 light outOMIINITIALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-12893916/27/19 8:00 AMNO0762836
19-45905913Room 327 light outOMIINITIALCLOSEOK0041ZZ-Floor 031289383OK0041F34A003OK0041ZZ-LGI-12893836/27/19 8:00 AMNO0762835
19-45905928Basement Women's Locker Room lights outOMIINITIALCLOSEOK0041ZZ-Basement1290427OK0041F34A006OK0041ZZ-LGI-12904276/27/19 8:00 AMNO0762830
19-46054106Room 403 lock not workingOMIINITIALCLOSEOK0041ZZ-Floor 047/2/19 8:00 AMNO0762836
19-46054116Basement Men's Restroom toilet cloggedOMIINITIALCLOSEOK0041ZZ-Basement7/2/19 8:00 AMNO0762830
19-46054136Basement Hall door needs adjustedOMIINITIALCLOSEOK0041ZZ-Basement7/2/19 8:00 AMNO0762830
19-46135307Probation Rooms 105, 106A and 107A too hotWRSERVCALLCLOSEOK0041ZZ-Floor 01367218OK0041A11A001OK0041ZZ-AHU-01-A11A-17/8/19 8:32 AMNO0762833
19-46210702Basement USMS Area too hotWRSERVCALLCLOSEOK0041ZZ-Basement367218OK0041A11A001OK0041ZZ-AHU-01-A11A-17/10/19 10:16 AMNO0762830
19-47006665Patch/repair holes in wall USMS Office Space (Tom's old office)WRSERVCALLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE7/17/19 8:55 AMNO0761246
19-470069054th Floor Men's Restroom (across from Room 411) toilet is constantly flushingWRSERVCALLCLOSEOK0041ZZ-Floor 047/17/19 9:51 AMNO0762836
19-470917981st Floor fire extinguisher sign needs remountedOMIINITIALCLOSEOK0041ZZ-Floor 017/23/19 8:00 AMNO0762833
19-47096100Light out in hallway by Room 411OMIINITIALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-12893917/23/19 8:00 AMNO0762836
19-47081953Backflow is leaking by the boilersGSAINORMALCLOSEOK0041ZZ-Basement-Boiler Mechanical Room954659OK0041V09A002OK0041ZZ-BFP-V09A-27/23/19 1:58 PMNO0788600
19-47085369All water fountain filters need to be changedGSAINORMALCLOSEOK0041ZZ-Entire Building1288104OK0041G26A001OK0041ZZ-EWC-12881047/23/19 2:28 PMNO0762831
19-47146507North outside spigot drippingGSAINORMALCLOSEOK0041ZZ-Exterior-Outside7/24/19 2:18 PMNO0788601
19-47412925Light out in 3rd Floor HallwayOMIINITIALCLOSEOK0041ZZ-Floor 031289383OK0041F34A003OK0041ZZ-LGI-12893837/31/19 8:00 AMNO0762835
19-47413808Light out in 4th Floor HallwayOMIINITIALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-12893917/31/19 8:00 AMNO0762836
19-47414182Basement Men's Restroom toilet stopped upOMIINITIALCLOSEOK0041ZZ-Basement7/31/19 8:00 AMNO0762830
19-47496532Parking lot spots numbers are fadingGSAINORMALCLOSEOK0041ZZ-Parking-Parking Lot8/7/19 8:41 AMNO0788777
19-479253751st Floor light out in LobbyOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-12898908/15/19 12:04 PMNO0762833
19-47925523Basement light cover broken by back doorOMIINITIALCLOSEOK0041ZZ-Basement8/15/19 12:10 PMNO0762830
19-479256002nd Floor Men's Restroom toilet handle brokenOMIINITIALCLOSEOK0041ZZ-Floor 028/15/19 12:15 PMNO0762834
19-47861460South Drive Thru Gate downGSAINORMALCLOSEOK0041ZZ-Parking-Parking Lot954745OK0041G03B002OK0041ZZ-FNG-G03B-28/19/19 12:35 PMNO0788777
19-48007900Leave the AC on the 1st and 5th floors on until 7pm for 8/21 and 8/22 (USMS 1.5 hours for both days)WROUTLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE8/21/19 2:07 PMNO0761246
19-48724552Leave the AC on until 7pm for 8/27, 8/28 and 8/29 - USMS working late 3 daysWROUTLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE8/27/19 11:56 AMNO0761246
19-487308151st Floor Probation no air flow in Room 111GSAINORMALCLOSEOK0041ZZ-Floor 01954813OK0041C05A015OK0041ZZ-VAV-C05A-158/28/19 2:58 PMNO0762833
19-487308271st Floor Probation light out in bathroom and light out in hallway outside bathroomGSAINORMALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-12898908/28/19 3:04 PMNO0762833
19-48777257Light out in 1st Floor Jail CellOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-12898908/30/19 9:03 AMNO0762833
19-48777281South gate not workingOMIINITIALCLOSEOK0041ZZ-Parking-Parking Lot954745OK0041G03B002OK0041ZZ-FNG-G03B-28/30/19 9:08 AMNO0788777
19-48929222Emergency light by secured entrance in the basement didn't stay on when testedGSAINORMALCLOSEOK0041ZZ-Basement1548230OK0041ZZ-ELT-15482309/5/19 10:59 AMNO0762830
19-48929240Lightning suppression is coming off on several places on the roofGSAINORMALCLOSEOK0041ZZ-Roof1287048OK0041F38A001OK0041ZZ-LPS-12870489/5/19 11:07 AMNO0762840
19-48929250Remove concrete debris from roof by chimneyGSAINORMALCLOSEOK0041ZZ-Roof9/5/19 11:12 AMNO0762840
19-48929260Exhaust fan by chimney was noisy and vibrating a lot. It needs to be marked as to what fan it is. (Restroom exhaust fan)GSAINORMALCLOSEOK0041ZZ-Roof367275OK0041F27A002OK0041ZZ-FAN-02-F27A-29/5/19 11:16 AMNO0762840
19-48929305AHU #7 condensate pan was overflowingGSAINORMALCLOSEOK0041ZZ-Floor 03367248OK0041A11B002OK0041ZZ-AHU-01-A11B-29/5/19 11:35 AMNO0762835
19-48929320AHU #6 filters weren't marked with an install date on themGSAINORMALCLOSEOK0041ZZ-Floor 02367308OK0041F32A006OK0041ZZ-FLT-F32A-69/5/19 11:40 AMNO0762834
19-48929824Hang 3 new soap dispensers (1 in Basement Hallway, 1st Floor Lobby Hallway, 1 in Marshals Hallway)WRUTILMISCCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE9/5/19 2:16 PMNO0761246
19-491845573rd Floor Men's Restroom toilet not flushingOMIINITIALCLOSEOK0041ZZ-Floor 039/13/19 3:29 PMNO0762835
19-50117047USMS Cell Block B toilet stopped upWRSERVCALLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE9/20/19 8:25 AMNO0761246
19-50444001Light out in back stairwell at 5th FloorGSAINORMALCLOSEOK0041ZZ-Floor 051289392OK0041F34A005OK0041ZZ-LGI-128939210/2/19 8:25 AMNO0762837
19-504440203 lights out in Marshals OfficeGSAINORMALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-128989010/2/19 8:32 AMNO0762833
19-50468796Install 4 TV mounts for USMS (2 - Gym, 1 - Warrant Sup Office in Basement, 1 - 5th Floor)WRSERVCALLCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE10/4/19 12:09 PMNO0761246
19-50468820Hang cork bulletin board in USMS OfficeWRUTILMISCCLOSEOK0041ZZ-Floor 0110/4/19 12:09 PMNO0762833
19-50494004Light fixtures out in passageways on 2nd FloorOMIINITIALCLOSEOK0041ZZ-Floor 021289765OK0041F34A002OK0041ZZ-LGI-128976510/8/19 8:00 AMNO0762834
19-50494041Light fixtures out in passageways on 3rd FloorOMIINITIALCLOSEOK0041ZZ-Floor 031289383OK0041F34A003OK0041ZZ-LGI-128938310/8/19 8:00 AMNO0762835
19-50494052Light fixtures out in passageways on 4th FloorOMIINITIALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-128939110/8/19 8:00 AMNO0762836
19-506142372 lights out in 1st Floor LobbyGSAINORMALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-128989010/11/19 11:42 AMNO0762833
19-51430716Door sticking Room 315OMIINITIALCLOSEOK0041ZZ-Floor 0310/21/19 12:27 PMNO0762835
19-51430835Fluorescent light out Basement Passageway by GymOMIINITIALCLOSEOK0041ZZ-Basement1290427OK0041F34A006OK0041ZZ-LGI-129042710/21/19 12:55 PMNO0762830
19-51633394Several lights out in USMS Area 1st FloorOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-128989010/28/19 8:00 AMNO0762833
19-51633419Lights out 1st Floor Main Entrance LobbyOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-128989010/28/19 8:00 AMNO0762833
19-518130414th Floor North Men's Bathroom sink leakingOMIINITIALCLOSEOK0041ZZ-Floor 0411/7/19 8:00 AMNO0762836
19-51813120Batteries for fire system need replaced on 5th FloorOMIINITIALCLOSEOK0041ZZ-Floor 0511/7/19 8:00 AMNO0762837
19-51813623All three condensing units are dirty in the parking garageGSAINORMALCLOSEOK0041ZZ-Parking11/7/19 2:51 PMNO0762838
19-51813652Room 402 door threshold is missing rubber pieceGSAINORMALCLOSEOK0041ZZ-Floor 0411/7/19 2:57 PMNO0762836
19-51813664Main Lobby has 2 lights outGSAINORMALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-128989011/7/19 3:01 PMNO0762833
19-51813683Stained ceiling tile in Judge Shreder's Kitchen/Check for leaks and replace ceiling tileGSAINORMALCLOSEOK0041ZZ-Floor 0411/7/19 3:06 PMNO0762836
19-51813696Stained ceiling tile in hallway between Judge West and Judge Shreder/Check for leaks and replace ceiling tileGSAINORMALCLOSEOK0041ZZ-Floor 0411/7/19 3:11 PMNO0762836
19-51813713Temperature in Room 401 is 77 degreesGSAINORMALCLOSEOK0041ZZ-Floor 0411/7/19 3:18 PMNO0762836
19-51888515Lights out in jail cells 1st FloorOMIINITIALCLOSEOK0041ZZ-Floor 011289890OK0041F34A001OK0041ZZ-LGI-128989011/14/19 8:00 AMNO0762833
19-52940293Loose bolts on cooling tower just laying on it rustingGSAINORMALCLOSEOK0041ZZ-Roof367274OK0041C09B001OK0041ZZ-CTR-C09B-111/19/19 1:00 PMNO0762840
19-52943033Lots of green in tower/May want to adjust the chemical treatment programGSAINORMALCLOSEOK0041ZZ-Roof367274OK0041C09B001OK0041ZZ-CTR-C09B-111/19/19 1:00 PMNO0762840
19-52943122Lighting in Mechanical Room 5th Floor needs upgraded/GSA to purchase the light fixturesGSAINORMALCLOSEOK0041ZZ-Floor 0511/19/19 1:00 PMNO0762837
19-52943146Conduit on supply air sensor on AHU9 needs re-attachedGSAINORMALCLOSEOK0041ZZ-Floor 05-Room-529954688OK0041A11C002OK0041ZZ-AHU-01-A11C-211/19/19 1:00 PMNO0788770
19-529439882 alarms on tower water controllerGSAINORMALCLOSEOK0041ZZ-Roof367274OK0041C09B001OK0041ZZ-CTR-C09B-111/19/19 1:00 PMNO0762840
19-52944024Insulation on heating water supply line by the fire cabinets in the basement needs repairedGSAINORMALCLOSEOK0041ZZ-Basement11/19/19 1:00 PMNO0762830
19-52944091AHU 2 missing cover on supply air sensorGSAINORMALCLOSEOK0041ZZ-Basement367223OK0041A11A002OK0041ZZ-AHU-01-A11A-211/19/19 1:00 PMNO0762830
19-52944137Remove rag and tape on piping on CHW supply line by the pumps in the plant/If there is a leak please repairGSAINORMALCLOSEOK0041ZZ-Basement11/19/19 1:00 PMNO0762830
19-52944192Exit light in the plant by the CHW pumps not working at the time of my inspectionGSAINORMALCLOSEOK0041ZZ-Basement1548228OK0041ZZ-EXS-154822811/19/19 1:00 PMNO0762830
19-52944244Pop off leaking on domestic hot water tankGSAINORMALCLOSEOK0041ZZ-Basement-Boiler Mechanical Room955078OK0041H03A001OK0041ZZ-WHT-02-H03A-111/19/19 1:00 PMNO0788600
19-527628341st Floor Women's Restroom handicap stall has a missing coat hangerGSAINORMALCLOSEOK0041ZZ-Floor 0111/20/19 9:07 AMNO0762833
19-52782884Hang pictures in Room B10 US MarshalsWRUTILMISCCLOSEOK0041ZZ-Basement11/20/19 10:58 AMNO0762830
19-527835113rd Floor Hallway exit light out just outside Room 317GSAINORMALCLOSEOK0041ZZ-Floor 031548228OK0041ZZ-EXS-154822811/20/19 1:00 PMNO0762835
19-527835494th Floor Hallway exit light out just outside Men's RestroomGSAINORMALCLOSEOK0041ZZ-Floor 041548228OK0041ZZ-EXS-154822811/20/19 1:00 PMNO0762836
19-52944392Replace dimmer switch in Probation area 1st FloorOMIINITIALCLOSEOK0041ZZ-Floor 0111/26/19 8:00 AMNO0762833
19-52944442Replace lamps Jury Assembly area 3rd FloorOMIINITIALCLOSEOK0041ZZ-Floor 0311/26/19 8:00 AMNO0762835
19-53121999Hang TV's in the Basement Marshals GymWRUTILMISCCLOSEOK0041ZZ-Basement12/3/19 8:12 AMNO0762830
19-531287625th Floor Judges Elevator Room has 2 missing ceiling tilesGSAINORMALCLOSEOK0041ZZ-Floor 0512/4/19 1:00 PMNO0762837
19-53128779Room 502 has a missing ceiling tileGSAINORMALCLOSEOK0041ZZ-Floor 0512/4/19 1:00 PMNO0762837
19-53128800Room 502 has 2 lights outGSAINORMALCLOSEOK0041ZZ-Floor 051289392OK0041F34A005OK0041ZZ-LGI-128939212/4/19 1:00 PMNO0762837
19-53129070Room 401 light out in vestibule area of bathrooms and light switch cover is looseGSAINORMALCLOSEOK0041ZZ-Floor 041289391OK0041F34A004OK0041ZZ-LGI-128939112/4/19 1:00 PMNO0762836
19-53136934Replace incandescent lamps with LED lamps in Judge Shreder's ChambersOMIINITIALCLOSEOK0041ZZ-Floor 0412/5/19 8:00 AMNO0762836
19-53139836Replace fluorescent lights out in Basement passageway SouthOMIINITIALCLOSEOK0041ZZ-Basement1290427OK0041F34A006OK0041ZZ-LGI-129042712/5/19 8:00 AMNO0762830
19-53131922Hang 2 AED's (1 on 5th Floor Hallway and 1 in Basement Hallway)WRUTILMISCCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE12/5/19 3:03 PMNO0761246
19-54241547Globe light out outside main entranceOMIINITIALCLOSEOK0041ZZ-Exterior-Outside12/19/19 8:00 AMNO0788601
19-54241565Two lights out in US Marshal Basement ElevatorOMIINITIALCLOSEOK0041ZZ-Basement1290427OK0041F34A006OK0041ZZ-LGI-129042712/19/19 8:00 AMNO0762830
19-42054863Next, go to the Specifications tab in this Work Order and fill in all 7 mandatory values with regard to the Master Fire Alarm Control Panel in this building. Save.WRCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE4/1/19 8:00 AMNO0761246
19-42054864Go back to the work order tab then down to the Multiple Assets, Locations and CIs section. Click on New Row. Using the double arrows next to the asset and select the Master Fire Alarm Panel. Save. (Basic Manual pg 191 to add an asset first if needed.)WRCLOSEOK0041ZZ-ED EDMONDSON U.S. COURTHOUSE4/1/19 8:00 AMNO0761246
18-38219961Judge Michael's Chambers Library (Janie's Office) too coldWRSERVCALLCLOSEOK0063ZZ-Floor 011/2/19 1:39 PMNO0762861
18-38219667Lobby CSO Station fingerprints on the top trim on the glass partitionsGSAINORMALCLOSEOK0063ZZ-Floor 011/2/19 2:30 PMNO0762861
18-38219942Throughout building cold at 7:45 as per BAS, at 9:16 the building is still cold (VAV 1A09F1 set point 73.0 actual 61.1)GSAINORMALCLOSEOK0063ZZ-Entire Building1/2/19 4:07 PMNO0762859
18-38229630Sweep Chiller RoomOMIINITIALCLOSEOK0063ZZ-Basement-Chiller Mechanical Room1/3/19 3:41 PMNO0788805
18-38229646Basement South Men's Restroom floor dirtyOMIINITIALCLOSEOK0063ZZ-Basement1/3/19 3:47 PMNO0762858
18-38234492Replaced diaphragm on urinal 2nd Floor North Men's RRCMCORRECTCLOSEOK0063ZZ-Floor 021/4/19 8:00 AMNO0762862
18-38234427Judge Michael's Office light outWRSERVCALLCLOSEOK0063ZZ-Floor 011/4/19 9:00 AMNO0762861
18-38234474Judge Kern's Courtroom too warmWRSERVCALLCLOSEOK0063ZZ-Floor 021/4/19 1:00 PMNO0762862
18-38256476Trash in exterior stairwell and window wellsGSAINORMALCLOSEOK0063ZZ-Exterior-Outside1/7/19 10:45 AMNO0788806
18-38256497Dead plants in flower potsGSAINORMALCLOSEOK0063ZZ-Exterior-Outside1/7/19 10:50 AMNO0788806
18-38257405Judge Kern's Kitchen light bulb outWRSERVCALLCLOSEOK0063ZZ-Floor 021/7/19 11:43 AMNO0762862
18-38264125Judge Michael's Chambers light out in Janie's Office (Library)WRSERVCALLCLOSEOK0063ZZ-Floor 011/8/19 8:19 AMNO0762861
18-382577561st floor south hallway HVAC register very noisyGSAINORMALCLOSEOK0063ZZ-Floor 011/8/19 8:30 AMNO0762861
18-38264217Clean backside of Basement North and South StairwellsGSAINORMALCLOSEOK0063ZZ-Basement1/8/19 11:12 AMNO0762858
18-382642262nd Floor North Men's Restroom door dirty inside by push plateGSAINORMALCLOSEOK0063ZZ-Floor 021/8/19 11:16 AMNO0762862
19-38285748Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building1/9/19 6:00 AMNO0762859
19-38285716DOL no hot waterWRSERVCALLCLOSEOK0063ZZ-Floor 031/9/19 9:45 AMNO0762863
19-38286503901 Space kitchen sink leakingWRSERVCALLCLOSEOK0063ZZ-Basement1/9/19 10:00 AMNO0762858
19-38287596Trash in Basement LobbyGSAINORMALCLOSEOK0063ZZ-Basement1/10/19 11:39 AMNO0762858
19-38287606Basement South Men's Restroom dirty under urinalGSAINORMALCLOSEOK0063ZZ-Basement1/10/19 11:43 AMNO0762858
19-38287747Bankruptcy Fitness Room Men's Shower drain dirtyGSAINORMALCLOSEOK0063ZZ-Basement1/10/19 12:41 PMNO0762858
19-382877703rd Floor South Women's Restroom smells/Check drainGSAINORMALCLOSEOK0063ZZ-Floor 031/10/19 12:52 PMNO0762863
19-382877823rd Floor South Men's Restroom floor under urinal is dirtyGSAINORMALCLOSEOK0063ZZ-Floor 031/10/19 12:57 PMNO0762863
19-382880292nd Floor Jury Restroom faucet making noiseGSAINORMALCLOSEOK0063ZZ-Floor 021/10/19 2:30 PMNO0762862
19-382880372nd Floor South Restroom Hall stained ceiling tileGSAINORMALCLOSEOK0063ZZ-Floor 021/10/19 2:36 PMNO0762862
19-38288074Lobby CSO Station cleaner residue on stainless barGSAINORMALCLOSEOK0063ZZ-Floor 011/10/19 2:51 PMNO0762861
19-38339040Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building1/11/19 6:00 AMNO0762859
19-38305377Light covers drooping in Hallway in front of 3rd Floor CourtroomGSAINORMALCLOSEOK0063ZZ-Floor 031/11/19 9:04 AMNO0762863
19-38338751Bankruptcy Court IT Office hears water drippingWRSERVCALLCLOSEOK0063ZZ-Floor 011/11/19 11:03 AMNO0762861
19-38838481Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building1/14/19 6:00 AMNO0762859
19-38801167Judge Rasure's Office lights outWRSERVCALLCLOSEOK0063ZZ-Floor 011/14/19 9:55 AMNO0762861
19-38836540Adjusted temperatures in DOLCMCORRECTCLOSEOK0063ZZ-Floor 031/14/19 11:00 AMNO0762863
19-38837656Judge Kern's Kitchen has broken glass on floorWRSERVCALLCLOSEOK0063ZZ-Floor 021/14/19 2:00 PMNO0762862
19-388630952nd Floor South Women's Restroom lights outCMCORRECTCLOSEOK0063ZZ-Floor 021/15/19 10:00 AMNO0762862
19-38901195Judge Rasure's Office too hotWRSERVCALLCLOSEOK0063ZZ-Floor 011/15/19 3:56 PMNO0762861
19-39029153Judge Michael's Chambers too coldWRSERVCALLCLOSEOK0063ZZ-Floor 011/16/19 10:39 AMNO0762861
19-390310131st Floor South Hallway needs sweptOMIINITIALCLOSEOK0063ZZ-Floor 011/17/19 11:23 AMNO0762861
19-390310272nd Floor North Hallway double doors have hand prints at top of doorOMIINITIALCLOSEOK0063ZZ-Floor 021/17/19 11:28 AMNO0762862
19-39151461DOL lights outWRSERVCALLCLOSEOK0063ZZ-Floor 031/22/19 10:05 AMNO0762863
19-39171404Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building1/23/19 6:00 AMNO0762859
19-39171340Michael Williams Office too cold/no air flowWRSERVCALLCLOSEOK0063ZZ-Floor 011/23/19 9:33 AMNO0762861
19-39199342Floor under door to CSO post has dirt buildup and floor dusty in the areaGSAINORMALCLOSEOK0063ZZ-Basement1/24/19 2:09 PMNO0762858
19-39199533Floor in front of South Elevator 2 is dirtyGSAINORMALCLOSEOK0063ZZ-Basement1/24/19 2:14 PMNO0762858
19-39199724Lobby West wall brass trim pieces above the wood are coming upGSAINORMALCLOSEOK0063ZZ-Floor 011/24/19 2:18 PMNO0762861
19-39229556Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building1/25/19 6:00 AMNO0762859
19-39229338Judge Rasure's Office too coldWRSERVCALLCLOSEOK0063ZZ-Floor 011/25/19 11:47 AMNO0762861
19-39248663Michael Williams Office getting cold/No air blowingWRSERVCALLCLOSEOK0063ZZ-Floor 011/28/19 11:00 AMNO0762861
19-392486862nd Floor Hallway floor dusty and has small bits of debrisGSAINORMALCLOSEOK0063ZZ-Floor 021/28/19 12:11 PMNO0762862
19-39248706Repeated flame failure alarms on Boiler 1GSAINORMALCLOSEOK0063ZZ-Basement-Boiler Mechanical Room955380OK0063B02F001OK0063ZZ-BLR-HW4-B02F-11/28/19 12:14 PMNO0788804
19-39256511DOL spilled white dots on floorWRSERVCALLCLOSEOK0063ZZ-Floor 031/29/19 7:58 AMNO0762863
19-39278186Pick up small recycling bin and deliver large one to IRSWRUTILMISCCLOSEOK0063ZZ-Floor 021/29/19 4:02 PMNO0762862
19-39279315Empty recycle bins on 2nd & 3rd Floors and GSA OfficesWRUTILMISCCLOSEOK0063ZZ-Entire Building1/29/19 4:11 PMNO0762859
19-39282497Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building1/30/19 6:00 AMNO0762859
19-39282451Replaced 2 bulbs 3rd Floor North Women's RestroomCMCORRECTCLOSEOK0063ZZ-Floor 031/30/19 9:38 AMNO0762863
19-39288223US Trustee Office lights outCMCORRECTCLOSEOK0063ZZ-Floor 021/30/19 10:42 AMNO0762862
19-39310059Judge Kern's Courtroom tables and bench are dustyWRSERVCALLCLOSEOK0063ZZ-Floor 021/31/19 9:00 AMNO0762862
19-39315656Heating water pump base needs cleanedOMIINITIALCLOSEOK0063ZZ-Basement1/31/19 3:17 PMNO0762858
19-393156643rd Floor North Stairwell door slamsOMIINITIALCLOSEOK0063ZZ-Floor 031/31/19 3:20 PMNO0762863
19-39315671Basement South Stairwell floor needs sweptOMIINITIALCLOSEOK0063ZZ-Basement1/31/19 3:23 PMNO0762858
19-39315876Basement North Stairwell floor has scuff marksOMIINITIALCLOSEOK0063ZZ-Basement1/31/19 3:49 PMNO0762858
19-393159501st Floor in front of South Elevator floor dirtyOMIINITIALCLOSEOK0063ZZ-Floor 011/31/19 3:52 PMNO0762861
19-393160572nd Floor Hallway has scuff marks and coffee stainsOMIINITIALCLOSEOK0063ZZ-Floor 021/31/19 3:56 PMNO0762862
19-39335650Judge Michael's Office 2 can lights outWRSERVCALLCLOSEOK0063ZZ-Floor 012/1/19 8:17 AMNO0762861
19-39335689Replace belt - Fan Coil Unit in USMS AreaCMCORRECTCLOSEOK0063ZZ-Basement2/1/19 11:21 AMNO0762858
19-39367461Basement by Elevator #3 cove base dusty in cornerGSAINORMALCLOSEOK0063ZZ-Basement2/4/19 8:58 AMNO0762858
19-39375244Patch holes in sidewalk left by contractorWRUTILMISCCLOSEOK0063ZZ-Exterior-Outside2/4/19 10:00 AMNO0788806
19-39406502Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building2/6/19 6:00 AMNO0762859
19-39406484Cleaned EMCOR shop areaCMCORRECTCLOSEOK0063ZZ-Basement2/6/19 8:00 AMNO0762858
19-40993741Catwalk to roof access has no hand, toe railsWRUTILMISCCLOSEOK0063ZZ-Penthouse2/7/19 8:00 AMNO0762865
19-39408162Michael Williams and Sue's Office lights outWRSERVCALLCLOSEOK0063ZZ-Floor 012/7/19 9:38 AMNO0762861
19-394139863rd Floor Women's Restroom faucet runs slowly, appears to be cloggedGSAINORMALCLOSEOK0063ZZ-Floor 032/7/19 11:16 AMNO0762863
19-39478026Judge Rasure's Office too coldWRSERVCALLCLOSEOK0063ZZ-Floor 012/8/19 11:05 AMNO0762861
19-394912841st Floor Hallway floor dirtyGSAINORMALCLOSEOK0063ZZ-Floor 012/8/19 4:29 PMNO0762861
19-394924013rd Floor Women's Restroom interior door handle dirtyGSAINORMALCLOSEOK0063ZZ-Floor 032/8/19 4:32 PMNO0762863
19-40213376Basement North Hallway 1st light fixture going into hallway is dimGSAINORMALCLOSEOK0063ZZ-Basement2/11/19 9:00 AMNO0762858
19-40213345South door to attic is not latching/There is no tape holding the latch so it is a mechanism issueGSAINORMALCLOSEOK0063ZZ-Penthouse2/11/19 11:22 AMNO0762865
19-402133662nd Floor Attorney Lounge faucet whistlesGSAINORMALCLOSEOK0063ZZ-Floor 022/11/19 11:27 AMNO0762862
19-40213397Elevator #4 floor and walls dirtyGSAINORMALCLOSEOK0063ZZ-TULSA FEDERAL BLDG2/11/19 11:36 AMNO0761247
19-40213410Attic stairs dirtyGSAINORMALCLOSEOK0063ZZ-Penthouse2/11/19 11:42 AMNO0762865
19-402134313rd Floor North Women's Restroom stall doors dirty by latchGSAINORMALCLOSEOK0063ZZ-Floor 032/11/19 11:48 AMNO0762863
19-402134453rd Floor North Women's Restroom 2nd stall flush valve making loud noiseGSAINORMALCLOSEOK0063ZZ-Floor 032/11/19 11:53 AMNO0762863
19-40213473All restrooms need water put in drains/Some have a smellGSAINORMALCLOSEOK0063ZZ-Entire Building2/11/19 11:58 AMNO0762859
19-402135003rd Floor Marble Staircase Landing floor dirtyGSAINORMALCLOSEOK0063ZZ-Floor 032/11/19 12:05 PMNO0762863
19-40213511All Restrooms exit door handles are dirtyGSAINORMALCLOSEOK0063ZZ-Entire Building2/11/19 12:08 PMNO0762859
19-40213522Attorney Lounge yellow ring in toiletGSAINORMALCLOSEOK0063ZZ-Floor 022/11/19 12:11 PMNO0762862
19-402135282nd Floor Mid Hallway doors kick plate dirtyGSAINORMALCLOSEOK0063ZZ-Floor 022/11/19 12:15 PMNO0762862
19-40213537North Stairwell 2-3 floor dusty under stairsGSAINORMALCLOSEOK0063ZZ-Floor 022/11/19 12:19 PMNO0762862
19-402135451st Floor Hallway floor dirty in multiple areas including Judges Hall, CSO Post door, CSO Post ext and CSO Post office exitGSAINORMALCLOSEOK0063ZZ-Floor 012/11/19 12:22 PMNO0762861
19-402162143rd Floor recycle bin full/EmptyGSAIUTILMISCCLOSEOK0063ZZ-Floor 032/11/19 2:47 PMNO0762863
19-40216224Remove trash from green roofGSAIUTILMISCCLOSEOK0063ZZ-Floor 022/11/19 2:51 PMNO0762862
19-40216237Chiller Room lights outOMIINITIALCLOSEOK0063ZZ-Basement-Chiller Mechanical Room1290428OK0063F34A004OK0063ZZ-LGI-12904282/11/19 3:00 PMNO0788805
19-40216243Basement ceiling tile missing by Elevator #1OMIINITIALCLOSEOK0063ZZ-Basement2/11/19 3:04 PMNO0762858
19-40216254Basement exit sign not working by NW doorOMIINITIALCLOSEOK0063ZZ-Basement1548292OK0063ZZ-EXS-15482922/11/19 3:08 PMNO0762858
19-402162693rd Floor Courtroom needs vacuumedOMIINITIALCLOSEOK0063ZZ-Floor 032/11/19 3:12 PMNO0762863
19-40216278Basement CSO Men's Restroom floor dirtyOMIINITIALCLOSEOK0063ZZ-Basement2/11/19 3:16 PMNO0762858
19-40264306Replace fluorescent tubes with LED tubes Elevator #4 Lobby/PassageCMCORRECTCLOSEOK0063ZZ-Basement2/12/19 7:30 AMNO0762858
19-40246136Michael Williams Office no heat and no air movingWRSERVCALLCLOSEOK0063ZZ-Floor 012/12/19 8:00 AMNO0762861
19-40262449Basement Lobby dark spot on carpet under fire extinguisherGSAINORMALCLOSEOK0063ZZ-Basement2/12/19 8:15 AMNO0762858
19-40286935Judge Kern's Chambers too cold in Linda's OfficeWRSERVCALLCLOSEOK0063ZZ-Floor 022/12/19 11:41 AMNO0762862
19-40298587Judge Rasure's Office too hotWRSERVCALLCLOSEOK0063ZZ-Floor 012/12/19 1:35 PMNO0762861
19-40298773Remove Senator Lankford decals from doorCMCORRECTCLOSEOK0063ZZ-Floor 022/12/19 3:00 PMNO0762862
19-40388307Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building2/13/19 6:00 AMNO0762859
19-403882712nd Floor South Women's Restroom lights outCMCORRECTCLOSEOK0063ZZ-Floor 021289766OK0063F34A002OK0063ZZ-LGI-12897662/13/19 8:00 AMNO0762862
19-40388295Basement South Women's Restroom light outCMCORRECTCLOSEOK0063ZZ-Basement1290428OK0063F34A004OK0063ZZ-LGI-12904282/13/19 8:00 AMNO0762858
19-403897641st Floor Court Clerks Office Men's Restroom toilet flushes excessivelyWRSERVCALLCLOSEOK0063ZZ-Floor 012/13/19 3:15 PMNO0762861
19-40391535Hang plaque on wall in Judge Kern's ChambersWRSERVCALLCLOSEOK0063ZZ-Floor 022/14/19 2:00 PMNO0762862
19-40416428Replaced 2 fluorescent lamps in passageway 1st Floor SouthCMCORRECTCLOSEOK0063ZZ-Floor 011548191OK0063ZZ-LGI-15481912/19/19 7:30 AMNO0762861
19-40416487Remove signage from Elevator LobbyCMCORRECTCLOSEOK0063ZZ-Basement2/19/19 7:45 AMNO0762858
19-40416271Judge Michael's West Hallway can light outWRSERVCALLCLOSEOK0063ZZ-Floor 012/19/19 8:00 AMNO0762861
19-40416305Judge Michael's Office breaker trippedWRSERVCALLCLOSEOK0063ZZ-Floor 012/19/19 8:00 AMNO0762861
19-40416509Basement North Hallway double doors slammingCMCORRECTCLOSEOK0063ZZ-Basement2/19/19 8:00 AMNO0762858
19-40416324Michael Williams Office too coldWRSERVCALLCLOSEOK0063ZZ-Floor 012/19/19 8:19 AMNO0762861
19-40416349Judge Michael's Courtroom and Office too coldWRSERVCALLCLOSEOK0063ZZ-Floor 012/19/19 8:35 AMNO0762861
19-40418082Judge Kern's Office three can lights outWRSERVCALLCLOSEOK0063ZZ-Floor 022/19/19 3:14 PMNO0762862
19-40431889Conduct building tour and machinery equipment roundsCMCORRECTCLOSEOK0063ZZ-Entire Building2/20/19 6:00 AMNO0762859
19-40431319Remove boxes from Senator Lankford's OfficeCMCORRECTCLOSEOK0063ZZ-Floor 022/20/19 10:00 AMNO0762862
19-40449744Front Entrance glass needs cleanedGSAINORMALCLOSEOK0063ZZ-Floor 012/21/19 10:11 AMNO0762861
19-40450147CSO Kitchen sink stopped upWRSERVCALLCLOSEOK0063ZZ-Basement2/21/19 12:05 PMNO0762858
19-40450903Replace can lights with LED in Judge Rasure's OfficeCMCORRECTCLOSEOK0063ZZ-Floor 012/21/19 3:45 PMNO0762861
19-404510092nd Floor North Women's Restroom toilet flush valve leakingGSAINORMALCLOSEOK0063ZZ-Floor 022/21/19 4:27 PMNO0762862
19-404545123rd Floor North Men's Restroom handicap stall door latch looseOMIINITIALCLOSEOK0063ZZ-Floor 032/22/19 11:09 AMNO0762863
19-404545263rd Floor Hallway by Room 333 light outOMIINITIALCLOSEOK0063ZZ-Floor 032/22/19 11:15 AMNO0762863
19-404545393rd Floor South Men's Restroom door handle looseOMIINITIALCLOSEOK0063ZZ-Floor 032/22/19 11:19 AMNO0762863
19-404545491st Floor North Elevator marble dustyOMIINITIALCLOSEOK0063ZZ-Floor 012/22/19 11:23 AMNO0762861
19-404545552nd Floor South Elevator marble dustyOMIINITIALCLOSEOK0063ZZ-Floor 022/22/19 11:27 AMNO0762862
19-404545723rd Floor North Elevator marble dustyOMIINITIALCLOSEOK0063ZZ-Floor 032/22/19 11:33 AMNO0762863
19-40476643Michael Williams Office too coldWRSERVCALLCLOSEOK0063ZZ-Floor 012/25/19 9:00 AMNO0762861
19-40483259Judge Rasure's South Passageway exit light outCMCORRECTCLOSEOK0063ZZ-Floor 012/26/19 8:00 AMNO0762861
19-40487972Basement ceiling tiles in rough conditionOMIINITIALCLOSEOK0063ZZ-Basement2/26/19 8:30 AMNO0762858
19-40487993VFD Fan #5 add ot contract, mounted blocking transformerOMIINITIALCLOSEOK0063ZZ-Penthouse-Mechanical Equipment Room955356OK0063X50B005OK0063ZZ-VFD-X50B-52/26/19 8:33 AMNO0788820
19-40514702Repair wiring to fan coil unit in Michael Williams OfficeCMCORRECTCLOSEOK0063ZZ-Floor 012/26/19 10:43 AMNO0762861
19-40511442Judge Michael's Chambers can light outWRSERVCALLCLOSEOK0063ZZ-Floor 012/26/19 9:47 AMNO0762861
19-40504333Penthouse has wall opening issue, area needs to be secured and marked as suchOMIINITIALCLOSEOK0063ZZ-Penthouse2/26/19 9:56 AMNO0762865
19-40506025Lighting in Penthouse is dimOMIINITIALCLOSEOK0063ZZ-Penthouse2/26/19 10:01 AMNO0762865
19-40506873Observed 5 gallon bucket of chlorine tablets at base of roof access ladder, storage issueOMIINITIALCLOSEOK0063ZZ-Penthouse2/26/19 10:04 AMNO0762865
19-40509603Janitor closet in Basement has loose chemicals, not properly storedOMIINITIALCLOSEOK0063ZZ-Basement2/26/19 10:16 AMNO0762858
19-40509611Sump pump in Basement Room has overloaded 120 V outlet, suggest adding second outletOMIINITIALCLOSEOK0063ZZ-Basement2/26/19 10:20 AMNO0762858
19-40509624Observed welding gasses connected while not in use, proper storage is to disconnect and cap bottles, store in confined conditionOMIINITIALCLOSEOK0063ZZ-Basement2/26/19 10:23 AMNO0762858