Bid Notice-ODOT Building M Sound Panel Replacement.pdf

PDF 176 KB Posted

Attached to
ODOT Building M Sound Panel Replacement
Solicitation number
S-73000-00018298
Issued by
Marion County, Oregon

About this file

This is a Technical Specifications document for the Oregon Department of Transportation (ODOT) Building M Sound Panel Replacement project, which involves the removal of existing sound panels and installation of new acoustic ceiling treatment throughout the facility. The contractor is responsible for designing the panel installation to achieve acoustic performance specifications, specifically a modeled reverberation time (RT60) of 1.5-1.7 seconds for the completed space. Acoustic absorption materials must have a minimum Noise Reduction Coefficient (NRC) of 0.80 and comply with ASTM C423 testing standards. The contractor shall perform acoustic modeling using EASE, SoundPlan, or equivalent software and submit results demonstrating compliance. Panels must be installed across the full length of the structure using either a horizontally suspended or suspended grid/panelized rail system.

The facility is a shop and repair service environment requiring materials that can withstand exposure to dust, airborne particulates, oils, mists, and mechanical vibration. Acceptable panel types include PVC-faced acoustic panels, factory-sealed scrubbable acoustic tiles, and high-impact polymer-faced absorption panels with non-fibrous or fully encapsulated surfaces designed for cleanability. All materials must comply with ASTM E84 Class A flame spread and smoke developed ratings and local building codes for industrial occupancy. Panels shall be washable and scrubbable per ASTM D4828, moisture-resistant, impact-resistant, and mounted using corrosion-resistant hardware rated for a minimum ten-year service life. The contractor must provide product data sheets, shop drawings, acoustic modeling results, and maintenance guidelines as submittals, and verify post-installation performance through RT60 testing if required by the owner.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment B – Technical Specifications

Contractor-Designed Acoustic Treatment – Ceiling Panels

1. Performance Requirements

• Provide an acoustic ceiling treatment that results in a modeled RT60 of 1.5–1.7 seconds for the completed space.

• Contractor shall perform acoustic modeling (EASE, SoundPlan, or equivalent) and submit results demonstrating compliance.

• Acoustic absorption materials shall have a minimum NRC 0.80 and comply with manufacturer testing per ASTM C423.

2. Environmental & Facility Conditions

• Facility is a shop and repair service environment with exposure to dust, airborne particulates, oils/mists, and mechanical activity.

• Materials shall be suitable for environments requiring frequent cleaning, high durability, and resistance to deterioration caused by:

o Vibration o Moisture o Light chemical exposure o Dust and debris accumulation

3. Material Requirements

• Panels shall have non-fibrous exposed surfaces or fully encapsulated mineral fiber, melamine, PET, or composite cores designed for cleanability. Panels shall be RECORE or approved equal.

• Acceptable surface types:

o PVC-faced acoustic panels o Factory-sealed scrubbable acoustic tiles o High-impact polymer-faced acoustic absorption panels

• Surface characteristics:

o Washable/scrubbable (minimum ASTM D4828 scrub resistance or manufacturer equivalent) o Moisture-resistant, not sag when exposed to humidity swings typical of shop areas o Impact-resistant, designed for spaces with tool or equipment contact potential

• Edges shall be sealed to prevent particulate shedding.

4. Fire & Safety Requirements

• Materials shall comply with ASTM E84 Class A flame spread and smoke developed.

• Panels, mounting hardware, and adhesives must meet local building/fire codes for shop and industrial occupancy classifications.

5. Mounting & Structural Requirements

• Ceiling-mounted system options:

o Horizontally suspended. Panels to be placed throughout the full length of the structure.

o Suspended grid or panelized rail system rated for facility conditions

• All mounting systems shall be corrosion-resistant and capable of supporting panels during vibration and temperature swings.

• No sagging, warping, or delamination over a minimum 10-year service life.

6. Cleaning & Maintenance Requirements

• Panels shall withstand:

o Wet wiping o Low-pressure spray cleaning o Use of common shop cleaners (Simple Green, mild detergents, disinfectants)

• Contractor shall provide manufacturer cleaning guidelines and chemical compatibility documentation.

7. Submittals

• Product data sheets including NRC values, fire ratings, cleanability, moisture resistance, and durability testing

• Shop drawings showing panel layout, mounting details, and coverage area

• Acoustic model demonstrating design performance (RT60 1.5–1.7 sec). Existing pretreatment measured (RT60 3.2-4.8 sec).

• Maintenance and cleaning instructions

8. Execution

• Install per manufacturer instructions and maintain tight joints, uniform alignment, and consistent finish.

• Protect adjacent surfaces from dust/overspray during installation.

• After installation, contractor shall verify performance using post-installation measurements (e.g., RT60 testing per ISO 3382) if required by the owner.