This document is a set of architectural and electrical drawings and specifications for a fire alarm system upgrade project for the Brighton Area Schools BECC Building in Brighton, Michigan. The project involves the design, installation, and integration of a new addressable fire alarm and emergency voice/alarm communication system, including manual fire alarm boxes, smoke detectors, notification appliances, and related components.
The document provides detailed requirements for the fire alarm system, including system operation, product specifications, installation guidelines, testing, and commissioning. It also includes general construction requirements, such as demolition, cutting and patching, and electrical identification. The successful contractor will need to hire a NICET Level 3 certified fire alarm designer to develop the final system design based on the drawings and specifications provided.
Text of this file
BRIGHTON AREA SCHOOLS - B.E.C.C. BLDG.
MISC. IMPROVEMENTS
ARCHITECTURAL & INTERIORS
PLUMBING
MECHANICAL
ELECTRICAL
ISSUANCE
FIRE ALARM
F
WP
IG
G
IG
P/P
WALL DIMMER, DIMMING TECHNOLOGY AS REQUIRED,
WATTAGE REQUIRED EQUAL TO CONNECTED LOAD
PLUS 25 PERCENT
FLUSH FLOOR MOUNTED TELE/DATA OUTLET. HUBBELL
#B2537 WITH #S3082/S2925 COVER ASSY. PROVIDE
3/4"C. TO CEILING SPACE.
FLUSH FLOOR MOUNTED 120V. 20A. CONVENIENCE
RECEPTACLE. HUBBELL #B2537 WITH #S3082/S3925
COVER ASSY.
DOUBLE DUPLEX RECEPTACLE, 120V. 20A.
GROUNDING TYPE
DOUBLE DUPLEX RECEPTACLE 120V. 20A.
GROUNDING TYPE
DUPLEX RECEPTACLE, 120V. 20A. GROUNDING TYPE
COMPUTER GRADE RECEPTACLE, 120V. 20A. WITH
ISOLATED GROUND
DUPLEX RECEPTACLE, 120V. 20A. GROUNDING TYPE
(2) SECTION TELE / POWER POLE TO SYSTEM FURNITURE
WITH POWER, TELEPHONE AND DATA CONNECTIONS TO
CEILING SPACE
BASE FEED TO SYSTEM FURNITURE WITH POWER,
TELEPHONE AND DATA CONNECTIONS TO CEILING
SPACE
FUSIBLE DISCONNECT SWITCH - UPPER NUMERAL
DENOTES SWITCH SIZE, LOWER NUMERAL DENOTES
FUSE SIZE
MANUAL MOTOR STARTER, OR ON MOTORIZED EQUIP.
NON-FUSED DISCONNECT SWITCH - NUMERAL
DENOTES SWITCH SIZE
SPECIAL RECEPTACLE, TYPE & MOUNTING HEIGHT AS
NOTED
FLUSH FLOOR MOUNTED POWER/DATA OUTLET.
HUBBELL #B4233 CAST IRON FLOOR BOX WITH #S3825
FLUSH COVER FOR POWER AND #S2825 FLUSH COVER
PLATE FOR TELE/DATA. PROVIDE 120V. 20A DUPLEX
RECEPTACLE.
RECESSED TROFFER
RECESSED TROFFER
WALL MOUNTED LUMINAIRE, HEIGHT AS NOTED
SINGLE FACE EXIT SIGN, CEILING MTD. ARROWS
AS INDICATED
DOUBLE FACE EXIT SIGN, CEILING MTD. ARROWS
AS INDICATED
BATTERY OPERATED EMERGENCY LIGHT
EMERGENCY LIGHT
SURFACE MOUNTED LIGHT
SURFACE MOUNTED LIGHT FIXTURE
PENDANT MOUNTED LIGHT FIXTURE
RECESSED DOWNLIGHT
STRIP LIGHT
OUTDOOR LIGHTING POLE & LUMINAIRE
SINGLE POLE TOGGLE SWITCH
THREE-WAY TOGGLE SWITCH
FOUR-WAY TOGGLE SWITCH
DUPLEX RECEPTACLE, GFCI TYPE,120V. 20A.,
GROUNDING TYPE
COMPUTER GRADE RECEPTACLE, 120V. 20A., WITH
ISOLATED GROUND
WEATHERPROOF RECEPTACLE
JUNCTION BOX - CEILING MOUNTED
MOTOR CONTROL SWITCH WITH PILOT LIGHT
MAGNETIC MOTOR STARTER
COMBINATION MOTOR STARTER
MOTOR CONNECTION
LIGHTING PANELBOARD
POWER PANELBOARD
DISTRIBUTION PANELBOARD
MAIN SWITCHBOARD
TRANSFORMER
CONTROL PANEL
CEILING FAN
ELECTRICAL SYMBOL LIST
FLUSH FLOOR MOUNTED RECEPTACLE IN NONMETALLIC
RECTANGULAR FLOOR BOX WITH 1-1/4" KNOCK-OUTS
AND REDUCERS FOR USE WITH 1/2", 3/4" & 1" CONDUITS.
PROVIDE WITH BRASS CARPET FLANGE, USE
MULTI-GANG WHERE DEVICES ARE SHOWN ADJACENT
TO EACH OTHER. PROVIDE BRASS RECTANGULAR
COVER PLATE, WITH 120V-20A DUPLEX RECEPTACLE.
WIREMOLD 880MP.
FLUSH FLOOR MOUNTED DATA OUTLET IN NONMETALLIC
RECTANGULAR FLOOR BOX WITH 1-1/4" KNOCK-OUTS
AND REDUCERS FOR USE WITH 1/2", 3/4" & 1" CONDUITS.
PROVIDE WITH BRASS CARPET FLANGE, USE
MULTI-GANG WHERE DEVICES ARE SHOWN ADJACENT TO
EACH OTHER. PROVIDE BRASS GFI COVER PLATE, WITH
COMMUNICATIONS MOUNTING PLATE. WIREMOLD 880MP.
1. CERTAIN AREAS IN THE EXISTING BUILDING SHALL BE MODIFIED TO SUIT
THE NEW REQUIREMENTS. THESE DRAWINGS ARE DIAGRAMMATIC AND
ARE INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED TO
COMPLETE A SAFE REMOVAL OF THE ELECTRICAL SYSTEMS AS
INDICATED BY THE NOTES ON THIS DRAWING.
2. WORK IN THE AREA SHALL INCLUDE THE DISCONNECTION, REMOVAL,
RELOCATION, AND RECONNECTION COMPLETE IN ALL RESPECTS OF ALL
ITEMS REQUIRED TO SUIT THE DESIGN INTENT. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE PROJECT SITE TO
CORRECTLY ASCERTAIN THE SCOPE OF SERVICES AND TO INCLUDE ALL
PERTINENT COSTS IN HIS BID. NO EXTRAS WILL BE ALLOWED.
3. ALL ELECTRICAL WORK INTERFERING WITH AND REQUIRING
MODIFICATION FOR THE NEW REQUIREMENTS SHALL BE RELOCATED AS
DIRECTED BY BUILDING MANAGEMENT PERSONNEL AND REINSTALLED
AND REWIRED AS NECESSARY TO THE SATISFACTION OF THE BUILDING
OWNER.
4. PROVIDE ALL EQUIPMENT, MATERIALS, LABOR AND SUPERVISION
NECESSARY TO PROVIDE A SAFE ELECTRICAL INSTALLATION. ALL
ELECTRICAL DEVICES AND SYSTEMS THAT ARE INDICATED AS EXISTING
TO REMAIN SHALL BE IN SAFE WORKING ORDER.
5. OBTAIN NECESSARY PERMITS FROM THE LOCAL AUTHORITY HAVING
JURISDICTION BEFORE PROCEEDING WITH ANY WORK IN THE FIELD.
6. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE, OSHA AND OTHER ELECTRICAL SAFETY STANDARDS
AND GUIDELINES. CONFORM TO ALL STATE AND LOCAL CODES AND
STANDARDS.
7. ALL EQUIPMENT AND WIRING NOT IN RENOVATION AREAS BUT
AFFECTED BY WORK IN RENOVATION AREAS SHALL BE RECONNECTED
AS REQUIRED FOR A COMPLETE WORKING SYSTEM.
8. ABANDONED AND INACTIVE CONDUITS, WIRE, DEVICES, EQUIPMENT,
ETC., SHALL BE REMOVED IN THEIR ENTIRETY. IN ADDITION TO THESE
ITEMS, THIS CONTRACTOR SHALL REMOVE ALL ITEMS AS INDICATED ON
THE PLANS, OR AS REQUIRED TO CLEAN UP THE ENTIRE AREA OF
UNUSED, ABANDONED, OR INACTIVE MATERIALS. CONDUIT AND WIRING
FEEDING DEVICES AND EQUIPMENT TO BE REMOVED SHALL ALSO BE
REMOVED UP TO THE NEXT ACTIVE PULLBOX, JUNCTION BOX, OR
PANELBOARD. HANGERS, MESSENGER CABLE, BRACKETS, ETC,
SUPPORTING ITEMS TO BE REMOVED SHALL ALSO BE UNFASTENED AND
REMOVED. OPEN HOLES IN DUCTS, BOXES, PANELBOARDS, AND
KNOCKOUTS SHALL BE CLOSED WITH SUITABLE SNAP PLUGS OR FILLER
PLATES.
9. THE CONTRACTOR SHALL REMOVE AND DELIVER TO A PLACE
DESIGNATED BY THE OWNER ALL EXISTING ELECTRICAL EQUIPMENT NO
LONGER INTENDED FOR USE. THIS EQUIPMENT REMAINS THE
PROPERTY OF THE OWNER.
10. ANY EQUIPMENT, DEVICES, MATERIALS, ETC., THE OWNER ELECTS NOT
TO RETAIN SHALL BE LEGALLY DISPOSED OF BY THE CONTRACTOR OFF
THE OWNER'S PREMISES.
11. AT COMPLETION OF ALL ELECTRICAL WORK, UPDATE CIRCUIT
DIRECTORIES IN PANELS AFFECTED BY NEW WORK WITH NEW
TYPEWRITTEN CIRCUIT DESCRIPTIONS. CIRCUIT DIRECTORIES SHALL BE
MOUNTED ON INSIDE OF FRONT PANEL COVER IN A CLEAR PLASTIC
ENCLOSURE.
12. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS, AND IN ACCORDANCE WITH
THEIR LISTING OR LABELING REQUIREMENTS. ANY PENETRATIONS
THROUGH FIRE RATED ASSEMBLIES THAT ARE CREATED BY THE
ELECTRICAL DEMOLITION, SHALL BE SEALED AND RESTORED IN
ACCORDANCE WITH THE UL FIRE RESISTANCE DIRECTORY.
13. WHERE CONDUIT AND/OR OUTLET BOXES INDICATED FOR DEMOLITION
ARE EMBEDDED IN CONCRETE OR BELOW CONCRETE SLAB, ABANDON
IN PLACE. CUT BACK AND SEAL EXPOSED CONDUIT. PROVIDE BLANK
COVERS FOR ABANDONED BOXES. REMOVE ALL ASSOCIATED WIRING
BACK TO SOURCE.
GENERAL NOTES - DEMOLITION
GENERAL NOTES
1. THE CONTRACTOR SHALL ABIDE BY ALL FEDERAL, STATE, AND/OR
LOCAL CODES. IF A DISCREPANCY BETWEEN CODES OCCURS, THE
MOST STRINGENT SHALL PREVAIL.
2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR
TO THE COMMENCEMENT OF ANY WORK. SHOULD DISCREPANCIES BE
DISCOVERED, THE CONTRACTOR SHALL VERIFY INTENT WITH THE
ENGINEER/OWNER BEFORE PROCEEDING.
3. COORDINATE LOCATIONS OF ALL CEILING MOUNTED DEVICES WITH
OTHER TRADES PRIOR TO INSTALLATION.
4. COORDINATE ALL ROUGH-IN REQUIREMENTS FOR OWNER FURNISHED
EQUIPMENT WITH THE OWNER PRIOR TO BEGINNING WORK. THESE
DRAWINGS ARE BASED ON THE BEST INFORMATION AVAILABLE DURING
THE DESIGN PHASE OF THE PROJECT.
5. COORDINATE WITH MILLWORK CONTRACTOR TO DETERMINE THE
EXACT LOCATION OF OUTLETS BEING PLACED IN MILLWORK.
6. ALL DEVICES ARE TO BE FLUSH MOUNTED UNLESS NOTED OTHERWISE.
7. DEVICES NOTED "GFI" SHALL INCLUDE GROUND FAULT INTERRUPTING
DEVICES.
8. DEVICES NOTED "WP" SHALL BE WEATHERPROOF, "WHILE-IN-USE" TYPE
WHERE APPLICABLE.
9. DEVICES NOTED "NL" SHALL BE NIGHT LIGHTS. PROVIDE UN-SWITCHED
BRANCH CIRCUIT CONDUCTORS TO EACH FIXTURE.
10. CONNECT ALL EXIT AND EMERGENCY LIGHTING FIXTURES TO LOCAL
LIGHTING CIRCUIT, AHEAD OF ALL SWITCHES, PER NEC.
11. ACTUAL CONDUIT SIZE AND ROUTING TO BE AS DIRECTED BY THE FIRE
ALARM NICET CERTIFIED DESIGNER.
12. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3 CERTIFIED
FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM AND EMERGENCY
VOICE/ALARM COMMUNICATION SYSTEM.
13. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES AND
SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE PLANS. A FIRE
ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM DESIGNER SHALL
DETERMINE THE ACTUAL DEVICE TYPES AND THEIR LOCATIONS,
OUTPUT AND THE ROUTING OF ALL RACEWAYS.
14. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS AND
DESCRIPTION OF SYSTEM.
15. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM DEVICES.
16. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA RATINGS SIZED
PER ANSI 117.1 AND NFPA 72.
17. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM SHALL
PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE AREA.
18. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
19. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70., ARTICLE 760.
20. ALL MOUNTING HEIGHTS PROVIDED ARE TO CENTER OF DEVICE,
UNLESS OTHERWISE INDICATED.
C DUPLEX RECEPTACLE, 120V. 20A. GROUNDING TYPE,
CEILING MOUNTED RECEPTACLE.
KEY OPERATED SWITCH
SWITCH WITH PILOT LIGHT
SITE LIGHTING BOLLARD
KWH METER
1. APPLICABLE CODES INCLUDE, BUT ARE NOT NECESSARILY LIMITED TO,
THE FOLLOWING:
1.1. 2015 MICHIGAN BUILDING CODE
1.2. 2017 NEC WITH MICHIGAN PART 8 AMENDMENTS (INCLUDING NEC
ART. 708)
1.3. NEC ARTICLE 708 - CRITICAL OPERATIONS POWER SYSTEMS
1.4. 2017 MICHIGAN ENERGY CODE (IECC 2015 / ASHRAE 90.1 - 2013)
1.5. 2009 ICC ANSI STANDARD A117.1-2009
1.6. 2015 INTERNATIONAL FIRE CODE
1.7. 2016 NFPA 1221 - STANDARD FOR INSTALLATION, MAINTENANCE AND
USE OF EMERGENCY COMMUNICATIONS SYSTEMS
1.8. 2013 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE
1.9. 2013 NFPA 110 - STANDARD FOR EMERGENCY AND STANDBY POWER
SYSTEMS.
2. OVERCURRENT PROTECTIVE DEVICES SERVING EMERGENCY SYSTEMS
SHALL BE SELECTIVELY COORDINATED WITH ALL SUPPLY-SIDE
OVERCURRENT PROTECTIVE DEVICES.
3. A SHORT-CIRCUIT, ARC-FLASH AND OVERCURRENT PROTECTIVE DEVICE
COORDINATION STUDY SHALL BE PROVIDED BY THE CONTRACTOR AT
THE SAME TIME SUBMITTALS ARE PREPARED.
4. CONTRACTOR SHALL PROVIDE NAMEPLATES FOR ALL ELECTRICAL
EQUIPMENT AND ARC-FLASH LABELS INDICATING REQUIRED PPE
PROTECTION.
5. ALL WIRING AND BUSSING SHALL BE COPPER, UNLESS OTHERWISE
NOTED.
6. SURGE PROTECTION DEVICES SHALL BE PROVIDED WHERE INDICATED
ON THE DRAWINGS AND/OR SPECIFICATIONS. SURGE PROTECTION
DEVICES SHALL BE COMPATIBLE WITH THE LIGHTNING PROTECTION
SYSTEM AND SHALL INCLUDE SURGE COUNTERS AND PROVISIONS FOR
REMOTE MONITORING. ROUTE LOW-VOLTAGE CABLE FOR MONITORING
BACK TO SERVER ROOM.
7. A SEPARATE EQUIPMENT GROUNDING CONDUCTORS, SIZED PER NEC,
SHALL BE INSTALLED WITH ALL CIRCUIT CONDUCTORS.
8. PROVIDE A THERMAL-ADHESIVE LABEL ON EACH DEVICE (LIGHT SWITCH,
RECEPTACLE, ETC.) INDICATING THE SOURCE PANEL AND CIRCUIT
NUMBER.
POWER SYMBOLS LIGHTING SYMBOLS
DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL
PROJECT SPECIFIC NOTES
F
JUNCTION BOX - FLOOR MOUNTEDF
JUNCTION BOX - WALL MOUNTED, HEIGHT AS NOTED
FLOOR MOUNTED BASE FEED TO SYSTEM FURNITURE
WITH POWER, TELEPHONE AND DATA CONNECTIONS TO
CEILING SPACE
F
LOAD CENTER
WALL MOUNTED SURFACE METAL RACE WAY
EMERGENCY LIGHT
SURFACE MOUNTED LIGHT
SINGLE FACE EXIT SIGN, WALL MTD. ARROWS AS
INDICATED
DOUBLE FACE EXIT SIGN, WALL MTD. ARROWS AS
INDICATED
REMOTE EMERGENCY LIGHT
TWIN HEAD REMOTE EMERGENCY LIGHT
COMBINATION EXIT / EMERGENCY LIGHT
SWITCHED DUPLEX RECEPTACLE, 120V. 20A.
GROUNDING TYPE
M MEDIA RECEPTACLE
F
F
POWER SYMBOLS
DESCRIPTIONSYMBOL
DATA OUTLET
PROXIMITY READER OUTLET
LOW VOLTAGE SYMBOLS
DESCRIPTIONSYMBOL
KEY SWITCH
TELEVISION OUTLET BOX
LEGRAND #EFB45 FLOOR BOX WITH FOUR 120V. 20A.
DUPLEX RECEPTACLES ON ONE SIDE AND ONE DATA
DEVICE PLATE WITH 3 CAT6 CONNECTORS, AND ONE AV
DEVICE PLATE WITH TWO-MDMI CONNECTORS ON THE
OPPOSITE SIDE.
A
LEGRAND #EFB45 FLOOR BOX WITH TWO 120V. 20A.
DUPLEX RECEPTACLES ON ONE SIDE AND ONE DATA
DEVICE PLATE AND ONE AV DEVICE PLATE WITH ON THE
OPPOSITE SIDE.
FIRE ALARM MANUAL PULL STATION +48" A.F.F.
FIRE ALARM SPEAKER/STROBE COMBINATION
DEVICE +80" A.F.F.
SMOKE DETECTOR
FIRE ALARM CONTROL PANEL
COMMUNICATION SYSTEM SYMBOLS
DESCRIPTIONSYMBOL
C
D FIRE ALARM & EMERGENCY VOICE/ALARM
FIRE ALARM VISUAL DEVICE +80" A.F.F.
FIRE ALARM SPEAKER AT CEILING
FIRE ALARM SPEAKER ON WALL +108" A.F.F.
DOOR HOLD OPEN DEVICE
HEAT DETECTOR
FIRE ALARM REMOTE ANNUNCIATOR
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
A T E O F M I C H I GA N
03/08/24
BUILDING FIRE ALARM NOTES:
1. ACTUAL CONDUIT SIZE AND ROUTING TO BE AS DIRECTED BY
THE FIRE ALARM NICET CERTIFIED DESIGNER.
2. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3
CERTIFIED FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM
AND EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
3. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES
AND SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE
PLANS. A FIRE ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM
DESIGNER SHALL DETERMINE THE ACTUAL DEVICE TYPES AND
THEIR LOCATIONS, OUTPUT AND THE ROUTING OF ALL
RACEWAYS.
4. REFER TO SPECIFICATIONS SECTION 28 31 11 - DIGITAL
ADDRESSABLE FIRE ALARM AND EMERGENCY VOICE/ALARM
COMMUNICATION SYSTEM FOR ADDITIONAL REQUIREMENTS
AND DESCRIPTION OF SYSTEM.
5. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM
DEVICES.
6. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA
RATINGS SIZED PER ANSI 117.1 AND NFPA 72.
7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
SHALL PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE
AREA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
9. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70.,
ARTICLE 760.
10. COORDINATE PLACEMENT OF CEILING SPEAKERS WITH
LIGHTING FIXTURE AND MECHANICAL GRILLES.
EF
1.
EF
1.
EF
1.
EF
1.
F.A.A.N
FACP
NOTE:
PROVIDE INITIATION AND ALARM
DEVICES AT LOWER LEVEL BOILER ROOM
AND SPACES
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
THE FIRE ALARM NICET CERTIFIED DESIGNER.
2. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3
CERTIFIED FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM
AND EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
3. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES
AND SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE
PLANS. A FIRE ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM
DESIGNER SHALL DETERMINE THE ACTUAL DEVICE TYPES AND
THEIR LOCATIONS, OUTPUT AND THE ROUTING OF ALL
RACEWAYS.
4. REFER TO SPECIFICATIONS SECTION 28 31 11 - DIGITAL
ADDRESSABLE FIRE ALARM AND EMERGENCY VOICE/ALARM
COMMUNICATION SYSTEM FOR ADDITIONAL REQUIREMENTS
AND DESCRIPTION OF SYSTEM.
5. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM
DEVICES.
6. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA
RATINGS SIZED PER ANSI 117.1 AND NFPA 72.
7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
SHALL PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE
AREA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
9. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70.,
ARTICLE 760.
10. COORDINATE PLACEMENT OF CEILING SPEAKERS WITH
LIGHTING FIXTURE AND MECHANICAL GRILLES.
EF
1.
EF
1.
EF
1.
EF
1.
EF
1.
EF
1.
EF
1.
EF
1.
EF
1.
EF
1.
EF1.4
EF1.2
WP
WP
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
EF
1.
EF
1.
EF
1.
EF
1.
BUILDING FIRE ALARM NOTES:
1. ACTUAL CONDUIT SIZE AND ROUTING TO BE AS DIRECTED BY
THE FIRE ALARM NICET CERTIFIED DESIGNER.
2. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3
CERTIFIED FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM
AND EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
3. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES
AND SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE
PLANS. A FIRE ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM
DESIGNER SHALL DETERMINE THE ACTUAL DEVICE TYPES AND
THEIR LOCATIONS, OUTPUT AND THE ROUTING OF ALL
RACEWAYS.
4. REFER TO SPECIFICATIONS SECTION 28 31 11 - DIGITAL
ADDRESSABLE FIRE ALARM AND EMERGENCY VOICE/ALARM
COMMUNICATION SYSTEM FOR ADDITIONAL REQUIREMENTS
AND DESCRIPTION OF SYSTEM.
5. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM
DEVICES.
6. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA
RATINGS SIZED PER ANSI 117.1 AND NFPA 72.
7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
SHALL PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE
AREA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
9. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70.,
ARTICLE 760.
10. COORDINATE PLACEMENT OF CEILING SPEAKERS WITH
LIGHTING FIXTURE AND MECHANICAL GRILLES.
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
EF
1.
EF1.4
EF1.2
EF1.5
EF1.4
EF1.5
EF1.4
BUILDING FIRE ALARM NOTES:
1. ACTUAL CONDUIT SIZE AND ROUTING TO BE AS DIRECTED BY
THE FIRE ALARM NICET CERTIFIED DESIGNER.
2. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3
CERTIFIED FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM
AND EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
3. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES
AND SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE
PLANS. A FIRE ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM
DESIGNER SHALL DETERMINE THE ACTUAL DEVICE TYPES AND
THEIR LOCATIONS, OUTPUT AND THE ROUTING OF ALL
RACEWAYS.
4. REFER TO SPECIFICATIONS SECTION 28 31 11 - DIGITAL
ADDRESSABLE FIRE ALARM AND EMERGENCY VOICE/ALARM
COMMUNICATION SYSTEM FOR ADDITIONAL REQUIREMENTS
AND DESCRIPTION OF SYSTEM.
5. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM
DEVICES.
6. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA
RATINGS SIZED PER ANSI 117.1 AND NFPA 72.
7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
SHALL PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE
AREA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
9. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70.,
ARTICLE 760.
10. COORDINATE PLACEMENT OF CEILING SPEAKERS WITH
LIGHTING FIXTURE AND MECHANICAL GRILLES.
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
EF
1.
EF
1.
EF
1.
BUILDING FIRE ALARM NOTES:
1. ACTUAL CONDUIT SIZE AND ROUTING TO BE AS DIRECTED BY
THE FIRE ALARM NICET CERTIFIED DESIGNER.
2. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3
CERTIFIED FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM
AND EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
3. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES
AND SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE
PLANS. A FIRE ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM
DESIGNER SHALL DETERMINE THE ACTUAL DEVICE TYPES AND
THEIR LOCATIONS, OUTPUT AND THE ROUTING OF ALL
RACEWAYS.
4. REFER TO SPECIFICATIONS SECTION 28 31 11 - DIGITAL
ADDRESSABLE FIRE ALARM AND EMERGENCY VOICE/ALARM
COMMUNICATION SYSTEM FOR ADDITIONAL REQUIREMENTS
AND DESCRIPTION OF SYSTEM.
5. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM
DEVICES.
6. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA
RATINGS SIZED PER ANSI 117.1 AND NFPA 72.
7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
SHALL PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE
AREA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
9. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70.,
ARTICLE 760.
10. COORDINATE PLACEMENT OF CEILING SPEAKERS WITH
LIGHTING FIXTURE AND MECHANICAL GRILLES.
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
THE FIRE ALARM NICET CERTIFIED DESIGNER.
2. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3
CERTIFIED FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM
AND EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
3. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES
AND SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE
PLANS. A FIRE ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM
DESIGNER SHALL DETERMINE THE ACTUAL DEVICE TYPES AND
THEIR LOCATIONS, OUTPUT AND THE ROUTING OF ALL
RACEWAYS.
4. REFER TO SPECIFICATIONS SECTION 28 31 11 - DIGITAL
ADDRESSABLE FIRE ALARM AND EMERGENCY VOICE/ALARM
COMMUNICATION SYSTEM FOR ADDITIONAL REQUIREMENTS
AND DESCRIPTION OF SYSTEM.
5. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM
DEVICES.
6. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA
RATINGS SIZED PER ANSI 117.1 AND NFPA 72.
7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
SHALL PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE
AREA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
9. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70,
ARTICLE 760.
10. COORDINATE PLACEMENT OF CEILING SPEAKERS WITH
LIGHTING FIXTURE AND MECHANICAL GRILLES.
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
THE FIRE ALARM NICET CERTIFIED DESIGNER.
2. THE ELECTRICAL CONTRACTOR SHALL HIRE A NICET LEVEL 3
CERTIFIED FIRE ALARM DESIGNER TO DESIGN THE FIRE ALARM
AND EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM.
3. THE DRAWINGS INDICATE ASSUMED LOCATIONS OF DEVICES
AND SUGGESTED CONDUIT ROUTING DIAGRAMS ON THE
PLANS. A FIRE ALARM NICET LEVEL 3 CERTIFIED FIRE ALARM
DESIGNER SHALL DETERMINE THE ACTUAL DEVICE TYPES AND
THEIR LOCATIONS, OUTPUT AND THE ROUTING OF ALL
RACEWAYS.
4. REFER TO SPECIFICATIONS SECTION 28 31 11 - DIGITAL
ADDRESSABLE FIRE ALARM AND EMERGENCY VOICE/ALARM
COMMUNICATION SYSTEM FOR ADDITIONAL REQUIREMENTS
AND DESCRIPTION OF SYSTEM.
5. REFER TO FLOOR PLANS FOR LOCATIONS OF FIRE ALARM
DEVICES.
6. PROVIDE VISUAL NOTIFICATION DEVICES WITH CANDELA
RATINGS SIZED PER ANSI 117.1 AND NFPA 72.
7. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
SHALL PROVIDE FULL INTELLIGIBILITY THROUGHOUT THE
AREA.
8. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NAC PANELS,
ACCESSORIES, CIRCUITS AS REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM.
9. ALL FIRE ALARM WIRING SHALL COMPLY WITH NFPA 70,
ARTICLE 760.
10. COORDINATE PLACEMENT OF CEILING SPEAKERS WITH
LIGHTING FIXTURE AND MECHANICAL GRILLES.
da te is su ed fo r dr ck 'd ap p' d:
co ns ul ta nt
THIS DRAWING IS DIAGRAMMATIC AND SHOULD BE USED TO
DETERMINE THE DESIGN INTENT. THE CONTRACTOR SHALL FIELD
VE RI F Y A LL W O R K A N D SH A L L N OT IF Y TH E A R C H I TEC T
IMMEDIATELY OF ANY DISCREPANCIES IN THE DOCUMENTS
BEFORE PROCEEDING. FAILURE TO DO SO WILL RESULT IN THE
CONTRACTOR TAKING FULL RESPONSIBILITY AND LIABILITY FOR
SAID DISCREPANCIES. NOTICE: THIS DRAWING AND THE DESIGN
ARE THE PROPERTY OF MECHANICAL ELECTRICAL ENGINEERING
CONSULTANTS, PC AND NO ALTERATIONS AND/OR TRANSFERS OF
WORK ARE PERMITTED UNLESS WRITTEN APPROVAL IS GRANTED
BY MECHANICAL ELECTRICAL ENGINEERING CONSULTANTS, PC.
M
EE
C J
O B
-0
Li nd ho ut
A ss oc ia te s ar ch ite ct s ai a pc w w w .li nd ho ut .c om (8
)2
-5 fa x:
(8
)2
-5 ci ta tio n dr iv e, b rig ht on , m ic hi ga n
6-
JORDAN
KOENIG
ENGINEER
6201059789 No.
L I C
E N
S E D
P R O F E S S I O N A L E NG
I N
E E
R
ST
DIGITAL, VOICE ALARM SIGNALING, ADDRESSABLE FIRE ALARM
SYSTEM SPECIFICATION
1. General Conditions:
A. Drawings and General Provisions of Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to work of this section. The electrical contractor shall assume all obligations contained therein that affect his work. The electrical engineer shall be consulted in case of any disputes and his decision shall be final.
B. The electrical contractor shall examine the architectural, plumbing and mechanical drawings and specifications and shall familiarize himself with all conditions of work affecting the contract. size and capacity of all equipment shall be as on plans or as indicated herein.
C. Furnish labor and materials to provide a complete electrical system as required by the plans and specifications.
D. Any item appearing on the drawings and not in the specification or vice versa, and any items appearing in neither but necessary to accomplish the intent of these specifications, shall be furnished by the electrical contractor.
E. Where equipment specifications or descriptions include a specific manufacturer and catalog number, any substituted equipment or equipment proposed to be provided by an alternative manufacturer shall functionally meet, or exceed, the requirements of the specified equipment in all respects.
Alternate manufacturers shall refer to product literature published by the manufacturer of the equipment specified to determine equivalency of their proposed alternate product.
2. Scope of Work: This specification contemplates the provision by the electrical contractor of all labor and materials required to install a complete system of electrical work as herein specified and as shown of the drawings. Without restricting the generality of the foregoing, the following shall be included:
a. New Voice Alarm Signaling Fire Alarm System. complete.
b. Grounding of complete per article 250 of the national electrical code and specifications.
c. Demolition of existing fire alarm system as required.
3. Character of Equipment: All equipment shall be new and shall conform in all respects to the latest approved standards of the IEEE,,ANSI and the "UL" Label or Listing.
4. Codes and Ordinances: All electrical work shall comply with the 2023 edition of the National Electrical Code, Michigan Building Code, all ordinances and regulations, and the Occupational Safety and Health Act (OSHA).
5. Permits and Fees:
a. The electrical contractor shall obtain all permits, pay all fees, including all costs accessed by the City of Brighton and arrange for all inspections for his work.
b. Before submitting his bid, the electrical contractor shall determine from them all of their requirements and charges. All such requirements and charges shall be included in the base bid proposal.
c. At the completion of electrical work, the electrical contractor shall furnish the owner with all certificates of final inspection and approvals.
6. Site Visit By Contractor:
a. The contractor shall visit the site and verify the conditions under which his work must be conducted before submitting his proposal.
b. The submitting of a proposal implies that the contractor has visited the site, is conversant with all site conditions, including existing services and equipment, obstructions and all conditions, which will be encountered in the removal and/or relocation of present materials and equipment, installation of new materials and cutting and patching, etc., for a complete fire alarm installation.
c. If any interferences or violations appear and departure from the design intent of the bid documents is required, the contractor shall notify the architect prior to entering into contract with the owner. Failure to provide the architect with the aforementioned notification will result in the contractor being held responsible to complete all work to meet the design intent of the bid documents with no additional expenses ("extras") being incurred by the owner, architect, or engineer.
7. Cooperation With Other Contractors:
a. Electrical contractor shall arrange all parts of his work in proper relation to the work of others and to the architectural finish. Where interferences occur, the electrical contractor shall, before installing the work involved, consult with the architect as to the exact location and level of his work. The architect's decision shall be final.
b. The electrical contractor shall be responsible for the arrangement of his work and equipment and shall maintain proper headroom under his work. Should work installed by him require modification to avoid interference with other work, as determined by the architect, such changes shall be made without additional cost.
8. Summary:
A. Section Includes:
1. Fire-alarm control unit.
2. Manual fire-alarm boxes.
3. System smoke detectors.
4. Notification appliances.
5. Magnetic door holders.
6. Remote annunciator.
7. Addressable interface device.
8. Digital alarm communicator transmitter.
9. System printer.
B. The drawings indicate locations of devices and suggested conduit routing diagrams on the plans
C. The fire alarm sub-contractor shall hire a NICET Level 3 Certified fire alarm designer to design the fire alarm system.
9. Definitions:
A. LED: Light-emitting diode.
B. NICET: National Institute for Certification in Engineering Technologies
10. System Description:
A. Non-coded, UL-certified, addressable system, with multiplexed signal transmission, dedicated to fire-alarm service only.
B. Non-coded addressable system, with automatic sensitivity control of certain smoke detectors and multiplexed signal transmission, dedicated to fire-alarm service only.
11. Submittals:
A. General Submittal Requirements:
1. Submittals shall be approved by authorities having jurisdiction prior to submitting them to Architect
2. Shop Drawings shall be prepared by persons with the following qualifications:
a) Trained and certified by manufacturer in fire-alarm system design.
b) NICET-certified fire-alarm technician Level 3 minimum.
B. Product Data: For each type of product indicated.
1. Shop Drawings: For fire-alarm system. Include plans, elevations, sections, details, and attachments to other work.
2. Comply with recommendations in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA 72.
3. Include voltage drop calculations for notification appliance circuits.
4. Include battery-size calculations.
5. Include performance parameters and installation details for each detector, verifying that each detector is listed for complete range of air velocity, temperature, and humidity possible when air-handling system is operating.
6. Include plans, sections, and elevations of heating, ventilating, and air-conditioning ducts, drawn to scale and coordinating installation of duct smoke detectors and access to them. Show critical dimensions that relate to placement and support of sampling tubes, detector housing, and remote status and alarm indicators. Locate detectors according to manufacturer's written recommendations.
7. Include voice/alarm signaling-service equipment rack or console layout, grounding schematic, amplifier power calculation, and single-line connection diagram.
8. Include floor plans to indicate final outlet locations showing address of each addressable device.
9. Show size and route of cable and conduits.
C. Delegated-Design Submittal: For smoke and heat detectors indicated to comply with Performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1. Drawings showing the location of each smoke and heat detector, ratings of each, and installation details as needed to comply with listing conditions of the detector.
2. Design Calculations: Calculate requirements for selecting the spacing and sensitivity of detection, complying with NFPA 72.
12. Quality Assurance:
D. NFPA Certification: Obtain certification according to NFPA 72.
13. Software Service Agreement:
14. Extra Materials:
G. Audible and Visual Notification Appliances: five (5) of each type installed.
H. Fuses: two (2) of each type installed in the system.
e) Bosch
1. Manual stations.
2. Heat detectors.
3. Smoke detectors.
4. Duct smoke detectors.
5. Verified automatic alarm operation of smoke detectors.
6. Automatic sprinkler system water flow.
7. Fire-extinguishing system operation.
9. Fire standpipe system.
1. Continuously operate alarm notification appliances.
2. Identify alarm at fire-alarm control unit and remote annunciators.
3. Transmit an alarm signal to the remote alarm receiving station.
4. Unlock electric door locks in designated egress paths.
5. Release fire and smoke doors held open by magnetic door holders.
6. Activate voice/alarm communication system.
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
B. Lamps for Remote Indicating Lamp Units: Quantity equal to ten (10) percent of amount in stalled, but no fewer than 1 unit.
C. Lamps for Strobe Units: Quantity equal to tem (10) percent of amount installed, but no fewer than 1 unit.
D. Smoke Detectors, Fire Detectors: Quantity equal to ten (10) percent of amount of each type installed, but no fewer than 1 unit of each type.
E. Detector Bases: Quantity equal to two (2) percent of amount of each type installed, but no fewer than 1 unit of each type.
F. Keys and Tools: One extra set for access to locked and tamper-proofed components.
A. Installer Qualifications: Installation shall be by personnel certified by NICET as fire-alarm Level 3 technician.
B. Source Limitations for Fire-Alarm System and Components: Obtain fire-alarm system from single source from single manufacturer.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
A. Comply with UL 864.
B. Technical Support: Beginning with Substantial Completion, provide software support for two (2) years.
C. Upgrade Service: Update software to latest version at Project completion.
Install and program software upgrades that become available within two (2) years from date of Substantial Completion. Upgrading software shall include operating system. Upgrade shall include new or revised licenses for use of software.
D. Provide thirty (30) days' notice to Owner to allow scheduling and access to system and to allow Owner to upgrade computer equipment if necessary.
15. Products:
A. Manufacturers:
1. Manufacturers: Available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a) National Time and Signal
b) Siemens Building Technologies, Inc. ; Fire Safety Division
c) Siemens Building Technologies, Inc.
d) Federal Signal Corporation.
16. Systems of Operational Description:
A. Fire-alarm signal initiation shall be by one or more of the following devices and systems:
B. Fire-alarm signal shall initiate the following actions:
7. Switch heating, ventilating, and air-conditioning equipment controls to fire-alarm mode.
8. Recall elevators to primary or alternate recall floors.
9. Record events in the system memory.
10. Record events by the system printer.
1. Open circuits, shorts, and grounds in designated circuits.
3. Loss of primary power at fire-alarm control unit.
4. Ground or a single break in fire-alarm control unit internal circuits.
5. Abnormal ac voltage at fire-alarm control unit.
6. Break in standby battery circuitry.
7. Failure of battery charging.
8. Abnormal position of any switch at fire-alarm control unit or annunciator.
E. Door Controls:
F. Remote Smoke-Detector Sensitivity Adjustment:
I. Status Annunciator:
C. System trouble signal initiation shall be by one or more of the following devices and actions:
2. Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating devices.
9. System Trouble and Supervisory Signal Actions: Initiate notification appliance and annunciate at fire-alarm control unit and remote annunciators. Record the event on system printer.
fire-alarm mode.
17. Fire-Alarm Control Unit:
A. General Requirements for Fire-Alarm Control Unit:
1. Field-programmable, microprocessor-based, modular, power-limited design with electronic modules, complying with UL 864 and listed and labeled by an NRTL.
2. System software and programs shall be held in flash electrically erasable programmable read-only memory (EEPROM), retaining the information through failure of primary and secondary power supplies.
3. Include a real-time clock for time annotation of events on the event recorder and printer.
4. Addressable initiation devices that communicate device identity and status.
5. Smoke sensors shall additionally communicate sensitivity setting and allow for adjustment of sensitivity at fire-alarm control unit.
6. Temperature sensors shall additionally test for and communicate the sensitivity range of the device.
7. Addressable control circuits for operation of mechanical equipment.
Alphanumeric Display and System Controls:
a) Arranged for interface between human operator at fire-alarm control unit and addressable system components including annunciation and supervision.
b) Display alarm, supervisory, and component status messages and the programming and control menu.
c) Annunciator and Display: Liquid-crystal type, 3 line(s) of 80 characters, minimum.
d) Keypad: Arranged to permit entry and execution of programming, display, and control commands and to indicate control commands to be entered into the system for control of smoke-detector sensitivity and other parameters.
B. Circuits:
1. Initiating Device, Notification Appliance, and Signaling Line Circuits: NFPA 72, Class A.
2. Initiating Device Circuits: Style 4.
3. Notification Appliance Circuits: Style Y.
4. Signaling Line Circuits: Style 4.
5. Install no more than 50 addressable devices on each signaling line circuit.
C. Serial Interfaces: Two RS-232 ports for printers.
D. Smoke-Alarm Verification:
1. Initiate audible and visible indication of an "alarm-verification" signal at fire-alarm control unit.
2. Activate an NRTL-listed and -approved "alarm-verification" sequence at fire-alarm control unit and detector.
3. Record events by the system printer.
4. Sound general alarm if the alarm is verified.
5. Cancel fire-alarm control unit indication and system reset if the alarm is not verified.
1. Door hold-open devices that are controlled by smoke detectors at doors in smoke barrier walls shall be connected to fire-alarm system.
2. For alarm verification, confirm that specified detector type is available with alarm verification.
1. Controls shall select specific addressable smoke detectors for adjustment, display their current status and sensitivity settings, and change those settings. Allow controls to be used to program repetitive, time-scheduled, and automated changes in sensitivity of specific detector groups. Record sensitivity adjustments and sensitivity-adjustment schedule changes in system memory, and print out the final adjusted values on system printer.
G. Transmission to Remote Alarm Receiving Station: Automatically transmit alarm, supervisory, and trouble signals to a remote alarm station.
H. Voice/Alarm Signaling Service:
1. Central emergency communication system with redundant microphones, preamplifiers, amplifiers, and tone generators provided as a special module that is part of fire-alarm control unit.
2. Indicated number of alarm channels for automatic, simultaneous transmission of different announcements to different zones or for manual transmission of announcements by use of the central-control microphone.
3. Amplifiers shall comply with UL 1711 and be listed by an NRTL.
4. Allow the application of an evacuation signal to indicated number of zones and, at same time, allow voice paging to the other zones selectively or in any combination.
5. Programmable tone and message sequence selection.
6. Standard digitally recorded messages for "Evacuation" and "All Clear."
7. Generate tones to be sequenced with audio messages of type recommended by
NFPA 72 and that are compatible with tone patterns of notification appliance circuits of fire-alarm control unit.
1. Indicate the status of various voice/alarm speaker zones and the status of firefighters' two-way telephone communication zones.
J. Preamplifiers, amplifiers, and tone generators shall automatically transfer to backup units, on primary equipment failure.
K. Printout of Events:
1. On receipt of signal, print alarm, supervisory, and trouble events.
2. Identify zone, device, and function. Include type of signal (alarm, supervisory, or trouble) and date and time of occurrence. Differentiate alarm signals from all other printed indications.
3. Print system reset event, including same information for device, location, date, and time.
4. Commands initiate the printing of a list of existing alarm, supervisory, and trouble conditions in the system and a historical log of events.
L. Primary Power:
1. 24-V dc obtained from 120-V ac service and a power-supply module.
2. Initiating devices, notification appliances, signaling lines, trouble signals, supervisory signals, supervisory and digital alarm communicator transmitters and, digital alarm radio transmitters shall be powered by 24-V dc source.
3. Alarm current draw of entire fire-alarm system shall not exceed 80 percent of the power-supply module rating.
M. Secondary Power:
1. Primary status.
2. Device type.
3. Present average value.
4. Present sensitivity selected.
5. Sensor range (normal, dirty, etc.).
A. Description:
M. Secondary Power:
1. 24-V dc supply system with batteries, automatic battery charger, and automatic transfer switch.
2. Batteries: Gel-cell type.
N. Instructions:
1. Computer printout or typewritten instruction card mounted behind a plastic or glass cover in a stainless-steel or aluminum frame.
2. Include interpretation and describe appropriate response for displays and signals.
3. Briefly describe the functional operation of the system under normal, alarm, and trouble conditions.
18. Manual Fire-Alarm Boxes:
A. General Requirements for Manual Fire-Alarm Boxes
1. Comply with UL 38. Boxes shall be finished in red with molded, raised-letter operating instructions in contrasting color; shall show visible indication of operation; and shall be mounted on recessed outlet box. If indicated as surface mounted, provide manufacturer's surface back box.
2. Single-action mechanism, pull-lever type; with integral addressable module arranged to communicate manual-station status (normal, alarm, or trouble) to fire-alarm control unit.
4. Indoor Protective Shield: Factory-fabricated clear plastic enclosure hinged at the top to permit lifting for access to initiate an alarm. Lifting the cover actuates an integral battery-powered audible horn intended to discourage false-alarm operation.
3. Station Reset: Key- or wrench-operated switch.
19. System Smoke Detectors:
A. General Requirements for System Smoke Detectors:
1. UL 268 covers detectors that are part of a fire-alarm system and detectors intended solely for control of releasing devices such as door holders and dampers.
2. Comply with UL 268; operating at 24-V dc, nominal.
3. Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble) to fire-alarm control unit.
4. Base Mounting: Detector and associated electronic components shall be mounted in a twist-lock module that connects to a fixed base. Provide terminals in the fixed base for connection to building wiring.
5. Self-Restoring: Detectors do not require resetting or readjustment after actuation to Restore them to normal operation.
6. Integral Visual-Indicating Light: LED type indicating detector has operated and power-on Status.
7. Photoelectric Smoke Detectors:
a) Detector address shall be accessible from fire-alarm control unit and shall be able to identify the detector's location within the system and its sensitivity setting.
b) An operator at fire-alarm control unit, having the designated access level, shall be able to manually access the following for each detector:
2. Device type.
3. Present average value.
4. Present sensitivity selected.
5. Sensor range (normal, dirty, etc.).
8. Ionization Smoke Detector:
a) Detector address shall be accessible from fire-alarm control unit and shall be able to identify the detector's location within the system and its sensitivity setting.
b) An operator at fire-alarm control unit, having the designated access level, shall be able to manually access the following for each detector:
1. Primary status.
20. Notification Appliances:
A. General Requirements for Notification Appliances: Individually addressed, connected to a signaling line circuit, equipped for mounting as indicated and with screw terminals for system connections.
B. Combination Devices: Factory-integrated audible and visible devices in a single-mounting assembly, equipped for mounting as indicated and with screw terminals for system connections.
C. Visible Notification Appliances: Xenon strobe lights comply with UL 1971, with clear or nominal white polycarbonate lens mounted on an aluminum faceplate.
The word "FIRE" is engraved in minimum 1-inch- (25-mm-) high letters on the lens.
1. Rated Light Output: 15/30/75/110 cd, selectable in the field.
2. Mounting: Wall mounted unless otherwise indicated.
3. Flashing shall be in a temporal pattern, synchronized with other units.
4. Strobe Leads: Factory connected to screw terminals.
5. Mounting Faceplate: Factory finished white.
D. Voice/Tone Notification Appliances:
1. Appliances shall comply with UL 1480 and shall be listed and labeled by an NRTL
2. Use high-range speakers in noisy environments and low-range speakers in quiet environments.
3. Select speakers for each location that comply with NFPA 72 requirements and
ADA-ABA Accessibility Guidelines.
4. Matching Transformers: Tap range matched to acoustical environment of speaker location.
21. Remote Annunciator:
1. Annunciator functions shall match those of fire-alarm control unit for alarm, supervisory, and trouble indications.
2. Manual switching functions shall match those of fire-alarm control unit, including acknowledging, silencing, resetting, and testing.
3. Remote Annunciator shall be installed at front lobby at location as directed by architect and with approval by local fire marshal.
4. Display Type and Functional Performance:
a) Alphanumeric display and LED indicating lights shall match those of fire-alarm control unit.
b) Provide controls to acknowledge,…
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| BAS-BECC Bldg Fire Alarm Panel Spec Book_ | — | |
| BAS BECC Building Addendum 01 03 15 2024.pdf |