Ballistic Guard House Specs.docx

DOCX document 17 KB Posted

Attached to
174 ATKW Security Forces Gate Shack
Solicitation number
W50S8N26QA013
Issued by

About this file

This document contains the minimum specifications for a ballistic guard house required under solicitation W50S8N-26-Q-A013 issued by the Department of the Army National Guard. The structure is a prefabricated building measuring 5 feet wide by 8 feet long by 8 feet high and must meet UL752 Level 3 ballistic protection standards. Key structural components include certified steel plate exterior walls, two 36" X 80" bullet-resistant sliding doors with UL Level 3 polycarbonate glazing, 360-degree tinted bullet-resistant windows (36" tall), a 3-inch structural steel tubing frame, R-18 insulation, VCT flooring, 11-gauge heavy-duty steel ceiling and roof panels, and 18-inch overhangs on doorways. All exterior wall panels must feature factory-finished UL752 Level 3 ballistic protection on the exterior face with galvanized and mechanically fastened construction.

The electrical and HVAC package must include 12-gauge minimum copper wiring in 1/2-inch EMT surface-mounted conduit with two single-pole switches, six 115V duplex receptacles, a 12-amp 12-space circuit breaker box with four circuits, four T8 fluorescent fixtures, six exterior floodlights with switch, and one wall-mounted HVAC unit with 18,000 BTU cooling and 16,000 BTU heating capacity featuring a ballistic shroud. The power box location must match the exact location and height of existing structures to avoid new cable runs. This RFQ is a 100% small business set-aside with a NAICS code of 332311 (750-employee size standard). A non-mandatory site visit is scheduled for February 18, 2026, at 10:00 EST, with participant information due by 2:00 PM EST on February 17, 2026.

View the file

Other files

File Type Posted
Old Shack Photos.pdf PDF
Solicitation - W50S8N26QA013.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ballistic Guard House Minimum Specifications

Size - Ballistic Guard House 5’ wide X 8’ long X 8’ High, UL752 Level 3 Prefabricated Building specs:

· UL 752 Level 3 Elements

· All material used for exterior walls: ¼” certified steel plates, UL752 Level 3

· (2) 36” X 80” Bullet resistant UL 752 Level 3 solid sliding door, latch lock, weather stripping. Door to be glazed with UL Level 3 clad polycarbonate glazing, tinted

· 360 Degree view UL 752 Level 3 bullet resistant windows tinted, and fixed glad polycarbonate glass mounted against ballistic walls, 36” tall.

· (1) UL 752 Level 3 AC shroud welded around the AC opening

· Other building elements

· 3” structural steel tubing frame

· Insulation: R-18

· VCT flooring (color TBD)

· Exterior wall panels factory finish UL 752 Level 3 bullet resistant protection exterior face, 16 ga heavy duty steel interior, panels galvanized and mechanically fastened.

· Ceiling finish with 11-ga heavy duty steel, mechanically fastened to provide smooth flat interior

· Roof finish 11-ga heavy duty steel galvanized and welded to provide smooth flat exterior if acceptable for aesthetic exterior.

· (2) 18” overhangs on doorways

· Electrical/HVAC

· Electrical package consists of 12-ga minimum copper wiring in 1/2” EMT surface mounted conduit and attached to surface mounted 2x4 boxes

· (2) single pole switches wired

· (6) 115V duple receptacles, wired

· 12 Amp 12 space circuit breaker box with 4 circuits

· (4) T8 fluorescent light fixtures, wired

· (6) Exterior floodlights with switch

· (1) Wall mounted HVAC unit, 18,000BTU cooling and 16,000 BTU heating with ballistics shroud

· (1) Power box location must match existing structure exact location and height to avoid running of new cables to location.

File details come from the government source that posted it. Updated .