Ballistic Guard House Specs.docx
DOCX document 17 KB Posted
- Attached to
- 174 ATKW Security Forces Gate Shack
- Solicitation number
- W50S8N26QA013
- Issued by
-
Department of the Army National Guard
About this file
This document contains the minimum specifications for a ballistic guard house required under solicitation W50S8N-26-Q-A013 issued by the Department of the Army National Guard. The structure is a prefabricated building measuring 5 feet wide by 8 feet long by 8 feet high and must meet UL752 Level 3 ballistic protection standards. Key structural components include certified steel plate exterior walls, two 36" X 80" bullet-resistant sliding doors with UL Level 3 polycarbonate glazing, 360-degree tinted bullet-resistant windows (36" tall), a 3-inch structural steel tubing frame, R-18 insulation, VCT flooring, 11-gauge heavy-duty steel ceiling and roof panels, and 18-inch overhangs on doorways. All exterior wall panels must feature factory-finished UL752 Level 3 ballistic protection on the exterior face with galvanized and mechanically fastened construction.
The electrical and HVAC package must include 12-gauge minimum copper wiring in 1/2-inch EMT surface-mounted conduit with two single-pole switches, six 115V duplex receptacles, a 12-amp 12-space circuit breaker box with four circuits, four T8 fluorescent fixtures, six exterior floodlights with switch, and one wall-mounted HVAC unit with 18,000 BTU cooling and 16,000 BTU heating capacity featuring a ballistic shroud. The power box location must match the exact location and height of existing structures to avoid new cable runs. This RFQ is a 100% small business set-aside with a NAICS code of 332311 (750-employee size standard). A non-mandatory site visit is scheduled for February 18, 2026, at 10:00 EST, with participant information due by 2:00 PM EST on February 17, 2026.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Old Shack Photos.pdf | ||
| Solicitation - W50S8N26QA013.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ballistic Guard House Minimum Specifications
Size - Ballistic Guard House 5’ wide X 8’ long X 8’ High, UL752 Level 3 Prefabricated Building specs:
· UL 752 Level 3 Elements
· All material used for exterior walls: ¼” certified steel plates, UL752 Level 3
· (2) 36” X 80” Bullet resistant UL 752 Level 3 solid sliding door, latch lock, weather stripping. Door to be glazed with UL Level 3 clad polycarbonate glazing, tinted
· 360 Degree view UL 752 Level 3 bullet resistant windows tinted, and fixed glad polycarbonate glass mounted against ballistic walls, 36” tall.
· (1) UL 752 Level 3 AC shroud welded around the AC opening
· Other building elements
· 3” structural steel tubing frame
· Insulation: R-18
· VCT flooring (color TBD)
· Exterior wall panels factory finish UL 752 Level 3 bullet resistant protection exterior face, 16 ga heavy duty steel interior, panels galvanized and mechanically fastened.
· Ceiling finish with 11-ga heavy duty steel, mechanically fastened to provide smooth flat interior
· Roof finish 11-ga heavy duty steel galvanized and welded to provide smooth flat exterior if acceptable for aesthetic exterior.
· (2) 18” overhangs on doorways
· Electrical/HVAC
· Electrical package consists of 12-ga minimum copper wiring in 1/2” EMT surface mounted conduit and attached to surface mounted 2x4 boxes
· (2) single pole switches wired
· (6) 115V duple receptacles, wired
· 12 Amp 12 space circuit breaker box with 4 circuits
· (4) T8 fluorescent light fixtures, wired
· (6) Exterior floodlights with switch
· (1) Wall mounted HVAC unit, 18,000BTU cooling and 16,000 BTU heating with ballistics shroud
· (1) Power box location must match existing structure exact location and height to avoid running of new cables to location.
File details come from the government source that posted it. Updated .