Baldwin Aquatic Addendum Number 3.pdf
PDF 5 MB Posted
- Attached to
- Baldwin County Aquatic Facility Project
- Solicitation number
- PE-60500-NONST-2024-000000003
- Issued by
- Barrow County, Georgia
About this file
This document is an addendum to the Baldwin County Aquatic Facility project, a state and local contract opportunity in Baldwin County, Georgia. The addendum provides updates and clarifications to the project, including details on the Lazy River Pool Collector Tank, the addition of water lines and hose bibbs, changes to the pool finish schedule and plumbing, the elimination of the fire alarm system, approval of equal products, revisions to the electrical drawings, and requirements for future security system conduits. The contractor is also responsible for paying water and sewer tap fees.
The document further outlines specific requirements for millwork, electrical panels, and CT metering. It also provides updated mechanical and electrical plan sheets that replace previously issued drawings. This state and local contract opportunity is being managed by Baldwin County, and the bid documents are available from the project engineer.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM NUMBER 3
BALDWIN COUNTY AQUATIC FACILITY
BALDWIN COUNTY, GEORGIA
March 11, 2024
1. Attached (Attachment Number 1) is the Lazy River Pool Collector Tank Installation Detail, Drawing
G00130, referenced on Drawing LR7.
2. Provide a two-inch water line connection to hose bibbs on the inside and outside of the pool mechanical building. Location of hose bibbs to be determined by Owner.
3. Provide hose bibb connections on all pump suction lines for pump priming.
4. Reference the Pool Finish Schedule on Drawing SWD1, for the Pool Vertical Surface- Freeboard and
Waterline, replace the two rows of 4-inch by 4-inch ceramic tile with one row of 6-inch by 6-inch ceramic tile.
5. Reference Drawing LR7 in Addendum Number 1, change the 10-inch diameter Equalizer Pipe to an 18-inch diameter.
6. Specification Section 28 3100, Fire Alarm System, is hereby eliminated from the Project Manual.
7. The following manufacturers are approved as equals to the specified products:
a. Picnic Pavilion – Drawing C-502, RCP Shelters, Inc.
b. Toilet Partitions- Specification Section 10 2113, Hadrian, must meet NFPA requirements.
8. Refer to the attached Electrical Drawings for a revised Single Line Power Riser Diagram.
9. Provide the following Gray Schedule 40 PVC conduits for future security system installation. The actual security system is not in the contract but installation of the conduits is:
a. Two-inch conduits from the Bathhouse Storage Room to the Pool Mechanical Building and the future
Splash Pad Mechanical Building. Terminate the conduit to the future Splash Pad Mechanical Building outside of the concrete deck near the bike racks.
b. One-inch conduits from the Bathhouse Storage Room to the Picnic Shelter and the two light poles south of the bathhouse.
c. One-inch conduits from the Pool Mechanical Building to the light poles west and north of the Lazy
River, five locations total.
10. Contractor is responsible for paying water and sewer tap fees to the City of Milledgeville.
11. Collector tanks are to be provided per the drawings.
Baldwin Aquatic Facility Addendum Number 3, March 11, 2024
12. All millwork in Lifeguard 102 & Concession 103A shall have the toe kick shown as part of Detail
5/A402 replaced by a cast-in-place concrete curb that is 4” tall and 1’-9” deep. The integral base being provided as part of the fluid-applied flooring shall be installed on all exposed faces of the curb. The millwork bottom panel shown as part of Detail 5/A402 will be attached to the top of the concrete curb.
All wood millwork materials in contact with cast-in-place concrete and masonry materials shall be pressure-treated exterior grade in all locations specified to receive millwork.
13. Electrical Questions and Responses:
a. Our supplier says that panel Ll to be a true single enclosure a 200 amp breaker will not fit (200 goes to 50 Kw water heater). Panel will have to be two separate panels. If two panels are used I don't believe there will be enough space in current location.
Response - In that case have your supplier provide single enclosure panel with feed thru lugs and provide an external enclosed 200 amp breaker for water heater adjacent to panel. We have confirmed with other vendors the specified configuration works for them.
b. Plans show panel Ll and LC recessed into wall is this a block wall if so and we use this wall panels need to be surface mounted.
Response - Surface mount on block is acceptable. Provide equipment pad below it if done surface mount.
c. What is being CT metered by GPC? GPC needs to look at new plans.
Response - GPC should have current plans. CT meter is for 800a 208v/3ph service on pool mechanical building, other services are feed thru meters.
d. Does panel for pool need 800 amp main shunt trip breaker or are branch circuits to pool packs shunted? Plans show on schedule shunted 800 amp main but also shunted branch circuits.
Response - Currently the EPO off pushbutton mounted near the center of the pool restroom building (near lifeguard) shunts power to the MAIN Breaker in LPOOL. (This cuts power to all pool circulating equipment). The EPO switch on the left of the pool restroom building shunts the main breaker in panel LSPLASH (phase 2). (Cuts splashpad only). The EPO switch mounted on the pool mech building Shunts the breaker to the skid for the main pool only. The EPO switch mounted on the slide shunts the breaker for the skid for the slide only.
e. On main building there are 2 - 30 amp outlets for pool vacs shows they are on same circuit these need to be on two different circuits due to possible overload of circuit.
Response – These receptacles will not be used simultaneously. It will be an either/or type situation where one or the other is used, but not both simultaneously.
14. The solid surface countertop color shall be picked from Corian’s Group 2.
15. The solid surface window sill and chase cap color shall be picked from Avonite’s solid color range that is standard for the North American market.
Baldwin Aquatic Facility Addendum Number 3, March 11, 2024
16. The upper portion of the Type B window shall provide awning operation.
17. The ceiling tile in Lifeguard 102 & Reception 101 shall be the perforated type specified. All other areas specified to receive acoustical ceiling tile shall receive the scrubbable tile type specified.
18. Attached are updated Mechanical plans, Attachment Number 2. These sheets replace the previously issued sheets.
19. Attached are updated Electrical plans, Attachment Number 3. These sheets replace the previously issued sheets.
A
B
A
B
THIRD ANGLE PROJECTION
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
TOL ANGLE ± 1.0°,
2 PL ±0.25, 3 PL ±0.125
INTERPRET DIM(S) & TOL(S)
HKINNUNEN 01/07/20
SLOVIN 01/08/20
LEVEL 00 TANK
FOR SPLASH PAD PARKS / IWF PARKS/ COMMERCIAL POOL
(CT4000IWF COLLECTOR TANK SHOWN)
1/4" = 1' R1 2 2 XXXXX-G00130
PE
RM
IT
R
EV
IE
W
N
OT
F
OR
C
ON
ST
RU
CT
IO
N
2,620
GENERAL NOTES:
GRAPHICS SHOWN ARE REPRESENTATIVE OF A 4,000 GALLON COLLECTOR TANK OR VAULT.
THIS DRAWING IS REFLECTIVE OF ALL MODEL TANKS & VAULT INSTALLATION REQUIREMENTS.
DRAWINGS CAN BE SUPERCEDED BASED ON THE ENGINEER OF RECORD (EOR) /LANDSCAPE ARCHITECT (LA) OF
RECORD, THE STATE, LOCAL CODES OR REGULATIONS.
E.C.N. NO.REV. DESCRIPTION DATE BYZONE
ALL R0 N/A RELEASED FOR SUBMITAL. 01/07/20 HK
ALL R1 N/A RM'VD GEOMETRY REFERENCE, ADDED HATCH NOTE 03/31/21 HK
AutoCAD SHX Text 1'-0 " 6"12"±6"
AutoCAD SHX Text 1'-0"±6"
AutoCAD SHX Text
(2'-0")MIN.
AutoCAD SHX Text
(2'-0")MIN.
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
MFG CHECK
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
DWG NO
AutoCAD SHX Text
REV
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text A
AutoCAD SHX Text
OF
AutoCAD SHX Text WT. (lbs.)
AutoCAD SHX Text DISTRIBUTION STATEMENT: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF VAK PAK INC., ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF VAK PAK INC., IS STRICTLY PROHIBITED.
AutoCAD SHX Text
ANSI-A (BASE_R1)
AutoCAD SHX Text
1.1. CONCRETE PADS WILL INCREASE OR DECREASE AS TANK/VAULT SIZE VARIES BY MODEL NUMBER. CONCRETE PADS WILL INCREASE OR DECREASE AS TANK/VAULT SIZE VARIES BY MODEL NUMBER. 1. ALL EXTERNAL PLUMBING & ANCHORING HARDWARE TO TANK IS SUPPLIED AND INSTALLED BY OTHERS. ALL EXTERNAL PLUMBING & ANCHORING HARDWARE TO TANK IS SUPPLIED AND INSTALLED BY OTHERS. 2. ALL BACK FILL MATERIAL AROUND TANK TO BE SELECTED AND SPECIFIED BY ENGINEER OF RECORD. ALL BACK FILL MATERIAL AROUND TANK TO BE SELECTED AND SPECIFIED BY ENGINEER OF RECORD. 3. THE ANCHOR POINTS ARE TO BE SPECIFIED BY ENGINEER OF RECORD. THE ANCHOR POINTS ARE TO BE SPECIFIED BY ENGINEER OF RECORD. 3.1. WHEN THE ANCHOR POINTS ARE NOT SPECIFIED BY THE ENGINEER OF RECORD, WHEN THE ANCHOR POINTS ARE NOT SPECIFIED BY THE ENGINEER OF RECORD, 3.1.1. GALVANIZED STEEL ANCHOR BOLTS AND GALVANIZED STEEL WIRE CABLE GALVANIZED STEEL ANCHOR BOLTS AND GALVANIZED STEEL WIRE CABLE 3.1.2. ATTACHED TO EXTERIOR OF TANK (OR) VAULT FOR CABLE ATTACHMENT, BY OTHERS. ATTACHED TO EXTERIOR OF TANK (OR) VAULT FOR CABLE ATTACHMENT, BY OTHERS. 3.2. ALL TANK/VAULT THAT ARE EQUIPPED WITH EYELETS ARE NOT USED FOR LIFTING OR SHIPPING TIE-DOWNS ALL TANK/VAULT THAT ARE EQUIPPED WITH EYELETS ARE NOT USED FOR LIFTING OR SHIPPING TIE-DOWNS 4. PREPARE EXCAVATED HOLE. MAINTAIN ACCURATE ELEVATION MEASUREMENTS. PREPARE EXCAVATED HOLE. MAINTAIN ACCURATE ELEVATION MEASUREMENTS. 4.1. DIG THE HOLE DEEP ENOUGH TO ALLOW FOR A CONCRETE PAD WITH A MINIMUM DIAMETER THAT ALLOWS FOR DIG THE HOLE DEEP ENOUGH TO ALLOW FOR A CONCRETE PAD WITH A MINIMUM DIAMETER THAT ALLOWS FOR EXCESSIVE WIDTH IN ALL DIRECTIONS FROM THE OUTSIDE WALLS OF THE TANK/VAULT. POUR CONCRETE INSPECTED TO THE ENGINEER OF RECORD'S DESIGN FOR THE CONCRETE SUBSTRUCTURE. 5. ONCE SET, ATTACH ANCHOR WIRE TIE-DOWN CABLES TO THE EXTERNAL EYEBOLTS ON THE TANK/VAULT. ONCE SET, ATTACH ANCHOR WIRE TIE-DOWN CABLES TO THE EXTERNAL EYEBOLTS ON THE TANK/VAULT. 5.1. FASTEN AND SECURE ALL EYEBOLT CONNECTIONS POINTS TO THE CONCRETE ANCHOR POINT. CONCRETE EMBEDMENT, FASTEN AND SECURE ALL EYEBOLT CONNECTIONS POINTS TO THE CONCRETE ANCHOR POINT. CONCRETE EMBEDMENT, FASTENER TYPE, ATTACHMENT METHOD ARE ALL ITEMS SPECIFIED BY THE ENGINEER OF RECORD. . 6. MAINTAIN TANK/VAULT LEVEL TO SET FINISHED GRADE ELEVATION TO BE PLUMB IN ALL DIRECTIONS. MAINTAIN TANK/VAULT LEVEL TO SET FINISHED GRADE ELEVATION TO BE PLUMB IN ALL DIRECTIONS. 6.1. (IF THE TANK/VAULT INSIDE FLOOR HAS A MANUFACTURED SLOPE TO ONE END AND SHOULD NOT BE USED AS A (IF THE TANK/VAULT INSIDE FLOOR HAS A MANUFACTURED SLOPE TO ONE END AND SHOULD NOT BE USED AS A LEVELING POINT) 7. STUB UP THE TANK DRAIN CONNECTION IN THE BOTTOM OF THE TANK BEFORE POURING THE CONCRETE SLURRY IF THE STUB UP THE TANK DRAIN CONNECTION IN THE BOTTOM OF THE TANK BEFORE POURING THE CONCRETE SLURRY IF THE SECOND METHOD OF CONCRETE APPLICATION IS SELECTED. 10. BEFORE BACK FILLING (WHEN THE VESSEL IS A TANK)FOLLOW THE REMAINING STEP IN NOTE 10, IF A VAULT PROCEED TO BEFORE BACK FILLING (WHEN THE VESSEL IS A TANK)FOLLOW THE REMAINING STEP IN NOTE 10, IF A VAULT PROCEED TO NOTE 11. 10.1. INITIAL FILL TANK W/POTABLE WATER TO 30%-50% WATER LEVEL, INITIAL FILL TANK W/POTABLE WATER TO 30%-50% WATER LEVEL, 10.1. THEN EXTERNALLY BACKFILL AROUND THE TANK, ADDED BACKFILL TO THE SAME LEVEL. THEN EXTERNALLY BACKFILL AROUND THE TANK, ADDED BACKFILL TO THE SAME LEVEL. 10.2. CONTINUE ADDING WATER TO THE TANK AND BACKFILL ON THE OUTSIDE AT 25% INCREMENTS UNTIL BACKFILL IS CONTINUE ADDING WATER TO THE TANK AND BACKFILL ON THE OUTSIDE AT 25% INCREMENTS UNTIL BACKFILL IS COMPLETE. THIS WILL HELP PREVENT STRESS ON THE TANK WALLS FROM THE INSIDE,WHEN BACKFILLING. 10.3. FAILURE TO COMPLY MAY VOID TANK WARRANTY. FAILURE TO COMPLY MAY VOID TANK WARRANTY. 11. AFTER ALL PLUMBING CONNECTIONS HAVE BEEN MADE, AFTER ALL PLUMBING CONNECTIONS HAVE BEEN MADE, 11.1. BACKFILL THE EXCAVATION WITH AN APPROVED MEDIA APPROVED PRIOR WITH THE GEOTECHNICAL ENGINEER OR BACKFILL THE EXCAVATION WITH AN APPROVED MEDIA APPROVED PRIOR WITH THE GEOTECHNICAL ENGINEER OR ENGINEER OF RECORD FOR THE LOCAL SOIL CONDITIONS. 11.2. TAKE PRECAUTIONS TO SUPPORT PIPE AND CONNECTIONS IN SUCH A MANNER THAT THEY ARE NOT DISTURBED OR TAKE PRECAUTIONS TO SUPPORT PIPE AND CONNECTIONS IN SUCH A MANNER THAT THEY ARE NOT DISTURBED OR DAMAGED DURING BACKFILLING PROCEDURES.
AutoCAD SHX Text
PLAN VIEW - COLLECTOR TANK - COLLECTOR TANK
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ANCHOR
AutoCAD SHX Text
SEE SHT#1 FOR CONCRETE DETAILS
AutoCAD SHX Text SPECIFIED BY ENGINEER OF RECORD GALVANIZED WIRE CABLE IS TO BE MECHANICALLY CONNECTED TO REBAR AND AT EYEBOLTS USING A MINIMUM OF THREE (3) GALVANIZED CABLE(S) PER SIDE W/3 CLAMPS @ EACH CONNECTION END POINT MINIMUM OF 3 ANCHORING POINT(S) ON THE SHORT SIDE MINIMUM OF 4 ANCHORING POINT(S) ON THE LONGER SIDE david Text Box
ATTACHMENT NUMBER 1
1 2 3 4 5
B
C D
1 2 3 4 5
A B
C D
P:\22107\22107m002.dgn
$REF001
$REF002
$REF003
$REF004
$REF005
$REF006
$REF007
$REF008
$REF009
$REF010
$REF011
$REF012
$REF013
$REF014
$REF015
$REF016
$REF017
$REF018
$REF019
$REF020
$REF021
$REF022
$REF023
$REF024
$REF025
$REF026
$REF027
$REF028
$REF029
$REF030
$REF031
$REF032
$REF033
$REF034
$REF035
$REF036
$REF037
$REF038
$REF039
$REF040
DATE PLOTTED
DGN FILE
10-MAR-2024
REFERENCE FILES
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
T H
IS
D
R A
W
IN
G I S T
H E P
R O
P E
R T
Y O
F L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y I
N C
O R
P O
R A
T E
D A
R C
H
IT
E C
T S I T I S N
O T T
O B
E R
E P
R O
D U
C E
D I
N W
H O
L E O
R I
N P
A R
T I T I S N
O T T
O B
E U
S E
D O
N A
N Y O
T H
E R P
R O J E
C T I T S
H A
L L B
E R
E T
U R
N E
D U
P O
N R
E Q
U E S
T C
O P
Y R
IG
H T A
S D
A T E
D L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y N
O T V
A L
ID
U
N L E S S S
IG
N E
D A
N D S
E A
L E
D
WSH
WSH
121035.00
W a lt e r
B
W il li a m s J r.
P a rk
B a ld w in C o u n ty A q u a ti c F a c il it y
M il le d g e v il le
G e o rg ia
Aquatic Facility
Baldwin County
59 GA-22
Milledgeville, GA 31061
Baldwin County 1601 N Columbia Street
Suite 220
Milledgeville, GA 31061
ARCHITECTURE
PLANNING
INTERIOR DESIGN
Lyman
Davidson
Dooley, Inc.
1640 Powers Ferry Road
Building One
Marietta, GA 30067
770.850.8494 t
770.956.9030 f lddi-architects.com
TITLE
STATUS
QC
DATE
DRAWN
JOB
SHEET
REVISIONS
EXPIRES: 06.30.2024
COA#PEF000774
NBP ENGINEERS, INC.
Permit Set
2/20/2024
M002
HVAC
SCHEDULES -
TYPE CFMMARK
MAX. MAX.
RPM
MOTOR
HP
FAN SCHEDULE
MIN.
FAN DIA.
(IN)
DRIVE
TYPE
SP
IN WG TS
EF-1
EF-2
EF-3
MARK
GRILLE SCHEDULE
VOLUME
DAMPERNECK
FINISH
NECK
RUNOUT
TITUSTYPE
FACE
SIZE
OFFWHITE
NOTES:
1 RUNOUT SIZE UNLESS OTHERWISE NOTED.
B OFFWHITE
12"x12"
20"x20"
NO ---
UNIT
MARK
INDOOR
UNIT
MARK
OUTDOOR
MBH
MIN
COOLING
SEER
MIN
INDOOR OUTDOOR
DUCTLESS SPLIT SYSTEM SCHEDULE
DCU-1
REMARKS
DAC-3
DAC-1A/B
ILC
PWF
0.5
0.5
0.2
27.0
20.0
DIRECT
DIRECT
DIRECT
CGC
CGC
12"x12"
20"x20" NO
50F
50F
SHEET METAL SCREW
8"O.C.
‚" X 18 GAUGE
HARDWARE CLOTH
1" WIDE 24 GAUGE FRAME
WITH HEMMED CORNERS
TURN IN ALL AROUNDDUCT
SCREENED DUCT OPENING DETAIL
NOTE: INSTALL SCREEN AT ALL VISIBLE DUCT OPENINGS
IN MECHANICAL ROOM(S) AND WHERE SHOWN.
NOT TO SCALE
GRILLE WITH DAMPER. GRILLE SHALL BE
SECURED TO SLEEVE. NOTE GRILLE/DAMPER
DEPTH IS 3•" . SLEEVE LENGTH SHALL+-
REFER TO U.L. LISTING FOR REQUIRED
CLEARANCE FOR DAMPER MANUFACTURER AND
SIZE FURNISHED. IN NO CASE SHALL
CLEARANCE BE LESS THAN ‚".
GRILLE FLANGE SHALL COVER REQUIRED
ANGLE OVERLAP.
BOLT, TACK, WELD OR SCREW DAMPER TO
SLEEVE AT 12" MAX. SPACING.
BOLT, TACK, WELD OR SCREW DAMPER TO
SLEEVE AT 12" MAX. SPACING.
MINIMUM 16 GAUGE ANGLE. MINIMUM
1" OVERLAP OF WALL.
TRANSFER GRILLE WITH FIRE DAMPER
WALL
ACCOMMODATE FIRE DAMPER AND GRILLE.
LOUVER
WALL MOUNTED LOUVER WITH PLENUM
COUNTER
FLASHING
20 GAUGE SLEEVE
16"MIN.
SUB FRAME
PROVIDE MINIMUM 16 INCH
PLENUM BEHIND LOUVER
FOR STRUCTURE MATERIALS
REFER TO ARCHITECTURAL
ON HEAD AND SILL
USE LINTELBLOCK
IN BLOCK WALLS,
INSULATED PLENUM
SUPPORT FROM STRUCTURE
TAKE-OFF IS INACCESSIBLE.
ACCESSIBLE CEILING IF
AS POSSIBLE OVER
FAR AWAY FROM GRILLE
LOCATE MVD IN DUCT AS
CEILING
EXHAUST GRILLE
NOT TO SCALE
NOTES:(THIS DETAIL ONLY)
DO NOT APPLY TO FUME EXHAUST GRILLES/REGISTERS.1
OR 12", WHICHEVER IS LARGER
THAN INDICATED RUN OUT SIZE
HEIGHT SHALL BE 2" LARGER
0.75 R
MAXIMUM OFFSET
SHALL NOT EXCEED
ONE DUCT DIAMTER
EXCEED 1/2" PER FT
MAXIMUM SAG SHALL NOT
DIRECTLY ON TOP OF PLENUM.
0.75 RADIUS, METAL ELBOW
IF TOP ENTRY IS USED, PROVIDE
DUCT PRESSURE CLASS.
SEAL JOINT AS SPECIFIED FOR
MIN. TWO PER SIDE, AND
WITH SHEET METAL SCREWS,
FASTEN PLENUM TO GRILLE
SHEETMETAL SCREWS)
TO PLENUM (MINIMUM OF 4
FLANGE, SEAL AND SECURE
5 FT. OF FLEX DUCT
PROVIDE MAXIMUM
WITH GASKETED FLANGE
45 DEGREE TAKE-OFF
2 3 4
C OFFWHITE
NO
NO
18/14
OFFWHITE
18"x14"
12"x8"
18"x14"WRAG
WRAG-SSD
350RL
NOTES:
1 LAYOUT BASIS: SOLER PALAU TD-150.
EF-4
65w
170 0.5 --- 2289 --- 65w
350RL-SS 12"x8"
DETAIL AT TYPICAL GENERAL EXHAUST GRILLE - UNLINED
DCU-2
DCU-3
MARK KW REMARKS
ELECTRIC HEATER SCHEDULE
EUH-1
EUH-2
EF-5
EF-6
EF-7
EF-8
0.5
0.5
0.2
0.5
PWF
ILC
MARK LENGTH WIDTH HEIGHT
SUPPLY AIR EXHAUST AIR
MAX. CFM MAX. S.P. MAX. CFM MAX. S.P.
KH-1
HOOD DIMENSIONS (FEET) LAYOUT BASIS:
CAPTIVEAIRE
REMARKS
KITCHEN HOOD SCHEDULE
KEF-1
SEF-1
DAC-2
KEF
ILC
610 0.05 760 0.34 5'-6" 4'-0" 2'-0" GHEW
14.6
1 1.1
20.1
16.8
65w
65w
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT610
0.6
0.7
1 03/01/24 Add. #1
2 Add. #303/08/24
EXT. S.P.
IN H O2 SENSIBLE TOTAL
ENTERING AIRMOTOR
HP
COOLING COIL
MIN.MIN. MIN.
LEAVING AIR
F FMBH MBH
CFM CFM
MARK
LBS.
WEIGHT
APPROX.
DB / WB DB / WB
REMARKS
AC-1 0.5 208 / 3
VOLT / PHASE
MIN. OA
ELECTRIC HEAT
Kw
MIN.
# STAGES
SUPPLY
TYPE
PACKAGED AIR CONDITIONER SCHEDULE
CV 1050 210 ƒ 24 34 80 / 67 59 / 57 7.9 1 510
E OFFWHITE NO
OFFWHITE
18"x18" 18"x18"ASEG
F
350FL
RLF TMS 24"x24" 12"{ YES
18"x18"
12"{
CARRIER MODEL #
19.5
19.5
40MBCQ12
40MBCQ12
38MAQB12R
38MAQB12R
--- NOT USED
david Text Box
ATTACHMENT NUMBER 2
B
C D
1 2 3 4 5
A B
C D
P:\22107\22107m201.dgn
$REF001
$REF002
$REF003
$REF004
$REF005
$REF006
$REF007
$REF008
$REF009
$REF010
$REF011
$REF012
$REF013
$REF014
$REF015
$REF016
$REF017
$REF018
$REF019
$REF020
$REF021
$REF022
$REF023
$REF024
$REF025
$REF026
$REF027
$REF028
$REF029
$REF030
$REF031
$REF032
$REF033
$REF034
$REF035
$REF036
$REF037
$REF038
$REF039
$REF040
DATE PLOTTED
DGN FILE
10-MAR-2024
REFERENCE FILES
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
T H
IS
D
R A
W
IN
G I S T
H E P
R O
P E
R T
Y O
F L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y I
N C
O R
P O
R A
T E
D A
R C
H
IT
E C
T S I T I S N
O T T
O B
E R
E P
R O
D U
C E
D I
N W
H O
L E O
R I
N P
A R
T I T I S N
O T T
O B
E U
S E
D O
N A
N Y O
T H
E R P
R O J E
C T I T S
H A
L L B
E R
E T
U R
N E
D U
P O
N R
E Q
U E S
T C
O P
Y R
IG
H T A
S D
A T E
D L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y N
O T V
A L
ID
U
N L E S S S
IG
N E
D A
N D S
E A
L E
D
WSH
WSH
121035.00
W a lt e r
B
W il li a m s J r.
P a rk
B a ld w in C o u n ty A q u a ti c F a c il it y
M il le d g e v il le
G e o rg ia
Aquatic Facility
Baldwin County
59 GA-22
Milledgeville, GA 31061
Baldwin County 1601 N Columbia Street
Suite 220
Milledgeville, GA 31061
ARCHITECTURE
PLANNING
INTERIOR DESIGN
Lyman
Davidson
Dooley, Inc.
1640 Powers Ferry Road
Building One
Marietta, GA 30067
770.850.8494 t
770.956.9030 f lddi-architects.com
TITLE
STATUS
QC
DATE
DRAWN
JOB
SHEET
REVISIONS
EXPIRES: 06.30.2024
COA#PEF000774
NBP ENGINEERS, INC.
Permit Set
2/20/2024
RECEPTION
LIFEGUARD
CONCESSION
103A
WOMEN'S
RESTROOM
105A
WOMEN'S
ADA
106A
MEN'S
RESTROOM
107A
CHASE
MEN'S
RESTROOM
107B
MEN'S ADA
106B
WOMEN'S
RESTROOM
105B
STORAGE
103C
JAN.
103B
SCALE:
= 1'-0
4 0 2 4 8
N O R T H
T R U E
N
M201
FLOOR PLAN - HVAC
T
T
DAC-3
DAC-2
C
B
A
B
EUH-1
EF-1
w/FULLSIZE 18" PLENUM
36"x18" OA INTAKE LOUVER w/FULLSIZE 18" PLENUM
36"x18" OA INTAKE LOUVER
12"x12" AVD
800|
375|
1100| w/FULLSIZE 18" PLENUM
30"x30" EA LOUVER
22/2222/2216/1616"{
10"{
14"x12" AVD
310|
SYSTEMS/HVAC POWER
FLOOR PLAN -
MVD
DCU-2 DCU-3
12"x12" AVD
20/20
310|
B
10"{
20/20
B 980|
16"{
16"{
EF-5
w/FULLSIZE 18" PLENUM
18"x18" OA INTAKE LOUVER
30|
A
4"{
875|
B w/FULLSIZE 18" PLENUM
18"x18" OA INTAKE LOUVER
12"x12" AVD w/FULLSIZE 18" PLENUM
24"x24" EA LOUVER
KEF-1
KH-1
10"{10"{
ESF-1
AC-1
CONCRETE PAD
16/10
B
T
16/10
F |350
F
|350
F
|350
16/10
1 03/11/24 Add. #3 david Text Box
ATTACHMENT NUMBER 2
B
C D
1 2 3 4 5
A B
C D
P:\22107\22107e001.dgn
$REF001
$REF002
$REF003
$REF004
$REF005
$REF006
$REF007
$REF008
$REF009
$REF010
$REF011
$REF012
$REF013
$REF014
$REF015
$REF016
$REF017
$REF018
$REF019
$REF020
$REF021
$REF022
$REF023
$REF024
$REF025
$REF026
$REF027
$REF028
$REF029
$REF030
$REF031
$REF032
$REF033
$REF034
$REF035
$REF036
$REF037
$REF038
$REF039
$REF040
DATE PLOTTED
DGN FILE
11-MAR-2024
REFERENCE FILES
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
T H
IS
D
R A
W
IN
G I S T
H E P
R O
P E
R T
Y O
F L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y I
N C
O R
P O
R A
T E
D A
R C
H
IT
E C
T S I T I S N
O T T
O B
E R
E P
R O
D U
C E
D I
N W
H O
L E O
R I
N P
A R
T I T I S N
O T T
O B
E U
S E
D O
N A
N Y O
T H
E R P
R O J E
C T I T S
H A
L L B
E R
E T
U R
N E
D U
P O
N R
E Q
U E S
T C
O P
Y R
IG
H T A
S D
A T E
D L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y N
O T V
A L
ID
U
N L E S S S
IG
N E
D A
N D S
E A
L E
D
KMS
JCW
121035.00
W a lt e r
B
W il li a m s J r.
P a rk
B a ld w in C o u n ty A q u a ti c F a c il it y
M il le d g e v il le
G e o rg ia
Aquatic Facility
Baldwin County
59 GA-22
Milledgeville, GA 31061
Baldwin County 1601 N Columbia Street
Suite 220
Milledgeville, GA 31061
ARCHITECTURE
PLANNING
INTERIOR DESIGN
Lyman
Davidson
Dooley, Inc.
1640 Powers Ferry Road
Building One
Marietta, GA 30067
770.850.8494 t
770.956.9030 f lddi-architects.com
TITLE
STATUS
QC
DATE
DRAWN
JOB
SHEET
REVISIONS
EXPIRES: 06.30.2024
COA#PEF000774
NBP ENGINEERS, INC.
Permit Set
2/20/2024
E001
ELECTRICAL
SCHEDULE -
LEGEND &
CT
TRACK LIGHTS: QUANTITY OF HEADS AS SHOWN EMERGENCY BATTERY PACK-CEILING
EMERGENCY BATTERY PACK-WALL
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
PANELBOARD-OVER 250 VAC
SURFACE MOUNTED
PANELBOARD-OVER 250 VAC
RECESSED
CABLE TRAY
BACKBOARD
CONNECTION TO EQUIPMENT
CAP
CONDUIT DOWN
CONDUIT UP
J
SLAB OR BELOW GRADE
GROUNDING CONDUCTOR- UNDER
U
SP
DP
PE
M
ICM
S
V
S
IC
MM
MC
GG
G
LIGHTING FIXTURES (SYMBOLS VARY BASED ON FIXTURES TYPE)
LIGHTING CONTROL
RECEPTACLES
CIRCUITS
GENERAL EQUIPMENT
COMMUNICATIONS
LIGHTNING PROTECTION AND GROUNDING
T
JJ
I
UI
I
ELECTRICAL LEGEND
TV
C
G
B
K
LED ON "NORMAL" POWER
CEILING MOUNTED FIXTURE
WALL MOUNTED FIXTURE
EXIT LIGHT (ARROWS AS SHOWN)
LIFE SAFETY EGRESS FIXTURE
CEILING MOUNTED ULTRASONIC OCCUPANCY
SENSOR AND RELAY
CEILING/WALL MOUNTED INFRARED OCCUPANCY
SENSOR AND RELAY
CEILING MOUNTED COMBINATION INFRARED/
ULTRASONIC OCCUPANCY SENSOR AND RELAY -
SWITCHING PHOTOCELL (INTERIOR TYPE) F.C. NOTED
DIMMING PHOTOCELL (INTERIOR TYPE)
EXTERIOR TYPE PHOTO SWITCH
LOW VOLTAGE OVERRIDE SWITCH
INFRARED OCCUPANCY SENSOR
WALL MOUNTED SWITCH
"P" INDICATES PILOT LIGHT
KEYED SWITCH
DIMMER SWITCH
FOUR WAY SWITCH
THREE WAY SWITCH
SINGLE POLE SWITCH
DUPLEX RECEPTACLE - NORMAL
QUAD - NORMAL
GFCI DUPLEX RECEPTACLE - NORMAL
GFCI QUAD - NORMAL
FLOOR DUPLEX RECEPTACLE - NORMAL
FLOOR QUAD - NORMAL
CEILING DUPLEX RECEPTACLE - NORMAL CLOCK OUTLET
WALL/CEILING RACEWAY
CEILING SPECIAL - TYPE NOTED OR SHOWN
SPECIAL - TYPE NOTED OR SHOWN
HORIZONTALLY MOUNTED DUPLEX RECEPTACLE
WEATHER PROOF RECEPTACLE (GFCI)
ELECTRIC WATER COOLER RECEPTACLE(GFCI)
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT IN GROUND, SLAB, OR UNDER FLOOR
FLEXIBLE RACEWAY
RACEWAY EXPOSED
TRANSFORMER
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
ENCLOSED BREAKER-RECESSED IN WALL
ENCLOSED CIRCUIT BREAKER
EMERGENCY PUSHBUTTON
COMBINATION STARTER AND DISCONNECT
EXHAUST FAN
MANUAL STARTER AND MOTOR RATED SWITCH
MOTOR
JUNCTION BOX - WALL/CEILING/FLOOR
SURGE SUPPRESSOR
VOICE OUTLET, QUANTITY OF JACKS AS NOTED
DATA OUTLET, QUANTITY OF JACKS AS NOTED
COMBINATION VOICE/DATA OUTLET, QUANTITY OF
VOICE/DATA JACKS AS NOTED
FLOOR VOICE OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR DATA OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR COMBINATION VOICE/DATA OUTLET,
QUANTITY OF JACKS AS NOTED
MASTER CLOCK
INTERCOM MASTER STATION
INTERCOM CALL-IN STATION
WALL MOUNTED VOLUME CONTROL
BOX, STUB-UP, AND MODULAR PLATE W/ BLANKS
TELEVISION OUTLET
SPEAKER: CEILING/WALL
MICROPHONE: FLOOR/WALL
FIBER OUTLET
GROUND ROD - C IF CHEMICAL
GROUND CONNECTION (SCHEMATIC)
CONCEALED IN ROOF OR WALLS
GROUNDING CONDUCTOR-
GROUNDING CONDUCTOR- EXPOSED
AIR TERMINAL
GROUNDING PLATE
EWC
WP
H
D
P
I
L
TWO ZONE LOW VOLTAGE SWITCHL2
VACANCY AUTO SHUT OFF
FOUR ZONE LOW VOLTAGE SWITCHL4
DUPLEX RECEPTACLE WITH INTEGRAL USBUSB
TV DUPLEX RECEPTACLETV
AC
ABOVE COUNTER DUPLEX RECEPTACLE (COORDINATE
HEIGHT WITH ARCHITECT)
J-HOOK
SECURITY
C CARD READER
P DOOR POSITION SENSOR
SECURITY CAMERA: CEILING/WALL MOUNTED
ES ELECTRIC STRIKE
C
CABLE TRAY
DUPLEX RECEPTACLE MOUNTED IN RACEWAYR
R DATA OUTLET MOUNTED IN RACEWAY
DUPLEX RECEPTACLE - TAMPER PROOFT
DUPLEX RECEPTACLE - GENERATOR CIRCUIT, RED IN COLOR
QUAD - GENERATOR CIRCUIT, RED IN COLOR
SINGLE ZONE LOW VOLTAGE SWITCHL1
DISCONNECT SWITCH: "F" IF FUSED
HOMERUN - ONE ARROW PER CIRCUIT
F
LIGHTING FIXTURE SCHEDULE
MARK LAMPS FIXTURE TYPE-SEE SPECIFICATIONS MOUNTING REMARKSVOLT.
X-1
K
J5
H5
G5
G4
E4
E3
D
C
B
A
LETTERS
GREEN
ARCHITECT
COLOR BY
DEGREES
AT 90
PER POLE
THREE
ARCHITECT
COLOR BY
DEGREES
AT 90
PER POLE
FOUR HEADS
ARCHITECT
COLOR BY
DEGREES
AT 180
PER POLE
TWO HEADS
ARCHITECT
COLOR BY
DEGREES
AT 180
PER POLE
TWO HEADS
ARCHITECT
COLOR BY
ARCHITECT
COLOR BY
RATED
NATATORIUM
LISTED
LOCATION
DAMP
LISTED
LOCATION
DAMP
X
LED
20 WATT
3500 LUMENS
4000K
LED
80 CRI
PER HEAD
4000K
545 WATTS
52725 LUM
LED
80 CRI
PER HEAD
4000K
545 WATTS
52725 LUM
LED
80 CRI
PER HEAD
4000K
545 WATTS
52725 LUM
LED
80 CRI
PER HEAD
4000K
545 WATTS
48250 LUM
LED
80 CRI
4000K
545 WATTS
48250 LUM
LED
80 CRI
4000K
545 WATTS
61,500 LUM
LED
3500K
37.8 WATTS
LUMENS
LED
3500K
39 WATTS
3800 LUM
LED
2500 LUM
LED
3500K
26 WATTS
3000 LUM
LED
BY:
EQUALS
UNIV
BY:
EQUALS
BY:
EQUALS
208V
BY:
EQUALS
208V
BY:
EQUALS
208V
BY:
EQUALS
208V
BY:
EQUALS
208V
BY:
EQUALS
208V
BY:
EQUALS
UNIV.
BY:
EQUALS
UNIV.
BY:
EQUALS
UNIV.
BY:
EQUALS
UNIV.
CEILING/WALL
RECESSED
8'-0" A.F.F.
WALL @
GRADE
@ 25' ABOVE
POLE, B.E.
GRADE
@ 25' ABOVE
POLE, B.E.
GRADE
@ 25' ABOVE
POLE, B.E.
GRADE
@ 25' ABOVE
POLE, B.E.
GRADE
@ 25' ABOVE
POLE, B.E.
GRADE
@ 25' ABOVE
POLE, B.E.
SURFACE
KIT
FLANGE
PROVIDE
PLYWOOD
RECESSED
PLYWOOD
RECESSED
GRID
RECESSED
SURE-LITES SCX SERIES
COMPASS CELR SERIES
ACUITY EDGR SERIES EXIT
SINGLE FACE EXIT SIGN
LSI TLWP Series
LUMARK LDWP-GL-6B-ED-7040-PE
LITHONIA TWX2LED P4 40K MVOLT PE DDBXD
EXO WGH1-50-LSCS-UNVC
LED WALLPACK
LUMARK PREVAIL DISCRETE
LITHONIA RSX2 LED SERIES,
VP-ST-4-162L-545-4K8-5QW-NXWS40F
BECON VIPER STRIKE TYPE 5QW DIST
LED AREA LIGHT ON SQUARE STRAIGHT STEEL POLE
LUMARK PREVAIL DISCRETE
LITHONIA RSX2 LED SERIES,
VP-ST-4-162L-545-4K8-5QW-NXWS40F
BECON VIPER STRIKE TYPE 5QW DIST
LED AREA LIGHT ON SQUARE STRAIGHT STEEL POLE
LUMARK PREVAIL DISCRETE
LITHONIA RSX2 LED SERIES,
VP-ST-4-162L-545-4K8-5QW-NXWS40F
BECON VIPER STRIKE TYPE 5QW DIST
LED AREA LIGHT ON SQUARE STRAIGHT STEEL POLE
LUMARK PREVAIL DISCRETE
LITHONIA RSX2 LED SERIES,
VP-ST-4-162L-545-4K8-4W-NXWS40F
BECON VIPER STRIKE TYPE 4W DIST
LED AREA LIGHT ON SQUARE STRAIGHT STEEL POLE
LUMARK PREVAIL DISCRETE
LITHONIA RSX2 LED SERIES,
VP-ST-4-162L-545-4K8-4W-NXWS40F
BECON VIPER STRIKE TYPE 4W DIST
LED AREA LIGHT ON SQUARE STRAIGHT STEEL POLE
LITHONIA RSX2 LED SERIES,
VP-ST-4-162L-545-4K8-3-NXWS40F
BECON VIPER STRIKE TYPE 3 DIST
LED AREA LIGHT ON SQUARE STRAIGHT STEEL POLE
COLUMBIA LXEM SERIES, METALUX 4VT3
HARDWARE
PROVIDE STAINLESS STEEL MOUNTING
ACUITY FEM SERIES
LED W/ FIBERGLASS ENCLOSURE
METALUX 14GR-LEA SERIES,
VISIONEERING LRTA SERIES,
COLUMBIA LJT SERIES, WILLIAMS 50F,
ACUITY GTL LED SERIES
4' LED LENSED TROFFER
PRESCOLITE LFR SERIES, HALO COMM PRS4
ACUITY LDN6SQ SERIES
6" SQUARE LED DOWNLIGHT
COLUMBIA SRP SERIES, METALUX FPS SERIES,
ACUITY CPANL SERIES
2X4 EDGE-LIT LED FLAT PANEL
03/11/24 Add. #31 david Text Box
ATTACHMENT NUMBER 3
B
C D
1 2 3 4 5
A B
C D
P:\22107\22107e102.dgn
$REF001
$REF002
$REF003
$REF004
$REF005
$REF006
$REF007
$REF008
$REF009
$REF010
$REF011
$REF012
$REF013
$REF014
$REF015
$REF016
$REF017
$REF018
$REF019
$REF020
$REF021
$REF022
$REF023
$REF024
$REF025
$REF026
$REF027
$REF028
$REF029
$REF030
$REF031
$REF032
$REF033
$REF034
$REF035
$REF036
$REF037
$REF038
$REF039
$REF040
DATE PLOTTED
DGN FILE
11-MAR-2024
REFERENCE FILES
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
T H
IS
D
R A
W
IN
G I S T
H E P
R O
P E
R T
Y O
F L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y I
N C
O R
P O
R A
T E
D A
R C
H
IT
E C
T S I T I S N
O T T
O B
E R
E P
R O
D U
C E
D I
N W
H O
L E O
R I
N P
A R
T I T I S N
O T T
O B
E U
S E
D O
N A
N Y O
T H
E R P
R O J E
C T I T S
H A
L L B
E R
E T
U R
N E
D U
P O
N R
E Q
U E S
T C
O P
Y R
IG
H T A
S D
A T E
D L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y N
O T V
A L
ID
U
N L E S S S
IG
N E
D A
N D S
E A
L E
D
KMS
JCW
121035.00
W a lt e r
B
W il li a m s J r.
P a rk
B a ld w in C o u n ty A q u a ti c F a c il it y
M il le d g e v il le
G e o rg ia
Aquatic Facility
Baldwin County
59 GA-22
Milledgeville, GA 31061
Baldwin County 1601 N Columbia Street
Suite 220
Milledgeville, GA 31061
ARCHITECTURE
PLANNING
INTERIOR DESIGN
Lyman
Davidson
Dooley, Inc.
1640 Powers Ferry Road
Building One
Marietta, GA 30067
770.850.8494 t
770.956.9030 f lddi-architects.com
TITLE
STATUS
QC
DATE
DRAWN
JOB
SHEET
REVISIONS
EXPIRES: 06.30.2024
COA#PEF000774
NBP ENGINEERS, INC.
Permit Set
2/20/2024
E102
NOT TO SCALE
GROUNDING LOOP
GROUNDING LOOP
STRUCTURAL STEEL
BUILDING METAL/
STARTING BLOCKS
METAL DRAINS
SUPPLY JETS
METAL WATER
WATER CIRCULATING EQUIPMENT
TO FUNBRELLA ANCHOR
FENCES AND METAL DOOR FRAMES
OF THE POOL AND <12'-0" ABOVE THE POOL
FIXED METAL OBJECTS <5'-0" FROM THE WALL
GG GG
G
G
G
G G
G
G G
G
G
G
G
GG
G
G
GG
G
GROUNDING LOOP
DIAGRAMATIC POOL EQUIPMENT BONDING
SHALL BE #8 AWG SOLID COPPER.
*NOTE* - UNLESS NOTED OTHERWISE ALL GROUND CONDUCTORS
QTY & LOCATIONS.
*NOTE* - NOT ALL ITEMS SHOWN. SEE PL SERIES DRAWINGS FOR
AND HANDRAILS
POOL LADDERS
POOL SHELL REINFORCING STEEL
HORZONTAL AND VERTICAL
GRADE
NOT TO SCALE
x
POLE: 110 MPH WIND WITHSTAND FOR
LUMINAIRES PROVIDED ON THIS POLE
REINFORCEMENT:
24" FOR 25'-35' POLE
18" FOR 15'-24' POLE
12" FOR 8'-14' POLE
6' FOR 25'-35' POLE
5' FOR 15'-24' POLE
3' FOR 8'-14' POLE
ANCHOR BOLTS, WASHERS, LOCKWASHERS,
GROUND ROD; IN BASE OR ADJACENT
BELOW GRADE
6X6X10 GA. WELD WIRE MESH IN A
CYLINDER WITH 4 #5 VERTICAL REBAR,
HEIGHT OF FOUNDATION; TIED TO
ANCHOR BOLTS.
HAND HOLE & COVER AS LARGE
AS POSSIBLE FOR THE POLE TYPE
EXPOSED FOUNDATION:
WITHIN 3 FT. OF DRIVE=24"
GRASSED WALK AREA=6"
PAVED WALK AREA=FLUSH
PLANTER=6"
CIRCUIT:
MINIMUM 1" PVC
BASE COVER
LEVELING NUTS, BASE COVER.
PROVIDE IN-LINE
FUSE AND HOLDER
MOUNTED AT HANDHOLE
FOR BALLAST.
POLE AND LUMINAIRE AS SCHEDULED
AND SPECIFIED
2" CHAMFER x 45 DEGREES CONCRETE:
3000 PSI AT 28 DAYS HAND FINISH
ABOVE GRADE.
MINIMUM 12" BELOW GRADE
GROUNDING LUG, EXOTHERMICALLY
WELDED TO GROUND ROD
" PVC BONDED TO POLE 1/21#6 -
" X 8"-0", TOP AT 12" 3/4TO BASE,
POLE BASE DETAIL (TYPICAL)
ELECTRICAL
SITE DETAILS -
T
LPOOL
800A
L1
400A PE
SINGLE LINE POWER RISER DIAGRAM
18"MIN BURIAL
GROUND
ROD SERVICE
5/8"X10' COPPER
10'-0" MIN
PE PE
GROUND
ROD SERVICE
5/8"X10' COPPER
LSPLASH
200A
SPLASHPAD MECHANICAL
T
GROUND
ROD SERVICE
5/8"X10' COPPER
POOL RESTROOM BLDG POOL/SLIDE/LAZY RIVER MECHANICAL
4#250MCM AL, 4"C
2 SETS OF
4#400MCM AL, 4"C
3 SETS OF
2"C
10'-0" MIN
BY GEORGIA POWER COMPANY
NEW UNDERGROUND PRIMARY
BY GEORGIA POWER COMPANY
NEW UNDERGROUND PRIMARY
ACUITY NLITE SERIES
SIMILAR TO CURRENT NX SERIES OR
TIMECLOCK & PHOTOCELL INPUT
PANEL W/ ASTRONOMICAL
LIGHTING CONTACTOR
MULTI-RELAY FEED THRU
ACUITY NLITE SERIES
SIMILAR TO CURRENT NX SERIES OR
TIMECLOCK & PHOTOCELL INPUT
PANEL W/ ASTRONOMICAL
LIGHTING CONTACTOR
MULTI-RELAY FEED THRU
NOT TO SCALE
NOTES:(THIS SHEET ONLY)
SEE PANEL SCHEDULES FOR QTY OF RELAYS REQUIRED.2
CABINET
UNDERGROUND CONNECTION
PADMOUNT XMFR OR
GEORGIA POWER COMPANY
208V/3PH
CABINET
UNDERGROUND CONNECTION
PADMOUNT XMFR OR
GEORGIA POWER COMPANY
208V/3PH
100A
UNISTRUT FRAME
LPRK
METER BASE BY CONTRACTOR.
MOUNTING HEIGHT WITH POWER COMPANY,
MOUNT ON UNISTRUT FRAME. COORDINATE
FROM PARKING POLES
DIRECTLY ABOVE EXISTING CONDUIT STUB UPS
WHICH MATCHES THE EXISTING.TO BE INSTALLED
WITH 12 POLES AND A BREAKER CONFIGURATION
PANEL WITH NEW 100A 240V/120V LOADCENTER
REPLACE PARKING LOT LIGHTING DISTRIBUTION
POLES
PARKING LOT
TO EXISTING
CIRCUITS TO NEW PANEL
CONNECT EXISTING
EXACT LOCATION WITH ARCHITECT
METER BASE BY CONTRACTOR. COORDINATE
MOUNTING HEIGHT WITH POWER COMPANY,
MOUNT ON BUILDING FASCADE COORDINATE
FEED THRU METER BASE.
EXACT LOCATION WITH ARCHITECT
METER BASE BY CONTRACTOR. COORDINATE
MOUNTING HEIGHT WITH POWER COMPANY,
MOUNT ON BUILDING FASCADE COORDINATE
CT'D METER BASE.
EXACT LOCATION WITH ARCHITECT
METER BASE BY CONTRACTOR. COORDINATE
MOUNTING HEIGHT WITH POWER COMPANY,
MOUNT ON BUILDING FASCADE COORDINATE
FEED THRU METER BASE.
4#250MCM AL, 4"C
GENERAL NOTES:(THIS SHEET ONLY)
A
CABINET BY GEORGIA POWER.
ALL PRIMARY UNDERGROUND CABLING TO TRANSFORMER OR CONNECTION
OR CONNECTION CABINET BY CONTRACTOR.
ALL SECONDARY UNDERGROUND CABLING INTO BUILDING FROM TRANSFORMER B
PHOTOCELL NORTH, AVOID MANMADE OBSTRUCTIONS.
MOUNT AT 8' ABOVE GRADE IN WP BOX WITH STAINLESS STEEL COVER, POINT
MAKE FINAL CONNECTIONS.
CONDUCTOR TO ALLOW GPCO TO ROUTE UP POLE &
DISTRIBUTION POLE AND PROVIDE APPROX 30' EXTRA
SECONDARY CABLE TO EXISTING TO REMAIN GPCO
CONTRACTOR TO ROUTE NEW UNDERGROUND
18"MIN BURIAL 18"MIN BURIAL 18"MIN BURIAL
AND ILC.
ACUITY NLITE SERIES, WATTSTOPPER,
SIMILAR TO CURRENT NX SERIES OR
TIMECLOCK & PHOTOCELL INPUT
PANEL W/ ASTRONOMICAL
LIGHTING CONTACTOR
MULTI-RELAY FEED THRU
POLE
GPCO AERIAL DISTRIBUTION
EXISTING TO REMAIN
LC LC LC
1 03/01/24 Add. #1
03/11/24 Add. #32 david Text Box
B
C D
1 2 3 4 5
A B
C D
P:\22107\22107e301.dgn
$REF001
$REF002
$REF003
$REF004
$REF005
$REF006
$REF007
$REF008
$REF009
$REF010
$REF011
$REF012
$REF013
$REF014
$REF015
$REF016
$REF017
$REF018
$REF019
$REF020
$REF021
$REF022
$REF023
$REF024
$REF025
$REF026
$REF027
$REF028
$REF029
$REF030
$REF031
$REF032
$REF033
$REF034
$REF035
$REF036
$REF037
$REF038
$REF039
$REF040
DATE PLOTTED
DGN FILE
11-MAR-2024
REFERENCE FILES
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
T H
IS
D
R A
W
IN
G I S T
H E P
R O
P E
R T
Y O
F L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y I
N C
O R
P O
R A
T E
D A
R C
H
IT
E C
T S I T I S N
O T T
O B
E R
E P
R O
D U
C E
D I
N W
H O
L E O
R I
N P
A R
T I T I S N
O T T
O B
E U
S E
D O
N A
N Y O
T H
E R P
R O J E
C T I T S
H A
L L B
E R
E T
U R
N E
D U
P O
N R
E Q
U E S
T C
O P
Y R
IG
H T A
S D
A T E
D L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y N
O T V
A L
ID
U
N L E S S S
IG
N E
D A
N D S
E A
L E
D
KMS
JCW
121035.00
W a lt e r
B
W il li a m s J r.
P a rk
B a ld w in C o u n ty A q u a ti c F a c il it y
M il le d g e v il le
G e o rg ia
Aquatic Facility
Baldwin County
59 GA-22
Milledgeville, GA 31061
Baldwin County 1601 N Columbia Street
Suite 220
Milledgeville, GA 31061
ARCHITECTURE
PLANNING
INTERIOR DESIGN
Lyman
Davidson
Dooley, Inc.
1640 Powers Ferry Road
Building One
Marietta, GA 30067
770.850.8494 t
770.956.9030 f lddi-architects.com
TITLE
STATUS
QC
DATE
DRAWN
JOB
SHEET
REVISIONS
EXPIRES: 06.30.2024
COA#PEF000774
NBP ENGINEERS, INC.
Permit Set
2/20/2024
RECEPTION
LIFEGUARD
CONCESSION
103A
WOMEN'S
RESTROOM
105A
WOMEN'S
ADA
106A
MEN'S
RESTROOM
107A
CHASE
MEN'S
RESTROOM
107B
MEN'S ADA
106B
WOMEN'S
RESTROOM
105B
STORAGE
103C
JAN.
103B
K8
K3
K11
K12
K2
K10
K5
K9 K9
K3
K7
K7
K7
K7
K4
K4
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
CKT
PANEL
TRIP
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
CD.
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
HANDDRYER 106
HANDDRYER 105
HANDDRYER 105
REC-108
REC-105
REC-107
EXT REC
DRINK COOLER
FREEZER REC-103
WARMING DRAWER
MICROWAVE-103
MICROWAVE-103
REC-103
REC-103
ICE MACH-103
REF REC-103
REC-102
REC-101
REC-101
EXT REC-BREEZEWY
SERVES
WIRE
PH,
AMPS
VOLT-
NEW
55423
14332
A
PHASE LOAD V.A.
55469
16282
C
GPCO PADMOUNT XMFR
TRIP
MOUNTED
AMPS
L1_SEC1
/ L1_SEC2
PANEL
47831
10564
B
FED BY
POWERSTYLE, APPROX. 30 INCHES WIDE, MAX 250 AMP BRANCH
LOCATION:
POWERSTYLE, APPROX. 30 INCHES WIDE, MAX 250 AMP BRANCH
LOCATION:
1/2"
2"
1/2"
3/4"
1/2"
1/2"
1/2"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1/2"
1/2"
CD.
MCB
4#12
1#8G AL
4#3AL
3#12
4#10
4#12
3#12
3#12
3#10
3#10
3#10
3#10
3#10
3#10
3#12
3#12
WIRE
SURFACE
3. PROVIDE SHUNT TRIP TYPE BREAKER FOR CIRCUITS # 63 & 79.
2. PROVIDE A LOCKOUT TYPE BREAKER FOR CIRCUIT #44.
1. PROVIDE ALL CIRCUITS SHOWN WITHIN THIS SECTION AND SECTION 2 WITHIN A COMMON SINGLE WIDTH ENCLOSURE.
NOTES
Minimum KAIC:
CKT
TRIP
3#12
3#12
3#12
3#12
3#12
3#12
3#12
3#12
3#12
4#10
3#12
3#12
3#12
3#12
3#12
3#12
3#12
3#12
3#12
3#12
WIRE
55423
41091
16666
A
PHASE LOAD V.A.
47831
37267
16666
B
FED BY
55469
39187
19166
C
GPCO PADMOUNT XMFR
TRIP
MOUNTED
AMPS
CKT
3. PROVIDE WITH FEED THRU LUGS. 4. SERVICE ENTRANCE RATED.
2. PROVIDE ALL CIRCUITS SHOWN WITHIN THIS SECTION AND SECTION 2 WITHIN A COMMON SINGLE WIDTH ENCLOSURE.
1. A (C ) IN THE SERVES COLUMN INDICATES THIS CIRCUIT IS ROUTED THRU AN ADJACENT LIGHTING CONTACTOR.
NOTES
Minimum KAIC:
CKT
AMPS
VOLT-
(1 HP)
EF-5
(10 KW)
EUH-1
REC-103A
POOL VACCUM
(1 HP)
EF-1
HANDDRYER-107
HANDDRYER-107
ICE CREME FZR
CEILING FAN 105
CEILING FAN 107
LTS-105,106,107,108
LTS-101,102,103
BREEZEWAY LTS (C )
EXT LTS (C )
SPARE
PAVILION REC (C )
PAVILION LTS (C )
SERVES
SECTION 1 of 2
16666
16666
16666
AMPS
VOLT-
3/4"
3/4"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
2"
CD.
MLO
1#10G
4#8
3#10
3#10
3#12
3#12
3#12
3#12
3#12
3#12
3#12
3#12
3#12
1#6G
4#3/0
WIRE
SURFACE
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
(SHUNT TRIP)
FRYER
HOOD
SPARE
SPARE
SPARE
FREEZER REC-103
(SHUNT TRIP)
RANGE
SPARE
WARMING DRAWER
DCU-3/DAC-3
DCU-2/DAC-2A/B
SPARE
SERVES
WIRE
PH,
SURGE
SPARE
AC-1
CEILING FAN 106B, 107B
LTS-105B,106B,107B,103B &C
SF-1
KEF-1
HANDDRYER 106B
REC-106B
HANDDRYER 107B
HANDDRYER 107B
REC-107B
REC-103B
RECIRC PUMP & DMV
( 50 KW)
WH-1
SERVES
SECTION 2 of 2
1#8G
4#3
3#12
3#12
1#8G
4#3
4#10
4#10
4#10
WIRE
1/2"
1/2"
1.25"
3/4"
3/4"
3/4"
CD.
AMPS
VOLT-
NEW
SCALE:
= 1'-0
4 0 2 4 8
N O R T H
T R U E
N
E301
LC
AC
AC
AC
MICROWAVE
MICROWAVE
WARMING DRAWER
FREEZER
DRINK
AC
AC
AC
FREEZER
FRIDGE/
ICE
L1
J
J
J
J
J
GENERAL NOTES:(THIS SHEET ONLY)
A
DEDICATED NEUTRALS, EQUIPMENT GROUND MAY BE SHARED.
THE CIRCUIT NUMBER. CONSOLIDATION OF HOME RUNS IS ACCEPTABLE UP TO THREE CIRCUITS. PROVIDE
ALL RECEPTACLES SHOWN THIS SHEET ARE SERVED FROM PANEL L1. THE NUMBER ADJACENT INDICATES
DIMENSION OUTLETS FROM THE ELECTRICAL SHEETS.
LOCATE ALL DATA AND RECEPTACLE OUTLETS PER ARCHITECTURAL CASEWORK ELEVATIONS. DO NOT B
C
NOTES:(THIS SHEET ONLY)
2-2"C TELECOM ENTRANCE - SEE E101 FOR CONTINUATION.3
TO THE DIALER. ROUTE TO ADJACENT TELEPHONE DEMARK.
PROVIDE TWO TELEPHONE JACKS INSIDE TO THE SECURITY CABINET FOR CONNECTION
EXACT LOCATION WITH ARCHITECT.
TERMINATE THE OTHER END AT DEMARK ON WALL MOUNT 110 BLOCKS. COORDINATE
THIS LOCATION. TERMINATE ON THIS END IN A RJ-11 WALL MOUNT PHONE HOLDER.
ROUTE 2 CATEGORY 6 CABLES IN 1" C UNDERGROUND FROM TELEPHONE DEMARK TO
CONSULANT PRIOR TO ANY ROUGHING. INSTALL 18" A.F.F.
(VACUUM) TO BE PROVIDED. COORDINATE EXACT LOCATION WITH CIVIL ENGINEER & POOL
COVER. COORDINATE NEMA RECEPTACLE TYPE WITH CORD & PLUG FOR ACTUAL EQUIPMENT
TWIST LOCK 30A RECEPTACLE FOR POOL VACUUM. PROVIDE VANDAL RESISTANT IN-USE4
D
WP WP
WP
WP
WP
WP
TELEPHONE DEMARK
1 /2
1 /2
29 29
5 HAND DRYER. COORDINATE ROUGH-IN HEIGHT AND LOCATION WITH ARCHITECTURAL ELEVATIONS.
IN INTERIOR SPACES.
INSULATION SHALL BE XHHW FOR CONDUCTORS ROUTED UNDERGROUND. THHN FOR CONDUCTORS
ALL BRANCH CIRCUIT CONDUCTORS SHALL BE COPPER. STRANDED FOR #8 AND LARGER. ALL
JUMBO STAINLESS COVERS.
ALL SWITCHES AND RECEPTACLES SHALL BE GREY IN COLOR, RATED FOR 20A MINIMUM. PROVIDE
ALL RECEPTACLES SHALL BE TAMPER RESIST TYPE.
PROVIDE PULLSTRINGS IN ALL EMPTY CONDUITS.
E
G
H
FLOOR PLAN - POWER/TELECOM
POWER/TELECOM
FLOOR PLAN -
(SHUNTS MAIN BREAKER IN LPOOL)
EMERGENCY PUSHBUTTON OFF
J J
J J
J
5 5
ACAC
AC
AC AC
AC
AC
WARMING DRAWER
AC
FREEZER
ICECREME
RANGE
FRYER
AC
AC
AC
AC
AC
AC
AC ACAC
(SHUNTS MAIN BREAKER IN LSPLASH)
EMERGENCY PUSHBUTTON OFF
64 64
1 /2
WAP
WAP
WAPWAP
RESTROOMS AND IN EXTERIOR LOCATIONS SHALL BE GFCI TYPE UNLESS GFCI BREAKERS ARE PROVIDED.
ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A WATER SOURCE AND ALL RECEPTACLES IN KITCHENS, WALLMOUNT DATA RACK @96"
I
@48"
@48"
@48"
J77
HOOD
EWC
EWC
11900-748, EQUALS BY HUBBELL AND PANDUIT.
CAT 6 PATCH PANELS, AND RACKMOUNT 110 BLOCKS. BASIS OF DESIGN IS THE CHATSWORTH
RACK SHALL BE LOCKABLE W/ TEMPERED GLASS DOOR & CAPABLE OF ACCEPTING FIBER TRAYS, PROVIDE A WALL MOUNT, PIANO HINGED, 19" ENCLOSED RACK.APPROX 48" TALL IN THIS LOCATION.
IN RACK
@96"
1" EMT UP TO ATTIC FROM THE DATA BACKBOX.
PLENUM RATED CAT 6 CABLE ROUTED IN THE ATTIC FROM WORK OUTLET TO RACK. USE
ALL DATA SHOWN TERMINATES IN WALL MOUNTED DATA RACK. SEE DETAIL 2 E401. USE
E401
AUTOMATICALLY SHUNTED OFF.
UPON ACTIVATION OF THE EXTINGUISHING SYSTEM POWER TO THE RANGE AND FRYER SHALL BE
100A/3P L1-61
E102
1 03/01/24 Add. #1
03/11/24 Add. #32 david Text Box
B
C D
1 2 3 4 5
A B
C D
P:\22107\22107e401.dgn
$REF001
$REF002
$REF003
$REF004
$REF005
$REF006
$REF007
$REF008
$REF009
$REF010
$REF011
$REF012
$REF013
$REF014
$REF015
$REF016
$REF017
$REF018
$REF019
$REF020
$REF021
$REF022
$REF023
$REF024
$REF025
$REF026
$REF027
$REF028
$REF029
$REF030
$REF031
$REF032
$REF033
$REF034
$REF035
$REF036
$REF037
$REF038
$REF039
$REF040
DATE PLOTTED
DGN FILE
11-MAR-2024
REFERENCE FILES
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
CONSULTANTS
T H
IS
D
R A
W
IN
G I S T
H E P
R O
P E
R T
Y O
F L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y I
N C
O R
P O
R A
T E
D A
R C
H
IT
E C
T S I T I S N
O T T
O B
E R
E P
R O
D U
C E
D I
N W
H O
L E O
R I
N P
A R
T I T I S N
O T T
O B
E U
S E
D O
N A
N Y O
T H
E R P
R O J E
C T I T S
H A
L L B
E R
E T
U R
N E
D U
P O
N R
E Q
U E S
T C
O P
Y R
IG
H T A
S D
A T E
D L
Y M
A N D
A V
ID
S O
N D
O O
L E
Y N
O T V
A L
ID
U
N L E S S S
IG
N E
D A
N D S
E A
L E
D
KMS
JCW
121035.00
W a lt e r
B
W il li a m s J r.
P a rk
B a ld w in C o u n ty A q u a ti c F a c il it y
M il le d g e v il le
G e o rg ia
Aquatic Facility
Baldwin County
59 GA-22
Milledgeville, GA 31061
Baldwin County 1601 N Columbia Street
Suite 220
Milledgeville, GA 31061
ARCHITECTURE
PLANNING
INTERIOR DESIGN
Lyman
Davidson
Dooley, Inc.
1640 Powers Ferry Road
Building One
Marietta, GA 30067
770.850.8494 t
770.956.9030 f lddi-architects.com
TITLE
STATUS
QC
DATE
DRAWN
JOB
SHEET
REVISIONS
EXPIRES: 06.30.2024
COA#PEF000774
NBP ENGINEERS, INC.
Permit Set
2/20/2024
RECEPTION
LIFEGUARD
CONCESSION
103A
WOMEN'S
RESTROOM
105A
WOMEN'S
ADA
106A
MEN'S
RESTROOM
107A
CHASE
MEN'S
RESTROOM
107B
MEN'S ADA
106B
WOMEN'S
RESTROOM
105B
STORAGE
103C
JAN.
103B
K8
K3
K11
K12
K2
K10
K5
K9 K9
K3
K7
K7
K7
K7
K4
K4
LCL1
DAC-3
DAC-2
EUH-1
EF-1
DCU-2 DCU-3
EF-5
KEF-1
SF-1
AC-1
SCALE:
= 1'-0
4 0 2 4 8
N O R T H
T R U E
N
E401
FLOOR PLAN - SYSTEMS/HVAC POWER
SYSTEMS/HVAC POWER
FLOOR PLAN -
F
NOTES:(THIS SHEET ONLY)
CONNECTIONS.
CONDUCTORS BETWEEN INTERIOR AND EXTERIOR UNITS. MAKE ALL FINAL
EXTERIOR UNIT SUPPLIES POWER TO INTERIOR UNIT. PROVIDE STRANDED
L1-26
L1-36
60A/2P
L1-47 L1-51
30A/2P/3R
L1-44
30A/2PL1-40
30A/2P
F
30A/2P/3R
J
RECIRC
DMV &
M
IN ATTIC
L1-64
M
L1-66
DATA RACK - ELEVATION
NO SCALE
FOR TELCO/FIBER ENTRANCE
CONDUIT OUT TO SITE
2-2" C
6"A.F.F. MIN.
STUB UP
PROVIDE QUAD RECEPTACLE WITHIN RACK
PROVIDE CAT 6 JACK WITHIN RACK
CAT 6 PATCH PANEL
FIBER TRAY AND 110 BLOCKS
2-4"C UP INTO ATTIC
60A/3P/3R
L1-72
Add. #31 03/11/24
F david Text Box
| Insert from: "Attachment Number 2 2024-03-08_BaldwinAqua_Add#3_Hvac.pdf" |
| 22107m002 |
| References |
| tb, 22107tb.dgn |
| 22107m201 |
| References |
| tb, 22107tb.dgn |
| afp, 22107afp.dgn |
| panels, 22107e301.dgn |
| plbg equip, 22107p301.dgn |
| Insert from: "Attachment Number 3 2024-03-11_BaldwinAqua_Add#3_Elec.pdf" |
| 22107e001 |
| References |
| tb, 22107tb.dgn |
| 22107e101 |
| References |
| tb, 22107tb.dgn |
| aSite, 22107aSite.dgn |
| Lighting.dgn |
| 23038e011.dgn |
| 22107e102 |
| References |
| tb, 22107tb.dgn |
| 22107e201 |
| References |
| tb, 22107tb.dgn |
| afp, 22107afp.dgn |
| panels, 22107e301.dgn |
| 22107e301 |
| References |
| tb, 22107tb.dgn |
| afp, 22107afp.dgn |
| PANELS, panel1-Excel.dgn |
| 22107e401 |
| References |
| tb, 22107tb.dgn |
| afp, 22107afp.dgn |
| panels, 22107e301.dgn |
| hvac, 22107m201.dgn |
| plbg equip, 22107p301.dgn |
| 22107em201 |
| References |
| tb, 22107tb.dgn |
| afp1, 22107afp_AquaticMech.dgn |
| afp3, 22107afp_AquaticMech.dgn |
| hvac, 22107mm201.dgn |
| panel, panel1-Excel.dgn |
| afp2, 22107afp_AquaticMech.dgn |
| Panels1, 22107em201.dgn |
| panels3, 22107em201.dgn |
| 22107em202 |
| References |
| tb, 22107tb.dgn |
| afp, 22107afp_SplashMech.dgn |
| afp-1, 22107afp_SplashMech.dgn |
| hvac, 22107mm201.dgn |
| panel1-Excel.dgn |
| afp2, 22107afp_SplashMech.dgn |
| Panels, 22107em202.dgn |
| Panels-1, 22107em202.dgn |
| 22107em201.dgn |
File details come from the government source that posted it. Updated .