B34250 Exhaust System BWE 0412.pdf
PDF 1 MB Posted
- Solicitation number
- W911SG24B0009
About this file
This document is a set of engineering drawings and specifications related to a federal contract opportunity for the repair of a vehicle exhaust system in Building 34250 at White Sands Missile Range (WSMR) in New Mexico.
The key details are:
- The existing vehicle exhaust system is deficient and does not meet the required airflow capacity standards. The scope of work includes replacing the major components of the exhaust system to meet the 800 CFM flow rate requirement at each exhaust nozzle.
- The work is located at Building 34250 at the Stallion Range Base Camp within WSMR.
- The total period of performance is 90 calendar days, with 30 days for pre-construction tasks and 60 days for construction.
- The solicitation number is W911SG24B0009 and is being issued by the Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET
OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34250-2023-G-GI-01
B34250
COVER SHEET/INDEX
SHEET
04/12/23
BWE
BWE
JIM STEPHENSON
JAMES NUNEZ
01 07
JOHN MORGAN
B34250
SHEET INDEX
DRAWING NUMBER TITLE
WS-34250-2023-G-GI-01 COVER SHEET/INDEX SHEET
WS-34250-2023-G-PL-02 B34250 PROJECT LOCATION
WS-34250-2023-G-100-03 B34250 GENERAL NOTES
WS-34250-2023-M-MD-04 B34250 EXHAUST SYSTEM DEMOLITION PLAN
WS-34250-2023-M-MH-05 B34250 NEW EXHAUST SYSTEM PLAN
WS-34250-2023-M-DT-06 B34250 NEW EXHAUST SYSTEM DETAILS
WS-34250-2023-E-DT-07 B34250 EXHAUST ELECTRICAL PLAN
VEHICLE EXHAUST SYSTEM REPAIR
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET
OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34250-2023-G-PL-02
B34250
PROJECT LOCATION
04/12/23
ARCH D
BWE
BWE
JIM STEPHENSON
JAMES NUNEZ
02 07
JOHN MORGAN
PROJECT LOCATION
B34250 MAINTENANCE SHOP
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET
OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34250-2023-G-100-03
B34250
GENERAL NOTES
04/12/23
ARCH D
BWE
BWE
JIM STEPHENSON
JAMES NUNEZ
03 07
JOHN MORGAN
GENERAL NOTES-
1. CONTRACTOR PERSONNEL ACCESS TO EACH SITE REQUIRES APPROVAL FROM THE WSMR
SECURITY OFFICE AND COMPLY WITH THE REQUIREMENTS OF THE WHITE SANDS MISSILE
RANGE VISITOR/ACCESS CONTROL POLICY (04JUNE2021).
2. THE CONTRACTOR SHALL COORDINATE ALL ACTIVITIES WITH THE CONTRACTING OFFICER'S
REPRESENTATIVE (C.O.R.). NO CONSTRUCTION WORK SHALL BE ACCOMPLISHED WITHOUT AN
APPROVED CONSTRUCTION SCHEDULE. THE CONTRACTOR SHALL NOTIFY THE C.O.R. OF THE
SCHEDULED OUTAGES 72 HOURS IN ADVANCE.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH EXISTING CONDITIONS AND CONSTRUCTION
DRAWINGS. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIAL AND LABOR AS
REQUIRED FOR COMPLETE FUNCTIONAL SYSTEMS.
4. CONTRACTOR SHALL NOTIFY AND COORDINATE WITH C.O.R. FOR ANY FORKLIFT OR SCISSOR
LIFT USE AT THE SITE WHICH MIGHT BE NEEDED TO REMOVE/INSTALL EXHAUST SYSTEM
DUCTWORK, MOTOR-FAN ASSEMBLY OR COMPONENTS. CONTRACTOR SHALL BARRICADE
HAZARDOUS OPERATIONS AREAS.
5. ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
PUBLISHED RECOMMENDATIONS, CONTRACT DOCUMENTS, INDUSTRY STANDARDS AND ALL
FEDERAL, STATE AND LOCAL CODES AND AMENDMENTS AS ADOPTED BY THE GOVERNMENT FOR
SERVICE INTENDED BY THE CONTRACTING OFFICER (KO). THE INSTALL OF ALL MATERIALS AND
EQUIPMENT SHALL BE MADE BY EXPERIENCED AND LICENSED CRAFTSMAN IN A NEAT WORKMAN
LIKE MANNER, ALL MATERIALS, SUPERVISION, LABOR, TOOL, COST AND SERVICES NECESSARY
TO COMPLETELY INSTALL A FUNCTIONAL SYSTEM SHALL BE FURNISHED BY THE CONTRACTOR.
6. THE TERM "PROVIDE" USED IN THE DRAWINGS AND SCOPE OF WORK IMPLIES THE CONTRACTOR
IS TO FURNISH, TRANSPORT, INSTALL, CONNECT, WARRANT, AND START-UP, INCLUSIVELY.
7. THE DRAWINGS ARE DIAGRAMMATIC ONLY BUT SHALL BE FOLLOWED AS CLOSELY AS ACTUAL
CONSTRUCTION CONDITIONS AND WORK OF OTHER TRADES PERMIT.
8. CONTRACTOR SHALL REPORT DISCREPANCIES BETWEEN FIELD CONDITIONS AND NEW
CONSTRUCTION DRAWINGS TO THE KO IN WRITING BEFORE THE RFI DEADLINE DURING THE
SOLICITATION PHASE, PRIOR TO PROVIDING THEIR BID.
9. THE DIMENSIONS IN THE DRAWING ARE FOR REFERENCE AND THE CONTRACTOR SHALL FIELD
VERIFY ALL NECESSARY DIMENSIONS REQUIRED PERFORM THE SCOPE OF WORK.
10. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING STRUCTURE, EQUIPMENT AND UTILITIES
WITHIN THE FACILITY TO ACCOMMODATE THE SYSTEM REPAIRS PRIOR TO THE START OF WORK.
11. CONTRACTOR SHALL PROTECT EXISTING STRUCTURE, EQUIPMENT AND UTILITIES WITHIN THE
FACILITY TO ENSURE NO DAMAGE DURING DEMOLITION AND NEW CONSTRUCTION. ANY DAMAGE
THAT IS DONE SHALL BE REPAIRED TO PRIOR CONDITION AND MATCH EXISTING.
12. UPON COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE WITHIN 10 DAYS,
MANUFACTURER'S OPERATING & MAINTENANCE MANUAL FOR ALL EQUIPMENT INCLUDING
REPLACEMENT PARTS LIST PER SOW 8.8.
13. THE CONTRACTOR SHALL TRANSPORT AND DISPOSE OF ANY CONSTRUCTION WASTE AND
DEBRIS TO AN OFF-SITE SOLID WASTE COLLECTION CENTER THAT HAS BEEN PERMITTED, BY
THE JURISDICTION HAVING AUTHORITY TO ACCEPT AND DISPOSE OF CONSTRUCTION WASTE
AND DEBRIS.
HAZARDOUS MATERIAL TESTING AND ABATEMENT
14. PRIOR TO PERFORMING WORK CONTRACTOR SHALL PERFORM HAZARDOUS BUILDING
MATERIALS SAMPLING OF ALL BUILDING MATERIALS THAT WILL BE DISTURBED IN AREAS
WORKED. TESTING SHALL BE PER SOW PART 10-HAZARDOUS BUILDING MATERIALS ABATEMENT,
CONTRACTOR SHALL FOLLOW GUIDELINES.
15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ABATING ALL HAZARDOUS BUILDING MATERIALS
FOUND IN THE WORK AREA. ABATEMENT OF HAZARDOUS MATERIALS (INCLUDING ASBESTOS
CONTAINING MATERIAL (ACM), LEAD BASED PAINT (LBP), OR MOLD SHALL TAKE PLACE PRIOR TO
PERFORMING OTHER WORK OF THE PROJECT.
ELECTRICAL WORK
16. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL ENERGY SOURCES TO EFFECTED
SYSTEM HAS BEEN SECURED AND LOCKED OUT/TAGGED OUT (LOTO).
17. CERTIFIED ELECTRICIAN SHALL INSPECT EXISTING WIRING TYPE AND SIZE AND CIRCUIT
BREAKER RATING TO ENSURE THEY MEETS THE REQUIREMENTS FOR NEW MOTOR AND
CONTROLLER PER NEC. FOR HIGHER RATED WIRING, THE ELECTRICIAN SHALL REMOVE
EXISTING WIRING TO THE EXTENT NEEDED AND INSTALL REQUIRED 600 VOLT, THHN COPPER
STRANDED ELECTRICAL CONDUCTOR. FOR HIGHER RATED CIRCUIT BREAKER, ELECTRICIAN
SHALL ENSURE THAT THE NEW CIRCUIT BREAKER DOES NOT UNBALANCE THE PANEL. ALL
ELECTRICAL POWER AND CONTROL WIRING SHALL BE ROUTED THROUGH EMT CONDUIT, USING
PROPER CONNECTION METHODS, J-BOXES, NIPPLES, ETC. ALL ELECTRICAL WORK SHALL BE
DONE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (NEC) 70 AS REVISED.
MECHANICAL WORK
16. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL POWER AND GAS SUPPLY SOURCES
TO SYSTEM BEING WORKED HAVE BEEN SECURED AND LOCKED OUT/TAGGED OUT (LOTO).
17. THE CONTRACTOR SHALL ENSURE THAT THE VEHICLE EXHAUST SYSTEM IS SIZED TO PRODUCE
A FLOWRATE OF NO LESS THAN 800 CFM AT EACH SYSTEM NOZZLE, WILL ALL OTHER NOZZLES
OPEN AND IN USE. THIS FLOWRATE SHALL BE DEMONSTRATED AND TESTED FOR COMPLIANCE
PRIOR TO FINAL SIGN-OFF AT PROJECT COMPLETION.
18. CONTRACTOR SHALL USE THE BASIS-OF-DESIGN FROM 'PLYMOVENT' MANUFACTURER IN ORDER
TO COMPLY WITH ALL THE EXHAUST SYSTEM REQUIREMENTS.
19. WHEN INSTALLING A NEW MOTOR-FAN ASSEMBLY, CAREFULLY DISCONNECT MOTOR AND FAN
ASSEMBLY, MOUNTING FRAME AND HOUSING FROM EXISTING DUCTWORK. DESIGNATED
DUCTWORK AND SUPPORTS TO REMAIN IN PLACE TO THE GREATEST EXTENT POSSIBLE IF
SUITABLE FOR REUSE. THE NEW MOTOR-FAN ASSEMBLY SHALL BE INSTALLED PER
MANUFACTURERS RECOMMENDATIONS BY LICENSED/CERTIFIED TECHNICIANS. THE UNIT WILL
BE INSTALLED WITH VIBRATION ISOLATORS PER MANUFACTURERS RECOMMENDATIONS.
20. A SEALANT WILL BE APPLIED TO ALL DUCTWORK AND CONDUIT WALL PENETRATIONS TO THE
EXTERIOR WITH A SEALANT THAT MEETS OR EXCEEDS CHEMLINK HIGH PERFORMANCE WALL
AND BLOCK ADHESIVE.
21. ALL MECHANICAL WORK SHALL BE DONE IN ACCORDANCE WITH INTERNATIONAL MECHANICAL
CODE (IMC) AND SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION
(SMACNA) AS REVISED. ANY NEW DUCTWORK AND ASSOCIATED FITTINGS WILL BE IN
ACCORDANCE WITH SMACNA AND CONFIGURED TO PROVIDE BEST FLOW CONDITIONS WITHIN
THE DUCTWORK.
22. THE CONTRACTOR SHALL ENSURE THAT THE ENTIRE EXHAUST SYSTEM DUCTWORK (INTERIOR
AND EXTERIOR) IS FREE OF CONTAMINATION AND DEBRIS.
23. ALL RIGID METAL DUCTWORK SEAMS WILL BE SEALED WITH FLEXIBLE ELASTOMETRIC SEALANT.
24.REPLACEMENT FLEXHOSE SHALL BE AN ABRASION AND CRUSH RESISTANT HOSE THAT IS
HIGHLY FLEXIBLE. MADE FROM HIGH-QUALITY MATERIALS DESIGNED TO WITHSTAND
TEMPERATURES UP TO 600°F. EQUIVALENT TO PLYMOVENT TYPE 'SNF2' EXHAUST HOSE.
25.UPON COMPLETION OF ALL NECESSARY SYSTEM REPAIRS OR MODIFICATIONS, THE
CONTRACTOR SHALL OPERATE THE SYSTEM AND DEMONSTRATE A REQUIRED MEASURED
FLOWRATE OF 800 CFM AT EACH NOZZLE OF THE SYSTEM.
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET
OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34250-2023-M-MD-04
B34250
EXHAUST SYSTEM
DEMOLITION PLAN
04/12/23
ARCH D
BWE
BWE
JIM STEPHENSON
JAMES NUNEZ
04 07
JOHN MORGAN
GENERAL NOTES-
1. PRIOR TO REMOVING ANY COMPONENT WHICH HAS ELECTRICAL CONTROLS AND
POWER AND/OR GAS LINE HOOK-UP, THE CONTRACTOR SHALL VERIFY THAT
ELECTRICAL POWER HAS BEEN SECURED AND IS LOCKED OUT-TAGGED OUT (LOTO).
2. THE EXHAUST SYSTEM DRAWING IS DIAGRAMMATIC ONLY AND DIMENSIONS AND
GEOMETRY MAY VARY. THE SYSTEM HAS ELECTRICAL BREAKERS, MOTOR STARTERS,
ELECTRIC MOTORS, SIX FLEX HOSE DOWN DROPS AND ONE FLEX HOSE TO A FUME
HOOD. EACH WITH A HOSE SUPPORT CABLE, PULLEYS AND A NOZZLE FOR ATTACHING
TO A VEHICLES EXHAUST PIPE.
3. THERE ARE TWO MOTOR-FAN ASSEMBLIES. THE MOTORS ARE 3 HP EACH. THE FAN
EXHAUSTS TO THE EXTERIOR THROUGH A WALL PENETRATION. THE DUCTWORK IS
SUSPENDED FROM THE CEILING JOISTS WHICH ARE APPROXIMATELY 14' A.F.F.
5. REMOVE AND DISPOSE OF ALL FLEX CONNECTIONS, CONDUITS BETWEEN EXHAUST
MOTORS, DISCONNECTS AND WIRES UP TO THE MOTOR STARTERS. REMOVE
DISCONNECTS MOTOR STARTERS FOR EACH UNIT AT THE MAIN DISTRIBUTION PANEL.
6. THE CONTRACTOR SHALL DISASSEMBLE AND DEMOLISH THE FOLLOWING
COMPONENTS FROM THE EXHAUST SYSTEM: EXHAUST SYSTEM RIGID DUCTWORK,
BLOWER MOTORS, ALL DUCT FLEX HOSES, NOZZLES, FLEX DUCT SUPPORT CABLES
AND PULLEYS, EXHAUST STACK AND ASSOCIATED EQUIPMENT, DISCONNECTS AND
MOTOR STARTERS. THE EXISTING BLOWER SUPPORT BRACING MAY REMAIN IN PLACE
PROVIDED IT IS SUITABLE FOR REUSE WITH THE NEW EXHAUST SYSTEM, OTHERWISE
REMOVE FROM SERVICE.
7. THE CONTRACTOR SHALL TRANSPORT AND DISPOSE OF CONSTRUCTION WASTE AND
DEBRIS TO AN OFF-SITE SOLID WASTE COLLECTION CENTER THAT HAS BEEN
PERMITTED, BY THE JURISDICTION HAVING AUTHORITY TO ACCEPT AND DISPOSE OF
CONSTRUCTION WASTE AND DEBRIS.
VEHICLE EXHAUST SYSTEM DEMOLITION PLAN
DIAGRAMATIC ONLY
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET
OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34250-2023-M-MH-05
B34250
NEW EXHAUST SYSTEM
PLAN
04/12/23
ARCH D
BWE
BWE
JIM STEPHENSON
JAMES NUNEZ
05 07
JOHN MORGAN
GENERAL NOTES-
1. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL POWER TO SYSTEM
BEING WORKED HAS BEEN SECURED AND LOCKED OUT/TAGGED OUT (LOTO).
2. THE EXHAUST SYSTEM DRAWING IS DIAGRAMMATIC ONLY AND DIMENSIONS AND
GEOMETRY MAY VARY AS NECESSARY TO ENSURE THAT SYSTEM COMPONENTS
ARE INSTALLED PROPERLY AND SUITABLE FOR MAXIMUM UTILIZATION AND
EFFICIENCY.
3. EXHAUST EXTRACTOR SYSTEM COMPONENTS REFERENCED FROM 'PLYMOVENT'
MANUFACTURER AND 'MAXFLOW' MANUFACTURER ARE USED AS THE
BASIS-OF-DESIGN, OR EQUIVALENT.
4. THE CONTRACTOR SHALL ENSURE THAT THE NEW MOTOR-FAN ASSEMBLY FOR
THE VEHICLE EXHAUST SYSTEM IS SIZED TO PRODUCE A FLOW RATE OF NO LESS
THAN 800 CFM AT EACH SYSTEM NOZZLE, WILL ALL OTHER NOZZLES OPEN AND IN
USE, AND AT AN ALTITUDE OF 5200 FEET ABOVE SEA LEVEL. THIS FLOW RATE
SHALL BE DEMONSTRATED AND TESTED FOR COMPLIANCE PRIOR TO FINAL
SIGN-OFF AT PROJECT COMPLETION. THE CONTRACTOR SHALL INCORPORATE
LOCKING BALANCER DAMPERS IN THE RIGID DUCTWORK AS REQUIRED TO
ENSURE BALANCED FLOW AT ALL NOZZLES. THE DUCT DESIGN SHALL HAVE AN
INTERNAL FLOW VELOCITY NO LESS THAN 2500 FPM TRANSPORT VELOCITY.
5. THE CONTRACTOR SHALL SUPPLY HARDWARE, EQUIPMENT, CONDUIT, WIRING,
CONTROLS, AS NECESSARY FOR THE COMPLETE INSTALLATION AND OPERATIONS
OF THE NEW EXHAUST EXTRACTION SYSTEMS. EXISTING HARDWARE AND
SUPPORTS MAY BE USED IF SUITABLE FOR REUSE AND ARE IN GOOD CONDITION.
6. ALL MECHANICAL WORK SHALL BE DONE IN ACCORDANCE WITH INTERNATIONAL
MECHANICAL CODE (IMC) AND SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION (SMACNA) AS REVISED. ALL DUCTWORK
AND ASSOCIATED FITTINGS WILL BE IN ACCORDANCE WITH SMACNA AND
CONFIGURED TO PROVIDE BEST FLOW CONDITIONS POSSIBLE. ALL WORK
PERFORMED WILL BE DONE BY CERTIFIED LICENSED TECHNICIANS.
7. LIGHT DUTY LOCK SEAM HVAC DUCT AND ELBOWS SHALL NOT BE USED IN
EXHAUST EXTRACTION SYSTEM DUCTWORK. ALL DUCTWORK WILL BE
GALVANIZED CONFORM TO ASTM A653 G90. ELBOWS AND FITTINGS WILL BE
DIE-STAMPED OR STITCH WELDED EQUIVALENT. MAIN BRANCH TEES WILL BE 45°
LATERAL OR LATERAL REDUCING TYPE. ALL DUCT SEAMS WILL BE WELDED OR
SEALED WITH FLEXIBLE ELASTOMERIC SEALANT.
8. A SEALANT WILL BE APPLIED TO ALL DUCTWORK AND CONDUIT WALL
PENETRATIONS TO THE EXTERIOR WITH A SEALANT THAT MEETS OR EXCEEDS
CHEMLINK HIGH PERFORMANCE WALL AND BLOCK ADHESIVE.
9. ALL BARE STEEL BRACING AND FABRICATED COMPONENTS OF THE NEW
EXHAUST SYSTEM WILL BE CLEANED, PRIMERED AND PAINTED WITH A FINISH
COAT TO MATCH THE EXISTING TO PRECLUDE CORROSION AND RUST.
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET
OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34250-2023-M-DT-06
B34250
NEW EXHAUST SYSTEM
DETAILS
04/12/23
ARCH D
BWE
BWE
JIM STEPHENSON
JAMES NUNEZ
06 07
JOHN MORGAN
M
M
M
M
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET
OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
NTS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34250-2023-E-DT-07
B34250
NEW EXHAUST SYSTEM
ELECTRICAL PLAN
04/12/23
ARCH D
BWE
BWE
JIM STEPHENSON
JAMES NUNEZ
07 07
JOHN MORGAN
GENERAL NOTES
1. PRIOR TO PERFORMING WORK ENSURE THAT ELECTRICAL ENERGY
SOURCES TO EFFECTED SYSTEM HAS BEEN SECURED AND LOCKED
OUT/TAGGED OUT (LOTO).
2. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH NATIONAL
ELECTRIC CODE (NEC) 70 AS REVISED.
3. GOVERNMENT SURVEYED THE MDPS AND WAS ABLE TO IDENTIFY ONLY A
FEW CIRCUITS DUE TO BAD LABELS OR NONE AT ALL. THEREFORE,
CONTRACTOR WILL NEED TO FIELD VERIFY AND TRACE THE EXHAUST
SYSTEM ELECTRICAL CIRCUITS AND ASSOCIATED CIRCUIT BREAKERS.
4. CERTIFIED ELECTRICIAN SHALL INSPECT EXISTING WIRING TYPE AND SIZE
AND CIRCUIT BREAKER RATING TO ENSURE THEY MEETS THE
REQUIREMENTS FOR NEW MOTORS AND CONTROLLERS PER NEC. FOR
HIGHER RATED WIRING (IF NEEDED) THE ELECTRICIAN SHALL REMOVE
EXISTING WIRING TO THE EXTENT NEEDED AND INSTALL REQUIRED 600
VOLT, THHN COPPER STRANDED ELECTRICAL CONDUCTOR. FOR HIGHER
RATED CIRCUIT BREAKER, ELECTRICIAN SHALL ENSURE THAT THE NEW
CIRCUIT BREAKER DOES NOT UNBALANCE THE PANEL. ALL ELECTRICAL
POWER AND CONTROL WIRING SHALL BE ROUTED THROUGH EMT CONDUIT,
USING PROPER CONNECTION METHODS, J-BOXES, NIPPLES, ETC.
5. DEMOLITION EXISTING 3 PHASE 208V CONTROLLER AND DEDICATED
DISCONNECTS TO BLOWER ASSEMBLIES. LABEL ALL CIRCUITS PRIOR TO
TRANSFER TO NEW CONTROLLER AND DISCONNECTS. USE EXISTING WIRE
FEED FROM DISTRIBUTION PANELS AND CONDUIT FOR NEW CONTROLLERS.
NEW CONTROLLERS WILL BE WALL MOUNTED AT OR NEAR THE EXISTING
LOCATIONS. THE NEW CONTROLLERS SHALL BE BUILT AND SUPPLIED BY
UL RECOGNIZED AN LISTED EXHAUST SYSTEM MANUFACTURER.
6. INSTALL NEW EMT CONDUIT TO MATCH EXISTING OR PER MANUFACTURER
RECOMMENDATIONS FROM EXISTING CONDUIT UP TO NEW COMPONENTS
AS NEEDED. USE PROPER CONNECTION METHODS SUCH AS J-BOX,
NIPPLES, ETC. FOR CONTINUATION OF CONDUIT AND SEAL PROPERLY. THE
USE OF FLEX CONDUIT IS ALLOWED ACCORDING PER NEC.
7. EACH BLOWER ASSEMBLY SHALL HAVE AN ELECTRICAL NEMA DISCONNECT
NEAR THE ELECTRIC MOTORS.
8. CONTRACTOR SHALL INSTALL A NEW WALL MOUNTED AUTOMATIC
CONTROL SYSTEM AND CONTROL WIRE COMPATIBLE WITH EACH BLOWER
ASSEMBLY IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
9. ALL GROUNDS FOR EQUIPMENT, BONDING AND NEUTRALS SHALL BE SIZED
ACCORDING TO NEC ARTICLE 250.
10. THE CONTRACTOR SHALL VERIFY THAT THE VEHICLE EXHAUST SYSTEM
CONTROLS AND INTERLOCKS ARE OPERATING CORRECTLY.
| Sheets and Views |
| B34250 Exhaust System BWE 0412-COVER SHEET |
| B34250 Exhaust System BWE 0412-LOCATION |
| B34250 Exhaust System BWE 0412-GENERAL NOTES |
| B34250 Exhaust System BWE 0412-B34250 EXHAUST DEMO |
| B34250 Exhaust System BWE 0412-B34250 NEW EXHAUST |
| B34250 Exhaust System BWE 0412-B34250 EXHAUST DETAILS |
| B34250 Exhaust System BWE 0412-B34250 ELECTRICAL |