This Excel spreadsheet contains air flow specifications and valve information for isolation rooms on the fourth and fifth floors of a facility. It provides details on room numbers, sizes, airflow requirements, and air control valve units and specifications for 16 isolation rooms across the two floors. The related pre-solicitation from the Department of Veterans Affairs seeks proposals to mitigate isolation rooms at the facility. It involves rooms specified in the spreadsheet and aims to address airflow and isolation requirements through valve replacement or installation. Relevant proposals would focus on proposed solutions to improve isolation functionality as outlined in the provided technical specifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROOM AIR FLOW

ISOLATION ROOMS AIR FLOW TABLE
AREAROOM #S NEWROOM #S OLDROOM NAMETU #MODES/A CFME/A - AE/A - BE/A - CPOS or NEGAX.VAX.XAX.ZDIAGAMM/A CFM
4TH FLRB41313C-107ANTE3.191100P2N 100 TO B4131A
….A3C-107AISOL3.191400460N4602P 100 FROM B4131A; P 50 FRO CORR B4
….B3C-107BBATH190N902P 90 FROM B4131A
B41313C-107ANTE3.192100230N2302P 80 FROM B4131A; P 50 FRO CORR B4
….A3C-107AISOL3.192400230P2302N 80 TO B4131; N 90 TO B4131B
….B3C-107BBATH290N902P 90 FROM B4131A
B41353C-112ANTE3.181100P2N 100 TO B4135A
….A3C-112AISOL3.181400460N4602P 100 FROM B4135A; P 50 FRO CORR B4
….B3C-112BBATH190N902P 90 FROM B4135A
B41353C-112ANTE2100230N2302P 80 FROM B4135A; P 50 FRO CORR B4
….A3C-112AISOL3.182400230P2302N 80 TO B4135; N 90 TO B4135B
….B3C-112BBATH3.18290N902P 90 FROM B4135A
B41923C-134ANTE3.71100P2N 100 TO B4192A
….A3C-134AISOL3.71620720N7202P 100 FROM B4192A; P 50 FRO CORR B4
….B3C-134BBATH190N902P 90 FROM B4192A
B41923C-134ANTE3.72100280N2802P 80 FROM B4192A; P 50 FRO CORR B4
….A3C-134AISOL3.72620440P4402N 80 TO B4192; N 90 TO B4192B
….B3C-134BBATH290N902P 90 FROM B4192A
B41883C-139ANTE3.61100P2N 100 TO B4188A
….A3C-139AISOL3.61620720N7202P 100 FROM B4188A; P 50 FRO CORR B4
….B3C-139BBATH190N902P 90 FROM B4188A
B41883C-139ANTE3.62100280N2802P 80 FROM B4188A; P 50 FRO CORR B4
….A3C-139AISOL3.62620440P4402N 80 TO B4188; N 90 TO B4188B
….B3C-139BBATH290N902P 90 FROM B4188A
5TH FLRB51314C-107ANTE4.191100P2N 100 TO B5131A
….A4C-107AISOL4.191400460N4602P 100 FROM B5131A; P 50 FRO CORR B5
….B4C-107BBATH190N902P 90 FROM B5131A
B51314C-107ANTE4.192100230N2302P 80 FROM B5131A; P 50 FRO CORR B5
….A4C-107AISOL4.192400230P2302N 80 TO B5131; N 90 TO B5131B
….B4C-107BBATH290N902P 90 FROM B5131A
B51354C-112ANTE4.181100P2N 100 TO B5135A
….A4C-112AISOL4.181400460N4602P 100 FROM B5135A; P 50 FRO CORR B5
….B4C-112BBATH190N902P 90 FROM B5135A
B51354C-112ANTE4.182100230N2302P 80 FROM B5135A; P 50 FRO CORR B5
….A4C-112AISOL4.182400230P2302N 80 TO B5135; N 90 TO B5135B
….B4C-112BBATH290N902P 90 FROM B5135A
B51924C-134ANTE4.71100P2N 100 TO B5192A
….A4C-134AISOL4.71620720N7202P 100 FROM B5192A; P 50 FRO CORR B5
….B4C-134BBATH190N902P 90 FROM B5192A
B51924C-134ANTE4.72100280N2802P 80 FROM B5192A; P 50 FRO CORR B5
….A4C-134AISOL4.72620440P4402N 80 TO B5192; N 90 TO B5192B
….B4C-134BBATH290N902P 90 FROM B5192A
B51884C-139ANTE4.61100P2N 100 TO B5188A
….A4C-139AISOL4.61620720N7202P 100 FROM B5188A; P 50 FRO CORR B5
….B4C-139BBATH190N902P 90 FROM B5188A
B51884C-139ANTE4.62100280N2802P 80 FROM B5188A; P 50 FRO CORR B5
….A4C-139AISOL4.62620440P4402N 80 TO B5188; N 90 TO B5188B
….B4C-139BBATH290N902P 90 FROM B5188A

AFCV

AIR FLOW CONTROL VALVES
AFCV UNIT #SYSTEMCFMSP AT MAX CFMINLET SIZESERVICE
MINMAX
A2.112-AHU-34602300.1210"B4131 ISOL3C-107
A2.212-AHU-32300.1210"….A ANTI3C-107A
A2.312-AHU-390900.126"….B BATH3C-107B
A2.412-AHU-34602300.1210"B4135 ISOL3C-112
A2.512-AHU-32300.1210"….A ANTI3C-112A
A2.612-AHU-390900.126"….B BATH3C-112B
A2.712-AHU-37204400.1210"B4192 ISOL3C-134
A2.812-AHU-32800.1210"….A ANTI3C-134A
A2.912-AHU-390900.126"….B BATH3C-134B
A2.1012-AHU-37204400.1210"B4188 ISOL3C-139
A2.1112-AHU-32800.1210"….A ANTI3C-139A
A2.1212-AHU-390900.126"….B BATH3C-139B
A3.112-AHU-44602300.1210"B5131 ISOL4C-107
A3.212-AHU-42300.1210"….A ANTI4C-107A
A3.312-AHU-490900.126"….B BATH4C-107B
A3.412-AHU-44602300.1210"B5135 ISOL4C-112
A3.512-AHU-42300.1210"….A ANTI4C-112A
A3.612-AHU-490900.126"….B BATH4C-112B
A3.712-AHU-47204400.1210"B5192 ISOL4C-134
A3.812-AHU-42800.1210"….A ANTI4C-134A
A3.912-AHU-490900.126"….B BATH4C-134B
A3.1012-AHU-47204400.1210"B5188 ISOL4C-139
A3.1112-AHU-42800.1210"….A ANTI4C-139A
A3.1212-AHU-490900.126"….B BATH4C-139B