Scope of Work for FRS Generator Overhaul Attachment 001 Dated: 6 February 2020

1. Background The Forward Repair System (FRS) is a mobile/deployable maintenance and repair shop used by the multiple Department of Defense military branches. A 35 KW Generator powers the FRS. A customer pump on the generator is used to provide hydraulic power from the generator to the FRS Crane. A custom programmed control panel is used to control the generator. Drawings RIA149333 and RIA151367 show the different versions of the generators that are in service.

2. General Contractor Requirements The contractor shall overhaul the FRS generators IAW the parameters outlines in this Scope of Work (SOW). The contractor shall provide all of the tools, equipment, and supplies required to perform he overhaul. The overhaul shall be performed IAW with Cummins specifications and service manuals. The customer pump and custom programmed control panel are not included in the original specifications and service manuals therefore the contractor must be an authorized Cummins service center.

3. Transportation The contractor shall be required to transport the generators from Rock Island Arsenal to their service shop for work and returned to Rock Island Arsenal once the work is completed.

4. Initial Classification The generators are required to be classified as either “Like New” or “Used” condition. The condition of the generator will determine the level of service required. The classification is to be performed by visual assessment.

A. Like new Condition - A generator is considered Like New when there is minimal to no signs of usage or wear. Interior paint is to be clean and shiny. Housings are to be free from any dents or damage. There can be no fluid leakage. Some dust is permitted on the generator is this is the result of long term storage.

B. Used Condition – A generator is considered Used is it fails and of the like new criteria.

5. “Like New” Generator Evaluation/Service (Clin 0001) Like New generators are required to be evaluated prior to being service. The evaluation process is outline below.

A. Oil and coolant levels are to be checked and topped off as required.

B. The Hydraulic pump is to be removed from the generator. The pump will be damaged if operated without fluid.

C. The control panel must be a 2100 series digital control panel. A new contrail panel is to be installed if it is not a 2100 series digital control panel. Most generators have already been upgraded to the 2100 series control panel. If replacement is required, the control panel shall be covered under paragraph 11 and a contract modification will be issued prior to proceeding.

D. A Load Bank test on the generator shall be performed IAW service documentation.

E. If the generator will not start, it is to be evaluated. An estimate to bring the generator to a starting condition is to be provided to RIA-JMTC. No further work is to be performed until the estimate has been approved by the COR and contracting officer. A contract modification will be issued to authorize the contractor to proceed.

F. The generator will be started and run for one hour at full load.

G. Load test requirements

1. The generator will have no leaks during the load test.

2. Water temperature must be monitored during the load test and cannot exceed the Cummins service manual requirements.

3. Oil pressure must be monitored during the load test and cannot exceed the Cummins service manual requirements.

4. Crankcase pressure must be monitored during the load testing and must meet the service manual requirements.

5. Any lose part noticed during load test must be tightened as required.

H. If the generator fails any of the load test requirements, it is to be evaluated. An estimate to repair the cause of the failure will be prepared and submitted to the COR for approval. No other work will be performed on the failed generator until approval is provided by the COR to the contractor. A contract modification will be issued to authorize the contractor to proceed.

I. Paragraph 7 and 8 contain the mandatory replacement part list for a “Like New” Generators.

6. “Used” Generator Evaluation/Service (Clin 0002) Generators classified as used are required to be evaluated prior to being serviced. The evaluation process is outlined below.

A. The generator is to be inspected for any missing parts or major damage that would prevent operation. An estimate to bring the generator to operating condition will be prepared and submitted to the COR for approval. No other work will be performed on the failed generator until approval is provided by the COR to the contractor. A contract modification will be issued to authorize the contractor to proceed.

B. The Hydraulic pump is to be removed from the generator. The pump will be damaged if operated without fluid.

C. The control panel must be a 2100 series digital control panel. A new contrail panel is to be installed if it is not a 2100 series digital control panel. Most generators have already been upgraded to the 2100 series control panel. If replacement is required, the control panel shall be covered under paragraph 11 and a contract modification will be issued prior to proceeding.

D. A Load Bank test on the generator shall be performed IAW service documentation.

E. If the generator fails any of the load test requirements, it is to be evaluated. An estimate to repair the cause of the failure will be prepared and submitted to the COR for approval. No other work will be performed on the failed generator until approval is provided by the COR to the contractor. A contract modification will be issued to authorize the contractor to proceed.

F. The generator will be started and run for one hour at full load.

G. Load test requirements

1. The generator will have no leaks during the load test.

2. Water temperature must be monitored during the load test and cannot exceed the Cummins service manual requirements.

3. Oil pressure must be monitored during the load test and cannot exceed the Cummins service manual requirements.

4. Crankcase pressure is to be monitored during load testing and must meet the Cummins service manual requirements.

5. Any lose part noticed during load test must be tightened as required

6. Overall condition is to be evaluated during and after the load testing for deficiencies. Frame damage, housing damage, engine damage, etc. are to be noted. Cracked or heavily rusted panels are too be noted. Latches are to be checked for operation and deficiencies are to be noted. The condition of the rain cap and shield are to be inspected and deficiencies are to be noted. Any torn or damaged insulation or insulation structure is to be noted. Circuit breakers are to be inspected for condition and proper operations. Any other deficiencies are to be noted. Only condition issues with non-mandatory replacement parts are to be noted.

7. The mandatory replacement parts for “Used” condition are listed in paragraphs 9 and 10.

H. If the generator fails any of the load test requirements, it is to be evaluated. An estimate to repair the cause of the failure will be prepared and submitted to the COR for approval. No other work will be performed on the failed generator until approval is provided by the COR to the contractor. A contract modification will be issued to authorize the contractor to proceed.

I. If the Generator fails any of the second load testing it is to be evaluated. An estimate is to be prepared to repair the deficiencies and submitted to the COR. No other work is to be performed until approval is provided by the COR. A contract modification will be issued to authorize the repairs.

7. Mandatory replacement parts for “Like New” condition for Tier 0,1,3 (Cline 3)

Mandatory replacement parts for "Like new" tier 0,1,2 (Clin 0003)

QTY
PART NUMBER
DESCRIPTION
PRODUCT CODDE
1
FS1251
PAC FS
FLETGUARD
1
LF3345
LF PKG
FLETGUARD
1
AF25553
PAC AF
FLETGUARD
AR
VV705290
PREMIUM BLUE OIL (BULK)
VALVOLINE
AR
CC2825
FLEETGUARD COMPLETE COOLANT
FLETGUARD

(AR STAND FOR AS REQUIRED)

A. Like new basic service requirements – Once the generator has passed the load bank testing basic service will be performed.

1. Fuel and air filters are to be changed IAW with the service manuals.

2. Oil is to be changed IAW the service manuals.

3. Interior paint is to be touched up.

4. Engine coolant is to be drained, purged, and replaced with new coolant according to the service manuals.

5. The Belt is to be tensioned IAW service manuals.

6. The generator is to be lightly cleaned as required.

7. The hydraulic pump is to be replaced with a new pump unless the pump fittings have been plugged and capped.

8. No further Load testing is required.

9. The fuel tank is to be filled with Five (5) gallons of fuel.

8. Mandatory replacement parts for “Like New” condition Tier 3 (Clin 0004)

Mandatory replacement parts for "Like New" tier 3 (Cline 0004)

QTY
PART NUMBER
DESCRIPTION
PRODUCT CODDE
1
FS20022
PAC FS
FLEETGUARD
1
FF5612
PAC FF
FLEETGUARD
1
AF25960
PAC AF
FLEETGUARD
1
LF3970
PAC LF
FLEETGUARD
AR
VV705290
PREMIUM BLUE OIL (BULK)
VALVOLINE
AR
CC2825
FLEETGUARD COMPLETE COOLANT
FLETGUARD

(AR STAND FOR AS REQUIRED)

A. Like new basic service requirements – Once the generator has passed the load bank testing basic service will be performed.

1. Fuel and air filters are to be changed IAW with the service manuals.

2. Oil is to be changed IAW the service manuals.

3. Interior paint is to be touched up.

4. Engine coolant is to be drained, purged, and replaced with new coolant according to the service manuals.

5. The Belt is to be tensioned IAW service manuals.

6. The generator is to be lightly cleaned as required.

7. The hydraulic pump is to be replaced with a new pump unless the pump fittings have been plugged and capped.

8. No further Load testing is required.

9. The fuel tank is to be filled with Five (5) gallons of fuel.

9. Mandatory Replacement parts for “Used” Tiers 0,1,2 (Clin 0005)

Mandatory replacement parts for "USED" tier 0,1,2 (Cline 0005)

QTY
PART NUMBER
DESCRIPTION
PRODUCT CODDE
1
3008400
GASKET, HYDRAULIC PUMP
CUMMINS
2
3278480
SCREW HEX FLANGE HED CAP
CUMMINS
1
3283767
GASKET PUSH ROD COVER
CUMMINS
1
3288768
BELT V RIBBD
CUMMINS
1
3802968
THERMOSTAT
CUMMINS
1
3903475
SAL RECTANGULAR RING
CUMMINS
1
3909888
BRACKET FAN
CUMMINS
1
3925100
HOSE FLEXIBLE
CUMMINS
6
3928759
SEAL GROMMET
CUMMINS
4
3930906
GASKET VALVE COVER
CUMMINS
1
3933104
PUMP FUEL
CUMMINS
4
3935449
ISOLATOR HOSE
CUMMINS
1
3936876
SEAL RECTANGULAR RING
CUMMINS
1
3938655
GASKET ACC DRIVE COVER
CUMMINS
1
3939258
GASKET COVER PLATE
CUMMINS
1
3939355
GASKET FULE PUMP
CUMMINS
1
3939961
DRIVE HYRDAULIC FUEL PUMP
CUMMINS
1
3941472
UNION MALE
CUMMINS
8
3963983
WASHRE SEALING
CUMMINS
1
4983584
PUMP FUEL TRANSFER
CUMMINS
1
3978022
TENSIONER BELT
CUMMINS
1
3286278
PUMP WATER
CUMMINS
7
CC2825
ES COMP EG
FLEETGUARD
1
TPS151GT8-000
KIM HEATER (333-0588-03)
KIM-HOTSTART
1
130-4596-02
RADIATOR
ONAN
1
150-2201
SENSOR-MAG SPEED
ONAN
1
150-2735-02
ACTUATOR ROTARY
ONAN
1
154-2708
GASKET EXHAUST
ONAN
1
191-2326-02
ALTERNATOR 24V
ONAN
1
1930468
SENDER LOW COOLANT
ONAN
1
402-0779-01
ISOLATOR VIBRATION
ONAN
2
402-0779-02
ISOLATOR VIBRATION
ONAN
1
406-0972
LATCH
ONAN
1
501-0502
LINE FLEX FUEL
ONAN
1
501-0627-03
LINE FLEX FUEL
ONAN
4
503-1634-02
HOSE SILICONE RUBBER
ONAN
1
503-1929
HOSE RADIATOR OUTLET
ONAN
1
503-2003-01
HOSE RADIATOR INLET
ONAN
48
508-1011
SEAL EDGE
ONAN
8
821-6002-03
SCREW HH SEMS
ONAN
12
821-6007-02
SCREW HH SEMS SST
ONAN
2
598-0384
WEATHR SEAL
ONAN
1
895-0385
WEATHR SEAL
ONAN
1
895-0386
WEATHR SEAL
ONAN
7
12RLA
GATES 70046 RETURN HOSE
GATES
2
1XGZ4
#32 HOSE CLAMP
GRAINGER
2
1XGZ6
#40 HOSE CLAMP
GRAINGER
9
8010R
CABLE WELLDING 1/0
SJ SMITH
1
PVP3336BRA21
HYDRAULIC PUMP
CENTRAL POWER
4
405-9549
INSULATION DOOR
ONAN
2
405-6000-06
INSULATION PANNEL
ONAN
8
405-5637
UNISOL SUPPORT DOOR
ONAN
8
1XGY6
#8 HOSE CLAMP
GRAINGER
1
405-6035
AIR BAFFLE DISCHARGE
ONAN
1
304-0807
VARISTOR ASSYNI #073-0805
ONAN
1
3675204RX
STR D/R 28MT 24V CW 10T D
DIESEL RECON
1
A034T921
SWITCH PUCHBUTTON
ONAN
4
3802338RX
INJ LUC B SERIES 12MI 7 MT
DIESEL RECON
1
327-1379-02FRS
PCB ASSY BASEBOARD MANDATORY TO UPDATE ONLY
CENTRAL POWER
1
338-3991
HARNESS CONTROL
ONAN
1
542019
M-284-09-B SWITCH DISCONNECT
PORT SUPPLY
1
ZBA710
SWITCHBOOT
SQUARE D
1
EC30EST
3" CLAMP
PACCAR
3
3885913
PAINT
CUMMINS
1
3802820
KIT SEAL
CUMMINS
1
3926126
KIT SEAL
CUMMINS
AR
VV705290
PREMIUM BLUE OIL (BULK)
VALVOLINE
AR
CC2825
FLEETGUARD COMPLETE COOLANT
FLETGUARD

(AR STAND FOR AS REQUIRED)

A. Used Service Overhaul

1. The generator is to be torn down to the frame rails and base. The bare enclosure/panels/skid, generator, engine, and radiator are to be removed.

2. The Individual parts are to be pressure washed, steam cleaned, and or degreased as required.

3. Sealed electrical components are to be inspected and re-epoxied as required.

4. Mandatory parts outlined in paragraph 9 are to be replaced IAW service manual requirements.

5. Engine coolant is to be drained, purged, and replaced with new.

6. The interior of the generator assembly is to be painted or touched up as required.

7. A second load test is to be performed on the generator.

i. The Generator will be run for One (1) hour at full load.

ii. The generator will have no leaks during the load test.

iii. Water temperature must be monitored during the load test and cannot exceed the Cummins service manual requirements.

iv. Oil pressure must be monitored during the load test and cannot exceed the Cummins service manual requirements.

v. Crankcase pressure must be monitored during the load testing and must meet the service manual requirements.

vi. Any lose part noticed during load test must be tightened as required.

10. Mandatory replacement parts for “Used” condition Tier 3 (Clin 006)

Mandatory replacement parts for "USED" tier 3 (Cline 0006)

QTY
PART NUMBER
DESCRIPTION
PRODUCT CODDE
1
3289941
BELT V RIBBED
CUMMINS
7
12RLA
GATES 70046 RETURN HOSE
GATES
1
A029Y148
LOW COOLANT LEVEL SENSOR
ONAN
4
1XGY6
#8 HOSE CLAMP
GRAINGER
1
4896897
GASKET ACC DRIVE COVER
CUMMINS
1
304-0807
VARISTOR ASSYNI #073-0805
ONAN
1
A034T921
SWITCH PUCHBUTTON
ONAN
1
327-1379-02FRS
PCB ASSY BASEBOARD MANDATORY TO UPDATE ONLY
CENTRAL POWER
2
402-0779-02
ISOLATOR VIBRATION
ONAN
8
405-5637
UNISOL SUPPORT DOOR
ONAN
2
405-6000-06
INSULATION PANNEL
ONAN
1
405-6035
AIR BAFFLE DISCHARGE
ONAN
4
405-9549
INSULATION DOOR
ONAN
1
406-0972-01
LATCH
ONAN
1
503-2791-05
HOSE COOLANT
ONAN
1
503-2791-06
HOSE COOLANT
ONAN
48
508-1011
SEAL EDGE
ONAN
1
542019
M-284-09-B SWITCH DISCONNECT
PORT SUPPLY
9
8010R
CABLE WELLDING 1/0
SJ SMITH
8
821-6002-03
SCREW HH SEMS
ONAN
12
821-6007-02
SCREW HH SEMS SST
ONAN
2
598-0384
WEATHR SEAL
ONAN
1
895-0385
WEATHR SEAL
ONAN
1
895-0386
WEATHR SEAL
ONAN
5
CC2825
ES COMP EG
FLEETGUARD
1
PVP33X3951/21
PARKR PUMP
PARKER
1
TPS151GT8-000
KIM HEATER (333-0588-03)
KIM-HOTSTART
1
A029B173
RADIATOR
ONAN
2
3920447
SCREW HEX FLANGE HEAD
CUMMINS
2
3910495
SCREW HEX FLANGE HEAD
CUMMINS
1
3800984
PUMP WATER
CUMMINS
4
5263262NX
INJECTOR HPCR
DIESEL RECON
4
4929864
CONNECTOR INJ FUEL SUPPLY
CUMMINS
1
5292708
THRMOSTAT
CUMMINS
1
3928902
ISOLATOR VIBRATION
CUMMINS
1
4955556
KIT SEAL
CUMMINS
1
4890832
SEAL OIL
CUMMINS
1
5260996
SUPPORT FAN
CUMMINS
1
4899228
GASKET VALVE COVER
CUMMINS
4
5271613
ISOLATOR NOISE
CUMMINS
1
5256607
PUMP FUEL
CUMMINS
1
3938655
GASKET ACC DRIVE COVER
CUMMINS
8
3963983
WASHER SEALING
CUMMINS
1
3935644
BEARING ROLLER
CUMMINS
4
3963988
WASHER SEALING
CUMMINS
1
3976834
TENSIONER BELT
CUMMINS
1
5282841
ALTERNATOR
CUMMINS
1
4955725
TURBO CHAGER HE221W
CUMMINS
2
501-0480-04
LINE FLEX FUEL
ONAN
1
399825
HOSE FLEXIBLE
CUMMINS
3
3823758
CONNECTOR ELC REPAIR
CUMMINS
3
3823759
COVR PROTECTIVE
CUMMINS
1
4896254
GASKET EXH OUT
CUMMINS
2
3958414
SEAL O-RING
CUMMINS
1
338-4424
HARNESS CONTRAOL
ONAN
1
428000-1830
DENSO STR 24V 10T
DENSO
1
ZBA710
SWITCH BOOT
SQUARE D
1
EC30EST
3" CLAMP
PACCAR
3
3885913
PAINT
CUMMINS
AR
VV705290
PREMIUM BLUE OIL (BULK)
VALVOLINE
AR
CC2825
FLEETGUARD COMPLETE COOLANT
FLETGUARD

(AR STAND FOR AS REQUIRED)

A. Used Service Overhaul

1. The generator is to be torn down to the frame rails and base. The bare enclosure/panels/skid, generator, engine, and radiator are to be removed.

2. The Individual parts are to be pressure washed, steam cleaned, and or degreased as required.

3. Sealed electrical components are to be inspected and re-epoxied as required.

4. Mandatory parts outlined in paragraph 9 are to be replaced IAW service manual requirements.

5. Engine coolant is to be drained, purged, and replaced with new.

6. The interior of the generator assembly is to be painted or touched up as required.

7. A second load test is to be performed on the generator.

i. The Generator will be run for One (1) hour at full load.

ii. The generator will have no leaks during the load test.

iii. Water temperature must be monitored during the load test and cannot exceed the Cummins service manual requirements.

iv. Oil pressure must be monitored during the load test and cannot exceed the Cummins service manual requirements.

v. Crankcase pressure must be monitored during the load testing and must meet the service manual requirements.

vi. Any lose part noticed during load test must be tightened as required.

11. Unidentified Repair/Replacement (Clin 0007) If there are repairs that are needed but were not identified or specified in this SOW then the contractor is required to notify the COR. The contractor will provide an itemized report and estimate identifying the additional repairs with the associated cost of the repairs. The COR and JMTC will review the repairs and cost and determine if they are fair and reasonable. A contract modification will be issued prior to the contractor proceeding with any work associated with the repairs.

12. Reporting Each completed generator shale be returned to RIA-JMTC with a detailed report identifying all replacements that occurred to the unit. The report shall also be dated and include the unit serial number.

13. ID Tagging Completed generators are to have ID tagging installed upon completion of the overhaul.

1. Unique Identification (UID) tag – A metallic UID tag is to be installed. The UID tag shall contain the following information:

A. (17V) Contractors Cage code B. (1P) RIA149333 or RIA151367 as applicable C. (S) Unit serial number D. UID symbol

2. RESET Tag - A hard plastic tag is to be installed. The RESET tag shall contain the following information:

A. RESET

B. Letter abbreviation for the month and Four (4) Digit year C. Number of Run hours at RESET D. Unit serial number

14. Warranty Contractor to provide 90 day warranty from the date that the overhauled generator is accepted by RIA-JMTC for parts and a 1 year warranty on labor from date of acceptance. The warranty shall cover all work performed and parts replaced under this SOW. If warranty re-work is required the COR will communicate with the contractor to schedule for the re-work to be performed during the warranty period.

15. Environmental Contractor must follow all applicable local, state, and federal environmental laws and regulations.

16. Schedule A. After a generator is received by the contractor, the contractor will have Five (5) business days to perform the initial evaluation of the generator and notify the COR with their findings.

B. The COR and RIA-JMTC will review the contractors findings to determine if the generator is finically feasible to repair. The COR and RIA-JMTC will reply to the contractor with Five (5) business days If the repairs are feasible. The Contractor will receive a contract modification to authorize the work is approved before they can proceed with the repairs.

C. After receipt of the contract modification authorizing the repairs, the contractor will have Fifteen (15) business days to perform the repairs and return the completed generator back to RIA-JMTC.

17. Quality assurance Surveillance Plan (QASP) image1.emf