B08_Solicitation_-_Systems_Deficiency_List.pdf

PDF 158 KB Posted

Attached to
AKRO STRUCTURAL FIRE SYSTEM REPAIRS AK
Solicitation number
140P9726Q0025
Issued by

About this file

This document is a comprehensive inspection report identifying fire suppression system deficiencies across multiple National Park Service facilities in Alaska (BELA, DENA, GAAR, GLBA, KATM, KLGO, LACL, WEAR, WRST parks). The report documents required repairs and maintenance across sprinkler systems, fire alarm systems, backflow preventers, check valves, gauges, and related fire protection components.

The deficiencies span recurring maintenance issues including sprinkler head replacements for systems over 20 years old (requiring UL laboratory testing for some installations), gauge replacements due for 5-year inspection cycles, system riser internal pipe inspections, check valve rebuilds and replacements, fire alarm panel repairs and battery replacements, strobe and horn installation/replacement, ProtectoWire accessibility corrections, and backflow preventer installation and drainage modifications. Specific technical requirements are referenced to NFPA 25 standards for fire sprinkler system inspection and maintenance. Notable facility-specific repairs include accelerator rebuilds, low-temperature sensor repositioning, mixed response sprinkler head conversions to ensure uniform head types per code, FDC (Fire Department Connection) signage installation, control valve sealing, antifreeze solution replacement with UL-listed products, pressure regulator replacement, and notification appliance installations in sleeping areas to meet decibel requirements. The document provides location details, FMSS asset numbers, building names, system types (SP for sprinkler, FA for fire alarm, BP for backflow preventer, CA for clean agent systems), specific deficiency descriptions, and recommended corrective actions organized by park and facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Park FMSS Location # Building Name/Description System FMSS Asset # Location Deficiency Description Recommendation/ Required

Repair Additional Comments

BELA 42599 0000456 Duplex 205 A, B SP 347346 FDC No FDC sign Install sign NFPA 25 13.7.1(5) BELA 42599 0000456 Duplex 205 A, B SP 347346 Backflow No valve signs x2 Install signs NFPA 25 13.3.1

BELA 42605 00BUNK01 Bunk House-- Nome SP 347310 System Due for 5 year internal inspection Perform 5 year internal inspection NFPA 25 14.3.2.1

BELA 42605 00BUNK01 Bunk House-- Nome SP 347310 System Gauges due for 5 year Replace gauges NFPA 25 5.3.2.1

BELA 42605 00BUNK01 Bunk House-- Nome BP 347310 Check #2 Leaked Clean and replace NFPA 25 13.7.1(5)

DENA 86498 Denali Visitor Center B548 SP 1475994 system riser Accelerator turned off on arrival, appears inoperable rebuild accelerator and retest

13.4.5.2.4

DENA 86498 Denali Visitor Center B548 BP 1475994 Check Valves 1

& 2 Both check valves failed to hold back pressure Replace check valves (whole checks, not just gaskets)

DENA 1521 HQ Apartment P12 A & B Historic FA 1475819 Attic Unable to access ProtectoWire without access to the attic from the exterior

Move the end of the line resistor down from the attic to an accessible site as agreed upon with park staff

DENA 1521 HQ Apartments P12 A & B Historic SP 1475822 Throughout both units

All quick response sprinkler heads are over 20 years old

Replace x10 residential pendants and x12 res. HSW

DENA 1522 HQ Apartments P13 A & B Historic FA 1475823 Residence P13

Attic ProtectoWire end of line is inaccessible in the attic

Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff

DENA 243278

HQ Area The Afterthought

Residence P640 SP 1476019 System riser Guage is over 5 years old Replace guage

DENA 243278

HQ Area The Afterthought

Residence P640 SP 1476019 System riser No supply of spare sprinklers

Add x6 res HSW heads and listed head wrench

DENA 1502 HQ Barn Office B106 Historic FA 1475370 Attic

ProtectoWire

Access was prevented due to wildlife. Access to attic is limited to exterior of the building

Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff

17.4.3

DENA 1512

HQ Commercial Services Office

B103 Historic FA 1475578 Bathroom

Strobe did not flash while in alarm state

Verify integrity of wiring in NAC appliance, replace if necessary

DENA 1512

HQ Commercial Services Office

B103 Historic SP 1475580 Riser Room No sprinkler head Add x1 sprinkler head in riser room

10.2.4.2.1

DENA 1512

HQ Commercial Services Office

B103 Historic

SP 1475580

One office and hallway

Not allowed to mix QR and SR heads in same area

Replace x4 SR pendants with x4 QR pendants

9.4.3.3

DENA 1512

HQ Commercial Services Office

B103 Historic SP 1475580 Hallway by FACP x2 heads need added (too far off walls)

Add x2 heads in hallway 10.2.4.2.1

DENA 1535 HQ Duplex P252 A SP 1475855 System Riser Flow switch is not connected to fire alarm panel Connect flow switch to steam plant

FACP

DENA 1535 HQ Duplex P252 B SP 1475855 System Riser Flow switch is not connected to alarm panel Connect flow switch to steam plant

FACP

Repair Additional Comments

DENA 1514

HQ Headquarters Office B21

Historic FA 1475583 Attic

Unable to access ProtectoWire without access to the attic from the exterior

Move the end of the line resistor down from the attic to an accessible site as agreed upon with park staff

DENA 1511

HQ Interpretation Office B101

Historic

FA 1475573 UIO6

Low temp sensor resistor is located in the UIO6 and is improperly installed/supervised.

Move low temperature sensor resistor to low temp sensor.

DENA 1511

HQ Interpretation Office B101

Historic

SP 1475575

Throughout Building

All quick response heads are 20 years old and should be commercial heads not residential heads

Replace all QR heads (x12 HSW & x10 P)

DENA 1511

HQ Interpretation Office B101

Historic SP 1475575 2 Closets No sprinkler coverage. Add one head in each closet

DENA 18821 HQ Residence P171 FA 1475937 Attic ProtectoWire end of line is inaccessible in the attic

Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff

DENA 1542 HQ Residence P26 FA 1475872 -- Unable to test ProtectoWire at EOL due to blockage Ensure access is clear for testing of

ProtectoWire at EOL

DENA 1542 HQ Residence P26 SP 1475877 System Riser Gauge is over 5 years old. Replace gauge

DENA 1545 HQ Residence P27 SP 1475886 Throughout building All quick response heads over 20 years old Replace x10 res. pendants and x12 res HSW

DENA 1544 HQ Residence P28 FA 1475881 Attic ProtectoWire end of line is inaccessible in the attic

Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff

DENA 1541 HQ Residence P34 FA 1475867 -- ProtectoWire end of line is inaccessible in the attic

Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff

DENA 1541 HQ Residence P34 FA 1475867 Sleeping rooms Sleeping rooms measured below

70dB while the FA system was in an alarm condition

Install a low frequency horn strobe in each sleeping room

DENA 1541 HQ Residence P34 SP 1475871 Throughout housing unit

All quick response sprinkler heads are over 20 years old

Replace x6 res. Pendants and x12 res HSW

DENA 1509

HQ Resource Management

Addition (non-historic) B118 SP 1475413 Upstairs storage

Dry heads are over 15 years old and should be replaced

Replace x9 dry sprinkler heads

DENA 1509

HQ Resource Management

Addition (non-historic) B118

SP 1475413

Room by Women's Restroom

Mixed response sprinkler heads Replace 1 SP upright with 1 QR upright

DENA 1509

HQ Resource Management

Addition (non-historic) B118

SP 1475413

Throughout building

Quick response sprinklers are over 20 years old (~60)

Test a sample of 4 heads at UL lab

Repair Additional Comments

DENA 1509

HQ Resource Management

Addition (non-historic) B118

SP 1475413

Stairwell, upper storage

Storage too close to sprinkler head Relocate storage away from sprinklers >18"

DENA 1515 Maintenance Auto Shop B164 FA 1475586 Breakroom NAC appliance blocked Remove blockage for proper access to NAC appliance

DENA 1515 Maintenance Auto Shop B164 FA 1475586 Washing Garage Strobe did not function while device was in alarm Replace the horn strobe with a like model

DENA 1515 Maintenance Auto Shop B164 BP 1475587 Check Valves 1

& 2 Failed to hold Rebuild / Replace both check valves

DENA 1515 Maintenance Auto Shop B164 SP 1475587

WASH BAY

GARAGE AND

NEIGHBORING

GARAGE

Improperly installed heads and branch lines (hangers too long, heads too far down from garage doors)

Remove x2 hsw heads, relocate x4 heads and re-pipe properly to spray under garage doors

NFPA 13: 10.2.6.1, 18.6

DENA 1515 Maintenance Auto Shop B164 BP 1475588 Discharge side of backflow System not arranged for forward flow test capability Add FDC bypass valve for forward flow testing

DENA 1518 Rock House Bldg 111 FA 1475817 Sleeping rooms Sleeping rooms are below 70dBs Install notification appliamces in the residence

GAAR 43084 00000109 BTTH House 109 BP 1750891 Crawlspace Both #1 and #2 check valves failed. Rebuild check valves #1 and #2.

GAAR 43084 00000109 BTTH House 109 FA TBD FACP Outstanding trouble on panel.

Troubleshooting willl be required, verified all EOL's.

Replace motherboard.

GAAR 43508

00000201 MACB-Ranger residence

(C1) SP 1776416 Garage

(1) 155° HSW next to unit heater should be 286° HSW

Replace 155° HSW with 286°

GAAR 43508

00000201 MACB-Ranger residence

(C1)

FA TBD

Hallway & Furnace rm

Smoke/CO detectors did not operate

Replace smoke/CO detectors

GAAR 88477 BTTB-113 Visitor Center SP 1057428 Antifreeze system Contractor believes anti freeze temperature needs to be checked.

Check anti freeze temperature.

GAAR 88477 BTTB-113 Visitor Center SP 1057428 Pump Room

Normal open valves (pump test valve, hose connection in crawl space) are installed where normal closed valve should be.

Change valves.

Repair Additional Comments

GAAR 88477 BTTB-113 Visitor Center SP/FA 1057428 Crawlspace waterflow device

Waterflow device only alarm exterior bell, does not alarm inside the building.

Troubleshoot wiring.

Did not alarm FACP of alarm only triggered bell. Verify that zone 3 for tamper switches and waterflow switches are wired correctly according to manufacturer's wiring installation. Firehose test valve has 3.6 EOL resistor. Need to verify wire's path is correct. Use Fireshield FS302-wiring diagram for waterflow/supervisory combination circuit. Fully troubleshoot and rewire.

GAAR 88477 BTTB-113 Visitor Center FP 1477363 Crawlspace Gauges are due for replacement. 1 suction 1 discharge 2 riser gauges.

Replace all gauges.

GLBA 42545

HQ - Resource Management / Ranger Office Building GBA06

SP 1168372

Middle of big room - stained ceiling tile

2 1/2" schedule 10 beginning to rot out

Replace with new pipe and couplers as needed.

GLBA 42545

HQ - Resource Management / Ranger Office Building GBA06

SP 1168372

Throughout

Building Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42548 UC - Power Plant Building GBA08 FA 1475415 Building wide Strobes did not sync Replace existing devices with new

Edwards Genesis LED devices

GLBA 42548 UC - Power Plant Building GBA08 BP 1477745 Relief valve Leaked Replacement kit and rebuild.

GLBA 42548 UC - Power Plant Building GBA08 SP 1477745 Work out Room

Mixed response - 2x standard sprinkler upright at entrance should be changed to quick response 1/2" standard sprinkler upright

Replace heads to 2x 1/2" standard sprinkler upright heads.

GLBA 42573 HA - Quarters GBQ03 SP 344135 Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42576 HA - Quarters GBQ04 SP 344143 Antifreeze solution only goes to +22 degrees F Replace with UL listed solution

GLBA 42576 HA - Quarters GBQ04 SP 344143 Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42580 HA - Quarters Duplex GBQ09 SP 344166 Antifreeze solution only holds to 13 degrees F.

Replace with UL listed solution

GLBA 42580 HA - Quarters Duplex GBQ09 SP 344166 Gauges are out of date and need replacing.

Replace 2x gauges.

Repair Additional Comments

GLBA 42583 GA - Gustavus FAA Cottage GBQ20 SP 1121928 Inspection test was after antifreeze loop and cannot test without draining solution.

Replace antifreeze and all heads, contact park for type of glycol before ordering

GLBA 42583 GA - Gustavus FAA Cottage GBQ20 SP 1121928 Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42586 GA - Gustavus FAA Cottage GBQ21 SP 1121930 Inspection test was after antifreeze loop and cannot test without draining solution.

Replace system antifreeze and all heads, contact park for type of glycol before ordering

GLBA 42586 GA - Gustavus FAA Cottage GBQ21 SP 1121930 Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42587 GA - Gustavus FAA Cottage GBQ22 BP 1121931 Check valve #1 leaked Rebuild check valve #1

GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 Inspection test was after antifreeze loop and cannot test without draining solution.

Replace system antifreeze, contact park for type of glycol before ordering

GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 No gauge prior to check valve.

Provide guage line side of check valve.

GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42606

HA - Quarters GBQ77 Apartment

Building BP 225160 Check valve #1 and #2 failed.

Complete rebuild of check valve #1 and #2 and clean out.

GLBA 42606

HA - Quarters GBQ77 Apartment

Building

SP 225160

Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

GLBA 42610 HA - Quarters GBQ80 BP 225972 Check valve #1 and #2 failed.

Complete rebuild of check valve #1 and #2 and clean out.

GLBA 42615 HA - Quarters Duplex GBQ81 SP 225902 Inspection test not outside and cannot test flow for Alarm.

40 ft 1/2" piping and fittings required for testing GLBA 42615 HA - Quarters Duplex GBQ81 SP 225902 System guage is out of date Replace gauge

GLBA 70959

MA - Maintenance Support

Building GBA99 FA 1475408 Engineer Rm 18

Office contains (2) occupants w/ no notification. Common-use areas require both visual and audible notification

Add horn/strobe in office

GLBA 70959

MA - Maintenance Support

Building GBA99

SP 1475419

Room 5 wash EQ/Antifreeze

Loop

4x corroded heads quick release 1/2" standard sprinkler pendant x3 quick release, 1/2" standard sprinkler upright x1

Replace sprinkler heads.

GLBA 70959

MA - Maintenance Support

Building GBA99 BP (DC) 1475419 Check valve #1 and #2 failed.

Complete rebuild of check valve #1 and #2 and clean out.

GLBA 70959

MA - Maintenance Support

Building GBA99

SP 1475419

Though out building

Sprinkler heads are 20 years old and due for 20 year inspection.

Replace all sprinkler heads 5.3.1.1.1.3

Repair Additional Comments

GLBA 73458

UC - Fuel / Gasoline Pump Building

GBA87

CA 1477857

FCH3 Control Manual

Controller

CO2 initiator cartridge out of date - Required to be replaced annually per manufacturer

Replace CO2 16g cartridge on next inspection

11.3.1 maintenance & inspection per manufactuer design sec. V pg 5.2 Annual maintenance #4 - replace cartridge annualy

GLBA 73458

UC - Fuel / Gasoline Pump Building

GBA87

CA 1477857

FCH3 Control Head for pre-engineered "The Attendant"

CO2 initiator cartridge out of date - Required to be replaced annually per manufacturer

Replace CO2 16g cartridge on next inspection

11.3.1 maintenance & inspection per manufactuer design sec. V pg 5.2 Annual maintenance #4 - replace cartridge annualy

GLBA 73458

UC - Fuel / Gasoline Pump Building

GBA87

CA 1477857

Pump Room, Control Room

Fuse links have been changed from original 212° to 160° by others, possibly at time of tank reoplacement. Assume correct pump. Did not have 160° links at time of inspection all links & cables are in good condition.

Replace links with 160° links at next inspection.

GLBA 92317 PD - Huna Tribal House - GBA140 SP 1670711 Throughout

Building

16" globe 5635 dry head brass standard sprinkler pendant sleeve + gasket X24, dated 2015 Replace dry heads

GLBA 92317 PD - Huna Tribal House - GBA140 SP 1670711 Outside Outside bell does not ring Replace

KATM 93637

KS Seasonal and Transient

Dormatory Q01 SP 1028959 sprinklers Heads due for 20 year testing Pull 4 heads for UL testing

KATM 93637

KS Seasonal and Transient

Dormatory Q01 SP 1028959 System Guage Gauge due for 5-year replacement Replace gauge

KATM 93637

KS Seasonal and Transient

Dormatory Q01 SP 1028959 FDC Auto Drain Improper Orientation Correct orrientation

KATM 93637

KS Seasonal and Transient

Dormatory Q01 SP 1028959 System Riser

System due for 5 year internal inspection

Perform 5 year internal pipe inspection

KATM 258860

KS - King Salmon Residence 149

FA 1787815

Throughout

Building All system heat detectors are due for their 15 year replacement Replace detectors

KATM 258860

KS - King Salmon Residence 149

FA 1787815

Throughout

Building All system smoke detectors are due for sensitivity testing Replace detectors

KATM 258862

KS - King Salmon Utility Building

#301 SP 1787823 System riser Guages due for 5 year replacement Replace guages x2

KATM 258863

KS - King Salmon Water treatment

Plant Building #52 FA 1787819 All of Building All system heat detectors are due for their 15 year replacement.

Replace heat detectors

KATM 258863

KS - King Salmon Water treatment

Plant Building #52 FA 1787819 All of Building

All system smoke detectors are due for sensitivity testing

Replace detectors

KATM 258863

KS - King Salmon Water treatment

Plant Building #52 FA 1787819 FACP Battery charger on panel is inoperable and does not keep batteries charged

Replace power supply

Repair Additional Comments

KLGO 68537

White Pass Depot Visitor Center/Admin Building

SP 1020922 System Due for 5 year internal pipe inspection Perform 5 yr internal pipe inspection

NFPA 25 14.2.1

KLGO 68537

White Pass Depot Visitor Center/Admin Building

SP 1020922 Dry Valve Guages Due for 5 year replacement Replace guages x2 1/4 NFPA 25 5.3.2.1

KLGO 68540 Boas Tailor & Furrier Shop SP 1157779 System Due for 5 year internal pipe inspection Perform 5 yr internal pipe inspection

NFPA 25 14.2.1

KLGO 68540 Boas Tailor & Furrier Shop SP 1157779 Dry valve Guages due for 5 year replacement Replace guages x2 NFPA 25 5.3.2.1

KLGO 68542 Boss Bakery SP 170259 Dry valve Guages due for 5 year replacement or recalibration Replace system guages x2 NFPA 25 5.3.2.1

KLGO 68642

Moore House (Chicken

Coop)/James Bernard/Captain William

SP 1021266 FDC Check Valve Autoball drain in improper orientation Switch to horizontal position

KLGO 108753 Arctic Meat Company / YMCA BP 1011382 Check #2 Failed Rebuild valve KLGO 236885 4th Avenue Dorm BP 1756424 Check #1 Failed Rebuild valve LACL 94890 PA-19 Redoubt Duplex SP 1173618 Riser Control valves not secured. Add seals to all control valves. NFPA 25 13.3.1.3 LACL 94905 PA-17 Tanalian Duplex SP 1173614 Riser Control valves not secured. Add seals to all control valves. NFPA 25 13.3.1.3 LACL 94906 PA-18 Iliamna Duplex SP 1173616 Riser Control valves not secured. Add seals to all control valves. NFPA 25 13.3.1.3

WEAR 42579 Residence 154 B SFU Corner House SP 1693108 Bell signage Need sign on Bell Provide sign on bell

WEAR 42579 Residence 154 B SFU Corner House SP 1693108 Pumps/riser One pump guage + riser guage needed needle's broke Replace pump guage and riser guage

WEAR 84667 Northwest Alaska Heritage Center SP 1475561 Exterior Main

Entrance

Exterior horn strobe - horn functions but strobe failed to operate replace device. Weatherproof exterior system sensor horn strobe

WEAR 84667 Northwest Alaska Heritage Center SP 1475562 Dry Heads Head's over 20 years old test or replace Replace heads

WEAR 84667 Northwest Alaska Heritage Center SP 1475562 Bell No sign and doesn’t ring Install sign and replace bell

WEAR 108797 Duplex 297 C,D SP 1478582 Head Need to replace or retest quick response over 20 years Replace 22 sprinker heads.

WEAR 108797 Duplex 297 C,D SP 1478582 Bell No sign on bell Provide sign for bell

WEAR 10108795 Residence 297B, SFU SP 1475554 Head Head's over 20 years old test or replace Replace 18 HSW white ISS + Head for head box WEAR 10108795 Residence 297B, SFU SP 1475554 Bell Need signage Install signage

WRST 12013

BPKNHLX Kennecott Recreation

Hall SP 1692621 Pump / Riser Guage older than 5 years Replace 300 PSI water guage

WRST 12014

BPKNHLX Kennecott Store

Warehouse SP 1692628 Pump / Tank Guage over than 5 years old Replace 300 PSI water guage

WRST 32888 BP HQ Comfort Station SP 530555 Riser, Piping Due for 5 year internal inspection Perform 5 year internal inspection

WRST 32889 BPVC HQ Visitor Center SP 303916 Riser piping Due for 5 year internal inspection Perform 5 year internal inspection

WRST 32889 BPVC HQ Visitor Center SP 303916 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)

WRST 32890 BP HQ Exhibit Building SP 530554 Riser piping Due for 5 year internal inspection Perform 5 year internal inspection

WRST 32890 BP HQ Exhibit Building SP 530554 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)

Repair Additional Comments

WRST 32891 BP HQ Theater SP 530553 Riser, Piping Due for 5 year internal inspection Perform 5 year internal inspection

WRST 32891 BP HQ Theater SP 530553 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)

WRST 32891 BP HQ Theater SP 530553 Riser, Piping Compressor is short cyclicing due to possible air leak in Riser

Trouble shoot & repair air leak in riser piping estimate no more than

3 hours of work

WRST 32892 BA HQ Administrative Main Office SP 334202 Riser, Pipe Due for 5 year internal inspection Perform 5 year internal inspection

WRST 32892 BA HQ Administrative Main Office SP 334202 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)

WRST 32892 BA HQ Administrative Main Office FA 349486 Main floor across from Russ' Office

Horn Strobe Failed Replace

WRST 32892 BA HQ Administrative Main Office FA 349486 FACP Outdated batteries Replace

WRST 32892 BA HQ Administrative Main Office SP 1475421 Riser, Pipe Due for 5 year internal inspection Perform 5 year internal inspection

WRST 32892 BA HQ Administrative Main Office SP 1475421 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)

WRST 32892 BA HQ Administrative Main Office SP 1475421 Pipe System pressure regulator is leaking and causing excessive compressor running.

Replace system pressure regulator.

WRST 32893 BA HQ Utility Building SP 1475051 Riser, Pipe Due for 5 year internal inspection Perform 5 year internal inspection

WRST 32893 BA HQ Utility Building SP 1475051 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)

WRST 38167

BQ Glennallen DOI Housing A

Duplex SP 1475512 Riser Guage older than 5 years old Replace Gauage (x1 water)

WRST 38167

BQ Glennallen DOI Housing A

Duplex

SP 1475512

Exterior alarm bell

No sign, required on unmonitored systems

Install alarm bell sign

WRST 38167

BQ Glennallen DOI Housing A

Duplex

SP 1475512

Backflow Preventer

Backflow preventor does not have a drain

Install backflow preventer drain

WRST 38171

BQ Gennallen DOI Housing B

Fourplex SP 349661 Riser Guages older than 5 years Replace Guage (x1 water)

WRST 38171

BQ Gennallen DOI Housing B

Fourplex

SP 349661

Exterior alarm bell

No sign, required on unmonitored systems

Install alarm bell sign

WRST 86005 BP HQ AHTNA Cultural Center SP 1474897 Riser Guages older than 5 years Replace Guage (x1 water)

WRST 86005 BP HQ AHTNA Cultural Center SP 1474897 Exterior alarm bell No sign, required on unmonitored systems Install alarm bell sign

WRST 38171

BQ GLENNALLEN DOI HOUSING B

FOURPLEX

SP 349661

Backflow Preventer

Backflow preventor does not have a drain

Install backflow preventer drain

Compiled List