B08_Solicitation_-_Systems_Deficiency_List.pdf
PDF 158 KB Posted
- Attached to
- AKRO STRUCTURAL FIRE SYSTEM REPAIRS AK
- Solicitation number
- 140P9726Q0025
About this file
This document is a comprehensive inspection report identifying fire suppression system deficiencies across multiple National Park Service facilities in Alaska (BELA, DENA, GAAR, GLBA, KATM, KLGO, LACL, WEAR, WRST parks). The report documents required repairs and maintenance across sprinkler systems, fire alarm systems, backflow preventers, check valves, gauges, and related fire protection components.
The deficiencies span recurring maintenance issues including sprinkler head replacements for systems over 20 years old (requiring UL laboratory testing for some installations), gauge replacements due for 5-year inspection cycles, system riser internal pipe inspections, check valve rebuilds and replacements, fire alarm panel repairs and battery replacements, strobe and horn installation/replacement, ProtectoWire accessibility corrections, and backflow preventer installation and drainage modifications. Specific technical requirements are referenced to NFPA 25 standards for fire sprinkler system inspection and maintenance. Notable facility-specific repairs include accelerator rebuilds, low-temperature sensor repositioning, mixed response sprinkler head conversions to ensure uniform head types per code, FDC (Fire Department Connection) signage installation, control valve sealing, antifreeze solution replacement with UL-listed products, pressure regulator replacement, and notification appliance installations in sleeping areas to meet decibel requirements. The document provides location details, FMSS asset numbers, building names, system types (SP for sprinkler, FA for fire alarm, BP for backflow preventer, CA for clean agent systems), specific deficiency descriptions, and recommended corrective actions organized by park and facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Park FMSS Location # Building Name/Description System FMSS Asset # Location Deficiency Description Recommendation/ Required
Repair Additional Comments
BELA 42599 0000456 Duplex 205 A, B SP 347346 FDC No FDC sign Install sign NFPA 25 13.7.1(5) BELA 42599 0000456 Duplex 205 A, B SP 347346 Backflow No valve signs x2 Install signs NFPA 25 13.3.1
BELA 42605 00BUNK01 Bunk House-- Nome SP 347310 System Due for 5 year internal inspection Perform 5 year internal inspection NFPA 25 14.3.2.1
BELA 42605 00BUNK01 Bunk House-- Nome SP 347310 System Gauges due for 5 year Replace gauges NFPA 25 5.3.2.1
BELA 42605 00BUNK01 Bunk House-- Nome BP 347310 Check #2 Leaked Clean and replace NFPA 25 13.7.1(5)
DENA 86498 Denali Visitor Center B548 SP 1475994 system riser Accelerator turned off on arrival, appears inoperable rebuild accelerator and retest
13.4.5.2.4
DENA 86498 Denali Visitor Center B548 BP 1475994 Check Valves 1
& 2 Both check valves failed to hold back pressure Replace check valves (whole checks, not just gaskets)
DENA 1521 HQ Apartment P12 A & B Historic FA 1475819 Attic Unable to access ProtectoWire without access to the attic from the exterior
Move the end of the line resistor down from the attic to an accessible site as agreed upon with park staff
DENA 1521 HQ Apartments P12 A & B Historic SP 1475822 Throughout both units
All quick response sprinkler heads are over 20 years old
Replace x10 residential pendants and x12 res. HSW
DENA 1522 HQ Apartments P13 A & B Historic FA 1475823 Residence P13
Attic ProtectoWire end of line is inaccessible in the attic
Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff
DENA 243278
HQ Area The Afterthought
Residence P640 SP 1476019 System riser Guage is over 5 years old Replace guage
DENA 243278
HQ Area The Afterthought
Residence P640 SP 1476019 System riser No supply of spare sprinklers
Add x6 res HSW heads and listed head wrench
DENA 1502 HQ Barn Office B106 Historic FA 1475370 Attic
ProtectoWire
Access was prevented due to wildlife. Access to attic is limited to exterior of the building
Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff
17.4.3
DENA 1512
HQ Commercial Services Office
B103 Historic FA 1475578 Bathroom
Strobe did not flash while in alarm state
Verify integrity of wiring in NAC appliance, replace if necessary
DENA 1512
HQ Commercial Services Office
B103 Historic SP 1475580 Riser Room No sprinkler head Add x1 sprinkler head in riser room
10.2.4.2.1
DENA 1512
HQ Commercial Services Office
B103 Historic
SP 1475580
One office and hallway
Not allowed to mix QR and SR heads in same area
Replace x4 SR pendants with x4 QR pendants
9.4.3.3
DENA 1512
HQ Commercial Services Office
B103 Historic SP 1475580 Hallway by FACP x2 heads need added (too far off walls)
Add x2 heads in hallway 10.2.4.2.1
DENA 1535 HQ Duplex P252 A SP 1475855 System Riser Flow switch is not connected to fire alarm panel Connect flow switch to steam plant
FACP
DENA 1535 HQ Duplex P252 B SP 1475855 System Riser Flow switch is not connected to alarm panel Connect flow switch to steam plant
FACP
Repair Additional Comments
DENA 1514
HQ Headquarters Office B21
Historic FA 1475583 Attic
Unable to access ProtectoWire without access to the attic from the exterior
Move the end of the line resistor down from the attic to an accessible site as agreed upon with park staff
DENA 1511
HQ Interpretation Office B101
Historic
FA 1475573 UIO6
Low temp sensor resistor is located in the UIO6 and is improperly installed/supervised.
Move low temperature sensor resistor to low temp sensor.
DENA 1511
HQ Interpretation Office B101
Historic
SP 1475575
Throughout Building
All quick response heads are 20 years old and should be commercial heads not residential heads
Replace all QR heads (x12 HSW & x10 P)
DENA 1511
HQ Interpretation Office B101
Historic SP 1475575 2 Closets No sprinkler coverage. Add one head in each closet
DENA 18821 HQ Residence P171 FA 1475937 Attic ProtectoWire end of line is inaccessible in the attic
Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff
DENA 1542 HQ Residence P26 FA 1475872 -- Unable to test ProtectoWire at EOL due to blockage Ensure access is clear for testing of
ProtectoWire at EOL
DENA 1542 HQ Residence P26 SP 1475877 System Riser Gauge is over 5 years old. Replace gauge
DENA 1545 HQ Residence P27 SP 1475886 Throughout building All quick response heads over 20 years old Replace x10 res. pendants and x12 res HSW
DENA 1544 HQ Residence P28 FA 1475881 Attic ProtectoWire end of line is inaccessible in the attic
Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff
DENA 1541 HQ Residence P34 FA 1475867 -- ProtectoWire end of line is inaccessible in the attic
Extend the ProtectoWire so the end of line is located below the attic in an accessible site agreed upon with park staff
DENA 1541 HQ Residence P34 FA 1475867 Sleeping rooms Sleeping rooms measured below
70dB while the FA system was in an alarm condition
Install a low frequency horn strobe in each sleeping room
DENA 1541 HQ Residence P34 SP 1475871 Throughout housing unit
All quick response sprinkler heads are over 20 years old
Replace x6 res. Pendants and x12 res HSW
DENA 1509
HQ Resource Management
Addition (non-historic) B118 SP 1475413 Upstairs storage
Dry heads are over 15 years old and should be replaced
Replace x9 dry sprinkler heads
DENA 1509
HQ Resource Management
Addition (non-historic) B118
SP 1475413
Room by Women's Restroom
Mixed response sprinkler heads Replace 1 SP upright with 1 QR upright
DENA 1509
HQ Resource Management
Addition (non-historic) B118
SP 1475413
Throughout building
Quick response sprinklers are over 20 years old (~60)
Test a sample of 4 heads at UL lab
Repair Additional Comments
DENA 1509
HQ Resource Management
Addition (non-historic) B118
SP 1475413
Stairwell, upper storage
Storage too close to sprinkler head Relocate storage away from sprinklers >18"
DENA 1515 Maintenance Auto Shop B164 FA 1475586 Breakroom NAC appliance blocked Remove blockage for proper access to NAC appliance
DENA 1515 Maintenance Auto Shop B164 FA 1475586 Washing Garage Strobe did not function while device was in alarm Replace the horn strobe with a like model
DENA 1515 Maintenance Auto Shop B164 BP 1475587 Check Valves 1
& 2 Failed to hold Rebuild / Replace both check valves
DENA 1515 Maintenance Auto Shop B164 SP 1475587
WASH BAY
GARAGE AND
NEIGHBORING
GARAGE
Improperly installed heads and branch lines (hangers too long, heads too far down from garage doors)
Remove x2 hsw heads, relocate x4 heads and re-pipe properly to spray under garage doors
NFPA 13: 10.2.6.1, 18.6
DENA 1515 Maintenance Auto Shop B164 BP 1475588 Discharge side of backflow System not arranged for forward flow test capability Add FDC bypass valve for forward flow testing
DENA 1518 Rock House Bldg 111 FA 1475817 Sleeping rooms Sleeping rooms are below 70dBs Install notification appliamces in the residence
GAAR 43084 00000109 BTTH House 109 BP 1750891 Crawlspace Both #1 and #2 check valves failed. Rebuild check valves #1 and #2.
GAAR 43084 00000109 BTTH House 109 FA TBD FACP Outstanding trouble on panel.
Troubleshooting willl be required, verified all EOL's.
Replace motherboard.
GAAR 43508
00000201 MACB-Ranger residence
(C1) SP 1776416 Garage
(1) 155° HSW next to unit heater should be 286° HSW
Replace 155° HSW with 286°
GAAR 43508
00000201 MACB-Ranger residence
(C1)
FA TBD
Hallway & Furnace rm
Smoke/CO detectors did not operate
Replace smoke/CO detectors
GAAR 88477 BTTB-113 Visitor Center SP 1057428 Antifreeze system Contractor believes anti freeze temperature needs to be checked.
Check anti freeze temperature.
GAAR 88477 BTTB-113 Visitor Center SP 1057428 Pump Room
Normal open valves (pump test valve, hose connection in crawl space) are installed where normal closed valve should be.
Change valves.
Repair Additional Comments
GAAR 88477 BTTB-113 Visitor Center SP/FA 1057428 Crawlspace waterflow device
Waterflow device only alarm exterior bell, does not alarm inside the building.
Troubleshoot wiring.
Did not alarm FACP of alarm only triggered bell. Verify that zone 3 for tamper switches and waterflow switches are wired correctly according to manufacturer's wiring installation. Firehose test valve has 3.6 EOL resistor. Need to verify wire's path is correct. Use Fireshield FS302-wiring diagram for waterflow/supervisory combination circuit. Fully troubleshoot and rewire.
GAAR 88477 BTTB-113 Visitor Center FP 1477363 Crawlspace Gauges are due for replacement. 1 suction 1 discharge 2 riser gauges.
Replace all gauges.
GLBA 42545
HQ - Resource Management / Ranger Office Building GBA06
SP 1168372
Middle of big room - stained ceiling tile
2 1/2" schedule 10 beginning to rot out
Replace with new pipe and couplers as needed.
GLBA 42545
HQ - Resource Management / Ranger Office Building GBA06
SP 1168372
Throughout
Building Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42548 UC - Power Plant Building GBA08 FA 1475415 Building wide Strobes did not sync Replace existing devices with new
Edwards Genesis LED devices
GLBA 42548 UC - Power Plant Building GBA08 BP 1477745 Relief valve Leaked Replacement kit and rebuild.
GLBA 42548 UC - Power Plant Building GBA08 SP 1477745 Work out Room
Mixed response - 2x standard sprinkler upright at entrance should be changed to quick response 1/2" standard sprinkler upright
Replace heads to 2x 1/2" standard sprinkler upright heads.
GLBA 42573 HA - Quarters GBQ03 SP 344135 Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42576 HA - Quarters GBQ04 SP 344143 Antifreeze solution only goes to +22 degrees F Replace with UL listed solution
GLBA 42576 HA - Quarters GBQ04 SP 344143 Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42580 HA - Quarters Duplex GBQ09 SP 344166 Antifreeze solution only holds to 13 degrees F.
Replace with UL listed solution
GLBA 42580 HA - Quarters Duplex GBQ09 SP 344166 Gauges are out of date and need replacing.
Replace 2x gauges.
Repair Additional Comments
GLBA 42583 GA - Gustavus FAA Cottage GBQ20 SP 1121928 Inspection test was after antifreeze loop and cannot test without draining solution.
Replace antifreeze and all heads, contact park for type of glycol before ordering
GLBA 42583 GA - Gustavus FAA Cottage GBQ20 SP 1121928 Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42586 GA - Gustavus FAA Cottage GBQ21 SP 1121930 Inspection test was after antifreeze loop and cannot test without draining solution.
Replace system antifreeze and all heads, contact park for type of glycol before ordering
GLBA 42586 GA - Gustavus FAA Cottage GBQ21 SP 1121930 Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42587 GA - Gustavus FAA Cottage GBQ22 BP 1121931 Check valve #1 leaked Rebuild check valve #1
GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 Inspection test was after antifreeze loop and cannot test without draining solution.
Replace system antifreeze, contact park for type of glycol before ordering
GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 No gauge prior to check valve.
Provide guage line side of check valve.
GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42587 GA - Gustavus FAA Cottage GBQ22 SP 1121931 Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42606
HA - Quarters GBQ77 Apartment
Building BP 225160 Check valve #1 and #2 failed.
Complete rebuild of check valve #1 and #2 and clean out.
GLBA 42606
HA - Quarters GBQ77 Apartment
Building
SP 225160
Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
GLBA 42610 HA - Quarters GBQ80 BP 225972 Check valve #1 and #2 failed.
Complete rebuild of check valve #1 and #2 and clean out.
GLBA 42615 HA - Quarters Duplex GBQ81 SP 225902 Inspection test not outside and cannot test flow for Alarm.
40 ft 1/2" piping and fittings required for testing GLBA 42615 HA - Quarters Duplex GBQ81 SP 225902 System guage is out of date Replace gauge
GLBA 70959
MA - Maintenance Support
Building GBA99 FA 1475408 Engineer Rm 18
Office contains (2) occupants w/ no notification. Common-use areas require both visual and audible notification
Add horn/strobe in office
GLBA 70959
MA - Maintenance Support
Building GBA99
SP 1475419
Room 5 wash EQ/Antifreeze
Loop
4x corroded heads quick release 1/2" standard sprinkler pendant x3 quick release, 1/2" standard sprinkler upright x1
Replace sprinkler heads.
GLBA 70959
MA - Maintenance Support
Building GBA99 BP (DC) 1475419 Check valve #1 and #2 failed.
Complete rebuild of check valve #1 and #2 and clean out.
GLBA 70959
MA - Maintenance Support
Building GBA99
SP 1475419
Though out building
Sprinkler heads are 20 years old and due for 20 year inspection.
Replace all sprinkler heads 5.3.1.1.1.3
Repair Additional Comments
GLBA 73458
UC - Fuel / Gasoline Pump Building
GBA87
CA 1477857
FCH3 Control Manual
Controller
CO2 initiator cartridge out of date - Required to be replaced annually per manufacturer
Replace CO2 16g cartridge on next inspection
11.3.1 maintenance & inspection per manufactuer design sec. V pg 5.2 Annual maintenance #4 - replace cartridge annualy
GLBA 73458
UC - Fuel / Gasoline Pump Building
GBA87
CA 1477857
FCH3 Control Head for pre-engineered "The Attendant"
CO2 initiator cartridge out of date - Required to be replaced annually per manufacturer
Replace CO2 16g cartridge on next inspection
11.3.1 maintenance & inspection per manufactuer design sec. V pg 5.2 Annual maintenance #4 - replace cartridge annualy
GLBA 73458
UC - Fuel / Gasoline Pump Building
GBA87
CA 1477857
Pump Room, Control Room
Fuse links have been changed from original 212° to 160° by others, possibly at time of tank reoplacement. Assume correct pump. Did not have 160° links at time of inspection all links & cables are in good condition.
Replace links with 160° links at next inspection.
GLBA 92317 PD - Huna Tribal House - GBA140 SP 1670711 Throughout
Building
16" globe 5635 dry head brass standard sprinkler pendant sleeve + gasket X24, dated 2015 Replace dry heads
GLBA 92317 PD - Huna Tribal House - GBA140 SP 1670711 Outside Outside bell does not ring Replace
KATM 93637
KS Seasonal and Transient
Dormatory Q01 SP 1028959 sprinklers Heads due for 20 year testing Pull 4 heads for UL testing
KATM 93637
KS Seasonal and Transient
Dormatory Q01 SP 1028959 System Guage Gauge due for 5-year replacement Replace gauge
KATM 93637
KS Seasonal and Transient
Dormatory Q01 SP 1028959 FDC Auto Drain Improper Orientation Correct orrientation
KATM 93637
KS Seasonal and Transient
Dormatory Q01 SP 1028959 System Riser
System due for 5 year internal inspection
Perform 5 year internal pipe inspection
KATM 258860
KS - King Salmon Residence 149
FA 1787815
Throughout
Building All system heat detectors are due for their 15 year replacement Replace detectors
KATM 258860
KS - King Salmon Residence 149
FA 1787815
Throughout
Building All system smoke detectors are due for sensitivity testing Replace detectors
KATM 258862
KS - King Salmon Utility Building
#301 SP 1787823 System riser Guages due for 5 year replacement Replace guages x2
KATM 258863
KS - King Salmon Water treatment
Plant Building #52 FA 1787819 All of Building All system heat detectors are due for their 15 year replacement.
Replace heat detectors
KATM 258863
KS - King Salmon Water treatment
Plant Building #52 FA 1787819 All of Building
All system smoke detectors are due for sensitivity testing
Replace detectors
KATM 258863
KS - King Salmon Water treatment
Plant Building #52 FA 1787819 FACP Battery charger on panel is inoperable and does not keep batteries charged
Replace power supply
Repair Additional Comments
KLGO 68537
White Pass Depot Visitor Center/Admin Building
SP 1020922 System Due for 5 year internal pipe inspection Perform 5 yr internal pipe inspection
NFPA 25 14.2.1
KLGO 68537
White Pass Depot Visitor Center/Admin Building
SP 1020922 Dry Valve Guages Due for 5 year replacement Replace guages x2 1/4 NFPA 25 5.3.2.1
KLGO 68540 Boas Tailor & Furrier Shop SP 1157779 System Due for 5 year internal pipe inspection Perform 5 yr internal pipe inspection
NFPA 25 14.2.1
KLGO 68540 Boas Tailor & Furrier Shop SP 1157779 Dry valve Guages due for 5 year replacement Replace guages x2 NFPA 25 5.3.2.1
KLGO 68542 Boss Bakery SP 170259 Dry valve Guages due for 5 year replacement or recalibration Replace system guages x2 NFPA 25 5.3.2.1
KLGO 68642
Moore House (Chicken
Coop)/James Bernard/Captain William
SP 1021266 FDC Check Valve Autoball drain in improper orientation Switch to horizontal position
KLGO 108753 Arctic Meat Company / YMCA BP 1011382 Check #2 Failed Rebuild valve KLGO 236885 4th Avenue Dorm BP 1756424 Check #1 Failed Rebuild valve LACL 94890 PA-19 Redoubt Duplex SP 1173618 Riser Control valves not secured. Add seals to all control valves. NFPA 25 13.3.1.3 LACL 94905 PA-17 Tanalian Duplex SP 1173614 Riser Control valves not secured. Add seals to all control valves. NFPA 25 13.3.1.3 LACL 94906 PA-18 Iliamna Duplex SP 1173616 Riser Control valves not secured. Add seals to all control valves. NFPA 25 13.3.1.3
WEAR 42579 Residence 154 B SFU Corner House SP 1693108 Bell signage Need sign on Bell Provide sign on bell
WEAR 42579 Residence 154 B SFU Corner House SP 1693108 Pumps/riser One pump guage + riser guage needed needle's broke Replace pump guage and riser guage
WEAR 84667 Northwest Alaska Heritage Center SP 1475561 Exterior Main
Entrance
Exterior horn strobe - horn functions but strobe failed to operate replace device. Weatherproof exterior system sensor horn strobe
WEAR 84667 Northwest Alaska Heritage Center SP 1475562 Dry Heads Head's over 20 years old test or replace Replace heads
WEAR 84667 Northwest Alaska Heritage Center SP 1475562 Bell No sign and doesn’t ring Install sign and replace bell
WEAR 108797 Duplex 297 C,D SP 1478582 Head Need to replace or retest quick response over 20 years Replace 22 sprinker heads.
WEAR 108797 Duplex 297 C,D SP 1478582 Bell No sign on bell Provide sign for bell
WEAR 10108795 Residence 297B, SFU SP 1475554 Head Head's over 20 years old test or replace Replace 18 HSW white ISS + Head for head box WEAR 10108795 Residence 297B, SFU SP 1475554 Bell Need signage Install signage
WRST 12013
BPKNHLX Kennecott Recreation
Hall SP 1692621 Pump / Riser Guage older than 5 years Replace 300 PSI water guage
WRST 12014
BPKNHLX Kennecott Store
Warehouse SP 1692628 Pump / Tank Guage over than 5 years old Replace 300 PSI water guage
WRST 32888 BP HQ Comfort Station SP 530555 Riser, Piping Due for 5 year internal inspection Perform 5 year internal inspection
WRST 32889 BPVC HQ Visitor Center SP 303916 Riser piping Due for 5 year internal inspection Perform 5 year internal inspection
WRST 32889 BPVC HQ Visitor Center SP 303916 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)
WRST 32890 BP HQ Exhibit Building SP 530554 Riser piping Due for 5 year internal inspection Perform 5 year internal inspection
WRST 32890 BP HQ Exhibit Building SP 530554 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)
Repair Additional Comments
WRST 32891 BP HQ Theater SP 530553 Riser, Piping Due for 5 year internal inspection Perform 5 year internal inspection
WRST 32891 BP HQ Theater SP 530553 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)
WRST 32891 BP HQ Theater SP 530553 Riser, Piping Compressor is short cyclicing due to possible air leak in Riser
Trouble shoot & repair air leak in riser piping estimate no more than
3 hours of work
WRST 32892 BA HQ Administrative Main Office SP 334202 Riser, Pipe Due for 5 year internal inspection Perform 5 year internal inspection
WRST 32892 BA HQ Administrative Main Office SP 334202 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)
WRST 32892 BA HQ Administrative Main Office FA 349486 Main floor across from Russ' Office
Horn Strobe Failed Replace
WRST 32892 BA HQ Administrative Main Office FA 349486 FACP Outdated batteries Replace
WRST 32892 BA HQ Administrative Main Office SP 1475421 Riser, Pipe Due for 5 year internal inspection Perform 5 year internal inspection
WRST 32892 BA HQ Administrative Main Office SP 1475421 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)
WRST 32892 BA HQ Administrative Main Office SP 1475421 Pipe System pressure regulator is leaking and causing excessive compressor running.
Replace system pressure regulator.
WRST 32893 BA HQ Utility Building SP 1475051 Riser, Pipe Due for 5 year internal inspection Perform 5 year internal inspection
WRST 32893 BA HQ Utility Building SP 1475051 Riser Guages older than 5 years Replace Guages (x2 air, x2 water)
WRST 38167
BQ Glennallen DOI Housing A
Duplex SP 1475512 Riser Guage older than 5 years old Replace Gauage (x1 water)
WRST 38167
BQ Glennallen DOI Housing A
Duplex
SP 1475512
Exterior alarm bell
No sign, required on unmonitored systems
Install alarm bell sign
WRST 38167
BQ Glennallen DOI Housing A
Duplex
SP 1475512
Backflow Preventer
Backflow preventor does not have a drain
Install backflow preventer drain
WRST 38171
BQ Gennallen DOI Housing B
Fourplex SP 349661 Riser Guages older than 5 years Replace Guage (x1 water)
WRST 38171
BQ Gennallen DOI Housing B
Fourplex
SP 349661
Exterior alarm bell
No sign, required on unmonitored systems
Install alarm bell sign
WRST 86005 BP HQ AHTNA Cultural Center SP 1474897 Riser Guages older than 5 years Replace Guage (x1 water)
WRST 86005 BP HQ AHTNA Cultural Center SP 1474897 Exterior alarm bell No sign, required on unmonitored systems Install alarm bell sign
WRST 38171
BQ GLENNALLEN DOI HOUSING B
FOURPLEX
SP 349661
Backflow Preventer
Backflow preventor does not have a drain
Install backflow preventer drain