B08_Salient_Characteristics.doc

DOC document 74 KB Posted

Attached to
POWER PEDESTALS - Brand Name or Equal To
Solicitation number
140G0122Q0259
Issued by

View the file

Other files

File Type Posted
B08_FISMA.pdf PDF
Sol_140G0122Q0259.pdf PDF
B08_Section_508.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF NEED REQUIREMENTS

Provide Replacement Power Pedestals in Mundt Building Furnish all supervision, labor, material and equipment necessary to provide the items listed below. Items listed below are to be delivered to the Mundt Federal Building, EROS Data Center, Sioux Falls, South Dakota. Normal duty hours are Monday through Friday, 7:30 a.m. to 4:00 p.m.

Items to be accomplished:

The USGS/EROS Center for Science is requiring additional power pedestal in existing computer rooms located throughout the Mundt Federal Building. The power pedestals are required for branch meter circuiting, and will be used with existing pedestals located in computer rooms. This Statement of need will involve the purchase of two(2) power pedestals on a BNE(brand name or equal) to following pedestals. The BNE will be for APC(Schneider Electric) pedestals with part numbers and salient characteristics listed below. This Statement of Need shall also incorporate the purchase of power pedestals under a FSS(Federal Supply Schedule) contract to meet or exceed the minimum specifications set forth.

RPN:

Quantity
Item
Description
Typical Dimension
Net Unit Weight

ISXD Design 1

Parts

1
PSX-PDU120V
120 V TYPE PDU
1
ELECTRICAL SYSTEM 120V
-ELECTRICAL SYSTEM 120V
1
0G-PDRPPNX10
- -TYPE C PDU 208V INPUT
81x24x34
450.00
1
DISTRIBUTION BREAKERS 120V
-TYPE & AMP OF DISTRIBUTION CKT BRKS
84
0M-0218
- -S/A BLANK PNL 1P CKTBRK NAM PSX-PDU
1x1x0
0.20
1
INSTRUMENTATION 120V
-INSTRUMENTATION OPTIONS
4
0M-0217
- -BRANCH CURRENT MONITORING 21 POLE
40x12x1
6.00
1
AR8108BLK
- -1U Airflow Management Blanking Panel Kit (Qty 2) Black
2x19x0
0.20
1
OPTIONS & ACCESSORIES 120V
-OPTIONS AND ACCESSORIES
1
0G-PSX-C-UM-EN
- -INFRASTRUXURE TYPE C DISTRIBUTION USER MANUAL
12x11x2
1.50
1
RACK COLOR
-RACK COLOR
1
0M-1699
- -KIT PSX-PDU TYPE C BLACK EXTERIOR

99.00

CONFIGURABLE POWER DISTRIBUTION - SPECIFICATIONS

SHAPE \* MERGEFORMAT

1. AC Input

1.1 Nominal voltage : 208 V 3PH WYE , 4W+G (provided by others)

1.2 Frequency : 60Hz

1.3 Input Circuit Breaker : 225A

1.4 Nominal current : 180A

1.5 Main Input conductor size : 4/ 0 AWG

2. AC Output

2.1 Nominal vo ltage

208V 3PH 4W+G

2.2 Nominal current

180A

2.3 Full Load rating

64.8kW

2.4 Distribution Panel : 2 x 225A, 42-position

2.5 Di stribution Breaker Size : 150A (Max)

3. ENVIRONMENTS

3.1 The assembly is made for an ambient temperature for operation of : o·c to 40'C.

3.2 The assembly is made for an ambient temperature for storage of : o·c to 45'C.

4. ENCLOSURE

4.1 The assembly material is steel with surface coating.

4.2 The assembly is made for Indoor floor Installation.

5. CONNECTIONS

5.1 Incoming and outgoing cables to be connected to terminals in component section.

5.2 Input cable entry is through side, top or bottom of the unit.

NOTES:

1.INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL,

THIS DRAWING AND SPECIFICATIONS HEREIN ARE THE PROPERTY OF

lTil:f coNFIGURABLE POWER rnsrnIsuTI0N DWG NO: p D R p pN X 1 0

R .EV0