STATEMENT OF NEED REQUIREMENTS
Provide Replacement Power Pedestals in Mundt Building Furnish all supervision, labor, material and equipment necessary to provide the items listed below. Items listed below are to be delivered to the Mundt Federal Building, EROS Data Center, Sioux Falls, South Dakota. Normal duty hours are Monday through Friday, 7:30 a.m. to 4:00 p.m.
Items to be accomplished:
The USGS/EROS Center for Science is requiring additional power pedestal in existing computer rooms located throughout the Mundt Federal Building. The power pedestals are required for branch meter circuiting, and will be used with existing pedestals located in computer rooms. This Statement of need will involve the purchase of two(2) power pedestals on a BNE(brand name or equal) to following pedestals. The BNE will be for APC(Schneider Electric) pedestals with part numbers and salient characteristics listed below. This Statement of Need shall also incorporate the purchase of power pedestals under a FSS(Federal Supply Schedule) contract to meet or exceed the minimum specifications set forth.
RPN:
| Quantity |
| Item |
| Description |
| Typical Dimension |
| Net Unit Weight |
ISXD Design 1
Parts
| 1 |
| PSX-PDU120V |
| 120 V TYPE PDU |
| 1 |
| ELECTRICAL SYSTEM 120V |
| -ELECTRICAL SYSTEM 120V |
| 1 |
| 0G-PDRPPNX10 |
| - -TYPE C PDU 208V INPUT |
| 81x24x34 |
| 450.00 |
| 1 |
| DISTRIBUTION BREAKERS 120V |
| -TYPE & AMP OF DISTRIBUTION CKT BRKS |
| 84 |
| 0M-0218 |
| - -S/A BLANK PNL 1P CKTBRK NAM PSX-PDU |
| 1x1x0 |
| 0.20 |
| 1 |
| INSTRUMENTATION 120V |
| -INSTRUMENTATION OPTIONS |
| 4 |
| 0M-0217 |
| - -BRANCH CURRENT MONITORING 21 POLE |
| 40x12x1 |
| 6.00 |
| 1 |
| AR8108BLK |
| - -1U Airflow Management Blanking Panel Kit (Qty 2) Black |
| 2x19x0 |
| 0.20 |
| 1 |
| OPTIONS & ACCESSORIES 120V |
| -OPTIONS AND ACCESSORIES |
| 1 |
| 0G-PSX-C-UM-EN |
| - -INFRASTRUXURE TYPE C DISTRIBUTION USER MANUAL |
| 12x11x2 |
| 1.50 |
| 1 |
| RACK COLOR |
| -RACK COLOR |
| 1 |
| 0M-1699 |
| - -KIT PSX-PDU TYPE C BLACK EXTERIOR |
99.00
CONFIGURABLE POWER DISTRIBUTION - SPECIFICATIONS
SHAPE \* MERGEFORMAT
1. AC Input
1.1 Nominal voltage : 208 V 3PH WYE , 4W+G (provided by others)
1.2 Frequency : 60Hz
1.3 Input Circuit Breaker : 225A
1.4 Nominal current : 180A
1.5 Main Input conductor size : 4/ 0 AWG
2. AC Output
2.1 Nominal vo ltage
208V 3PH 4W+G
2.2 Nominal current
180A
2.3 Full Load rating
64.8kW
2.4 Distribution Panel : 2 x 225A, 42-position
2.5 Di stribution Breaker Size : 150A (Max)
3. ENVIRONMENTS
3.1 The assembly is made for an ambient temperature for operation of : o·c to 40'C.
3.2 The assembly is made for an ambient temperature for storage of : o·c to 45'C.
4. ENCLOSURE
4.1 The assembly material is steel with surface coating.
4.2 The assembly is made for Indoor floor Installation.
5. CONNECTIONS
5.1 Incoming and outgoing cables to be connected to terminals in component section.
5.2 Input cable entry is through side, top or bottom of the unit.
NOTES:
1.INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL,
THIS DRAWING AND SPECIFICATIONS HEREIN ARE THE PROPERTY OF
lTil:f coNFIGURABLE POWER rnsrnIsuTI0N DWG NO: p D R p pN X 1 0
R .EV0
File details come from the government source that posted it. Updated .