B08-December_2025_Inspection_Report.xlsx

XLSX spreadsheet 20 KB Posted

Attached to
BOST 2026 FIRE SPRINKLER REPAIR
Solicitation number
140P4326R0031
Issued by

About this file

This is a Building Inspection Deficiencies Report dated December 2025 for Boston National Historical Park's fire sprinkler systems across ten buildings requiring comprehensive repairs and upgrades to achieve compliance with NFPA 25-2014 and NFPA 25-2026 standards.

The report identifies deficiencies across multiple facility locations: Building 4&5 (Visitors Center & Navy Barracks/Office), Building I (Marine Barracks/Administrative Office), Quarters G (Commandants House), Bunker Hill Museum, Building 109 (Interpretation & Protection), Building 24 (Navy Maintenance Offices), Building 125 (DC Bean), Building 32 (Marine Society), Building 10 (Shipyard Galley), and Building 107 (Yard Maintenance). Required work includes hydrostatic testing of fire department connection piping at 150 psi for 2 hours (mandatory every 5 years), replacement of 1,059 total sprinkler heads (primarily old upright models in service 75+ years), replacement of 28 escutcheons and coverplates, replacement of multiple flow switches (4-inch and 6-inch sizes) that failed semiannual testing, installation of visible FDC signage at multiple locations, placement of hydraulic placards on standpipes, replacement of damaged control valves and angle valves, installation of electric bells to replace inoperative water motor gongs, air leakage testing of dry systems, addition of check valves to trim lines, installation of inspector test connections, and repair or replacement of butterfly valve supervisory alarm devices. Work is required across multiple valve sizes (1-inch, 1.25-inch, 2-inch) and piping configurations to ensure all systems function within regulatory requirements.

View the file

Other files

File Type Posted
Sol_140P4326R0031_Amd_0003.pdf PDF
Sol_140P4326R0031_Amd_0002.pdf PDF
B09-RFI_1_0001.docx DOCX document
Sol_140P4326R0031_Amd_0001.pdf PDF
B11-Pre-bid_site_visit_sign-in_BOST_Sprinkler_Repair_0001.pdf PDF
Sol_140P4326R0031.pdf PDF
B03-WD-MA20260001-Mod1-5_18_26.pdf PDF
B08-Boston_NHP_Fire_Sprinkler_SOW_Dec2025.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Building (Bldg)Inspection Deficiencies
1Bldg #4&5 Visitors Center & Navy Barracks/Officeconduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsReplace the 4 inch flow switch on east side navy system 3rd floor did not operate. NFPA 25-2014 5.3.3.2 - Vane-type and pressure switch–type waterflow alarm devices shall be tested semiannually.replace 62 sprinkler heads NFPA 25-2014 5.2.1.1.2 - Any sprinkler that shows signs of any of the following shall be replaced (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading (6) Painting unless painted by the sprinkler manufacturerReplace 28 Escutcheons or coverplates NFPA 25-2014 5.2.1.1.6 - Escutcheons and coverplates for recessed, flush, and concealed sprinklers shall be replaced with their listed escutcheon or coverplate if found missing during the inspection.Replace 5 old upright sprinkler heads NFPA 25-2014 5.3.1.1.1.5 - Where sprinklers have been in service for 75 years or more
2Bldg I, Marine Barracks/Administrative OfficeA hydraulic placard is required to be placed on the sprinkler system standpipe NFPA 25-2026 5.2.6.11.25" Check valve needs to be added to the trim line to avoid water flooding the archieve. Does Valve and Trim appear to be in its appropriate open or closed positions at time of inspection? NFPA 25-2026 13.1Conduct air leakage test of the dry system(s) is required every 3 years NFPA 25-2026 13.4.5.2.9replace 10 sprinkler heads NFPA 25-2014 5.2.1.1.2 - Any sprinkler that shows signs of any of the following shall be replaced (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading (6) Painting unless painted by the sprinkler manufacturerReplace 48 old upright sprinkler heads NFPA 25-2014 5.3.1.1.1.5 - Where sprinklers have been in service for 75 years or moreAdd visible FDC signage NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.conduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsMain floor switch in sprinkle room did not work. Replacement of 6 inch flow switch needed. NFPA 25-2014 5.3.3.2 - Vane-type and pressure switch–type waterflow alarm devices shall be tested semiannually.Replace the 4 inch flow switch on east side navy system 3rd floor did not operate. NFPA 25-2014 5.3.3.2 - Vane-type and pressure switch–type waterflow alarm devices shall be tested semiannually.
3Quarters G Commandants HouseReplace simese caps on FDC. NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.Add visible FDC signage NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.conduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsInstall inspector test connection to sprinkler system. NFPA 25-2014 13.4.1.1 Alarm valves and system riser check valves shall be externally inspected monthly and shall verify the following: (2) The valves and trim are free of
physical damage.A hydraulic placard is required to be placed on the sprinkler system standpipe NFPA 25-2026 5.2.6.1
4Bunker Hill MuseumAdd visible FDC signage NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.conduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 years
5Bldg #109 Interpretation & Protectionconduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsA hydraulic placard is required to be placed on the sprinkler system standpipe NFPA 25-2026 5.2.6.1replace 4 sprinkler heads NFPA 25-2014 5.2.1.1.2 - Any sprinkler that shows signs of any of the following shall be replaced (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading (6) Painting unless painted by the sprinkler manufacturerReplace 24 old upright sprinkler heads NFPA 25-2014 5.3.1.1.1.5 - Where sprinklers have been in service for 75 years or more
6Bldg #24 Navy Maintainence OfficesAdd 3 (three) visible FDC signage NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.conduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsReplace 1.25” angle valve in tool room 1st floor NFPA 25-2014 13.4.1.1 Alarm valves and system riser check valves shall be externally inspected monthly and shall verify the following: (2) The valves and trim are free of physical damage.A hydraulic placard is required to be placed on the sprinkler system standpipe NFPA 25-2026 5.2.6.1install three electric bells to replace the inoperative water motor gongs. The gong needs to be removed and its piping plugged off
NFPA 25-2014 13.4.1.1replace 5 sprinkler heads NFPA 25-2014 5.2.1.1.2 - Any sprinkler that shows signs of any of the following shall be replaced (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading (6) Painting unless painted by the sprinkler manufacturerReplace missing escutcheons and cover plates for recessed, flush, and concealed sprinklers generally appe? Missing plate chrome in men’s head navy side 2nd floor

NFPA 25-2014 5.2.1.1.6nd coverplates for recessed, flush, and concealed sprinklers shall be replaced with their listed escutcheon or coverplate if found

missing during the inspection.Replace 771 old upright sprinkler heads NFPA 25-2014 5.3.1.1.1.5 - Where sprinklers have been in service for 75 years or more
7Bldg #125 DC BeanReplace caps on Simese FDC - NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.Replace 1 inch angle valve on stretcher test on second floor this valve leaks unless you use a wrench to close it NFPA 25-2014 13.4.1.1 Alarm valves and system riser check valves shall be externally inspected monthly and shall verify the following: (2) The valves and trim are free of physical damage.replace 20 sprinkler heads NFPA 25-2014 5.2.1.1.2 - Any sprinkler that shows signs of any of the following shall be replaced (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading (6) Painting unless painted by the sprinkler manufacturer
8Bldg #32 Marine SocietyBackflow valves (2 need signage NFPA 25-2014 13.3.1 Each controlvalveshall be identified and have a sign indicating the system or portion of the system it controlsconduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsinstall and electric bell to replace the inoperative water motor gong. The gong needs to be removed and its piping plugged off
NFPA 25-2014 13.4.1.1A hydraulic placard is required to be placed on the sprinkler system standpipe NFPA 25-2026 5.2.6.1replace 5 sprinkler heads NFPA 25-2014 5.2.1.1.2 - Any sprinkler that shows signs of any of the following shall be replaced (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading (6) Painting unless painted by the sprinkler manufacturerReplace 57 old upright sprinkler heads NFPA 25-2014 5.3.1.1.1.5 - Where sprinklers have been in service for 75 years or more
9Bldg #10 Shipyard GalleyAdd visible FDC signage NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.conduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsInspector test on second floor needs to be piped outside for proper testing of flow. Approximately 10 feet of 1 inch pipe, two.-1” elbows,1-galvanized 1”45° elbow with wall plate 2 inch angled valve on main drain needs to be replaced. This valve will not shut completely and water consistently dripped past. NFPA 25-2014 13.4.1.1 Alarm valves and system riser check valves shall be externally inspected monthly and shall verify the following: (2) The valves and trim are free of physical damage.A hydraulic placard is required to be placed on the sprinkler system standpipe NFPA 25-2026 5.2.6.1replace 8 sprinkler heads NFPA 25-2014 5.2.1.1.2 - Any sprinkler that shows signs of any of the following shall be replaced (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading (6) Painting unless painted by the sprinkler manufacturer
10Bldg #107 Yard MaintenanceRepair/replace 1 1/4" butterfly valve control supervisory alarm device NFPA 25-2014 13.3.2.1.2 - Control valve supervisory alarm devices shall be inspected quarterly to verify that they are free of physical damage.Add FDC signage on brick NFPA 25-2014 13.7.1 Fire department connections shall be inspected quarterly to verify the following: Couplings or swivels are not damaged and rotate smoothly; Plugs or caps are in place and undamaged; Fire department connections are visible and accessible; Identification signs are in place.conduct five years hydrostatic test on piping from the fire department connection to the fire department check valve NFPA 25-2026 13.7.4 The piping from the fire department connection to the fire department check valve shall be hydrostatically tested at 150 psi (10 bar) for 2 hours at least once every 5 yearsA hydraulic placard is required to be placed on the sprinkler system standpipe NFPA 25-2026 5.2.6.1Replace 1.25” butterfly valve on 2nd floor did not operate properly NFPA 25-2014 13.3.2.1.2 control valve supervisory alarm devices shall be inspected quarterly to verify that they are free of physical damage.

File details come from the government source that posted it. Updated .