B08_Attach_2_Final_Drawings.pdf

PDF 7 MB Posted

Attached to
HAVO 332164-REPLACE HVAC IN OHIA WING Federal contract opportunity
Solicitation number
140P8226B0002
Issued by
Department of the Interior National Park Service

About this file

This document is a set of construction drawings for the replacement of an HVAC system at the Ohi'a Wing of Hawaii Volcanoes National Park. The project involves removing existing chiller equipment and installing a new Variable Refrigerant Flow (VRF) ductless split-system air conditioning solution. The mechanical system consists of two air-cooled condensing units (ACCU-1 rated at 36,000 BTU/hr and ACCU-2 rated at 48,000 BTU/hr) serving six wall-mounted fan coil units (FCUs) distributed across first and second floors with capacities ranging from 9,000 to 18,000 BTU/hr. All equipment is specified as Mitsubishi models with smart touch-screen controllers, and the system includes condensate drain pumps for first-floor units. Refrigerant piping uses R-454B refrigerant with specified liquid and suction line sizes, and the ACCU-1 system operates 24 hours daily while ACCU-2 operates 12 hours daily, both with a room temperature setpoint of 72°F (adjustable).

The drawings detail site plans, first and second floor layouts, mechanical demolition plans showing removal of the existing chiller yard equipment and associated piping, and electrical plans for system connections. Construction notes specify compliance with the International Code Council suite of codes effective January 1, 2024, and NFPA 70 (National Electric Code). Key requirements include contractor responsibility for site inspection prior to bidding, coordination with the contracting officer regarding field conditions and equipment clearances, proper fire-stopping of all penetrations through fire-rated assemblies, and coordination of all electrical characteristics with the electrical contractor. The contractor must provide shop drawings for equipment layout and piping coordination, repair any construction damage, and patch and paint all exposed and disturbed work to match existing surfaces.

View the file

Other files for this federal contract opportunity

Other files attached to HAVO 332164-REPLACE HVAC IN OHIA WING, newest first.
File Type Posted
Sol_140P8226B0002_Amd_0004.pdf PDF
Sol_140P8226B0002_Amd_0003.pdf PDF
Sol_140P8226B0002_Amd_0002.pdf PDF
Sol_140P8226B0002_Amd_0001.pdf PDF
B08_Attach_1_Final_Specifications_(REV3-2-26)_0001.pdf PDF
B08_Attach_1_Final_Specifications_(REV12-18-25).pdf PDF
B08_Attach_3_Payment_Bond_SF25A-23a_Exp_2027.pdf PDF
B08_Attach_6_Contractor_Price_Proposal_Form_(rev6-26-25).xlsx XLSX spreadsheet
B08_Attach_5_WD_16_Jan_2026.pdf PDF
Sol_140P8226B0002.pdf PDF
B08_Attach_4_Performance_Bond_SF25-23a_Exp_2027.pdf PDF
B08_Attach_7_Contract_Bid_Schedule.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLAN

NORTH

64'0 32'16'

A1 G3

No. 4073

W

N

ARCHITECT

PROFESSIONAL

LICENSED

AH

NELG

A.

,IIA S.

U.

NO

ME. AS

1. THE CONTRACTOR SHALL INSPECT THE PROJECT SITE BEFORE BIDDING AND

PROCEEDING WITH THE CONSTRUCTION.

2. THE CONTRACTOR SHALL NOTIFY AND COORDINATE WITH THE CONTRACTING OFFICER

FOR ANY MAJOR DEVIATIONS OR DISCREPANCIES DISCOVERED IN THE PLANS AND

SPECIFICATIONS DUE TO UNFORESEEN OR VARYING FIELD CONDITIONS.

3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO COVER THE COMPLETE

INSTALLATION OF SYSTEMS TO FUNCTION AS DESCRIBED AND SPECIFIED. OMISSIONS IN

THE DRAWINGS, OR SPECIFICATIONS, OR THE OMISSION OF DETAILS OF WORK, SHALL

NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED, OR INCORRECTLY

DESCRIBED DETAILS OF THE WORK, BUT SHALL BE PERFORMED AS IF FULLY AND

CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS. THE

CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER VERBALLY OF SUCH

OMISSIONS AND PROVIDE A WRITTEN STATEMENT OF THE OMISSIONS WITHIN (5)

WORKING DAYS OF VERBAL NOTIFICATION.

4. THE CONTRACTOR SHALL VERIFY ALL CLEARANCES FOR EQUIPMENT TO BE INSTALLED

PRIOR TO ORDERING OF EQUIPMENT AND NOTIFY THE CONTRACTING OFFICER OF ANY

INADEQUATE CLEARANCES OR CONDITIONS THAT WILL PREVENT THE PROPER

INSTALLATION, MAINTENANCE, AND OPERATION OF THE EQUIPMENT.

5. PROVIDE SHOP DRAWINGS FOR THE LAYOUT OF EQUIPMENT AND PIPING SHOWING

COORDINATION OF ALL WORK WITH ALL OTHER TRADES.

6. COORDINATION OF EQUIPMENT ELECTRICAL CHARACTERISTICS: COORDINATE VOLTAGE

AND PHASE OF EACH PIECE OF EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR

TO ORDERING.

7. DRAWINGS DO NOT ATTEMPT TO SHOW EXACT DETAILS OF PIPING AND DUCTWORK.

PROVIDE OFFSETS AS NECESSARY TO AVOID LOCAL OBSTRUCTIONS OR INTERFERENCE

WITH OTHER TRADES.

8. PROPERLY FIRE STOP ALL PENETRATIONS THROUGH FIRE RATED WALLS, FLOORS, OR

PARTITIONS WITH A UL APPROVED SYSTEM APPROPRIATE FOR THE PENETRATION TYPE

AND FIRE RATING. FIRE STOP ALL PENETRATIONS BETWEEN FLOORS.

9. ROUTE ALL CONTROL AND MOTOR STARTER WIRING IN CONDUIT.

10. REPAIR ANY DAMAGES TO EXISTING CONSTRUCTION RESULTING FROM THE

INSTALLATION OF MECHANICAL ITEMS. THE AREAS REPAIRED SHALL MATCH THE

ADJACENT SURFACES IN TEXTURE AND COLOR.

11. VERIFY AND COORDINATE ALL WALL AND FLOOR PENETRATIONS WITH THE

ARCHITECTURAL DRAWINGS AND NOTIFY THE CONTRACTING OFFICER OF ANY CONFLICTS

PRIOR TO THE START OF CONSTRUCTION.

12. PROVIDE ACCESS PANEL TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT.

COORDINATE THE LOCATION OF ACCESS PANEL TO ENSURE THAT THE EQUIPMENT CAN

BE MAINTAINED ADEQUATELY.

13. PATCH AND PAINT ALL NEW EXPOSED WORK, COLOR TO MATCH EXISTING SURFACES.

PATCH AND PAINT ALL EXISTING DISTURBED WORK, COLOR TO MATCH EXISTING

ADJACENT SURFACES, UNLESS OTHERWISE NOTED IN THE ARCHITECTURAL DRAWINGS.

GENERAL NOTES

ADDITIONAL NOTES

1. CODES, STANDARDS REGULATIONS AND GUIDELINES: ALL WORK SHALL COMPLY WITH

THE LATEST VERSIONS OF APPLICABLE CODES, STANDARDS, REGULATIONS, AND

GUIDELINES. PER POLICY MEMORANDUM 23-01 APPROVED ON MAY 9, 2023, THE NATIONAL

PARK SERVICES (NPS) HAS ADOPTED THE INTERNATIONAL CODE COUNCIL'S (ICC) SUITE

OF CODES AND STANDARDS EFFECTIVE JANUARY 1, 2024. ADDITIONALLY, THE LATEST

NFPA 70 (NATIONAL ELECTRIC CODE) IS ALSO ADOPTED EFFECTIVE JANUARY 1, 2024. ALL

WORK SHALL COMPLY WITH THE ICC SUITE OF CODES AND STANDARDS AND NFPA 70, AS

APPLICABLE. ADDITIONAL CODES, STANDARDS, REGULATIONS, AND GUIDELINES MAY

ALSO APPLY.

SYMBOL ABBRV. DESCRIPTION

T-STAT THERMOSTATT

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

EXHAUST FANEF

ACCU AIR-COOLED CONDENSING UNIT

FAN COIL UNITFCU

LIST OF ABBREVIATIONS & SYMBOLS

M1

MECHANICAL NOTES AND

SCHEDULE

FAN COIL UNITS, VRF SPLIT-DX

ID LOCATION

SERVED EQUIPMENT TYPE

NOMINAL

COOLING

CAP. (BTU/HR)

FAN

LAT (°F)

MOTOR REFRIGERANT

PIPING (INCHES)

CD

(INCHES)

UNIT

WEIGHT

(LBS)

MAX SOUND

LEVEL (dBA) REMARKS

SA (CFM) FAN (W) V/1PH/60HZ

FCU 1-1 STORAGE #1

WALL-MOUNTED

UNIT 9,000 381 55 30 208-230 1/4" RL, 3/8" RG 1-1/4" 23 43

MITSUBISHI MODEL MSZ-GS09NA-U1 OR APPROVED

EQUAL, PROVIDE WITH INTEGRAL CONDENSATE PUMP,

SMART FCU TOUCH-SCREEN CONTROLLER (MITSUBISHI

PAR-U01MEDU-K OR EQUAL)

FCU 1-2

COLLECTION

STORAGE #2

WALL-MOUNTED

UNIT 12,000 381 55 30 208-230 1/4" RL, 3/8" RG 1-1/4" 23 45

MITSUBISHI MODEL MSZ-GS12NA-U1 OR APPROVED

EQUAL, PROVIDE WITH INTEGRAL CONDENSATE PUMP,

SMART FCU TOUCH-SCREEN CONTROLLER (MITSUBISHI

PAR-U01MEDU-K OR EQUAL)

FCU 1-2

COLLECTION

PROCESSING

WALL-MOUNTED

UNIT 12,000 381 55 30 208-230 1/4" RL, 3/8" RG 1-1/4" 23 45

MITSUBISHI MODEL MSZ-GS12NA-U1 OR APPROVED

EQUAL, PROVIDE WITH INTEGRAL CONDENSATE PUMP,

SMART FCU TOUCH-SCREEN CONTROLLER (MITSUBISHI

PAR-U01MEDU-K OR EQUAL)

FCU 2-1 EXHIBIT #1

WALL-MOUNTED

UNIT 18,000 629 55 40 208-230 1/4" RL, 1/2" RG 1-1/4" 28 49

MITSUBISHI MODEL MSZ-GS18NA-U1 OR APPROVED

EQUAL, PROVIDE WITH SMART FCU TOUCH-SCREEN

CONTROLLER (MITSUBISHI PAR-U01MEDU-K OR EQUAL)

FCU 2-2 EXHIBIT #2

WALL-MOUNTED

UNIT 18,000 629 55 40 208-230 1/4" RL, 1/2" RG 1-1/4" 28 49

MITSUBISHI MODEL MSZ-GS18NA-U1 OR APPROVED

EQUAL, PROVIDE WITH SMART FCU TOUCH-SCREEN

CONTROLLER (MITSUBISHI PAR-U01MEDU-K OR EQUAL)

FCU 2-3 EXHIBIT #3

WALL-MOUNTED

UNIT 9,000 381 55 30 208-230 1/4" RL, 3/8" RG 1-1/4" 23 43

MITSUBISHI MODEL MSZ-GS09NA-U1 OR APPROVED

EQUAL, PROVIDE WITH SMART FCU TOUCH-SCREEN

CONTROLLER (MITSUBISHI PAR-U01MEDU-K OR EQUAL)

AIR COOLED CONDENSING UNIT, VRF DUCTLESS SPLIT-DX

ID LOCATION

SERVED

NOMINAL

COOLING

CAP. (BTU/HR)

AMBIENT

AIR TEMP

(°F)

REFRIG

TYPE

OUTDOOR FAN

TYPE & NO.

ELECTRICAL REFRIGERANT

PIPING (INCHES)

UNIT

WEIGHT

(LBS)

MAX SOUND LEVEL

(dBA) REMARKSV/1PH/60HZ MCA MOCP

ACCU-1 STORAGE 36,000 95 R-454B 2 208-230 36 64 3/8" RL, 5/8" RG 271 53 MITSUBISHI MODEL MXZ-SM36NAM2-U1 OR APPROVED

EQUAL

ACCU-2 LOBBY &

EXHIBITS 48,000 95 R-454B 2 208-230 36 64 3/8" RL, 5/8" RG 271 54 MITSUBISHI MODEL MXZ-SM48NAM2-U1 OR APPROVED

EQUAL

AIR CONDITIONING UNIT NOTES:

1. CONTRACTOR SHALL COORDINATE AND VERIFY FINAL INSTALLATION LOCATION WITH MANUFACTURER'S RECOMMENDED MINIMUM CLEAR SPACE REQUIREMENTS AND CLEARANCES FROM EXISTING

EQUIPMENT.

SEQUENCE OF OPERATIONS:

1. THE ACCU-1 DIRECT EXPANSION SYSTEM SHALL START AND STOP IN ACCORDANCE WITH THE SCHEDULE PROGRAMMED AT THE CONTROLLER, PROGRAMMED FOR 24 HOUR OPERATION. THE ROOM

TEMPERATURE SETPOINT SHALL BE 72°F (ADJ)

2. THE ACCU-2 DIRECT EXPANSION SYSTEM SHALL START AND STOP IN ACCORDANCE WITH THE SCHEDULE PROGRAMMED AT THE CONTROLLER, PROGRAMMED FOR 12 HOUR OPERATION. THE ROOM

TEMPERATURE SETPOINT SHALL BE 72°F (ADJ)

CUT AND CAP CHILLED WATER

PIPING 2" ABOVE THE FLOOR

IN THE MECHANICAL ROOM.

EXISTING RESTROOM

EXHAUST FANS TO REMAIN

REMOVE CHILLER AND

ALL OTHER EQUIPMENT

IN CHILLER YARD AND

CUT AND CAP CHILLED

WATER PIPING 2" ABOVE

FINISHED GRADE.

M2

MECHANICAL FIRST FLOOR

DEMO

EXISTING RESTROOM

EXHAUST FAN TO REMAIN

EXISTING RESTROOM

EXHAUST FAN

DUCTWORK TO REMAINEXISTING JANITOR'S CLOSET

EXHAUST FAN TO REMAIN

M3

MECHANICAL SECOND FLOOR

DEMO

ACCU-1 ACCU-2

FCU 1-1,

WALL-MOUNT UNIT

FCU 1-2,

WALL-MOUNT UNIT

FCU 1-3,

WALL-MOUNT UNIT

DRAIN CONDENSATE

TO EXISTING FLOOR

DRAIN IN MECHANICAL

ROOM

CO CO

CO

CO

PROVIDE WITH

CONDENSATE DRAIN PUMPPROVIDE WITH

CONDENSATE DRAIN PUMP

PROVIDE WITH

CONDENSATE DRAIN PUMP

REFRIGERANT PIPING

INTO BUILDING

THROUGH (E) OPENING

SEE ARCHITECTURAL

DRAWINGS FOR

HOUSEKEEPING PAD DETAIL

CO

CO

CO

EXIST. ALARM TO REMAIN

M4

MECHANICAL FIRST FLOOR

NEW

NEW WORK NOTES:

1. REFRIGERANT AND CONDENSATE DRAIN LINES TO BE

MOUNTED TO THE CEILING.

2. PROVIDE CONDENSATE DRAIN PUMPS FOR THE 1ST

FLOOR FAN COIL UNITS.

T

T T

FCU 2-1,

WALL-MOUNTED UNIT

FCU 2-2,

WALL-MOUNTED UNIT

FCU 2-3,

WALL-MOUNTED UNIT

M5

MECHANICAL SECOND FLOOR

NEW

TT

T

T1 - Cover Sheet
G1 Project Info
G2 Site Plan
G2 Site Plan
PLOT
G3 Enlarged Site Plan
A1 First Floor Plan
A2 Second Floor Plan
M1
M1
M2
M2
M3
M3
M4
M4
M5
M5