B08_Attach_2_(1877_Volcano_House_Fire_Pro)_-_Final_Drawings_(REV1).pdf
PDF 3 MB Posted
- Attached to
- HAVO 337265-1877 VOLCANO HOUSE FIRE PRO
- Solicitation number
- 140P8226B0001
About this file
This document is a set of architectural and engineering drawings for the Replace 1877 Volcano House Fire Suppression System project at Hawaii Volcanoes National Park. The project involves comprehensive renovation of the historic Volcano House structure, including installation of a new automatic wet pipe fire sprinkler system throughout the entire building.
The scope of work requires demolition of the existing fire sprinkler system and installation of new sprinkler heads and piping utilizing existing wall and ceiling openings. The new system must be designed and installed in accordance with NFPA 1 (2021), NFPA 13 (2025), NFPA 70 (2021), Hawaii Revised Statutes Section 132, and Hawaii County Code Chapter 17. The sprinkler design shall use the area/density method for light ordinary hazard occupancy at 1,500 square feet, with a 10% cushion to water supply. All sprinklers must be ordinary temperature quick response type with corrosion-resistant electroless nickel-PTFE coating, except storage rooms which require intermediate temperature sprinklers. The system design is conceptual; the contractor must install in accordance with applicable codes, manufacturer recommendations, and equipment listings. All piping shall be black steel (Schedule 40 for sizes less than 2.5 inches), and all exposed piping and accessories must be painted to match adjacent surfaces. Additional requirements include provision of a pressure relief valve set at 175 PSI, hydrant flow testing to establish baseline water supply parameters, and replacement of portable fire extinguishers with wall-bracket-mounted 10-pound multipurpose dry chemical units. Existing smoke detectors shall remain in service throughout construction.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
No. 4073
W
N
ARCHITECT
PROFESSIONAL
LICENSED
AH
NELG
A.
,IIA S.
U.
NO
ME. AS
This work was prepared by me or under my supervision and construction of this project will be under my observation.
Signature Expiration Date of the License 4/30/2026
A
C
BD
NORTH
60'0 30'15'
No. 4073
W
N
ARCHITECT
PROFESSIONAL
LICENSED
AH
NELG
A.
,IIA S.
U.
NO
ME. AS
This work was prepared by me or under my supervision and construction of this project will be under my observation.
Signature Expiration Date of the License 4/30/2026
1 WET PIPE FIRE SPRINKLER RISER
PROVIDE 4-WAY SWAY
BRACING AT TOP OF
RISER
ALARM PRESSURE
SWITCH
RETARD CHAMBER
ALARM CHECK VALVE,
ALL ALARM VALVES TO
BE MONITORED WITH
TAMPER SWITCHES
OS&Y CONTROL VALVE
IN WITH TAMPER
SWITCH
FLEXIBLE COUPLING
WITHIN 24" OF TOP AND
BOTTOM OF THE RISER
(TYP)
CONCRETE SLAB
PRESSURE GAUGES
(E) UNDER GROUND
WATER SUPPLY
WATER MOTOR GONG
MOUNTED ON EXTERIOR
OF BUILDING
DRAIN LINE
CHECK VALVE
1" PRESSURE RELIEF VALVE
SET AT 175 PSI
WORK BY FIRE
SPRINKLER
CONTRACTOR
DETAILS
1. PROVIDE AUTOMATIC FIRE SPRINKLER SYSTEM FOR THE ENTIRE BUILDING UNDER
THIS PROJECT SCOPE OF WORK. BUILDING IS TYPE VB CONSTRUCTION.
2. REFERENCES: THE SPRINKLER SYSTEM DESIGN AND INSTALLATION SHALL BE IN
ACCORDANCE
NFPA 1, 2021 EDITION
NFPA 10, 2018 EDITION
NFPA 13, 2025 EDITION
NFPA 54 (NATIONAL FUEL GAS CODE), 2021 EDITION
NFPA 70 (NATIONAL ELECTRICAL CODE), 2021 EDITION
NFPA 101 (LIFE SAFETY CODE), 2024 EDITION
HAWAII REVISED STATUTES (HRS) SECTION 132
HAWAII COUNTY CODE CHAPTER 17 FIRE CODE AMENDMENTS
CURRENT UNIFORM FIRE CODE AS AMENDED BY COUNTY OF HAWAII.
THE CONTRACTOR SHALL COMPLETE ALL WORK IN ACCORDANCE WITH THE LATEST
VERSIONS OF APPLICABLE FEDERAL, STATE, AND LOCAL CODES, STANDARDS, AND
REGULATIONS. PER POLICY MEMORANDUM 23-01 APPROVED ON MAY 9, 2023, THE
NATIONAL PARK SERVICES (NPS) HAS ADOPTED THE INTERNATIONAL CODE
COUNCIL'S (ICC) SUITE OF CODES AND STANDARDS EFFECTIVE JANUARY 1, 2024.
ADDITIONALLY, THE LATEST NFPA 70 (NATIONAL ELECTRIC CODE) IS ALSO ADOPTED
EFFECTIVE JANUARY 1, 2024. ALL WORK SHALL COMPLY WITH THE ICC SUITE OF
CODES AND STANDARDS AND NFPA 70, WHERE APPLICABLE. ADDITIONAL CODES,
STANDARDS, AND REGULATIONS MAY ALSO APPLY. IN THE EVENT OF A CONFLICT
BETWEEN CODES, STANDARDS, REGULATIONS, AND THE CONTRACT DOCUMENTS,
SUBMIT A REQUEST FOR INFORMATION (RFI) WITH CODE REFERENCES / CITATIONS
TO THE CONTRACTING OFFICER FOR A DETERMINATION.
3. ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM APPROVED.
4. ALL SPRINKLERS SHALL BE ORDINARY TEMPERATURE QUICK RESPONSE TYPE
EXCEPT THE STORAGE ROOMS SHALL BE INTERMEDIATE TEMPERATURE.
5. ALL SPRINKLERS SHALL BE CORROSION RESISTANT WITH ELECTROLESS NICKEL-PTFE
COATING.
6. AUTOMATIC WET PIPE SPRINKLER PROTECTION SHALL BE PROVIDED THROUGHOUT
THE BUILDING, INCLUDING CONCEALED COMBUSTIBLE SPACES ABOVE CEILINGS,
UNDER COMBUSTIBLE STAIRWAYS, ALL COMBUSTIBLE ROOF ASSEMBLIES, COVERED
WALKWAYS OR CANOPY OVERHANGS. REFER TO ARCHITECTURAL DRAWINGS FOR
ELEVATIONS, SECTIONS, CEILING HEIGHTS AND MATERIALS OF CONSTRUCTION.
7. DESIGN WATER SUPPLY: CONTRACTOR TO PERFORM HYDRANT FLOW TEST FROM
EXISTING AREA HYDRANTS TO ESTABLISH A BASELINE FOR EXISTING AVAILABLE
STATIC, RESIDUAL PRESSURES AND FLOW AT RESIDUAL PRESSURE PRIOR TO START
OF ANY WORK.
8. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED USING
AREA/DENSITY METHOD IN ACCORDANCE WITH NFPA 13 AND DESIGN CRITERIA
SPACE OCCUPANCY DESIGN AREA (SF)
PUBLIC ASSEMBLY LIGHT ORDINARY 1,500
PROVIDE HYDRAULIC CALCULATION WITH A 10% CUSHION TO THE WATER SUPPLY.
THE HYDRAULIC CALCULATIONS SHALL INCLUDE A 12 PSI LOSS THROUGH THE
BACKFLOW PREVENTER OR USE FRICTION LOSS THROUGH ACTUAL BACKFLOW
PREVENTER TO BE INSTALLED, WHICHEVER LOSS IS GREATER. BACKFLOW
PREVENTER SHALL BE SUBMITTED TO MECHANICAL ENGINEER FOR REVIEW PRIOR TO
PURCHASING.
PIPE SCHEDULE METHOD IS NOT ALLOWED.
9. SPRINKLER SPACING SHALL CONFORM TO NFPA 13 AND SHALL NOT EXCEED 225 SF
FOR LIGHT HAZARD, 130 SF FOR ORDINARY HAZARD.
10. STORAGE AREAS: HIGH PILED STORAGE IS NOT ALLOWED. STORAGE HEIGHT SHALL
NOT EXCEED 8'-0" HIGH ABOVE FINISHED FLOOR.
11. SPRINKLER PIPING SHALL COMPLY WITH NFPA 13, EXCEPT THAT PLASTIC PIPE OR
COPPER TUBING WILL NOT BE PERMITTED. ALL PIPING SHALL BE BLACK STEEL AND
BLACK STEEL LESS THAN 2-1/2 INCHES SHALL BE SCHEDULE 40.
12. THE SPRINKLER DESIGN IS CONCEPTUAL. THE CONTRACTOR SHALL INSTALL THE
SYSTEM IN ACCORDANCE WITH THE APPLICABLE CODES, MANUFACTURER'S
RECOMMENDATIONS AND EQUIPMENT LISTINGS.
13. PROVIDE A LISTED PRESSURE RELIEF VALVE ABOVE THE ALARM CHECK VALVE OR AS
PART OF THE INSPECTORS TEST CONNECTION. RELIEF VALVE SHALL BE FACTORY
SET TO 175 PSI AND SHALL OPERATE TO THE OPEN POSITION BETWEEN 90% AND
105% OF THE SET PRESSURE. PRESSURE RELIEF VALVES SHALL RESEAT OR CLOSE
AT A MINIMUM OF 80% OF THE SET PRESSURE. THE PRESSURE RELIEF VALVE SHALL
DISCHARGE INTO A DRAIN MANIFOLD OR TO THE OUTSIDE.
14. ALL EXPOSED SPRINKLER PIPING AND ACCESSORIES SHALL BE PAINTED TO MATCH
ADJACENT SURFACES. SPRINKLER HEADS SHALL NOT BE PAINTED.
AUTOMATIC FIRE SPRINKLER SYSTEM NOTES
2" DRAIN TO TERMINATE
OUTSIDE 6" ABOVE
CONCRETE SLAB
FIRE PROTECTION LEGEND
EXISTING(E)
DESCRIPTIONABBRV.SYMBOL
(N) NEW WORK
POC POINT OF CONNECTION
POR POINT OF REMOVAL
FDC FIRE DEPARTMENT CONNECTION
DEMO DEMOLITION
FIRE SPRINKLER HEAD, CONCEALED PENDANT DOWN
FIRE SPRINKLER HEAD, SIDEWALL
FIRE SPRINKLER HEAD, UPRIGHT
SMOKE DETECTORSD
FIRE DEPARTMENT
CONNECTION
M1
MECHANICAL NOTES AND
DETAILS
1. THE CONTRACTOR SHALL INSPECT THE PROJECT SITE
BEFORE BIDDING AND PROCEEDING WITH THE
CONSTRUCTION.
2. THE CONTRACTOR SHALL NOTIFY AND COORDINATE WITH
THE CONTRACTING OFFICER FOR ANY MAJOR DEVIATIONS
OR DISCREPANCIES DISCOVERED IN THE PLANS AND
SPECIFICATIONS DUE TO UNFORESEEN OR VARYING FIELD
CONDITIONS.
3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO
COVER THE COMPLETE INSTALLATION OF SYSTEMS TO
FUNCTION AS DESCRIBED AND SPECIFIED. OMISSIONS IN
THE DRAWINGS, OR SPECIFICATIONS, OR THE OMISSION OF
DETAILS OF WORK, SHALL NOT RELIEVE THE CONTRACTOR
FROM PERFORMING SUCH OMITTED, OR INCORRECTLY
DESCRIBED DETAILS OF THE WORK, BUT SHALL BE
PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND
DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS. THE
CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER
VERBALLY OF SUCH OMISSIONS AND PROVIDE A WRITTEN
STATEMENT OF THE OMISSIONS WITHIN (5) WORKING DAYS
OF VERBAL NOTIFICATION.
4. THE CONTRACTOR SHALL VERIFY ALL CLEARANCES FOR
EQUIPMENT TO BE INSTALLED PRIOR TO ORDERING OF
EQUIPMENT AND NOTIFY THE CONTRACTING OFFICER OF
ANY INADEQUATE CLEARANCES OR CONDITIONS THAT WILL
PREVENT THE PROPER INSTALLATION, MAINTENANCE, AND
OPERATION OF THE EQUIPMENT.
5. PROVIDE SHOP DRAWINGS FOR THE LAYOUT OF
EQUIPMENT AND PIPING SHOWING COORDINATION OF ALL
WORK WITH ALL OTHER TRADES.
6. DRAWINGS DO NOT ATTEMPT TO SHOW EXACT DETAILS OF
PIPING. PROVIDE OFFSETS AS NECESSARY TO AVOID LOCAL
OBSTRUCTIONS OR INTERFERENCE WITH OTHER TRADES.
7. NEW PIPING SHALL BE INSTALLED WITHIN THE EXISTING
WALL AND CEILING PERFORATIONS. DRILLING NEW HOLES
IN EXTERIOR/INTERIOR WALLS OR CEILING IS NOT
PERMITTED. IF THE CONTRACTOR MUST DRILL A NEW HOLE
IN THE WALL/CEILING. SUBMIT A RFI FOR RESPONSE PRIOR
TO DRILLING THE HOLE. DO NOT DRILL HOLES IN BUILDING
FABRIC WITHOUT PRIOR APPROVAL.
8. REPAIR ANY DAMAGES TO EXISTING CONSTRUCTION
RESULTING FROM THE INSTALLATION. THE AREAS
REPAIRED SHALL MATCH THE ADJACENT SURFACES IN
TEXTURE AND COLOR.
9. PROVIDE ACCESS PANEL TO ALL CONCEALED VALVES,
DAMPERS, AND EQUIPMENT. COORDINATE THE LOCATION
OF ACCESS PANEL TO ENSURE THAT THE EQUIPMENT CAN
BE MAINTAINED ADEQUATELY.
10. PATCH AND PAINT ALL NEW EXPOSED WORK, COLOR TO
MATCH EXISTING SURFACES. PATCH AND PAINT ALL
EXISTING DISTURBED WORK, COLOR TO MATCH EXISTING
ADJACENT SURFACES, UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL PAINT THE PIPES AND FITTINGS IN A
SHOP OFFSITE UNDER A CONTROLLED ENVIRONMENT. NO
PAINTING SHALL BE ALLOWED INSIDE OF THE BUILDING. NO
EXTERIOR PAINTING WILL BE ALLOWED UNLESS
CONDITIONS ARE OPTIMAL. NUTS, BOLTS, PIPE THREADS,
VALVES, VALVE COVERS, GONGS, GAUGES, SWITCHES,
DAMPERS, SPRINKLER HEADS, AND OTHER MECHANICAL
COMPONENTS SHALL NOT BE PAINTED, AS PAINTING MAY
AFFECT THE OPERATION AND MAINTENANCE OF THE FIRE
SUPPRESSION SYSTEM.
GENERAL NOTES
FIRE SPRINKLER HEAD, PENDANT DOWN
WHEN A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE
THAN 4-HOURS IN A 24-HOUR PERIOD, THE AUTHORITY HAVING
JURISDICTION, AHJ, SHALL BE PERMITTED TO TO REQUIRE THE
BUILDING TO BE EVACUATED OR AN APPROVED FIRE WATCH TO BE
PROVIDED FOR ALL PORTIONS LEFT UNPROTECTED BY THE FIRE
PROTECTION SYSTEM SHUTDOWN UNTIL THE FIRE PROTECTION
SYSTEM HAS BEEN RETURNED TO SERVICE.
BASED ON THE ADOPTED FIRE CODE, NFPA 1, 2021.
16.1 GENERAL REQUIREMENTS
16.1.1 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
DEMOLITION OPERATIONS, INCLUDING THOSE IN UNDERGROUND
LOCATIONS, SHALL COMPLY WITH NFPA 241, STANDARD FOR
SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
OPERATIONS, AND THIS CHAPTER.
16.1.2 A FIRE PROTECTION PLAN SHALL BE ESTABLISHED WHERE
REQUIRED BY THE AHJ.
16.1.3 IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE ESCAPE
FACILITIES SHALL BE MAINTAINED AT ALL TIMES FOR THE USE OF
CONSTRUCTION WORKERS. ESCAPE FACILITIES SHALL CONSIST OF
DOORS, WALKWAYS, STAIRS, RAMPS, FIRE ESCAPES, LADDERS, OR
THE GENERAL PRINCIPLES OF NFPA 101, INSOFAR AS THEY CAN
REASONABLY BE APPLIED TO BUILDINGS UNDER CONSTRUCTION.
[101:4.6.101.2]
16.1.4 FIRE ACCESS ROADS PROVIDED IN ACCORDANCE WITH
18.2.3 SHALL BE PROVIDED AT THE START OF A PROJECT AND SHALL
BE MAINTAINED THROUGHOUT CONSTRUCTION.
16.3.5 STANDPIPES. IN ALL NEW BUILDINGS IN WHICH STANDPIPES
ARE REQUIRED OR WHERE STANDPIPES EXIST IN BUILDINGS BEING
ALTERED OR DEMOLISHED, SUCH STANDPIPES SHALL BE
MAINTAINED IN CONFORMITY WITH THE PROGRESS OF BUILDING
CONSTRUCTION IN SUCH A MANNER THAT THEY ARE ALWAYS READY
FOR USE. [241:7.6]
16.4.3.3.2.10 NO TEMPORARY STANDPIPES SHALL REMAIN IN SERVICE
UNTIL THE PERMANENT STANDPIPE INSTALLATION IS COMPLETE.
[241:8.7.4.2.10]
16.4.4 ALTERATION OF BUILDINGS
16.4.4.1 WHERE THE BUILDING IS PROTECTED BY THE FIRE
PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED
OPERATIONAL AT ALL TIMES DURING ALTERATION.
16.4.4.2 WHERE ALTERATION REQUIRES MODIFICATION OF A PORTION
OF THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE SYSTEM
SHALL BE KEPT IN SERVICE AND THE FIRE DEPARTMENT SHALL BE
NOTIFIED.
16.4.4.3 WHEN IT IS NECESSARY TO SHUT DOWN THE SYSTEM, THE
AHJ SHALL HAVE THE AUTHORITY TO REQUIRE ALTERNATE
MEASURES OF PROTECTION UNTIL THE SYSTEM IS RETURNED TO
SERVICE.
16.4.4.4 THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE
SYSTEM IS SHUT DOWN AND WHEN THE SYSTEM IS RETURNED TO
SERVICE.
16.4.4.5 ALL REQUIRED EXIT COMPONENTS SHALL BE MAINTAINED IN
ACCORDANCE WITH THIS CODE AS DEEMED NECESSARY BY THE AHJ.
16.4.4.6 FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE
MAINTAINED.
16.5.2 DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING
AND WELDING SHALL BE DONE IN ACCORDANCE WITH CHAPTER 41.
16.5.3 COMBUSTIBLE WASTE MATERIAL SHALL NOT BE BURNED AT
THE DEMOLITION SITE UNLESS APPROVED BY THE AHJ.
COMBUSTIBLE MATERIALS SHALL BE REMOVED FROM THE SITE AS
OFTEN AS NECESSARY TO MINIMIZE THE HAZARDS THEREFROM.
(SEE SECTION 10.11.)
16.5.4 WHERE IN THE OPINION OF THE AHJ THE DEMOLITION SITE IS
OF A HAZARDOUS NATURE, QUALIFIED PERSONNEL SHALL SERVE AS
AN ON-SITE FIRE WATCH.
FIRE DEPARTMENT NOTES
DRAIN WITH VALVE
FIRE SPRINKLER
RISER
UPRIGHT SPRINKLERS
IN ATTIC, TYP.
PENDANT
SPRINKLERS, TYP.
SIDEWALL
SPRINKLERS, TYP.
SD
SD
SD SDSD
SD
SD
SDSDSD
SD
SD
SD
SD
(E) SMOKE
DETECTORS TO
REMAIN (TYP)
FE
FE
FE
(E) FIRE EXTINGUISHER (TYP)
(E) FIRE ALARM PANEL
(E) FIRE ALARM
PULL STATION
UPRIGHT SPRINKLERS, TYP.
EDGE OF ROOF ABV
1 FLOOR PLAN - FIRE PROTECTION - DEMO
NOTES:
1. DEMO & REMOVE EXISTING FIRE SPRINKLER SYSTEM. NEW
SPRINKLER HEADS AND FIRE SPRINKLER PIPING TO USE
EXISTING WALL AND CEILING OPENINGS.
2. EXISTING SMOKE DETECTORS TO REMAIN.
M2
MECHANICAL DEMOLITION
PLANS
SD
SD
SD SDSD
SD
SD
SDSDSD
SD
SD
SD
SD
(N) DRAIN WITH VALVE
(N) FIRE SPRINKLER
RISER, SEE 1/M1
FOR DETAIL
(N) UPRIGHT SPRINKLERS
IN ATTIC, TYP OF 8
(N) CONCEALED PENDANT
SPRINKLERS, TYP.
(N) SIDEWALL
SPRINKLERS,
TYP.
(E) SMOKE
DETECTOR, TYP.
FE
FE
FE
(E) FIRE ALARM
CONTROL PANEL
(E) FIRE EXTINGUISHER, TYP
(E) SMOKE
DETECTOR IN ATTIC
(E) SMOKE
DETECTOR IN ATTIC
(E) FIRE ALARM
PULL STATION
(N) UPRIGHT SPRINKLERS
IN ROOMS, TYP OF 3
EDGE OF ROOF ABV
(N) SURFACE
MOUNTED FS PIPING
BELOW LANAI CEILING
(N) UPRIGHT
SPRINKLERS,
TYP OF 4
2" 1-1/2" 1-1/4" 1"
2-1/2" 3"
2"
1-1/4" 1"1-1/2"2"
1-1/4"2"2-1/2" 3"
3"
1-1/4"1-1/2"2"2"2-1/2"2-1/2"
1"
1"
1"1"
1"1"
1"
1" 1"
1"
1"
(N) PENDANT
SPRINKLERS,
TYP. OF 7
(N) CONCEALED PENDANT
SPRINKLERS, TYP.
1 FLOOR PLAN - FIRE PROTECTION - NEW
M3
MECHANICAL NEW PLANS
NOTES:
1. PROVIDE NEW SPRINKLER HEADS AS REQUIRED TO PROVIDE
ADEQUATE COVERAGE PER NFPA 13. REUSE EXISTING CEILING
AND WALL OPENINGS FOR FIRE SPRINKLERS AND FIRE
SPRINKLER PIPING.
2. EXISTING SMOKE DETECTORS TO REMAIN.
3. REPLACE PORTABLE FIRE EXTINGUISHERS WITH WALL BRACKET
MOUNTED 4A:80B:C UL LISTED 10 LB. MULTIPURPOSE DRY FIRE
EXTINGUISHER.
| T1 - Title Sheet |
| T2 - Project Info |
| A1 - Floor Plan |
| A2 - Reflected Ceiling Plan |
| A3 - Exterior Elevations |
| A4 - Building Sections |
| M1 - Mechanical Notes and Details |
| M2 - Mechanical Demolition Plan |
| M3 - Mechanical New Plan |
File details come from the government source that posted it. Updated .