B01_08_Sources_Sought-_Nimbus_Station_Service_Replacement_1.pdf
PDF 57 KB Posted
- Attached to
- Nimbus Station Service Replacement
- Solicitation number
- 140R2024Q0080
About this file
This document is a Sources Sought announcement from the Bureau of Reclamation for the Nimbus Station Service Replacement project. The work involves furnishing various electrical equipment, including a standby engine-generator, secondary unit substation, medium voltage switchgear, distribution panelboards, and motor control centers. The estimated cost of the project is $3.0 million, with a delivery location at the Nimbus Powerplant near Sacramento, California.
The Bureau is seeking responses from small businesses, including 8(a), HUBZone, service-disabled veteran-owned, and women-owned small businesses. Interested parties should provide information on their business, experience, and resources. The closing date for responses is April 19, 2024. The applicable NAICS code is 335314 with a small business size standard of 750 employees. The government may set this acquisition aside or proceed with an unrestricted solicitation based on the responses received.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
This announcement is to all Small Business, 8(a) Small Business, HUBZone Small Business, Service-Disabled Veteran-Owned Small Business and Women-Owned Small Business concerns that may be interested in performing a contract for the Mid-Pacific Region of the Bureau of Reclamation. The work to be performed is described below. Based upon response to this announcement, the Government may determine to set this acquisition aside or proceed with an unrestricted solicitation. The applicable North American Industry Classification System (NAICS) Code is 335314 and the related small business size standard is 750 employees. This notice is not a request for proposal and the information presented in this announcement will not obligate the Bureau of Reclamation in any manner. The estimated cost of this project is $3.0 million.
The delivery will be at Nimbus Powerplant located approximately 19.2 miles east of Sacramento, California in Sacramento County.
Interested parties should include the following information in their response:
(a) Business name, address, cage code, size classification based on NAICS size standard, socioeconomic classification (i.e. HUBZone; 8(a), etc.), and a point of contact;
(b) A positive statement of your intention to submit an offer for this solicitation as a prime contractor.
(c) Evidence of your experience performing work similar in type and scope to the work in this announcement within the last five years. The evidence should include: contract numbers, project titles, dollar amounts and points of contacts with telephone numbers. Please do not include more than three past projects; and
(d) Include attachments cataloging the company's equipment assets, personnel resources and financial resources that demonstrate company responsibility and capability to perform required work.
(e) If bonding is required, also provide evidence of your bonding capacity.
All interested parties are encouraged to respond to this notice, by e-mail to cseibure@usbr.gov not later than close of business on 04/19/2024. The information provided in this announcement is all information the Government has available at this time. There are no specifications, drawings, bid packages, or source lists available.
System for Award Management (SAM) applies to this procurement. Prospective contractors must be registered in the System for Award Management (SAM) prior to award. Lack of registration in the SAM database will make an offeror ineligible for award. Information on SAM registration can be obtained via the Internet at http://www.sam.gov
PRINCIPAL COMPONENTS OF WORK:
CLIN UPC Supplies Quantity Unit 1 61150200 Standby Engine-Generator 1 EA 2 61501000 Secondary Unit Substation 1 EA 3 61100200 Medium Voltage Metal-Clad Switchgear 2 EA 4 61100200 Distribution Panelboards 1 EA 5 61100200 600 Volt Motor Control Centers 2 EA
A. Furnish secondary unit substation including station service transformers, 480-volt station service lineup, associated protective relay systems, and associated instrumentation transformers:
1. D1A: 480-volt, 600 ampere bus lineup with motor control buckets, draw out breakers, and panelboards.
2. K1B and K1C: 300 kVA, 4.16 kilovolt-480 volt dry-type transformers.
3. 52C: 4.16 kilovolt, 2,000 ampere vacuum circuit breaker.
B. Furnish motor control centers (MCCs), associated protective relay systems, and associated instrumentation transformers:
1. N2A: 480-volt, 600 ampere heating and ventilating MCC.
2. MSA: 480-volt, 600 ampere miscellaneous power MCC.
C. Furnish metal-clad unit and station service breakers and associated instrument transformers:
1. U1A2 and U2A2: 4.16 kilovolt, 2,000 ampere unit breakers.
2. U1A3 and U2A3: 4.16 kilovolt, 2,000 ampere station service breakers.
D. Furnish 125-volt DC, 250 ampere distribution panelboards.
E. Drawings and Data:
1. Furnish required drawings and data.
File details come from the government source that posted it. Updated .