Text version
Audio‐booth Systems Request
Mini‐booth Requirements:
Eight (8) left hinge booths and eight (8) right hinge booths
Style Dimensions:
o 1st preference: Inside ‐ 28” x 36” x 65”, Outside ‐ 40” x 32” x 79”, Door ‐ 36” (on 40” wall), Lights – One (1) o 2nd preference: Inside ‐ 34” x 24” x 65”, Outside ‐ 39” x 29” x 79”, Door ‐ 24” (on 29” wall), Lights – One (1)
4” thick acoustic floor with two locking and two non‐locking casters
Wall panels constructed of Acoustic Systems’ Type 2, 2” thick panels, with electrostatic powder coat paint. Color – platinum preferred.
Pre‐wired jack panel containing 4 each 1/4” phono stereo plugs and a 1‐1/2” diameter pass‐ thru, with a cover plate.
Acoustically engineered integrated ventilation system
Double glazed, laminated, acoustical safety glass window on opposite of hinge side
Carpeting with cove base trim
Electrical service via 12 feet, 12‐volt power supply
Audio Test System:
Two (2) Computer Controlled Audiometer (CCA) systems w/ Fourteen (14) Audiometer
Expansions; Sixteen (16) Bio‐Acoustic Simulators o Compatible with DOEHRS‐HC audio testing system o Windows software functions for HIPAA security requirements o Automatic instructions, on‐screen audiogram graphs, automatic retests, programmable test sequences, full manual control, etc.
Database Management capability o Network database access o Automatic baseline revision o Customizable notification letters & hearing history questionnaire o Query Wizard o Daily calibration reports o OSHA 3074 (revised) hearing conservation compliance o Import/export capabilities to DOEHRS‐DR, data entry, and print capability
OSHA conservation compliance o Demographic/exposure data collection o STS calculation and recordable hearing loss o Bio‐acoustic simulator (daily biologic calibration checks) o Sound level meter for ambient noise level monitoring o Meets/exceeds ANSI S3.6 standard for audiometers
Additionally: MUST include freight and shipping, as well as on‐site installation at Camp Shelby