Attachment Two - Building 469 Cooling Tower Salient Characteristics.pdf

PDF 108 KB Posted

Attached to
B469 Cooling Tower Federal contract opportunity
Solicitation number
FA441826Q0008
Issued by
Department of the Air Force Air Mobility Command

About this file

This document is a Salient Characteristics specification for a federal procurement by the Department of the Air Force, Headquarters 628th Air Base Wing (AMC) at Joint Base Charleston, South Carolina, dated 11 December 2025.

The procurement concerns an Open Circuit Induced-draft Vertical Discharge Cooling Tower, specified as EVAPCO MODEL AT 29-4K21 or equivalent, for the FY26 HVAC(AB) B469 project. The cooling tower must be delivered to the government for installation and include a five-year parts and labor warranty with factory start-up and commissioning provided by a manufacturer representative. Key equipment requirements include design conditions of 95°F dry bulb and 80.7°F wet bulb, water inlet and outlet temperatures of 95°F and 85°F respectively, and a water flow rate of 1,418.1 gallons per minute. The tower must feature 316 stainless steel construction for both the cold water basin and upper components, a 5-probe electronic water level control package, stainless steel basin heaters with a heater package contactor, transformer and disconnect rated to 0°F, fan vibration switch, sump sweeper piping with high-flow eductors, fan motor shaft grounding rings, and VFD service-rated fan motors (Variable Frequency Drives not included). The equipment footprint is constrained to a maximum dimension of 9 feet by 23 feet.

View the file

Other files for this federal contract opportunity

Other files attached to B469 Cooling Tower, newest first.
File Type Posted
Attachment One - RFQ Pricing Sheet.pdf PDF
Attachment Three - Provisions and Clauses.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CUI

CUI

DEPARTMENT OF THE AIR FORCE

HEADQUARTERS 628TH AIR BASE WING (AMC)

JOINT BASE CHARLESTON SC

Salient characteristics

FY26 HVAC(AB) B469 Cooling Tower

Joint Base Charleston Air Base

South Carolina

11 December 2025

Salient characteristics:

Open Circuit Induced-draft Vertical Discharge Cooling Tower, EVAPCO MODEL AT 29-4K21 or equivalent

Delivered for Government installation.

Include 5 year Parts/Labor Warranty, Factory Start-up and Commissioning from Manufacturer Rep.

Equipment Requirements:

-Design conditions: 95°F db / 80.7°F wb -Water in/out: 95°F / 85°F -Water Flow: 1,418.1 gpm -316 stainless steel cold water basin -316 stainless steel upper -5-probe electronic water level control package -Stainless steel basin heaters, heater package contactor w/ transformer and disconnect (rated to 0°F) -Fan vibration switch -Sump sweeper piping (high flow eductors) -Fan motor shaft grounding rings -VFD service-rated fan motors (VFDs NOT included) -9’ x 23’ MAX DIMENSION footprint

Equipment Requirements:

File details come from the government source that posted it. Updated .