Attachment L - VOL4_1363603dwg9of9.pdf

PDF 5 MB Posted

Attached to
P475 Aircraft Maintenance Hangar
Solicitation number
N4008526R0148
Issued by

About this file

These documents are electrical design drawings for a Navy parking garage facility at MCAS Beaufort in South Carolina, specifically Volume 4 of the project specifications. The electrical plans cover a multi-floor parking structure with comprehensive electrical systems including lighting, power distribution, photovoltaic (PV) solar panel installation, lightning protection, and grounding systems.

Key details include a 253 kW PV solar system with 550 modules mounted on the canopy structure, utilizing a zero-export control system to prevent power feedback to the utility grid. The lighting design features energy-efficient LED fixtures with advanced control systems incorporating occupancy sensors, daylight harvesting, and dimming capabilities across different floor levels. The electrical infrastructure includes multiple panelboards (1PBLN1 and 1PBLN2), a 250 kW inverter, DC combiner boxes, and a sophisticated grounding and lightning protection system designed to meet NFPA 780 standards. The project is part of a larger Aircraft Maintenance Hangar complex, with electrical design prepared by BMF Earth engineers and drawings dated December 15, 2022, with modifications anticipated through October 2025.

View the file

Other files

File Type Posted
N4008526R0148_0009.pdf PDF
1363603Amend0006dwg_VOL 3 ARCHITECTURAL.pdf PDF
1363603Amend0006dwg_VOL 3 STRUCTURAL_1of2.pdf PDF
1363603Amend0005dwg_VOL 1_COMBINED.pdf PDF
Solicitation Amendment N4008526R0148_0005.pdf PDF
1363603Amend0005dwg_VOL 4_COMBINED.pdf PDF
1363603Amend0005dwg_VOL 3_COMBINED.pdf PDF
N4008526R0148-0003.pdf PDF
26R0148 P475 Site visit log_Redacted.pdf PDF
JandA ML-23-33 P475 Interior Finishes Brand Name or Equal_Redacted.pdf PDF
Attachment P - SECNAV 5512.pdf PDF
Attachment N - VOL6_1363603dwg2of10.pdf PDF
Attachment N - VOL6_1363603dwg4of10.pdf PDF
Attachment N - VOL6_1363603dwg9of10.pdf PDF
Attachment N - VOL6_1363603dwg8of10.pdf PDF
Attachment M - VOL5_1363603dwg2of2.pdf PDF
Attachment L - VOL4_1363603dwg1of9.pdf PDF
Attachment K - VOL3_1363603dwg4of11.pdf PDF
Attachment K - VOL3_1363603dwg9of11.pdf PDF
Attachment J - VOL1_1363603dwg4of14.pdf PDF
Attachment J - VOL1_1363603dwg11of14.pdf PDF
Attachment J - VOL1_1363603dwg5of14.pdf PDF
Attachment F - Individual Small Business Subcontracting Plan.pdf PDF
Attachment N - VOL6_1363603dwg5of10.pdf PDF
Attachment N - VOL6_1363603dwg6of10.pdf PDF
Attachment N - VOL6_1363603dwg7of10.pdf PDF
Attachment L - VOL4_1363603dwg7of9.pdf PDF
Attachment K - VOL3_1363603dwg3of11.pdf PDF
Attachment K - VOL3_1363603dwg11of11.pdf PDF
Attachment K - VOL3_1363603dwg1of11.pdf PDF
Attachment J - VOL1_1363603dwg7of14.pdf PDF
Attachment J - VOL1_1363603dwg3of14.pdf PDF
Attachment J - VOL1_1363603dwg1of14.pdf PDF
Attachment J - VOL1_1363603dwg2of14.pdf PDF
Attachment G - Price Proposal Form_P475.pdf PDF
Attachment A - PPI_P475 F35 Aircraft Maint Hanger.xlsx XLSX spreadsheet
Attachment C - Past Performance Questionnaire (PPQ).pdf PDF
Attachment D - Historical Small Business Utilization.pdf PDF
Attachment O - P475 RTA Specs VOL 1 OF 2.pdf PDF
Attachment N - VOL6_1363603dwg3of10.pdf PDF
Attachment N - VOL6_1363603dwg10of10.pdf PDF
Attachment M - VOL5_1363603dwg1of2.pdf PDF
Attachment L - VOL4_1363603dwg3of9.pdf PDF
Attachment L - VOL4_1363603dwg8of9.pdf PDF
Attachment K - VOL3_1363603dwg10of11.pdf PDF
Attachment K - VOL3_1363603dwg7of11.pdf PDF
Attachment K - VOL3_1363603dwg6of11.pdf PDF
Attachment J - VOL1_1363603dwg8of14.pdf PDF
Attachment J - VOL1_1363603dwg14of14.pdf PDF
Attachment J - VOL1_1363603dwg6of14.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LINE-VOLTAGE LIGHTING CONTROL DEVICES

NOTES:

1. ALL WIRING SHALL BE #12 AWG IN 1/2" CONDUIT, MINIMUM.

2. PROVIDE EQUIPMENT GROUNDING CONDUCTOR FOR ALL CIRCUITS.

48" AFF TO

CENTER, UON

SYMBOL DESCRIPTION MOUNTING

20A, 120/277V SINGLE POLE SWITCH, UON.

SUBSCRIPTS INDICATE THE FOLLOWING:

SWITCH LEG BEING CONTROLLEDa,b -

ABBREVIATIONS

A AMPERES

AFC

AFF

HV

AFG

INC

AIC

JB

ATS

KAIC

AWG

KV

BFC

KVA

BFG

KVAR

C

KW

CAB

KWH

CATV

LAN

CCTV

LED

CKT

LTG

CL

m

CLG

mm

CT's

MAX

CU

MCB

DISC

MCC

DWG

MCP

EA

MFR

EF

MIN

EMT

MISC

EQUIP

MTR

EUH

MTD

EWC

MTS

EWH

N.C.

EXH

N.O.

EXIST

NA

FA

NC

FLUOR

NEC

GEN

NFPA

GFI

PNL

GFGI

PVC

GFP

REC

RGS

GND

TEL

HGT

TYP

HOA

UON

HP

V

VAV

W

G

ABOVE FINISHED CEILING

ABOVE FINISHED FLOOR

HIGH VOLTAGE

ABOVE FINISHED GRADE

INCANDESCENT

AMPERES INTERRUPTING CAPACITY

JUNCTION BOX

AUTOMATIC TRANSFER SWITCH

KILO-AMPERES INTERRUPTING

CAPACITY

AMERICAN WIRE GAUGE

KILO-VOLTS

BELOW FINISHED CEILING

KILO-VOLTS-AMPERES

BELOW FINISHED GRADE

KILO-VOLTS-AMPERES REACTIVE

CONDUIT

KILO-WATTS

CABINET

KILO-WATT-HOURS

CABLE TELEVISION

LOCAL AREA NETWORK

CLOSED CIRCUIT TELEVISION

LIGHT-EMITTING DIODE

CIRCUIT

LIGHTING

CENTERLINE

METER

CEILING

MILLIMETER

CURRENT TRANSFORMERS

MAXIMUM

COPPER

MAIN CIRCUIT BREAKER

DISCONNECT(ING)

MOTOR CONTROL CENTER

DRAWING(S)

MOTOR CIRCUIT PROTECTOR

EACH

MANUFACTURER

EXHAUST FAN

MINIMUM

ELECTRICAL METALLIC TUBING

MISCELLANEOUS

EQUIPMENT

MOTOR

ELECTRIC UNIT HEATER

MOUNTED

ELECTRIC WATER COOLER

MOUNTING

ELECTRIC WATER HEATER

MANUAL TRANSFER SWITCH

EXHAUST

NORMALLY CLOSED

EXISTING

NORMALLY OPEN

FIRE ALARM

NOT APPLICABLE

FLUORESCENT

NURSE CALL

GROUND

NATIONAL ELECTRICAL CODE

ENGINE GENERATOR SET

NATIONAL FIRE PROTECTION

ASSOCIATION

GROUND FAULT INTERRUPTER

GROUND FAULT CIRCUIT INTERRUPTER

PANEL

GOVERNMENT FURNISHED,

GOVERNMENT INSTALLED

POLYVINYL CHLORIDE

GROUND

RECEPTACLE

HEIGHT

RIGID GALVANIZED STEEL

HAND-OFF-AUTOMATIC

TELEPHONE

HORSEPOWER

TYPICAL

UNLESS OTHERWISE NOTED

VOLTS

GFCI

GROUND FAULT PROTECTION

WAP

VARIABLE AIR VOLUME UNIT

WP

WATTS

XFMR

WIRELESS ACCESS POINTHVAC HEATING/VENTILATING / AIR

CONDITIONING WEATHER PROOF

MTG

TRANSFORMER

AHU AIR HANDLING UNIT

CH CHILLER

UH UNIT HEATER

VA VOLT-AMPERES

SF SUPPLY FAN

PANELBOARD DESIGNATION.

CIRCUIT DESIGNATION.

SYMBOL DESCRIPTION

CONDUIT AND CONDUCTORS

BRANCH CIRCUIT WIRING IN CONDUIT. 1/2"C - 2#12 + 1#12 GND UON. PROVIDE

ADDITIONAL SWITCHED CONDUCTORS OR TRAVELER CONDUCTORS FOR LIGHTING

CIRCUITS AS REQUIRED TO SUPPORT THE INDICATED SWITCHING.

HOMERUN TO PANELBOARD: 1PBLN1 - 1,3,5

GENERAL NOTES

A. INSTALL ALL EQUIPMENT AND DEVICES AT THE HEIGHT INDICATED. REFER TO ARCHITECTURAL

INTERIOR ELEVATIONS FOR SPECIAL MOUNTING HEIGHTS AND LOCATIONS OF ELECTRICAL AND

COMMUNICATIONS DEVICES. MOUNTING HEIGHTS AND LOCATIONS INDICATED ON

ARCHITECTURAL ELEVATIONS TAKE PRECEDENCE OVER OTHER MOUNTING HEIGHTS AND

LOCATIONS.

B. LUMINAIRE TYPES INDICATED AS FOLLOWS: UPPER CASE LETTER WITH NUMERAL DENOTES

FIXTURE TYPE (SEE LUMINAIRE SCHEDULE), LOWER CASE LETTER (IF SHOWN) DENOTES

SWITCHING ARRANGEMENT.

C. ALL MATERIALS AND EQUIPMENT WILL BE LISTED AS COMPLYING WITH THE APPLICABLE

STANDARDS OF UNDERWRITER'S LABORATORIES, INC OR OTHER APPROVED LISTING

AGENCIES.

D. CONDUCTOR AMPACITIES ARE BASED ON 60° C COPPER FOR #12 AWG THROUGH #1 AWG

CONDUCTORS. CONDUCTOR AMPACITIES ARE BASED ON 75° C COPPER FOR CONDUCTORS

LARGER THAN #1 AWG.

E. ALL CONDUIT SIZES ARE BASED ON ELECTRICAL METALLIC TUBING (EMT) WITH TYPE

THHN/THWN COPPER CONDUCTORS. ADJUST CONDUIT SIZE AS REQUIRED FOR OTHER

CONDUIT MATERIALS AND CONDUCTOR TYPES.

F. THE PANELBOARD SUPPLIER SHALL BE RESPONSIBLE FOR PROVIDING OVERCURRENT

PROTECTIVE DEVICES THAT ARE SELECTIVELY COORDINATED. REFER TO SPECIFICATION

SECTION 26 28 01.00 10 FOR REQUIREMENTS.

G. ADJUST MOUNTING HEIGHTS FOR CEILING MOUNTED EXIT SIGNS AS REQUIRED TO PROVIDE

PROPER VISIBILITY. PROVIDE PENDANTS WHERE REQUIRED TO LOWER MOUNTING HEIGHTS AS

REQUIRED TO COORDINATE WITH DROP SOFFITS THAT MAY OBSCURE THE EXIT SIGNS.

H. WHEN CONTRACTOR FURNISHED EQUIPMENT INCLUDING BUT NOT LIMITED TO ARCHITECTURAL

HARDWARE (I.E. WINDOW SHADES, OVERHEAD COILING DOORS AND GRILLS, POWER OPERATED

DOORS, ETC...) AND HVAC EQUIPMENT SIZE OR ELECTRICAL CHARACTERISTICS PROVIDED

DIFFERS FROM SIZE OR ELECTRICAL CHARACTERISTICS INDICATED OR SPECIFIED, MAKE ALL

NECESSARY ADJUSTMENTS TO ELECTRICAL BOXES, CONDUIT, WIRING, DISCONNECT DEVICES,

BRANCH CIRCUIT PROTECTION, AND RELATED ELECTRICAL DISTRIBUTION EQUIPMENT

INCLUDING ANY ELECTRICAL REDESIGN AS REQUIRED TO ACCOMMODATE EQUIPMENT

ACTUALLY PROVIDED.

I. PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR EACH 277V AND 120V BRANCH CIRCUIT, UON.

MULTIPLE 20A BRANCH CIRCUITS FROM THE SAME PANELBOARD MAY BE COMBINED IN A

SINGLE 1/2" CONDUIT HOME RUN, MAXIMUM OF (3) CIRCUIT PER HOME RUN.

J. SEE B4/PEP501 FOR EQUIPMENT IDENTIFICATION LABEL DETAIL.

K. SEE A4/PEP501 FOR MISCELLANEOUS EQUIPMENT IDENTIFICATION LABEL DETAIL.

L. PROVIDE DISCONNECTING MEANS FOR MISCELLANEOUS MOTOR LOADS AS REQUIRED BY NFPA

70.RELAY-BASED LIGHTING CONTROL DEVICES

NOTES:

1. REFER TO C1/PEL601 FOR RELAY-BASED CONTROL SYSTEM RISER DIAGRAM.

2. REFER TO SHEET PEL601 FOR RELAY PANEL SCHEDULES.

SYMBOL DESCRIPTION MOUNTING

RELAY PANEL. PANEL IDENTIFICATION INDICATES THE

FOLLOWING:

SURFACE AT 72"

AFF TO TOP.

PLRP1

LRP - LIGHTING RELAY PANEL

LRP 1

1,2,3...- SEQUENCE OF PANELS

DIGITAL INFRARED ONLY, OCCUPANCY SENSOR CONNECTED TO

RELAY-BASED LIGHTING CONTROL SYSTEM. SUBSCRIPTS

INDICATE THE FOLLOWING:

a,b - SWITCHLEG(S)

CEILING.

DIGITAL INTERIOR DAYLIGHT SENSOR CONNECTED TO RELAY-

BASED LIGHTING CONTROL SYSTEM. SUBSCRIPTS INDICATE THE

FOLLOWING:

a,b - SWITCHLEG(S)

CEILING.

EXTERIOR PHOTOCELL CONNECTED TO RELAY-BASED LIGHTING

CONTROL SYSTEM. AS INDICATED.

PE

DESCRIPTION SYMBOLSYMBOL

LUMINAIRES

NORMAL POWER.

BATTERY INVERTER

NORMAL POWER.

BATTERY INVERTER

BATTERY INVERTER IDENTIFICATION (TYPICAL FOR ALL FIXTURES)

WALL MOUNTED LUMINAIRE. WALL

PENDANT MOUNTED AREA LIGHT. CEILING

CEILING

EXIT SIGN. SHADED PORTION DENOTES FACE(S). DIRECTIONAL

ARROWS AS INDICATED.

CEILING OR

PENDANT

EXIT SIGN. SHADED PORTION DENOTES FACE(S). DIRECTIONAL

ARROWS AS INDICATED.

4" ABOVE TOP OF

DOOR FRAME TO

BOTTOM OF

FIXTURE

NOTES:

1. SEE LIGHTING FIXTURE SCHEDULE FOR FIXTURE TYPES.

2. OTHER FIXTURE DIMENSIONS AND SHAPES ARE AS INDICATED ON LIGHTING PLANS.

PENDANT MOUNTED INDUSTRIAL LUMINAIRE.

WALL MOUNTED LUMINAIRE. WALL

FCU/A

SYMBOL DESCRIPTION MOUNTING

EQUIPMENT CONNECTIONS

AS REQUIREDCONNECTION TO EQUIPMENT LEADS, TERMINAL STRIPS OR

CONTROL PANEL INCLUDING ALL CONDUCTORS, CONDUIT,

FLEXIBLE CONDUIT, JUNCTION BOXES, CONNECTORS, FITTINGS,

ETC., REQUIRED FOR PROPER CONNECTION. COORDINATE

EXACT LOCATION WITH THE SUPPLIED EQUIPMENT. SUBSCRIPT

INDICATES EQUIPMENT IDENTIFICATION.

E

SYMBOL DESCRIPTION MOUNTING

MISCELLANEOUS

KEY NOTE SYMBOL. 00

ELECTRICAL GROUND

CONDUCTOR CONNECTION

NA

NA

NA

MOUNTINGSYMBOL DESCRIPTION

POWER DISTRIBUTION

SURFACE MOUNTED PANELBOARD

SURFACE MOUNTED DISTRIBUTION PANELBOARD

GROUNDING BUS BAR, SUBSCRIPT INDICATES NAME.

REFER TO C1/PEP501 FOR DETAIL.

72" AFF TO TOP

72" AFF TO TOP

18" AFF TO TOP

600V, 3P, NON-FUSED DISCONNECT SWITCH. ALL DISCONNECT

SWITCHES SHALL BE NEMA 1 UNLESS OTHERWISE INDICATED.

SUBSCRIPTS INDICATE THE FOLLOWING:

30A - 3R -

30A 3R

72" AFF TO TOP

NEMA ENCLOSURE OTHER THAN NEMA 1 (3R, 4X, ETC...)

AMPERE RATING

FEEDER CONTINUATION SYMBOL

FEEDER REFERENCE

SHEET ON WHICH FEEDER IS CONTINUED

EQUIPMENT OR PANEL TO WHICH FEEDER IS CONNECTED

A1

OEP600

1PBLD1

SYMBOL DESCRIPTION

SINGLE LINE DIAGRAM

PANELBOARD. WHEN ADDITIONAL SYMBOL(S) ARE INCLUDED, THEY INDICATE

THE FOLLOWING:

1AHN1

CIRCUIT BREAKER WITH NUMBER OF POLES AND TRIP RATING AS INDICATED.

ADDITIONAL CIRCUIT BREAKER SUBSCRIPTS INDICATE THE FOLLOWING:

3P

100 A

PARALLEL CONNECTED SURGE PROTECTIVE DEVICE. SEE SURGE

PROTECTIVE DEVICE SCHEDULE ON SHEET PEP800.

SPD

MULTIFUNCTION DIGITAL POWER CIRCUIT MONITOR.

POWER TRANSFORMER WITH DELTA CONNECTED PRIMARY, WYE

CONNECTED SECONDARY AND RATING AS INDICATED.

M

ET - SOLID STATE ELECTRONIC TRIP CIRCUIT BREAKER WITH FIELD

ADJUSTABLE LONG TIME PICKUP, SHORT TIME PICKUP, SHORT TIME

DELAY, AND INSTANTANEOUS TRIP FUNCTIONS. INCLUDE ADJUSTABLE

GROUND FAULT PICKUP AND GROUND FAULT DELAY TRIP FUNCTIONS

WHERE GROUND FAULT PROTECTION IS INDICATED.

MAIN CIRCUIT BREAKER. SEE PANEL SCHEDULE FOR SIZE. IF

NOT PRESENT, PANELBOARD WITH MAIN LUGS ONLY.

ELECTRONIC TRIP CIRCUIT BREAKER INTEGRAL POWER MONITORING

METER. NUMBER OF POLES AND TRIP RATING AS INDICATED. METERING

IDENTIFICATION CODES AS FOLLOWS:

3P

ETM

100 A

L

L - LIGHTING LOADS

R - RECEPTACLE LOADS

M - HVAC LOADS

WIRING DEVICES

DESCRIPTION MOUNTING

18" AFF

SYMBOL

NOTES: ALL MOUNTING HEIGHTS ARE TO TOP, UON

SUBSCRIPTS FOR RECEPTACLES INDICATE THE FOLLOWING:

G - RECEPTACLE WITH INTEGRAL GFCI.

20A, 125V DUPLEX RECEPTACLE.

WP - RECEPTACLE WITH WEATHER RESISTANT MARKING (WR) MOUNTED IN A IN-

USE WEATHER PROOF ENCLOSURE.

+48"- MOUNT AT 48" AFF TO CENTER. OTHER MOUNTING HEIGHTS AS

INDICATED.

SYMBOL DESCRIPTION

LIGHTNING PROTECTION SYSTEM

LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR.

GL

DNP

A

B

STANDING SEAM METAL ROOF MOUNTED AIR TERMINAL. SEE C2/PEQ501 FOR

DETAIL.

ADHESIVE TYPE AIR TERMINAL MOUNTED ON PHOTOVOLTAIC CANOPY

STRUCTURE. SEE A4/PEQ501 FOR DETAIL. TYPE "B" AIR TERMINALS SHALL BE

24" TALL.

AIR TERMINAL.

SUBSCRIPTS INDICATE THE FOLLOWING:

LIGHTNING PROTECTION SYSTEM GROUND LOOP CONDUCTOR. BURY IN DIRECT

CONTACT WITH EARTH AT 24" BELOW FINISHED GRADE.

GROUND RODS BONDED TO GROUND LOOP CONDUCTOR. SEE A2/PEQ501 FOR DETAIL.

BONDING CONNECTION.

DOWN CONDUCTOR. SEE SHEET PEQ131 FOR REQUIREMENTS.

SOLID LINES INDICATE EQUIPMENT PROVIDED IN THIS CONTRACT.

SCREENED LINES INDICATE EXISTING EQUIPMENT.

LINE TYPE DESCRIPTION

LINE TYPES

DASHED LINES INDICATE EQUIPMENT REMOVED IN THIS CONTRACT.

HATCH LINES INDICATE EQUIPMENT REMOVED IN THIS CONTRACT.

POWER DISTRIBUTION EQUIPMENT CODES

1 P B L D 1

1,2,3 - SEQUENCE

N - NORMAL BRANCH

D - DISTRIBUTION PANEL (WHERE PRESENT)

L - 208Y/120V

FLOOR LEVEL

P - PARKING GARAGE

EQUIPMENT CODE:

BUILDING DESIGNATION:

B - BUILDING AREA

20A 120V RECEPTACLE BRANCH CIRCUIT

HOMERUN SCHEDULE

HOMERUN LENGTH CONDUCTOR SIZE

0-50 FEET #12 AWG COPPER

51-100 FEET

101-150 FEET

#10 AWG COPPER

#8 AWG COPPER

NOTES:

A. THE CONDUCTOR SIZES SHOWN ARE FOR THE PHASE, NUETRAL AND GROUND CONDUCTORS.

B. FINAL CONNECTIONS TO RECEPTACLES WILL BE #12 AWG COPPER MAXIMUM. PROVIDE

JUNCTION BOX ABOVE FINISHED ACCESSIBLE CEILING AS CLOSE AS POSSIBLE TO THE

RECEPTACLES SERVED FOR CONDUCTOR TRANSISTIONS.

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:4

P

M

As indicated

E

LE

C T

R

IC

A L

L E

G E

N D

A N

D A

B B

R E

V

IA

T

IO

N S

V

O L

U M

E

PEG001

RLW RLW KLM

12860393

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

1 3 4 5 6 7 8 9 10

A.2

B

C

C.8

D

PS101

STAIR 1

PS104

STAIR 4

PS103

STAIR 3

PS102

STAIR 2

P103

SOLAR INV

P104

ELEC

G1DG1DB G1DB G1D G1DB G1D G1DB G1D G1DB

G2D G2DB

G1DBG1D G1D G1DB G1D G1DB G1D G1DB G1D

G2DB G2DB

G2D

G2D G2DB

G2DBG2D G1DB G1DB G1D

G2DB

G1D G1DB

G2DBG2D

G1DB G1D

G1DG1DB G1DB G1D G1DB G1D G1DB G1D G1DB G1D G1DB

G1DB G1D G1DB G1D G1DB G1D G1DB G1D G1DB

H1B H1B

X1 X1

X1

H2B

H2B

H2B

G1D

G2DG2D

S1B S1B X1

G1DB

G1D

G1D

H1H1BH1

H2B

1c,1d,1e,1f 1e,1f 1e,1f,1g,1h 1g,1h 1g,1h,1i,1j 1i,1j 1i,1j,1k,1l,1m

1d 1d 1f 1f 1g 1g 1j 1j 1l 1l1d

1h

1n,1o 1n,1o,1p,1q 1q,1p 1p,1q,1r,1s 1r,1s 1r,1s,1t,1u 1t,1u 1t,1u

1s

1o1o 1o 1q 1q 1s 1s 1u

1n1n 1n 1p 1p 1r 1r 1t

X1 1c1c 1c 1e 1e 1g 1g 1j 1j 1k 1m

1c,1d

1n,1o

X1

G2D

1m

1m

1m

1m

1k

1k

1k

X1

1PBLN1-25

X1

(VIA PLRP1-9,10,11,12,13)

1v

1v

1v

P101

PARKING

S1B

S1B

S1B

S1B

S1B

S1B

W2DB

W2DB

W2DB

1PBLN1-14

1PBLN1-15

(VIA PLRP1-15)

(VIA PLRP1-51)

X1 X1

G2DB

G2DB

G2D

G2D

G2DB

G2D

G2D

G2DB

G2DB

G2D

G2DB

G2DB

G2DB

G2D

G2D

G1DB

1PBLN1-18

G2D

(VIA PLRP1-3,4,5,6,7,8)

1v,1w

1k,1m

1k,1m

1k,1m

1u

1a

1t 1a

1a

91b

1b 1v

1b

1b 1v

(VIA PLRP1-2)

(VIA PLRP1-1)

1o 1q 1u

1a

1c,1d

1b,1v 1w 1w,1y 1y

G1D

1w

G1DB

1w

G1D

1w

G1DB

1w

G1D

1y

G1DB

1y

G1D

1y

G1DB

1y

1j 1l

1a

SLOPE UP TO SECOND FLOOR DECK

12 12 12

12 12

(VIA PLRP1-22,23,24)

1PBLN1-13

1f1d

1b

1b 1b

1b 1b

1b 1b

1b 1b

1b 1b

1b1b

1b 1b

1a

1a 1a

1a

1a

1a 1a

1a 1a

X1

1PBLN1-2

(VIA PLRP1-14,15,16,17)

1PBLN1-5

(VIA PLRP1-18,19,20,21)

1PBLN1-4 1PBLN1-1

1PBLN1-19

P105

SPKLR

H1B

H1B

1PBLN1-30

= DAYLIGHT CONTROL ZONE (SEQUENCE CODE A)

= GENERAL CONTROL ZONE (SEQUENCE CODE B)

= DAYLIGHT TRANSITION CONTROL ZONE (SEQUENCE CODE C)

ZONE "1a"ZONE "1t"

ZONE "1y"

ZONE "1r"ZONE "1p"ZONE "1n"

ZONE "1b" ZONE "1v" ZONE "1w"

ZONE "1c" ZONE "1e" ZONE "1g" ZONE "1i"

ZONE "1k"

ZONE "1u"ZONE "1s"ZONE "1q"ZONE "1o"

ZONE "1d" ZONE "1f" ZONE "1h" ZONE "1j" ZONE "1l"

ZONE "1m"

SLOPE UP

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

KEY NOTES 00

SHEET NOTES:

NOTES:

0 10'

1/16" = 1'-0" GRAPHIC SCALE

20' 40' 60'

N

PLAN

NORTH

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:5

P

M

As indicated

P A

R K

IN

G

G A

R A

G E

LI

G H

T

IN

G P

LA

N

G

R O

U N

D F

L O

O R

PEL101

RLW RLW KLM

12860394

1/16" = 1'-0"A1

LIGHTING PLAN, GROUND FLOOR, OVERALL

A B

KEYPLAN

1 SEE A1/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

2 SEE A3/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

3 MOUNT FIXTURE AT 3" ABOVE TOP OF DOOR FRAME TO BOTTOM.

4 1/2"C - (2)#10 + (1)#10 GND.

5 3/4"C - (2)#8 + (1)#8 GND.

6 DAYLIGHT TRANSITION ZONE IN THIS AREA. LIGHTS IN DAYLIGHT TRANSITION

ZONE ARE EXEMPT FROM DAYLIGHTING CONTROL.

7 SEE C3/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

8 SEE C1/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

9 DAYLIGHT TRANSITION ZONE IN THIS AREA. LIGHTS IN DAYLIGHT TRANSITION

ZONE ARE EXEMPT FROM DAYLIGHTING CONTROL.

10 MOUNT FIXTURE AT 3" ABOVE TOP OF DOOR FRAME TO BOTTOM.

11 SURFACE MOUNT EXIT SIGN TO THE BOTTOM OF THE STRUCTURAL TEE UNIT

ABOVE.

12 LIGHTS ARE MOUNTED TO THE UNDERSIDE OF THE LEVEL 2 RAMP UP TO

LEVEL 3. SEE A1/PEL302 FOR LOCATION.

13 SEE A1/PEL302 FOR FIXTURE MOUNTING DETAIL. TYPICAL FOR ALL FIXTURES.

A. LIGHTING FIXTURES G1D AND G1DB WILL BE CONTROLLED VIA LIGHTING RELAY

PANEL "PLRP1" LOCATED IN ELECTRICAL ROOM P104. REFER TO SHEET PEL601

FOR RELAY PANEL SYSTEM WIRING DIAGRAM AND SCHEDULES.

B. ADJUST MOUNTING HEIGHTS FOR CEILING MOUNTED EXIT SIGNS AS REQUIRED

TO PROVIDE PROPER VISIBILITY. PROVIDE PENDANTS WHERE REQUIRED TO

LOWER MOUNTING HEIGHTS AS REQUIRED TO COORDINATE WITH STRUCTURE

THAT MAY OBSCURE THE EXIT SIGNS.

C. EXTERIOR LIGHTING FIXTURES WILL BE CONTROLLED VIA LIGHTING RELAY

PANEL "PLRP1" LOCATED IN ELECTRICAL ROOM P104.

D. PROVIDE AN UNSWITCHED PHASE CONDUCTOR TO ALL EMERGENCY BATTERY

BACK-UP LIGHTING FIXTURES AND EXIT SIGNS.

E. REFER TO SHEET PEG001 FOR LIGHTING FIXTURE SYMBOLS LEGEND. REFER TO

SHEET PEL701 FOR LIGHTING FIXTURE SCHEDULE.

F. ALL VACANCY SENSORS AND DAYLIGHT SENSORS IN THE PARKING GARAGE

WILL BE UL LISTED FOR EXTERIOR USE.

G. REFER TO DETAIL D2/PEL101 FOR LIGHTING CONTROL ZONES DIAGRAM.

NOT TO SCALE

D2

LIGHTING PLAN, GROUND FLOOR, OVERALL - LIGHTING CONTROL ZONES

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

A.2

B

C

C.8

D

G1DG1DB G1DB G1D G1DB G1D G1DB G1D G1DB G1D G1DB

G1DBG1D G1D G1DB G1D G1DB G1D G1DB G1D G1DB G1D

G1DG1DB

G1D G1DB

G3DBG1D G1D G1DB G1D

G1DB G1DB G1D G1DB

G1DBG1D G1DB G1D

G1DG1DB G1DB G1D G1DB G1D G1DB G1D G1DB G1D G1DB

G1DBG1D G1D G1DB G1D G1DB G1D G1DB G1D G1DB G1D

S1B

S1B S1B

X1

S1B

S1B X1 S1B

X1 S1B

2d,2e 2d,2e,2f,2g 2f,2g 2f,2g,2h,2i 2h,2i 2h,2i,2j,2k 2j,2k 2j,2k,2l,2n

2u,2v 2s,2t,2u,2v 2s,2t 2q,2r,2s,2t 2q,2r 2o,2p,2q,2r 2o,2p 2l,2m,2o,2p

2c,2d,2e

2b,2c

2b,2u,2v

2v2v 2v 2t 2t 2r 2r 2p 2p 2p 2m

2u2b 2u 2s 2s 2q 2q 2o 2o 2l 2m

2d2c 2d 2f 2f 2h 2h 2j 2j 2l 2n

2e2e 2e 2g 2g 2i 2i 2k 2k 2k 2n

2m

2m

2n

2n

2l

2l

2l

2l

X1

X1

X1

X1

X1 X2

2l

2l

P201

PARKING

1PBLN1-8

(VIA PLRP1-34,36,39,41)

(VIA PLRP1-35,37,38,40,42)

2r

2b

2n

S1B

PS201

STAIR 1

PS202

STAIR 2

PS204

STAIR 4

PS203

STAIR 3

X1

(VIA PLRP1-26,27,29,31,33,44,46)

(VIA PLRP1-28,30,32,43,45)

1y,2l

2l,2n

2l,2m

2c

2c

2b

2b

2d

2u

1PBLN1-22

(VIA PLRP1-25)

2m

2p2t

2k

1PBLN1-7

1PBLN1-6

2v

2e 2g 2i

2a

2a

G3D

2a

G3DB

2a

G3DB

2a

G3DB

2a

G3D

2a

G3D

2a

G3D

2a

G3D

2a

2c

SLOPE UP TO THIRD FLOOR DECK

1PBLN1-20

= DAYLIGHT CONTROL ZONE (CONTROL SEQUENCE A)

= GENERAL CONTROL ZONE (CONTROL SEQUENCE B)

= DAYLIGHT TRANSITION CONTROL ZONE (CONTROL SEQUENCE C)

ZONE "2a"

SLOPE UP

ZONE "2b"

ZONE "2c" ZONE "2d"

ZONE "2e"

ZONE "2f"

ZONE "2g"

ZONE "2h"

ZONE "2i"

ZONE "2j"

ZONE "2k"

ZONE "2p"

ZONE "2o"

ZONE "2r"

ZONE "2q"

ZONE "2t"

ZONE "2s"

ZONE "2v"

ZONE "2u"

ZONE "2l"

ZONE "2m"

ZONE "2n"

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

KEY NOTES 00

SHEET NOTES:

NOTES:

0 10'

1/16" = 1'-0" GRAPHIC SCALE

20' 40' 60'

N

PLAN

NORTH

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:0

P

M

As indicated

P A

R K

IN

G

G A

R A

G E

LI

G H

T

IN

G P

LA

N

S

E C

O N

D F

L O

O R

PEL102

RLW RLW KLM

12860395

1/16" = 1'-0"A1

LIGHTING PLAN, SECOND FLOOR, OVERALL

A B

KEYPLAN

1 SURFACE MOUNT EXIT SIGN TO THE BOTTOM OF THE STRUCTURAL TEE

UNIT ABOVE.

2 SEE A1/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

3 SEE A3/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

4 1/2"C - (2)#10 + (1)#10 GND.

5 DAYLIGHT TRANSITION ZONE IN THIS AREA. LIGHTS IN DAYLIGHT

TRANSITION ZONE ARE EXEMPT FROM DAYLIGHTING CONTROL.

6 SEE C1/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

7 SEE C3/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

8 LIGHTS ARE MOUNTED TO THE UNDERSIDE OF THE LEVEL 2 RAMP UP TO

LEVEL 3. SEE A1/PEL302 FOR LOCATION.

9 SEE B1/PEL502 FOR FIXTURE MOUNTING DETAIL. TYPICAL FOR ALL

FIXTURES.

NOT TO SCALE

D2

LIGHTING PLAN, SECOND FLOOR, OVERALL - LIGHTING CONTROL ZONES

A. LIGHTING FIXTURES G1D AND G1DB WILL BE CONTROLLED VIA LIGHTING RELAY

PANEL "PLRP1" LOCATED IN ELECTRICAL ROOM P104. REFER TO SHEET PEL601

FOR RELAY PANEL SYSTEM WIRING DIAGRAM AND SCHEDULES.

B. ADJUST MOUNTING HEIGHTS FOR CEILING MOUNTED EXIT SIGNS AS REQUIRED

TO PROVIDE PROPER VISIBILITY. PROVIDE PENDANTS WHERE REQUIRED TO

LOWER MOUNTING HEIGHTS AS REQUIRED TO COORDINATE WITH STRUCTURE

THAT MAY OBSCURE THE EXIT SIGNS.

C. EXTERIOR LIGHTING FIXTURES WILL BE CONTROLLED VIA LIGHTING RELAY

PANEL "PLRP1" LOCATED IN ELECTRICAL ROOM P104.

D. PROVIDE AN UNSWITCHED PHASE CONDUCTOR TO ALL EMERGENCY BATTERY

BACK-UP LIGHTING FIXTURES AND EXIT SIGNS.

E. REFER TO SHEET PEG001 FOR LIGHTING FIXTURE SYMBOLS LEGEND. REFER TO

SHEET PEL701 FOR LIGHTING FIXTURE SCHEDULE.

F. ALL VACANCY SENSORS AND DAYLIGHT SENSORS IN THE PARKING GARAGE

WILL BE UL LISTED FOR EXTERIOR USE.

G. REFER TO DETAIL D2/PEL101 FOR LIGHTING CONTROL ZONES DIAGRAM. 1

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

A.2

B

C

C.8

D

S1B

X3

X3

S1B X3

X3

G4DB

G4DB G4D G4DB G4D G4DB G4D G4DB G4D

G4D

G4D G4DB G4D G4DB G4DB G4D G4DB G4DG4DB G4DB

G4DB

G5DB

G5D

G5DB

G5D

G5DB

G5DB

G5D

G5DB

G5D

G5DB

G5DB G5D G5DB G5D G5DB G5D G5DB

G5D G5DB G5D G5DB

G5D

G5D

S1B

S1B

S1BS1B

S1B

G5DBG5DG5DB

S1B

1PBLN1-9

(VIA PLRP1-48)

G4D

SO1

SO1

SO1SO1

1PBLN1-10

1PBLN1-12

1PBLN1-11

(VIA PLRP1-50)

(VIA PLRP1-47)

(VIA PLRP1-49)

G4DG4DB G4DG4DB G4DG4DB G4DG4DB G4DB

G4D G4DB G4D G4DB G4D G4DB G4D

PE

111111111

1111111

11111111

11111111111

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

KEY NOTES 00

SHEET NOTES:

NOTES:

0 10'

1/16" = 1'-0" GRAPHIC SCALE

20' 40' 60'

N

PLAN

NORTH

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:1

P

M

1/16" = 1'-0"

P A

R K

IN

G

G A

R A

G E

L

IG

H

T

IN

G P

LA

N

T

H

IR

D F

L O

O R

PEL103

RLW RLW KLM

12860396

1/16" = 1'-0"A1

LIGHTING PLAN, THIRD FLOOR, OVERALL

A B

KEYPLAN

1 MOUNT FIXTURE TO THE BACK OF THE PHOTOVOLTAIC SUPPORT

STRUCTURE. MOUNT AT 9'-0" ABOVE LEVEL 3 FINISHED FLOOR,

2 1/2"C - (2)#10 + (1)#10 GND.

3 SEE C3/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

4 SEE C1/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

5 BUILDING MOUNTED PHOTOCELL CONNECTED TO LIGHTING CONTROL PANEL

"PLRP1" LOCATED IN ELECTRICAL ROOM P104. ORIENT NORTH. MOUNT

PHOTOCELL ON EXTERIOR WALL AT 12" BELOW TOP OF WALL TO TOP OF

DEVICE.

6 3/4"C - (2)#8 + (1)#8 GND.

7 1/2"C - (2)#10 + (1)#10 GND.

8 SEE A3/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

9 SEE A1/PEL301 FOR MOUNTING HEIGHTS AND CIRCUIT INFORMATION.

10 MOUNT TO A JUNCTION BOX THATS SECURELY ATTACHED TO THE METAL

ROOF, TYPICAL.

11 MOUNT FIXTURE TO PRECAST CONCRETE BEAM. MOUNT AT 9'-0" ABOVE

LEVEL 3 FINISHED FLOOR,

A. LIGHTING FIXTURES G3D, G3DB, G4D AND G4DB WILL BE CONTROLLED VIA

LIGHTING RELAY PANEL "PLRP1" LOCATED IN ELECTRICAL ROOM P104. REFER

TO SHEET PEL601 FOR RELAY PANEL SYSTEM WIRING DIAGRAM AND

SCHEDULES.

B. PROVIDE AN UNSWITCHED PHASE CONDUCTOR TO ALL EMERGENCY BATTERY

BACK-UP LIGHTING FIXTURES AND EXIT SIGNS.

C. REFER TO SHEET PEG001 FOR LIGHTING FIXTURE SYMBOLS LEGEND. REFER TO

SHEET PEL701 FOR LIGHTING FIXTURE SCHEDULE.

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

FIRST FLOOR

0' - 0"

ROOF

34' - 6"

THIRD FLOOR

23' - 0"

SECOND FLOOR

11' - 6"

S1B

S1B

S1B

S1B

S1B

S1B

1PBLN1- 21

1PBLN1- 21

1PBLN1- 21

1PBLN1- 21

1PBLN1- 21

1PBLN1- 21

X1

1PBLN1- 21

C.8D

FIRST FLOOR

0' - 0"

ROOF

34' - 6"

THIRD FLOOR

23' - 0"

SECOND FLOOR

11' - 6"

S1B

S1B

S1B

1PBLN1- 24

1PBLN1- 24

1PBLN1- 24

S1B

S1B

S1B

1PBLN1- 24

1PBLN1- 24

1PBLN1- 24

X1

1PBLN1- 24

D

FIRST FLOOR

0' - 0"

ROOF

34' - 6"

THIRD FLOOR

23' - 0"

SECOND FLOOR

11' - 6"

S1B

S1B

S1B

1PBLN1- 23

1PBLN1- 23

1PBLN1- 23

S1B

S1B

S1B

1PBLN1- 23

1PBLN1- 23

1PBLN1- 23

A

FIRST FLOOR

0' - 0"

ROOF

34' - 6"

THIRD FLOOR

23' - 0"

SECOND FLOOR

11' - 6"

S1B

S1B

S1B

S1B

S1B

S1B

1PBLN1- 26

1PBLN1- 26

1PBLN1- 26

1PBLN1- 26

1PBLN1- 26

1PBLN1- 26

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

0 1'

3/16" = 1'-0" GRAPHIC SCALE

5' 10' 15' 20'

N

PLAN

NORTH

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:2

P

M

3/16" = 1'-0"

P A

R K

IN

G

G A

R A

G E

S

T A

IR

S

E C

T

IO

N S

PEL301

RLW RLW KLM

12860397

3/16" = 1'-0"A1

STAIR 1 ELEVATION

3/16" = 1'-0"A3

STAIR 2 ELEVATION

3/16" = 1'-0"C1

STAIR 3 ELEVATION

3/16" = 1'-0"C3

STAIR 4 ELEVATION

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

FIRST FLOOR

0' - 0"

ROOF

34' - 6"

THIRD FLOOR

23' - 0"

SECOND FLOOR

11' - 6"G1D

G1DB

G1D

G1DB

G1D G1DB

G3DBG1DB G1DB G1D G1DB

G1D

G2DG2D

G5DB

G5DB

G2D

G3D G3DB

G1DB

A A.2 B C C.8 D

FIRST FLOOR

0' - 0"

ROOF

34' - 6"

THIRD FLOOR

23' - 0"

SECOND FLOOR

11' - 6"

G1D G1DB G2D G2DB G2DB G1D G1DB

G1D G1DB G1D G3DB G1DB G1D G1DB

G2D

G3DB

G4D G4DB

G4DB G4DG5DG5D

/3

/2

G3D

/3

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

KEY NOTES 00

NOTES:

0 10'

1/16" = 1'-0" GRAPHIC SCALE

20' 40' 60'

N

PLAN

NORTH

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:2

P

M

1/16" = 1'-0"

P A

R K

IN

G

G A

R A

G E

R

A M

P S

E C

T

IO

N

PEL302

RLW RLW KLM

12860398

1/16" = 1'-0"A1

PARKING GARAGE - SOUTH ELEVATION

1/16" = 1'-0"C1

PARKING GARAGE - WEST ELEVATION

1 FIXTURE MOUNTING IS TO BOTTOM OF FIXTURE. TYPICAL.

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

LED INDUSTRIAL STRIP

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR

RIGIDITY AND SPECULAR ALUMINUM OR HIGHLY-REFLECTIVE PAINTED STEEL

REFLECTORS. 4FT LENGTH.

2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH

HIGH-REFLECTANCE, WHITE POLYESTER POWDER COAT, PAINTED AFTER FABRICATION.

3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 60K HOURS RATED LIFE AT L90,

4000K CCT UON, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING

TOLERANCE FOR COLOR CONSISTENCY, AND MINIMUM EFFICACY OF 100 LUMENS/WATT.

EMERGENCY LUMEN OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.

LUMINANCE OF LESS THAN 650 cd/ft2 BETWEEN 45 AND 90 DEGREES FROM NADIR.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,

OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC

DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.

5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.

COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED

WITH EMERGENCY BATTERY BACK-UP.

6. MOUNTING - SURFACE ON CEILING OR SUSPENDED.

7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE

THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

WALL MOUNTED LED

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL OR ALUMINUM, WITH REINFORCEMENT

RIBS FOR RIGIDITY; END CAPS SAME MATERIAL AS HOUSING, SECURED WITH TABS,

SCREWS, OR RIVETS. WHITE ENAMEL FINISH APPLIED AFTER FABRICATION.

4FT LENGTH.

2. LENS - ACRYLIC PRISMATIC OR WHITE OPAL TO PROVIDE EVEN ILLUMINATION AND TO

ELIMINATE PIXILATION FROM LED LIGHT SOURCE.

3. LIGHT SOURCE - SOLID STATE LEDS WITH MINIMUM 60K HOURS RATED LIFE AT L70,

4000K CCT, MINIMUM 80 CRI, MAXIMUM 4-STEP MCADAM ELLIPSE BINNING

TOLERANCE FOR COLOR CONSISTENCY, AND MINIMUM EFFICACY OF 90 LUMENS/WATT.

INITIAL LUMEN OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE.

4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,

OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, < 20% TOTAL HARMONIC

DISTORTION. ON-OFF CONTROL, STEP-DIMMABLE OR FULLY DIMMABLE AS INDICATED.

5. CERTIFICATION - UL 1598, DAMP LOCATION, DLC QUALIFIED, AND ROHS COMPLIANT.

COMPLIES WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED

WITH EMERGENCY BATTERY BACK-UP.

6. MOUNTING - SURFACE.

7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE

THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-CAST ALUMINUM WITH INTEGRAL, SELF-CLEANING HEAT SINK FINS, RIBS, OR EQUIVALENT PASSIVE COOLING MECHANISM. HEAT SINK SHALL BE INCORPORATED

DIRECTLY INTO HOUSING TO ENSURE MAXIMUM HEAT TRANSFER AND DISSIPATION.

2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED IN SILVER BAKED-ON POLYESTER

POWDER COAT. FINISH SHALL PASS 2500 HOUR SALT SPRAY TEST PER ASTM B117.

3. POWER SUPPLY/LED DRIVER - CLASS 1 DRIVER SHALL OPERATE AT 120/277V, 50/60 HZ;

OTHER VOLTAGES OPTIONAL. POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20%

AT FULL LOAD. MINIMUM EFFICACY SHALL BE 70 LM/W AT MAXIMUM 600 mA OPERATING

CURRENT.

4. LED OPTICAL ASSEMBLY - NUMBER OF LED ARRAYS SHALL VARY TO ACCOMMODATE

DESIRED LUMINAIRE OUTPUT. PROVIDE WITH EQUIVALENT NEMA DISTRIBUTION TYPE AS

INDICATED ON FIXTURE SCHEDULE. BUG UPLIGHT RATING OF U0, WITH BACKLIGHT AND

GLARE RATINGS AS DETERMINED BY LIGHTING ZONE INSTALLED. MINIMUM COLOR

RENDERING INDEX (CRI) SHALL BE 70 FOR CORRELATED COLOR TEMPERATURE (CCT) OF

4000-4500 DEGREES K. MAXIMUM BUG RATING OF B3-U0-G2.

5. SURGE PROTECTION - 6 kV MINIMUM, COMPLIANT WITH ANSI C62.41.2.

6. CERTIFICATION - UL AND/OR ETL LISTED, MINIMUM IP65 RATED PER ANSI/IEC 60529, AND RoHS COMPLIANT.

7. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETY GRAPHIC REPRESENTATION OF A

LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS AND IS NOT INTENDED TO

INDICATE A CERTAIN MANUFACTURER'S PREFERENCE. ALL DIMENSIONS ARE NOMINAL AND

VARY PER MANUFACTURER.

LED PARKING GARAGE LUMINAIRE

LUMINAIRE REQUIREMENTS:

1. HOUSING - DIE-CAST ALUMINUM WITH INTEGRAL PASSIVE COOLING MECHANISM.

HEAT SINK SHALL BE INCORPORATED DIRECTLY INTO HOUSING OR DRIVER

COMPARTMENT TO ENSURE MAXIMUM HEAT TRANSFER AND DISSIPATION.

2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER

POWDER COAT. FINISH SHALL PASS 2500 HOUR SALT SPRAY TEST PER ASTM B117.

DARK BRONZE FINISH.

3. POWER SUPPLY/LED DRIVER - CLASS 1 DRIVER SHALL OPERATE AT 120/277 VOLTS,

50/60 HZ; POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL

LOAD. MINIMUM EFFICACY SHALL BE 60 LM/W AT MAXIMUM 600mA OPERATING

CURRENT. MAXIMUM BUG RATING OF B1-U0-G2.

4. LED OPTICAL ASSEMBLY - PRECISION MOLDED ACRYLIC LENS PROVIDED FOR

MULTIPLE HIGH-POWERED LEDS PRODUCING NEMA DISTRIBUTION TYPE AS NOTED

ON FIXTURE SCHEDULE. BUG UPLIGHT RATING OF U0, WITH GLARE RATING AS

DETERMINED BY LIGHTING ZONE INSTALLED.

5. CERTIFICATION - UL AND/OR ETL LISTED FOR WET LOCATIONS, AND RoHS

COMPLIANT.

6. OTHER - THE ABOVE SKETCH IS A NON-PROPRIETY GRAPHIC REPRESENTATION OF A

LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS AND IS NOT

INTENDED TO INDICATE A CERTAIN MANUFACTURER'S PREFERENCE. ALL

DIMENSIONS ARE NOMINAL AND VARY PER MANUFACTURER.

LED WALL PACK

1.

2.

3.

4.

5.

LUMINAIRE REQUIREMENTS:

HOUSING - HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED THERMOPLASTIC. SINGLE

OR DOUBLE-FACED AS INDICATED.

LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. GREEN LETTERS AS

INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH

DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS

REQUIRED.

EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH

MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND TEST

SWITCH.

MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE

MOUNTING.

ILLUMINATION - PROVIDED GREEN HIGH-OUTPUT LEDS INSIDE OF FIXTURE HOUSING.

PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH FREQUENCY-MATCHED

SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.

CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.6.

LED EXIT SIGN

1.

2.

3.

4.

5.

LUMINAIRE REQUIREMENTS:

HOUSING - HIGH-IMPACT, UV-STABILIZED, POLYCARBONATE, HIGH-IMPACT

POLYCARBONATE LENS. SINGLE OR DOUBLE-FACED AS INDICATED.

LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. GREEN LETTERS AS

INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH

DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS

REQUIRED.

EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER WITH

MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND TEST

SWITCH.

MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE

MOUNTING.

ILLUMINATION - PROVIDED GREEN HIGH-OUTPUT LEDS INSIDE OF FIXTURE HOUSING.

PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH FREQUENCY-MATCHED

SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.

CERTIFICATION - UL LISTED AND CERTIFIED FOR WET LOCATIONS.6.

WET LISTED LED EXIT SIGN

LUMINAIRE REQUIREMENTS:

1. HOUSING - WEATHER RESISTANT STAINLESS STEEL. IP66/NEMA 4X RATED.

2.

3.

LED DRIVER - DRIVER SHALL OPERATE AT 120 VOLTS, 50/60 HZ; POWER FACTOR

GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL LOAD.

4.

OPTICAL ASSEMBLY - UV STABILIZED RED POLYCARBONATE LENS, RED LED.

5.

CERTIFICATION - UL AND/OR ETL LISTED FOR WET LOCATIONS, MEET OR EXCEED

FAA STANDARDS.

OTHER - THE ABOVE SKETCH IS A NON-PROPRIETY GRAPHIC REPRESENTATION OF A

LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS AND IS NOT

INTENDED TO INDICATE A CERTAIN MANUFACTURER'S PREFERENCE. ALL

DIMENSIONS ARE NOMINAL AND VARY PER MANUFACTURER.

SITE OBSTRUCTION LUMINAIRE

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F

ESSION L ENGIN

E E

R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:3

P

M

12" = 1'-0"

LI

G

H T

IN

G

F

IX

T U

R E

D E

T A

IL

S

PEL501

RLW RLW KLM

12860399

NOT TO SCALE

C2

FIXTURE DETAIL FOR H1, H1B, H2B

NOT TO SCALE

C3

FIXTURE DETAIL FOR S1B

NOT TO SCALE

C1

FIXTURE DETAIL FOR G1, G2, G3, G4, G5, G6

NOT TO SCALE

C4

FIXTURE TYPES W2DB

NOT TO SCALE

A1

FIXTURE DETAIL FOR X1, X2

NOT TO SCALE

A2

FIXTURE DETAIL FOR X3

NOT TO SCALE

A3

FIXTURE DETAIL FOR S01

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

6" (MIN.)

TEE BUTT JOINT

LOCATIONS (TYP.)

PROVIDE LIGHT

FIXTURE 6" OFFSET AT

ALL TEE BUTT JOINTS

(TYP.)

LIGHT FIXTURE

CENTERED IN TEE

LIGHT FIXTURE REVISED

LOCATION (TYP.)

TREADED INSERT PER

MANUFACTURER (TYP.)

J-BOX WITH FIXTURE

PENDENT SWIVEL BALL

SUPPORT (TYP.)

FIXTURE

MANUFACTURE

SUPPORT J-BOX (TYP.)

FIXTURE

MANUFACTURE

PENDENT SWIVEL BALL

SUPPORT (TYP.)

3/4" THREADED

RIGID CONDUIT

BOTTOM OF TEE

FIXTURE PENDENT MOUNT

EXIT

3/4"

THREADED

RIGID

CONDUIT

J-BOX

BOTTOM OF TEE OR BEAM

FIXTURE "EXIT" PENDANT

MOUNT

CONDUIT

STRAPS AS

REQUIRED

TEE SLOT

OPENING

BOTTOM OF TEE

FIXTURE PENDENT MOUNT

TEE SLOT

OPENING

SECTION A

DETAIL 1

NTS

DETAIL 1

EQEQ

A

A

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

CUI

CUI

C U

I

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:3

P

M

NTS

LI

G

H T

IN

G

F

IX

T U

R E

D E

T A

IL

S

PEL502

RLW RLW KLM

12860400

NTS

B1

PRECAST TEE FIXTURE MOUNTING ELEVATION

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

GROUND FLOOR

THIRD FLOOR

RM. P104

PE 5

PLRP1

3 5

120V

(REFER TO C2/PEP101)

RELAY PANEL CONTROL SEQUENCE CODES

CONTROL FUNCTIONSSEQUENCE

CODE

TIME CLOCK OCCUPANCY SENSOR DAYLIGHT SENSOR DIMMING

A

ON - ALL TIMES AUTOMATICALLY DIMMING

LIGHTS TO 30% OUTPUT

WHEN ADEQUATE DAYLIGHT

IS PRESENT.

AUTOMATIC DIM

IN RESPONSE TO

DAYLIGHT

SENSOR.

C

NOTES:

1. AUTOMATIC DAY LIGHT DIMMING WILL BE SMOOTH AND CONTINUOUS WITH A DIMMING RESPONSE TIME OF 30 SECONDS TO MAINTAIN

REQUIRED SPACE LIGHTING LEVEL WHILE AVOIDING RESPONSE TO TEMPORARY CONDITIONS SUCH AS PASSING CLOUDS.

AUTOMATICALLY REDUCE

LIGHTING POWER TO 30%

OUTPUT WHEN NO ACTIVITY

IS DETECTED WITHIN A

LIGHTING ZONE FOR NO

MORE THAN 10 MINUTES.

LIGHTING SHALL INCREASE

TO 100% OUTPUT UPON

DETECTION OF OCCUPANCY

IN A LIGHTING ZONE

D

ON - 15 MINUTES BEFORE DUSK N/A

PHOTOCELL

N/A

N/A

OVERRIDE ON IF

INADEQUATE

DAYLIGHT.

N/A

N/A N/A

AUTOMATICALLY TO 100%

OUTPUT DURING HOURS OF

DAYLIGHT.

AUTOMATICALLY DIMS TO

10% OUTPUT DURING HOURS

OF DARKNESS.

AUTOMATIC

DIMMING IN

RESPONSE TO

DAYLIGHT

SENSOR.

ON - ALL TIMES

B

ON - ALL TIMES AUTOMATICALLY REDUCE

LIGHTING POWER TO 30%

OUTPUT WHEN NO ACTIVITY

IS DETECTED WITHIN A

LIGHTING ZONE FOR NO

MORE THAN 10 MINUTES.

LIGHTING SHALL INCREASE

TO 100% OUTPUT UPON

DETECTION OF OCCUPANCY

IN A LIGHTING ZONE

N/AN/A N/A

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F

ESSION L ENGIN

E E

R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:4

P

M

As indicated

LI

G

H T

IN

G

C O

N T

R O

L D

IA

G

R A

M S

A N

D S

C H

E D

U L

E S

PEL601

RLW RLW KLM

12860401

NTS

C1

RELAY PANEL LIGHTING CONTROL SYSTEM CONNECTION DIAGRAM

1 LIGHTING CIRCUIT FROM LIGHTING BRANCH PANEL. SEE

FLOOR PLANS FOR CIRCUITS. (TYPICAL)

2 CONTROLLED LIGHT CIRCUIT TO FIXTURES. SEE FLOOR PLANS

FOR CIRCUITS. (TYPICAL)

3 TYPICAL DAYLIGHT SENSOR.

4 ROOF MOUNTED PHOTOCELL. SEE PEL103 FOR LOCATION.

5 1/2" CONDUIT WITH LOW VOLTAGE CONTROL WIRING AS

REQUIRED.

6 RELAY PANEL TO CONTROL EXTERIOR AND PARKING LIGHTING

FIXTURES.

7 TYPICAL OCCUPANCY SENSOR.

8 TYPICAL CONTROL STATION.

9 1/2" CONDUIT WITH LOW VOLTAGE WIRING AS REQUIRED TO

ADDITIONAL OCCUPANCY SENSORS AS INDICATED ON PLANS.

KEY NOTES: 00 (C1/PEL601)

RELAY PANEL NOTES:

1. RELAY PANEL, INCLUDING RELAYS, WILL HAVE A SHORT CIRCUIT CURRENT RATING OF 35,000A.

2. PROVIDE 6 SPACES PER RELAY PANEL FOR FUTURE RELAYS.

PLRP1 RELAY PANEL SCHEDULE

RELAY NUMBER

(SWITCH LEG)

CIRCUIT

LOAD DESCRIPTION

CONTROL

SEQUENCE CODE

(SWITCH LEG)PANEL CIRCUIT #

1(1a) 1PBLN1 19 LTG - FIRST FLOOR - EAST ENTRANCE C(1a)

2(1b) 1PBLN1 18 LTG - FIRST FLOOR - WEST ENTRANCE C(1b)

3(1c), 4(1d), 5(1e), 6(1f), 7(1g), 8(1h)

1PBLN1 4 LTG - FIRST FLOOR A(1d,1f,1h), B(1c,1e,1g)

9(1i), 10(1j), 11(1k), 12(1l), 13(1m)

1PBLN1 1 LTG - FIRST FLOOR A(1j,1l,1m), B(1i,1k)

14(1n), 15(1o), 16(1p), 17(1q)

1PBLN1 2 LTG - FIRST FLOOR A(1o,1q), B(1n,1p)

18(1r), 19(1s), 20(1t), 21(1u)

1PBLN1 5 LTG - SECOND FLOOR A(1s,1u), B(1r,1t)

22(1v), 23(1w), 24(1y) 1PBLN1 13 LTG - SECOND FLOOR - RAMP B(1v,1y,1w)

25(2a) 1PBLN1 22 LTG - SECOND FLOOR C(2a)

26(2b), 27(2c), 29(2e), 31(2g), 33(2i), 44(2t), 46(2v)

1PBLN1 7 LTG - SECOND FLOOR A(2b,2c,2e,2g,2i,2t,2v)

28(2d), 30(2f), 32(2h), 43(2s), 45(2u)

1PBLN1 6 LTG - SECOND FLOOR B(2d,2f,2h,2s,2u)

34(2j), 36(2l), 39(2o), 41(2q)

1PBLN1 8 LTG - SECOND FLOOR B(2j,2l,2o,2q)

35(2k), 37(2m), 38(2n), 40(2p), 42(2r)

1PBLN1 20 LTG - SECOND FLOOR A(2k,2m,2n,2p,2r)

47 1PBLN1 10 LTG - THIRD FLOOR D

48 1PBLN1 9 LTG - THIRD FLOOR D

49 1PBLN1 12 LTG - THIRD FLOOR D

50 1PBLN1 11 LTG - THIRD FLOOR D

51 1PBLN1 14 LTG - EXTERIOR D

52 1PBLN1 16 LTG - SITE LIGHTING D

53 1PBLN1 17 LTG - SITE LIGHTING D

54 1PBLN1 3 LTG - SITE LIGHTING D

55 1PBLN1 28 LTG - SITE LIGHTING D

M

O D

P

/2

M

O D

P

A N

D M

O D

P

/2

LICENSE

No 64299

STATE OF

FLORIDA

P

A

R O

F E

SSION L ENG

IN

E

E R

N

IC

HO

LAS G. ZUBRZYC

K

I

ENGINEERS + SURVEYORS

1 2 3 4 5

3 4 5

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

P -4

A

IR

C

R A

F T

M A

IN

T

E N

A N

C E

H A

N G

A R

V

O

LU

M E

P A

R K

IN

G

G A

R A

G E

O P

T

IO

N

D C

C O

R E

B E

A U

F O

R T

, S C

N O

R F

O

LK

, V A

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

M C

A S

B E

A U

F O

R T

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1363603

DRAWFORM REVISION: 25 AUGUST 2020

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

D

C

B

A

1 2

KTB / RLH

Approved by J. Scott Roberts, Asset Management Branch Head &

Supervisory Facility Planner, PWD

Beaufort, SC via email.

EJA

DSN

JAS

12/15/2022

A ut od es k D oc s:

//2

V

M F

A T

F

M ai nt en an ce

H an ga r/

F m ai nt

H an ga r_

P ar ki ng

F ac ili ty

-E L-

R V

T

.rv t

/6

/2

6:

:5

P

M

LI

G

H T

IN

G

F

IX

T U

R E

S C

H E

D U

L E

PEL701

RLW RLW KLM

12860402

LIGHTING FIXTURES SCHEDULE

FIXTURE

TYPE FIXTURE DESCRIPTION VOLTAGE LAMP LUMEN CCT CRI MOUNTING NOTES LOAD

DETAIL

REFERENCE

G1D 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, WIDE OPTICAL DISTRIBUTION, 2.5MIL BRONZE POWDER COAT FINISH,

STANDARD 0-10V DIMMING, AND IP66 RATING.

120V LED 3875 4000K 70 SUSPENDED SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. 28 VA C1/PEL501

G1DB 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, WIDE OPTICAL DISTRIBUTION, 2.5MIL BRONZE POWDER COAT FINISH,

STANDARD 0-10V DIMMING, AND IP66 RATING. PROVIDE WITH

EMERGENCY BATTERY.

120V LED 3875 4000K 70 SUSPENDED SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS.. PROVIDE INTEGRAL

BATTERY WITH 90 MINUTE RUN TIME.

28 VA C1/PEL501

G2D 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, WIDE OPTICAL DISTRIBUTION, 2.5MIL BRONZE POWDER COAT FINISH,

STANDARD 0-10V DIMMING, AND IP66 RATING.

120V LED 12500 4000K 70 SUSPENDED SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. 105 VA C1/PEL501

G2DB 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, WIDE OPTICAL DISTRIBUTION, 2.5MIL BRONZE POWDER COAT FINISH,

STANDARD 0-10V DIMMING, AND IP66 RATING. PROVIDE WITH EMERGENCY BATTERY.

120V LED 12500 4000K 70 SUSPENDED SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. PROVIDE INTEGRAL

BATTERY WITH 90 MINUTE RUN TIME.

105 VA C1/PEL501

G3D 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, WIDE OPTICAL DISTRIBUTION, 2.5MIL BRONZE POWDER COAT FINISH,

STANDARD 0-10V DIMMING, AND IP66 RATING.

120V LED 9500 4000K 70 SUSPENDED SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. 75 VA C1/PEL501

G3DB 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, WIDE OPTICAL DISTRIBUTION, 2.5MIL BRONZE POWDER COAT FINISH,

STANDARD 0-10V DIMMING, AND IP66 RATING. PROVIDE WITH EMERGENCY BATTERY.

120V LED 9500 4000K 70 SUSPENDED SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. PROVIDE INTEGRAL

BATTERY WITH 90 MINUTE RUN TIME.

75 VA C1/PEL501

G4D 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, DRIVE LANE ASYMMETRIC OPTICAL DISTRIBUTION, 2.5MIL SILVER

POWDER COAT FINISH, AND IP66 RATING. PROVIDE WITH INTEGRAL DIMMING OCCUPANCY

SENSOR. INTEGRAL CONTROLS SHALL BE PROGRAMMED SUCH THAT LIGHT OUTPUT IS AT

50% FULL BRIGHTNESS FROM DUSK TO DAWN, UNLESS MOTION IS DETEDCTED, WHICH SHALL

TRIGGER THE FIXTURE TO SWITCH TO 100% FULL BRIGHTNESS WITH A 10 MINUTE VACANCY

TIMEOUT.

120V LED 3300 4000K 70 WALL SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. AIM ASYMMETRIC

DISTRIBUTION TOWARDS CENTER OF DRIVE LANE.

29 VA C1/PEL501

G4DB 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, DRIVE LANE ASYMMETRIC OPTICAL DISTRIBUTION, 2.5MIL SILVER

POWDER COAT FINISH, AND IP66 RATING. PROVIDE WITH INTEGRAL DIMMING OCCUPANCY

SENSOR AND EMERGENCY BATTERY. INTEGRAL CONTROLS SHALL BE PROGRAMMED SUCH

THAT LIGHT OUTPUT IS AT 50% FULL BRIGHTNESS FROM DUSK TO DAWN, UNLESS MOTION IS

DETEDCTED, WHICH SHALL TRIGGER THE FIXTURE TO SWITCH TO 100% FULL BRIGHTNESS

WITH A 10 MINUTE VACANCY TIMEOUT.

120V LED 3300 4000K 70 WALL SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. PROVIDE INTEGRAL

BATTERY WITH 90 MINUTE RUN TIME. AIM ASYMMETRIC DISTRIBUTION TOWARDS CENTER

OF DRIVE LANE.

29 VA C1/PEL501

G5D 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, DRIVE LANE ASYMMETRIC OPTICAL DISTRIBUTION, 2.5MIL SILVER

POWDER COAT FINISH, AND IP66 RATING. PROVIDE WITH INTEGRAL DIMMING OCCUPANCY

SENSOR. INTEGRAL CONTROLS SHALL BE PROGRAMMED SUCH THAT LIGHT OUTPUT IS AT

50% FULL BRIGHTNESS FROM DUSK TO DAWN, UNLESS MOTION IS DETEDCTED, WHICH SHALL

TRIGGER THE FIXTURE TO SWITCH TO 100% FULL BRIGHTNESS WITH A 10 MINUTE VACANCY

TIMEOUT.

120V LED 4475 4000K 70 WALL SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. AIM ASYMMETRIC

DISTRIBUTION TOWARDS CENTER OF DRIVE LANE.

41 VA C1/PEL501

G5DB 18" DIAMETER X 4-13/16" DEEP PENDANT PARKING GARAGE FIXTURE WITH DIE-CAST

ALUMINUM HOUSING, DRIVE LANE ASYMMETRIC OPTICAL DISTRIBUTION, 2.5MIL SILVER

POWDER COAT FINISH, AND IP66 RATING. PROVIDE WITH INTEGRAL DIMMING OCCUPANCY

SENSOR AND EMERGENCY BATTERY. INTEGRAL CONTROLS SHALL BE PROGRAMMED SUCH

THAT LIGHT OUTPUT IS AT 50% FULL BRIGHTNESS FROM DUSK TO DAWN, UNLESS MOTION IS

DETEDCTED, WHICH SHALL TRIGGER THE FIXTURE TO SWITCH TO 100% FULL BRIGHTNESS

WITH A 10 MINUTE VACANCY TIMEOUT.

120V LED 4475 4000K 70 WALL SEE PEL302 AND PEL502 FOR MOUNTING HEIGHTS AND DETAILS. PROVIDE INTEGRAL

BATTERY WITH 90 MINUTE RUN TIME. AIM ASYMMETRIC DISTRIBUTION TOWARDS CENTER

OF DRIVE LANE.

41 VA C1/PEL501

H1 4' LENSED LED STRIP FIXTURE, 22-GAUGE DIE-FORMED STEEL WITH WHITE POLYESTER

POWDER COAT FINISH, 0.125" THICK FROSTED ACRYLIC LENS.

120V LED 3138 4000K 80 SUSPENDED SUSPEND AT 9'-0" AFF TO BOTTOM UON. FIXTURE SHALL BE UL LISTED AS A RACEWAY

SUITABLE FOR THROUGH WIRING.

22 VA C2/PEL501

H1B 4' LENSED LED STRIP FIXTURE, 22-GAUGE DIE-FORMED STEEL WITH WHITE POLYESTER

POWDER COAT FINISH, 0.125" THICK FROSTED ACRYLIC LENS. PROVIDE WITH EMERGENCY

BATTERY.

120V LED 3138 4000K 80 SUSPENDED SUSPEND AT 9'-0" AFF TO BOTTOM UON. FIXTURE SHALL BE UL LISTED AS A RACEWAY

SUITABLE FOR THROUGH WIRING. PROVIDE INTEGRAL BATTERY WITH 90 MINUTE RUN

TIME.

22 VA C2/PEL501

H2B 4' LENSED LED STRIP FIXTURE, 22-GAUGE DIE-FORMED STEEL WITH WHITE POLYESTER

POWDER COAT FINISH, 0.125" THICK FROSTED ACRYLIC LENS. PROVIDE WITH EMERGENCY

BATTERY.

120V LED 5858 4000K 80 SUSPENDED SUSPEND AT 9'-0" AFF TO BOTTOM UON. FIXTURE SHALL BE UL LISTED AS A RACEWAY

SUITABLE FOR THROUGH WIRING. PROVIDE INTEGRAL BATTERY WITH 90 MINUTE RUN

TIME.

22 VA C2/PEL501

S1B 4'L LED WALL DIRECT/INDIRECT FIXTURE WITH ALUMINUM ENCLOSURE, WHITE FINISH, AND

INTEGRAL OCCUPANCY SENSOR TO DIM TO 50% WHEN VACANT. PROVIDE EMERGENCY

BATTERY.

120V LED 6000 4000K 80 SURFACE SEE PEL301 FOR MOUNTING HEIGHTS. PROVIDE INTEGRAL BATTERY WITH 90 MINUTE RUN

TIME AT 25% BRIGHTNESS MINIMUM. UL LISTED FOR DAMP LOCATIONS.

42 VA C3/PEL501

SO1 4.6" DIAMETER ROUND RED LED OBSTRUCTION LUMINAIRE WITH UV STABILIZED

POLYCARBONATE LENS, SHOCK AND VIBRATION RESISTANT, STEADY OPERATION, WEATHER

AND CORROSION RESISTANT LAMP ASSEMBLY AND HOUSING, AND SELF-CONTAINED WIRING

COMPARTMENT.

120V LED SURFACE,

ON METAL

ROOF

OBSTRUCTION LIGHT SHALL MEET FAA REQUIREMENTS AND BE IP66/NEMA 4X RATED.

PROVIDE WITH PHOTOCELL AND BACKUP BATTERY FOR 12-HOUR OPERATION.

3 VA A3/PEL501

W2DB EXTERIOR WALL MOUNTED FIXTURE WITH DIE CAST ALUMINUM ENCLOSURE, IP66 RATED

HOUSING, 2.5MIL THICKNESS DARK BRONZE POWDER COAT FINISH, AND TYPE IV WIDE

DISTRIBUTION. PROVIDE WITH INTEGRAL DIMMING OCCUPANCY SENSOR AND EMERGENCY

BATTERY. INTEGRAL CONTROLS SHALL BE PROGRAMMED SUCH THAT LIGHT OUTPUT IS AT

50% FULL BRIGHTNESS FROM DUSK TO DAWN, UNLESS MOTION IS DETEDCTED, WHICH SHALL

TRIGGER THE FIXTURE TO SWITCH TO 100% FULL BRIGHTNESS WITH A 10 MINUTE VACANCY

TIMEOUT.

120V LED 6458 4000K 80 WALL MOUNTED AT 15'-0" AFG TO BOTTOM UON. 59 VA C4/PEL501

X1 SINGLE FACE LED EXIT SIGN WITH THERMOPLASTIC HOUSING, INTEGRAL NICKEL CADMIUM

BATTERY, GREEN LETTERS, AND SELF-DIAGNOSTICS.

120V LED N/A N/A N/A UNIVERSAL WHERE WALL-MOUNTED ABOVE DOOR, MOUNT AT 1" ABOVE DOOR FRAME TO BOTTOM OF

SIGN. UL LISTED FOR DAMP LOCATIONS.

2 VA A1/PEL501

X2 DOUBLE FACE LED EXIT SIGN WITH…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .