This is a Statement of Work (SOW) for the design, furnishing, installation, programming, integration, testing, commissioning, and documentation of ADA-compliant automatic door operator systems at the Denver ARTCC facility in Longmont, Colorado. The Base Bid work is mandatory for the West Control Room door, with two optional bid items for the East Control Room door and the M1 Room door from the Locker Room. Each door installation must be complete and independently operational. The contractor must provide all labor, supervision, engineering, programming, materials, equipment, tools, permits, transportation, testing equipment, safety equipment, and documentation necessary for a complete turnkey solution.
The automatic door operator systems must integrate seamlessly with the existing access control system, allowing designated badge holders to activate automatic door opening while permitting other authorized users manual operation. Each system must be commercial-grade, designed for approximately 1,200 cycles per day, and capable of continuous 24/7 operation while maintaining facility security, fire protection, life-safety requirements, and emergency egress capabilities. The work must comply with ADA, ABA, OSHA, NFPA, and FAA requirements. The contractor must conduct site investigations, develop and obtain Government approval of a Sequence of Operations, integrate with the existing access control system, install all required conduit and wiring, modify or replace door hardware as necessary, perform comprehensive testing and commissioning in the Government's presence, and provide deliverables including approved sequences of operations, as-built drawings, wiring diagrams, programming documentation, equipment manuals, warranty documentation, and training documentation. Normal work hours are Monday through Friday, 7:30 AM to 4:00 PM, with disruptive work on grave shift, and the period of performance must not exceed 45 days after Notice to Proceed. The contractor must maintain a clean work area, protect all Government property, and must be escorted by facility representatives at all times while on the facility campus.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF Work (SOW)
Automatic ADA Door Operator Installation
West Control Room Door Federal Aviation Administration
Denver ARTCC 2211 W. 17th Avenue Longmont, CO 80501
1.1 Objective
The objective of this project is to provide a complete turnkey solution for the design, furnishing, installation, programming, integration, testing, commissioning, and documentation of ADA-compliant automatic door operator systems at the Denver ARTCC.
Base Bid work must include the West Control Room door.
The Government may elect to award one or more optional bid items for additional automatic door operator installations identified in this SOO.
The completed installations must improve accessibility for authorized personnel while maintaining facility security, fire protection, life-safety, operational reliability, and access control requirements.
Each automatic door operator system must integrate with the existing access control system and permit designated badge holders to activate the automatic door opening feature while maintaining manual operation for other authorized users.
1.2 Location of Work
All work must be performed at:
Federal Aviation Administration Denver ARTCC 2211 W. 17th Avenue Longmont, CO 80501
1.3 Background
The West Control Room door is a secured interior door with an estimated usage rate of approximately 1,200 cycles per day. The existing door frame is recessed within structural concrete on the entrance side and is flush with acoustic wall panels on the interior.
The East Control Room door and the M1 Room door from the Locker Room are similarly secured interior doors that present comparable accessibility, security, and operational requirements.
The Government requires automatic door operator systems to accommodate personnel requiring accessible entry while maintaining existing security controls, fire protection, and operational requirements.
The Government seeks a complete turnkey solution. The Contractor may utilize the existing door assemblies and hardware or provide replacement door assemblies where necessary to meet the performance requirements identified herein.
1.4 Scope of Work
The Contractor must furnish all labor, supervision, engineering, programming, materials, equipment, tools, permits, transportation, testing equipment, safety equipment, documentation, and incidental items necessary to provide a complete and operational system.
The Base Bid must include all work necessary for the West Control Room door. Optional Bid Item No. 1 must include identical work for the East Control Room door. Optional Bid Item No. 2 must include identical work for the M1 Room door from the Locker Room. Each bid item must be complete and independently operational.
The Contractor must:
Conduct site investigations and field verification.
Design and provide a complete automatic door operator solution.
Coordinate with the Government-designated security contractor.
Integrate the system with the existing access control system.
Furnish and install all required conduit, wiring, power circuits, control circuits, relays, controllers, interfaces, sensors, and associated components required.
Modify existing hardware or replace the door assembly as necessary to meet performance requirements.
Develop and obtain approval of a Sequence of Operations prior to installation.
Perform testing, commissioning, training, and documentation.
Provide all warranties and closeout documentation.
1.5 Site Visit
OƯerors can attend a site visit prior to proposal submission.
Submission of a proposal constitutes acknowledgement that the OƯeror has verified field conditions, dimensions, electrical requirements, access control requirements, and installation constraints.
1.6 Performance Requirements
Each installed automatic door operator system must:
Integrate with the existing access control system.
Permit designated badge holders to automatically activate the door operator through the access control system.
Permit all other authorized badge holders to unlock the door while requiring manual operation.
Permit manual and/or automatic entry and egress.
Provide adjustable hold-open timing.
Include obstruction detection and anti-crush safety features.
Prevent injury to personnel during opening and closing cycles.
Be designed for approximately 1,200 cycles per day.
Be commercial-grade and suitable for continuous 24/7 operation.
Maintain security functionality.
Maintain emergency egress requirements.
Comply with ADA, ABA, OSHA, NFPA, FAA requirements, and all applicable
Federal, State, and local codes.
Operate during normal facility conditions with minimal disruption.
Allow manual operation during equipment failures or power outages as required by code.
1.7 Fire Protection Requirements
If the Contractor elects to replace the existing door, frame, or associated hardware, the replacement assembly must meet or exceed the existing fire rating and maintain all applicable fire protection and life-safety requirements.
1.8 Working Hours and Period of Performance
Normal work hours must be Monday through Friday between 7:30 AM and 4:00 PM excluding Federal holidays and maintenance moratoriums.
Disruptive work needs to be completed on grave shift
Work outside these hours must require prior Government approval.
Activities aƯecting Air TraƯic operations, access control systems, utilities, or facility operations must be coordinated in advance with the COR 14 day in advance.
Construction constraints, work-hour limitations, coordination requirements, escort requirements, and operational restrictions applicable to the Base Bid must apply equally to all awarded optional bid items.
Period of performance for the work described herein must be no more then 45 days after NTP.
1.9 Security and Cybersecurity Requirements
Contractors requiring site access must be escorted by facility designated representatives at all times while on facility campus.
The Contractor must coordinate all access control integration activities with the Government and Government-designated security contractor.
No equipment must be connected to FAA networks or information systems without written Government approval.
The Government must retain ownership and administrative control of all programming, software, licenses, and system configurations developed under this contract.
1.10 Submittals
Prior to procurement or installation, the Contractor must submit for FAA approval:
• Product data sheets
• Shop drawings
• Electrical drawings
• Access control integration drawings
• Sequence of Operations
• Project schedule
• Warranty information
• Safety plan
• High-cycle duty documentation
• Fire-rating documentation (if applicable)
1.11 Sequence of Operations
The Contractor must develop and submit a detailed Sequence of Operations for Government approval prior to installation.
The Sequence of Operations must describe:
• Standard badge-holder operation
• ADA-authorized badge-holder operation
• Exit operation
• Unlocking and relocking functions
• Automatic activation functions
• Safety device operation
• Fire alarm interaction
• Power failure operation
• System recovery operation
• Access control interfaces
• Controller logic and relay functions
1.12 Testing and Commissioning
Each awarded bid item must be independently tested, commissioned, and accepted by the Government prior to final project acceptance.
The Contractor must perform comprehensive testing and commissioning in the presence of the Government.
Testing must include all operational modes, safety functions, access control functions, power loss conditions, failure modes, and recovery modes.
Protection of Government Property
The Contractor must protect all Government property and repair any damage resulting from project activities at no cost to the Government.
1.13 Waste Removal and Cleanup
The Contractor must maintain a clean work area and remove all waste materials from the site at the end of each working shift.
FAA dumpsters must not be used unless specifically authorized.
1.14 Warranty Requirements
The Contractor must provide warranty documents at significant completion of contract performance in accordance with requirements in contract clauses.
1.14 Deliverables
The Contractor must provide:
• Approved Sequence of Operations
• Final Sequence of Operations
• As-built drawings
• Wiring diagrams
• Programming documentation
• Equipment manuals
• Warranty documentation
• Test reports
• Training documentation
1.15 Acceptance Criteria
Final acceptance must occur upon successful completion of the Base Bid and any awarded Optional Bid Items when:
• Installation is complete.
• Access control integration functions properly.
• Designated users can activate automatic operation.
• Standard users can manually operate the door after badge authentication.
• Safety systems function properly.
• Testing and commissioning are successfully completed.
• Documentation has been delivered and accepted.
• The installation complies with all requirements of this SOO.
1.16 Existing Conditions
West Control Room Door:
East Control Room Door:
M1 Door from Locker room:
Attachment A – Sequence of Operations Template
Attachment B – Existing Door and Access Control Information (if available)
ATTACHMENT A
SEQUENCE OF OPERATIONS TEMPLATE
Automatic ADA Door Operator Installation Door ___________________ Denver ARTCC OƯerors must complete and submit this template with their proposal. Information provided will be used by the Government to evaluate the proposed technical approach and system functionality.
1. Proposed Equipment Door Operator Manufacturer: __________________________ Model Number: ______________________________________ Duty Cycle Rating: ___________________________________ Expected Service Life: ________________________________ Door Hardware Manufacturer/Model: ____________________ Safety Sensor Manufacturer/Model: _____________________ Access Control Interface Equipment: ____________________ Power Requirements: _________________________________
2. Standard Badge Holder Entry Describe the sequence of operation when a standard authorized badge holder presents a valid credential.
3. ADA Authorized User Entry Describe the sequence of operation when an authorized badge holder presents a credential programmed to activate the automatic door operator.
Include:
• Unlock sequence
• Automatic operator activation
• Hold-open timing
• Door closing sequence
• Relocking sequence
4. Egress Operation Describe all methods of exiting the room.
5. Safety Features Describe all personnel protection features.
Include:
• Presence sensors
• Obstruction detection
• Reversal functions
• Entrapment protection
• Door closing protection
6. Power Failure Operation Describe system operation during loss of power.
7. Equipment Failure Operation Describe operation during equipment or controller failure.
8. Fire Alarm / Life Safety Operation Describe system operation during fire alarm conditions.
9. Adjustable Settings Opening Speed: ______________________________________ Closing Speed: ______________________________________ Hold Open Duration: __________________________________ Safety Sensitivity: ____________________________________ Other Adjustable Settings: _____________________________
10. Access Control Integration Describe interfaces with the existing access control system.
11. Preventive Maintenance Requirements
12. Testing Plan Describe testing procedures and acceptance verification.
Contractor Certification Company: ___________________________________________ Name: ______________________________________________ Title: _______________________________________________ Signature: ___________________________________________ Date: _______________________________________________
ATTACHMENT B
EXISTING DOOR AND ACCESS CONTROL INFORMATION
(To be completed by the Government if information is available) Facility:
Denver ARTCC Door Location:
Door ____________________________________ Existing Door Information Door Type: __________________________________________ Door Width: _________________________________________ Door Height: _________________________________________ Door Thickness: ______________________________________ Frame Type: _________________________________________ Fire Rating: _________________________________________ Door Swing Direction: _________________________________ Existing Hardware Lock Type: __________________________________________ Closer Type: _________________________________________ Exit Device Type: ____________________________________ Card Reader Type: ___________________________________ Request-to-Exit Device: _______________________________ Door Position Switch: _________________________________ Access Control System Information Access Control Vendor: _______________________________ Controller Type: ______________________________________ Badge Credential Type: _______________________________ Available Inputs: _____________________________________ Available Outputs: ___________________________________ Power Available at Door Location 120VAC Available: Yes / No Location of Power Source: _____________________________ Additional Information
Photographs Attached: Yes / No Drawings Attached: Yes / No
Prepared By: ________________________________________ Date: _______________________________________________