This document provides details for a federal contract solicitation to provide maintenance, inspection and repair services for oil/water separators. The solicitation is issued by the Department of the Army Materiel Command Army Contracting Command for work on oil/water separators within the United States Army Garrisons of Ansbach and Illesheim in Germany. The non-personal services contract requires the contractor to perform base operation and support services to standards specified in the performance work statement, including providing all personnel, equipment, supplies, transportation, tools and other items necessary. The contractor is responsible for supplying all parts for preventative maintenance orders and repair parts for demand maintenance orders.

View the file

Other files

File Type Posted
Attachment I - PWS - OWS Maintenance.pdf PDF
W912PB24R3007 OWS.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Abscheider Liste

OWS ID - TÜV ReportBldg.DPW TitleUseOWS ManufacturerOWS TypeNominal size (NS/NG)
[in l/s]Sludge Capacity (SF)
[in L]Oil Capacity (A)
[in L]Oil Layer Max
[in mm]Year BuiltAlarm system?Last Tightness TestTightness test passed?Repair after 2017Work after last testingCommentsDeficiencies
1#01_58015801/5802Airfield Retention Basin - Katterbach creekDywidag / BENE Aqua Pro ImplantatS-I-P2x100420011072005N/A1-May-17YES
2#02_58065806Helicopter wash rackDywidag PA II 2648S-I-P2036007501989N/A1-May-17NOInspection on 07DEC2020:

greyish-silver film on organic material

Reply from "Safeway de-icer" manufacturer pendingKarl Heinz's project M.0071505
3#03_58365836Vehicle Wash rackMall NeutraSpinS-I20500014232018YES1-Apr-18YES2FY17 Project?
4#04_58265826Motorpool, near ACPPassavant PA ll 2879S-I-P3x100=3001850044001981N/A9-Jul-05NOStructural condition too bad for further processing, no WA, No PS, BA leaking, SF joint joint construction defective, internal coating defective / no resistance to resistance according to DIN 1999-100 / 101 availableNeed replacement project
5#05_58405840Old MWR Scrap YardPassavant Coalisator CRB PA-II 4000S-I-P401000019001998NO9-Jul-05NONeed repair project or decommission
6#06_81338133AAFES Gas StationACO Oleomax Z-54.3.-486S-I-P619305762011YES9-Jul-05YES1Completed replacement in 2018
7#07_59255925Airfield Retention Basin - Milmersbach creekMall NeutraStarI-P80NA14692020YES1-Mar-20YES2Replacement complete early 2020
8#08_58095809in front of Fire Department baysBuderus Eurolizzer CI Z-54.8-78S-I-P1025005102001YES9-Jul-05NOReplacement complete
9#09_90329032South of vehicle maintenance facilityBene Mega Z-54.3.-399S-I-P625006562013YES9-Jul-05YES1Shaft coating completed 2019
10#10_59075907Bismarck Motorpool after retention basinBene Actron Z-54.3.397S-I-P2x301000014422013YES9-Jul-05YES1
11#11_52565256Barton next to Bldg. 5265Bene AquaProS-I-P2x1002500011072006YES9-Jul-05NODue to scheduled Barton closure - NO FUNDING AUTHORIZEDMust be officially closed
12#12_52535253Parade placeDywidag PA-II 2729S-II-P3x100=300360005615NAYES9-Jul-05NODue to scheduled Barton closure - NO FUNDING AUTHORIZEDMust be officially closed
13#13_52595259Old wash rackPassavant PARAT PA-II 2879S-II-P100340004400NANO9-Jul-05YESDue to scheduled Barton closure - NO FUNDING AUTHORIZEDRepair?Festgestellte Mängel:

-kein Probeentnahmeschacht -keine Warnanlage; keine Überhöhung -Waschfläche Fugen schadhaft (80 laufende Meter) -Nenngrösse nicht ausreichend Abscheideranlage wurde 2010 Grundsaniert.

14#14_80148014Wash rackACO PR-C-NST 90 Z-54.3.522S-I-P90500039782019YES11-Jul-05YES2Completed replacement in 2020
15#15_80308030Refueling Pad - MOUT siteBuderus Z-54.8-271S-I-P1510001502002YES9-Jul-05NONo future need - must be officially closed
OWS has it's own water discharge permit. After decommission, report to host nation for deleting the permit.Die Abscheideranlage ist undicht. Vorschlammfang nicht Beschichtet und Sanierungsbedürftig und in

Bestandsunterlagen nicht aufgenommen.

Festgestellte Mängel:

-undichtheit der Anlage -Sanierung dringend erforderlich -Warnanalage Batterie defekt

16#16_81098109Fire training areaMall NeutraSpinS-I20200014232017YES5-Dec-17YES2Replacement on 05-DEC-2017
17#17_81308130Auto skills centerBene SecuronS-I-P655009032012YES9-Jul-05NO1coating of dome shafts and tightness test completed on 26-OCT-2017
18#18_56715671Wash rack at IRP sitePassavant AKKUMATS-II-P832002001995YES9-Jul-05NOInspection on 10DEC2020:

Maintenance/Monthly inspection not regulary performed OWS must be emptied because it contains sewage check floater and repair if necessary WO request for "repair wash rack including OWS" keine Überhöhung -Anlage undicht Schwimmer nicht in Führung 19 #19_5773_Refuel 5773 Helicopter Refueling Pad Buderus Z-54816 S-I-P 20 5000 700 1999 YES 9-Jul-05 YES 1 Alarm system replaced including new solar panel Solar power not sufficient; often fuel in OWS Festgestellte Mängel:

- kein Probeentnahmeschacht

- Warnanlage nicht Funktionstüchtig 20 #20_5773_IRP 5773 Refueling Pad - MOUT site Buderus S-I-P 15 4000 1150 2002 YES 9-Jul-05 NO 1 Alarmsystem replaced including new solar panel; coating of dome shaft and tightness test completed on 20-Oct-2017 Solar power not sufficient; often fuel in OWS Festgestellte Mängel:

- Warnanlage ohne Funktion

- Abscheideranlage undicht Prüfresultat: nicht bestanden

21#21_FrankenK59Next to Bldg. 59 (old Bundeswehr Motor pool Bays)ACO Oleomax Z-54.8.364S-I-P66005122009YES9-Jul-05NOlast detailed inspection report from 31-MAY-2010Must be officially closed
22#22_65016501Helicopter wash rackDywidag PA II - 2648S-i-II-P40Sludge basin18803061991YES16-Nov-16YES1Renovation in 2010; Completed conversion to gravity feed 30-JUL-2020
23#23_65036503TASMO Blade ShopBENE ACTRON Z-54.3.-397S-I-P6126010682010YES9-Jul-05YES1coating of dome shaft and tightness test completed on 20-Oct-2017Schachtaufbauten nicht beschichtet

-Überhöhung nicht messbar, dafür Warnanlage -kein Typenschild 24 #24_6512 6512 B&G vehicle bay Passavant S-I-P 6 NA NA 1990 NO 9-Jul-05 NO Inspection on 10DEC2020:

OWS must be officially closed not tight, no floater, no montly inspection/maintenance

Must be officially closed!!!!
25#25_6512_416512/41MotorpoolBuderus PA-II3914S-I-P1253200059501995YES9-Jul-05YESInspection on 10DEC2020:

monthly inpection not regulary performed flushing lines defect and swimming in separator (see picture) Alarm box/flash light disconnected => must be checked sludge trap at 70 cm and must be emptied

NEEDS REPLACEMENT PROJECT!!!!
WO request for "replace of OWS 6512" but not including in Jared's projectFestgestellte Mängel:

-Einlaufschacht optisch Undicht -kein Typenschild Überhöhung nicht messbar.

Koaleszenzmaterial müsste gereinigt ggf. getauscht werden, da kein oder wenig durchfluss ist.

Einlaufschacht muss saniert werden, Rohrleitung nicht mitgeprüft.

26 #26_6645 6645 AAFES Gas Station Passavant Curator Z-54.5.67 S-I-P 10 2500 345 2018 YES 9-Jul-05 NO 1 coating of dome shaft and tightness test completed on 20-Oct-2017 Festgestellte Mängel:

-kein Typenschild -Schachtaufbauten Schadhaft (undicht) kein Diesel an der Tankstelle.

27 #27_6689 6689 Stripping yard Buderus Z-54.8.-16 S-I-P 20 9500 220 210.00 2001 YES 9-Jul-05 NO Need repair project Bemerkungen:

Überhöhung nicht messbar Anlage zu klein bemessen Abscheideranlage undicht.

28 #28_M293 M293 B-470 Retention Basin Bene AquaPro S-I-P 2x80 Retention basin 1107 2005 YES 9-Jul-05 YES 1 Need project to increase retention basin by 1 meter and OWS with 2x NG130 IAW new storm water permit for Storck Barracks Festgestellte Mängel:

- Schachtaufbauten Schlammfang SF 1002, SF 1004 unbeschichtet

29#29_TalgrabenAm TalgrabenAirfield Storm Water Retention basin to Talgraben creekDywidag PA-II-2729
Dywiday PA-II-3744S-I-II-P2x=50+100160005615/29401992/1991YES9-Jul-05YESNeed replacement projectFestgestellte Mängel:

- Schachtaufbauten unbeschichtet

- NS 100 Benzinabscheider zu NS 50 Koaleszenzabscheider parallel geschaltet keine gleichmäßige der NS entsprechende Durchströmung und Reinigungsleistung möglich.

Prüfresultat: nicht bestanden 30 #30_6633_MotorPool1 6633 Motorpool Buderus AvistoB/O PA-II-3914 S-I-P 125 20000 5950 1995 YES 9-Jul-05 YES Inspection on 10DEC2020:

undefined liquid in OWS, request lab analysis Oil in sludge trap but not in OWS Replacement design w/ Bauamt project. DPW-ENG PM Sven Wichmann Festgestellte Mängel:

- kein Typenschild

- Beschichtung Schachtaufbauten schadhaft 31 #31_6633 6633 "Hinter Zaun" Behind fence motor pool and hardstands Buderus Aristos Z54.8-286 S-I-P 200 22730 4020 155.00 1999 YES 9-Jul-05 YES Inspection on 10DEC2020:

coating sludge trap defect

32#32.1_6500east6500Geb. 6500 OstPOV wash rack and hangarBuderus Aristos-P PAII 3831S-I-P40725115001995NO9-Jul-05NOInspection on 10DEC2020:
check floater, seems to be too lightNeed replacement projectFestgestellte Mängel:

-keine Warnanlage; Überhöhung nicht messbar -Schlammfang nicht frei begehbar -kein Typenschild -Steigeisen im Koa -Schachtaufbauten optisch undicht.

- Schwimmer defekt -Anlage undicht -Anlage zu klein Bemessen Abscheider wurde nur über Rohrscheitel gefüllt. Schlammfang nicht Einsehbar, da Container darüber steht.

33#33_65026502south of archway to Fire Dept backyardDYWIDAG PA-II2648S-II-P62500NAYES9-Jul-05NOReplacement project awarded. Will be replaced 1 by 1, DPW-ENG PM Charles GoochReplacement project awarded. Will be replaced 1 by 1, DPW-ENG PM Charles Gooch
34#34_Rampe6512An der Rampesouth east corner of railheadBuderus Aristos PA-II3914S-I-P125250001251995YES9-Jul-05NONEEDS REPLACEMENT PROJECT!!!!
WO request but not including in Jared's projectFestgestellte Mängel:

- Schadhafte Innenbeschichtung

- Schadhaftes Koaleszenzmaterial 35 #35_6634washrack 6634 New washrack MALL NeutroSpin S-II-P 15 5000 (450mm) 1431 294 2019 YES 11-May-20 YES General inspection before initial use

Table 1

Apx: OWS and Drainage Area Field Assessment, AECOM 2019
InstallationBuildingTÜV Report #TÜV
Assessment dateTÜV Due dateOWS Site IDOWS Feature NameOWS
Operational StatusAECOM Field Assessment DateDrainage Area (DA) Details (Usage, Condition, Drainage towards*)Drainage Area [m²] (BENE Report 03/2018: Analysis of OWS Sizing)Drainage Area [m²] (AECOM field assessment, calculated in GIS)
KATTERBACH KASERNE09004 /
05801#01_580109.05.201709.05.2022GE43T09004_#01_5801GE43T09004_#01_5801inService25.03.2019Construction site RWRB, OW S downstream of RWRB. Concrete and asphalt surface in good condition with minor cracks. Drainage area is western part of air field. Drainage towards various drains.-121766
KATTERBACH KASERNE05806#02_580608.05.201708.05.2022GE43T05806_#02_5806GE43T05806_#02_5806inService26.03.2019Helicopter wash rack. Concrete surface in good condition with minor cracks. Drainage towards central drain ditch.840848
KATTERBACH KASERNE05836#03_583605.05.201705.05.2022GE43T05836_#03_5836_OWS002GE43T05836_#03_5836_OWS002inService14.10.2019W ash rack. Concrete surface in good condition. Drainage towards drain ditch at road entrance.-262
KATTERBACH KASERNE09009 /
05826#04_582604.05.201704.05.2022GE43T09009_#04_5826GE43T09009_#04_5826_BA1-1004 GE43T09009_#04_5826_BA2-1005
GE43T09009_#04_5826_BA3-1006inService25.03.2019MPOL 1+2+3 (close to 5824). MPOL3 connection to OW S in question. Concrete surface in good condition, repairs visible. Drainage towards several drainage ditches.59805638
KATTERBACH KASERNE05840#05_584004.05.201704.05.2022GE43T05840_#05_5840GE43T05840_#05_5840inService14.10.2019Parking lot. Concrete surface in good condition with minor cracks in surface and along joints. Some
curbstones broken or displaced. Drainage towards two drain lines.11551199
URLAS/SHIPTON KASERNE08133#06_813307.06.201707.06.2022GE89108133_#06_8133GE89108133_#06_8133inService26.03.2019Gas station. Concrete surface in good condition with minor stains. Drainage towards several drains.-185
KATTERBACH KASERNE05925#07_592512.05.201712.05.2022GE43T05925_#07_5925GE43T05925_#07_5925_KOA1001 GE43T05925_#07_5925_KOA1002inService25.03.2019RWRB. Drainage area is eastern part of air field. Concrete and asphalt surface in good condition with minor cracks. Drainage towards various drains.Nominal Size:
discharge of ret. basin (75 l/s)89846
KATTERBACH KASERNE05809#08_580908.05.201708.05.2022GE43T05809_#08_5809_OWS005GE43T05809_#08_5809_OWS005inService14.10.2019Fire department. Concrete surface with cracks along drains and rubber seams; rubber seams cracked or broken. Southern part of concrete surface possibly not connected to OW S.475392
BISMARCK KASERNE09032#09_903211.05.201711.05.2022GE43T09032_#09_9032GE43T09032_#09_9032inService26.03.2019Motor Pool: Interior wash rack. Concrete surface in good condition. Interior drainage towards central drain.-111
BISMARCK KASERNE05907#10_590711.05.201711.05.2022GE43T05907_#10_5907GE43T05907_#10_5907_KOA1_1003
GE43T05907_#10_5907_KOA2_1004inService25.03.2019Former Gas station. Concrete surface with cracks. Rubber seams in poor condition, some broken.
Vegetation partially growing in seam. Drainage towards SW .-26990
BARTON BARRACKS05256#11_525615.05.201716.05.2022GE07H05256_#11_5256GE43T05907_#10_5907_KOA1_1003
GE43T05907_#10_5907_KOA2_1004closed16.10.2019OW S in grassy area. Unknown usage, unknown drainage area. Planned to be decommissioned.will be decommissioned-
BARTON BARRACKS05253#12_525317.05.201717.05.2022GE07H05253_#12_5253GE07H05253_#12_5253_BA1002 GE07H05253_#12_5253_BA1003 GE07H05253_#12_5253_BA1004inService16.10.2019Parking lot. Interlocking pavers, some stones missing. Drainage towards various drain lines.will be decommissioned7041
BARTON BARRACKS05259#13_525915.05.201715.05.2022GE07H05259_#13_5259GE07H05259_#13_5259inService16.10.2019W ash rack. Concrete surface in good condition. Rubber seams in poor condition, some broken. Vegetation
partially growing in seam. Drainage towards central drain (Bldg. 5258).will be decommissioned183
URLAS/SHIPTON KASERNE08014#14_801409.05.201709.05.2022GE89108014_#14_8014_OWS009GE89108014_#14_8014_OW S009inService16.10.2019Vehicle washing at upper and lower wash rack. OW S downstream of RWRB. DA concrete surface in good condition. Drainage towards drain lines.-926
URLAS/SHIPTON KASERNE08030#15_803010.05.201710.06.2017GE89108030_#15_8030GE89108030_#15_8030closed17.10.2019Former wash rack at training area. Concrete surface in good condition. Vegetation growing along curbs. Drainage towards central drain.will be decommissioned266
URLAS/SHIPTON KASERNE08109#16_810910.05.201710.05.2022GE89108109_#16_8109GE89108109_#16_8109inService26.03.2019Fire department training area with two drainage areas. Concrete surface in good condition. Rubber seams
repaired in 2018. Drainage towards central drain line.-1137
URLAS/SHIPTON KASERNE08130#17_813010.05.201710.05.2022GE89108130_#17_8130GE89108130_#17_8130inService26.03.2019POV salvage yard at MWR car repair shop. Concrete surface in good condition. Drainage towards central
drain.-886
OBERDACHSTETTEN TNG AREA05671#18_567101.06.201701.06.2022GE61805671_#18_5671GE61805671_#18_5671inService27.03.2019W ash rack. Concrete surface in good condition. Rubber seams in poor condition, some broken.
Vegetation partially growing in seam. Cracked and displaced curbs with vegetation growing. Bay with central drain.8083
OBERDACHSTETTEN TNG
AREA05773 /
05759#19_5773_Refuel06.06.201706.06.2022GE61805773(5759Heli)_#19_5773_RefuelGE61805773(5759Heli)_#19_5773_RefuelinService27.03.2019Field fueling pad with two drainage areas (one for trucks, one for helicopters). Concrete surface in good
condition. Truck pad with dirt (soil) on surface and along seams. Drainage towards drains.-1275
OBERDACHSTETTEN TNG AREA05773#20_5773_IRP06.06.201706.06.2022GE61805773_#20_5773_IRPGE61805773_#20_5773_IRPclosed27.03.2019Training complex. OW S not operational. Concrete surface in good condition. Rubber seams with
vegetation growing in seam. Curbs cracked, vegetation growing. Drainage area with dirt (soil) from vehicles. Bay with central drain.-279
OBERDACHSTETTEN TNG
AREA00059#21_FrankenK07.06.201707.06.2022GE61800059_#21_FrankenK_OWS028GE61800059_#21_FrankenK_OWS028unknownNot assessedNot assessed-390
STORCK BARRACKS06710 /
06501#22_650115.11.2016no dataGE81A06710_#22_6501GE81A06710_#22_6501inService18.10.2019TASM-O wash rack. Concrete surface in good condition with minor cracks. Repairs along rubber seams
and along curbs. Drainage towards central ditch.16401716
STORCK BARRACKS06503#23_650327.06.201727.06.2022GE81A06503_#23_6503GE81A06503_#23_6503closedNot assessedSupply Support Activity: former rotor blade shop. Interior drainage area. Not assessed (contaminated site with restricted access).No exterior area connected63
STORCK BARRACKS06512#24_651217.05.2017no dataGE81A06512_#24_6512GE81A06512_#24_6512closed18.10.2019DPW. Interior wash rack / bay. Concrete surface in good condition.No exterior area connected, will be decommissioned36
STORCK BARRACKS06512#25_6512_4118.05.201718.05.2022GE81A06512_#25_6512_41GE81A06512_#25_6512_41inService18.10.2019Motorpool wash rack. Concrete surface in good condition, repairs visible. Drain contains debris (soil, leaves). Drainage towards central drain ditch.53505450
STORCK BARRACKS06645#26_664518.05.201718.05.2017GE81A06645_#26_6645GE81A06645_#26_6645inService27.03.2019AAFES Filling station / Gas station. Concrete surface in good condition (surface rebuilt in 2018).-141
STORCK BARRACKSR6694 /
06689#27_668901.06.201701.06.2022GE81A06694_#27_6689_StorageYardGE81A06694_#27_6689_StorageYardinService18.10.2019Storage Yard. Concrete in good condition. Vegetation growing along curbs. Drainage towards eastern edge
drain lines.13351324
STORCK BARRACKS06680#28_M-29309.06.201709.06.2022GE81A06680_#28_M-293GE81A06680_#28_M-293inServiceNot assessedAirfield fueling pad. Not assessed (within the airfield safety zone). Drainage area unknown (possibly parts of NW and SW Storck Barracks).--
STORCK BARRACKSUNK (6646)#29_Talgraben14.06.201714.06.2022GE81AUNK(6646)_#29_TalgrabenGE81AUNK(6646)_#29_Talgraben_KOA1001 GE81AUNK(6646)_#29_Talgraben_BA1002inService28.03.2019Retention pond at main gate. Concrete and asphalt surface in good condition with minor cracks. Drainage of Airfield.-196381
STORCK BARRACKS06633#30_6633_MotorPool108.06.201708.06.2022GE81A06633_#30_6633_MotorPool1GE81A06633_#30_6633_MotorPool1inService18.10.2019Motor Pool. Concrete surface in poor condition with cracks and patches. Rubber seams in poor condition,
some broken. Vegetation partially growing in seam. One central drain line. Drainage towards OW S north of building.1509515062
STORCK BARRACKS06633#31_663308.06.201708.06.2022GE81A06633_#31_6633GE81A06633_#31_6633inService18.10.2019Motor Pool: DA1: Interlocking pavers in good condition. Seams with minor cracks. Vegetation growing along curbs. Drainage towards two drain lines. DA2: Concrete surface in good condition with minor cracks and stains. Drainage towards two drain lines within the area.1867020760
STORCK BARRACKS06500#32.1_6500east30.05.201730.05.2022GE81A06500_#32.1_6500eastGE81A06500_#32.1_6500eastinService18.10.2019POV W ash Rack located north of Bldg. 6500. Concrete surface in good condition. Some leaves in corner. Three bays draining towards drain ditch along entrance of W ash Rack.162186
STORCK BARRACKS06500#32.2_6500west31.05.2017no dataGE81A06500_#32.2_6500west_OW S019GE81A06500_#32.2_6500west_OW S019closed18.10.2019TASM-O, former gas station. Concrete surface old but in good condition. Seams with minor cracks. Drainage towards two drain ditches.will be decommissioned776
STORCK BARRACKS06502#33_650231.05.201731.05.2022GE81A06502_#33_6502GE81A06502_#33_6502inService18.10.2019Motor Pool. Concrete surface in good condition. Some evidence of spills and stains. Drainage towards
central drain ditch.-5505
STORCK BARRACKS06512#34_Rampe19.05.201719.05.2022GE81A06512_#34_Rampe_OWS026GE81A06512_#34_Rampe_OWS026inService28.03.2019Motor Pool. DA1 (along bldg. 6512): Asphalt surface in poor condition: cracks, broken, large potholes, patches. DA2 (in road, next to train tracks): Asphalt surface with cracks. Drainage towards various drain
lines.49604978
Legend: OWS Oil / Water Seperator

DA Discharge / Drainage Area RWRB Rain Water Retention Basin

* Direction of Drainage as shown in Map 60589622 FY18 Katterbach Storm W ater

US titles

Nr.Loc.Bldg.useOil CapacitySludge capacityConstructionvessel forminlet depthuseparallel systemintroductionManufactureradmissionTypeyear builtSurfaceAlarm system available?Tightness testing passed?req. oil capreq sludge capPassed Gen inspection?
1Katterbach5801/02Fluplatz entw.20042002x - S-I-PRegenwasserxIndirektDywidag / BENE ImplantatAqua Prounbekannt / 2005unbefestigtjajaDrosselDrosselja
2Katterbach5806Helicopter Wash203600S-I-P1 x R 2,05x2,6008SchmutzwasserIndirektDywidagPA II 2648x1989unbefestigtneinnein3,5243524nein
3Katterbach5836Wash rack153000S-I-P1 x R 2,1*1,75
1 x R 2,1*2,208SchmutzwasserIndirektBuderusPA II 3834Kratos PIxbefestigtneinnein1,6044812nein
4Katterbach5826Motor Pool30018502xS-3xII5 x RE 2,13*4,78*1,9314RegenwasserxIndirektPasavantPA II 2879Parat1981unbefestigtneinnein17917904nein
5Katterbach5840Stripping Yard4010000S-I-P1 x R 2,75*2,50
1 x R 2,20*2,5012RegenwasserIndirektPasavantPA II 4000Coalisator CRB1998befestigtneinnein3,2253225nein
6Urlas8133US ARMY
Tankstelle61930S-I-P1 x R 1,50*1,6711VAWSIndirektACOZ-54.3-486Oleomax2011unbefestigtjaja1,0212042nein
7Katterbach5925Sewage Syst. Airfld30002x - S-I-Pje 1 x RE 2,24*13,80*307RegenwasserxDirektDywidagPA II 2729xxunbefestigt(Ja)neinDrosselDrosselnein
8Katterbach5809Wash Rack Firest.102500S-I-P1 x R 1,48*3,5008SchmutzwasserIndirektBuderusZ-54.8-78Eurolizer CI2001befestigtjanein3583580nein
9Katterbach9032Motor Pool62500S-I-P1 x R 1,5*1,51SchmutzwasserIndirektBENEZ-54.3-399MEGA2013befestigtjajaDrosselDrosselja
10Katterbach5907RRB6031200SF1-SF2+ 2x S-I-P2 x SF R 2,5*2,45
2 x KA Parralel R 2,50*2,453RegenwasserxIndirektBENEZ-54.3-397Actron2013befestigtjajaDrosselDrosselja
11Barton525620025000S-2xI-PImplantat BENE
SF RE 2,2*8,4*2,5523RegenwasserxIndirektDywidag / BENE ImplantatAqua Prounbekannt / 2005unbefestigt(Ja)neinDrosselDrosselnein
12Barton5253Parade Place30036000S-3xI-P4 RE 2,2*8,3*2,5522RegenwasserxIndirektDywidagPA II 2729xxbefestigtneinnein30030000nein
13Barton5259Wash rack10034000S-II-P1 X RE 2,1*3,6*2,208SchmutzwasserIndirektPasavantPA II 2879Paratxunbefestigtneinja17,44234884nein
14Shipton8014Wash rack8010000S-II-P1 x RE 2*5*2,5124SchmutzwasserIndirektDywidagPA II 2729x1986befestigtjaneinDrosselDrosselnein
15Urlas8030Refueling Havarie155000S-I-P1 R 2,7*2,408SchmutzwasserIndirektBuderusZ-54.8-271x2002befestigtjanein61200nein
16Urlas8109Fire Trng Area15228S-I-P1 x R 1,0*1,413SchmutzwasserIndirektBuderusZ-54.8-16Eurolizer CI1999befestigtjaja1,9782000nein
17Urlas8130/31ASF/Car Wash65500S-II-I-P1 R 1,5*208SchmutzwasserIndirektBENEZ-54.3-497SECURON2012befestigtjanein85000nein
18Oberdachstetten5671IRP-Site83200S-II-Pje 1 x R 1,75*215VAWSxxPassavantxAKKUMAT1995xneinnein258xnein
19Oberdachstetten5773Refueling Havarie205000S-I1 x R 2*2
1 x R 2,5*2,415VAWSindirektBuderusZ-54.8-161999befestigtjaja375375ja
20Oberdachstetten5773Weslach- hof154000S-I-P1 x R 2,5*2,51RegenwasserdirektBuderusxx2002befestigtjanein627627nein
21OberdachstettenFranken- kasernexxS-I-P1 x R 1*1,8808SchmutzwasserIndirektACOxxxunbefestigtjajaDrosselDrosselja
22Illesheim6501Helicopter Wash40xII-I-P1 x R 2,5*2,75
1 x R 2,5*3,7508SchmutzwasserDywidagPA II 2648x1991unbefestigtjajaDrosselDrosselnein
23Illesheim6503Motor Pool62500S-I-P1 x R 2*1,4508IndirektBENEZ-54.3-397ACTRON2010befestigtjaja2400ja
24Illesheim65126350S-II1 x R 0,6*1
1 x RE 0,72*0,35*0,71SchmutzwasserxPassavantxx1990unbefestigtneinnein34340nein
25Illesheim6512/41Motor Pool12532000S-I1 x Liegend 2,5*12,6008SchmutzwasserxBuderusPA II 3914x1995befestigtjaja15,55231104nein
26Illesheim6645AAFES
Tankst.102500S-I-P1 x R 1,8*208SchmutzwasserxPassavantZ-54.5-67Curatorxbefestigtjanein168168nein
27Illesheim6689Stripping Yard209500S-I-P1 x R 2,5x2,4
1 x R 1,2*1,408RegenwasserxBuderusZ-54.8-16x2001befestigtjanein2945880nein
28IllesheimM-293Überlauf- bahn16002 x S-I-Pje 1 x RE 2,2*5,3*2,48
1 x RE 2,2*9,6*315RegenwasserxDirektDywidag / BENE ImplantatxAqua Prounbekannt / 2005unbefestigtjajaDrosselDrosselja
29IllesheimAm Talgrab- en10016000S - I - P1 x RE 2,3*3*2,4

1 x RE 2,3*6*2,4

1 x RE 2,2*4,9*2,525xxxDywidagPA II 2729
PA II 3744BA NS 100
KA NS 501992
1991unbefestigtjaja150Drosselnein
30Illesheim6633Motor Pool 112520000S-I-P1 x Z 2,7*4,0
1 X Z 2,5*6,4521RegenwasserIndirektBuderusPA II 3914Avisto B/O1995unbefestigtjajaDrosselDrosselja
31Illesheim6633behind fence200xS-I-P1 x Z

2,7*9,10

1 x Z 2,7*9,102RegenwasserIndirektBuderusZ-54.8-286Aristos1999befestigtjajaDrosselDrosselja
32Illesheim6500 ostMotor Pool 24012000S-I-P1 x Z 1,8*3,9518RegenwasserxBuderusPA II 3831Aristos-P1995befestigtneinnein6012000nein
32Illesheim6500 WestMotor Pool 24016000S-II-P1 x RE 1,5*1,5*2RegenwasserxBuderusxxxbefestigtneinnein4959900nein
33Illesheim6502Motor Pool62500S-II-P1 x R 1,5*1,8
1 x R 1*1,2508SchmutzwasserxDywidagPA II 2648xxbefestigtneinnein2400nein
34IllesheimRampe12525000S-I-P2 x Z 2,5*12,615RegenwasserIndirektBuderusPA II 3914Aristos1995befestigtjanein2,2952295nein
* Sanierung ist hier eine Denkbare Mängelbehebungsvariante. Es ist zu empfehlen die Kosten der Sanierung und Kosten Austausch/Implantattechnik zu vergleichen und Stand: 18.07.2017
daraus zu entscheiden welche Ausführung die sinnvollste wäre. Auch bei Bedrachtung der Haltbarkeit der gewählten Ausführung.
Allgemein: Es ist noch zu klären ob nicht eine Emulsionsbehandlungsstufe an den Abscheideranlagen zu ergänzen ist. Hierzu fehlen Kundenseits noch Informationen PDF ist optimiert auf
zur Abwasserableitung vor Ort. Wir empfehlen einen vor Ort Besichtigungs und Besprechungstermin. DIN A3 im Querformat
Phase I - sofort beantragen
Phase II - FY18 beantragen
Phase III - FY19 beantragen
Stilllegung

In der Spalte Mängel aus dem Prüfbericht sind gegebenfalls die Hauptargumente für den Erforderlichen austausch angegeben.