This document provides drawings and specifications for concrete pads to be constructed at three locations for air monitoring shelter installations: the Buckner DOT (Oldham Co.) KYTC Maintenance Facility, the Lexington Primary (Fayette Co) Fayette County Health Department, and the Lexington Primary Nature Center. Each pad will be 10 feet by either 12 or 16 feet, with a 4-inch minimum thickness. The concrete will be 4,000 psi, with a rebar grid at 12-inch spacings, and the pads will be broom finished with a cure and seal application. Existing electrical poles will be used, with underground electrical lines run to the shelters. The document provides the latitude and longitude coordinates for each location.
The document does not include any pricing information, set-asides, incumbent contractors, funding requirements, or contract term details. It appears to be solely focused on the technical specifications and drawings for the concrete pad installations at the three designated sites.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment B - Bid Documents.pdf | ||
| Attachment C - MOVEit Instructions for Vendor.pdf | ||
| Final_RFB_785_2400000029_1_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Buckner DOT (Oldham Co.)
KYTC Maintenance Facility 1601 South Hwy 393 Buckner, KY. 40031
Concrete Slab for Air Monitoring Shelter
12 Feet
12 feet
(Drawing not to scale)
F ee t
In ch es
4/21/2023
• Gravel (#57 or equivalent) will be hauled on site and compacted for sub-base.
• Pad will be formed and ½” rebar grid at 12” spacings will be set to strengthen concrete.
• Grade 60 rebar or equivalent will be used.
• Rebar will be located 1 to 2 inches from the slab edge.
• 4000 psi concrete will be poured to a minimum thickness of 4”.
• Pad will be broom finished.
• Cure and seal will be applied to concrete once finished.
• Use existing Electrical pole and Electrical lines are to be run underground to shelter.
Buckner Shelter
Buckner-KYTC Maintenance Facility
Concrete Pad 10’x12’x4”
Lat: 38.4001911 Long: -85.444291
Use existing Electrical Pole lines are underground to shelter
Lexington Primary (Fayette Co) Fayette County Health Department 650 Newtown Pike Lexington, KY. 40508
16 Feet
16 Feet
F
• Gravel (# 57 or equivalent) will be hauled on site and compacted for sub-base.
• Grade 60 rebar or equivalent will be used.
• Rebar will be located 1 to 2 inches from the slab edge.
• 4000 psi concrete will be poured to a minimum thickness of 4”.
• Pad will be broom finished.
• Cure and seal will be applied to concrete once finished.
Lat: 38.065056 Long:-84.497556
Use existing Electrical Pole lines are underground to shelter
Concrete Pad 10’x16’x4”
Lexington Primary
Nature Center 9101 Camp Ernst Road Union, KY. 41091
F
• Gravel (#57 or equivalent) will be hauled on site and compacted for sub-base.
• Grade 60 rebar or equivalent will be used.
• Rebar will be located 1 to 2 inches from the slab edge.
• 4000 psi concrete will be poured to a minimum thickness of 4”.
• Pad will be broom finished.
• Cure and seal will be applied to concrete once finished.
Use existing Electrical pole Electrical lines are underground to shelter.
Nature Center
Concrete Pad 10’x12’x4”
Lat: 38.9674434 Long: -84.7213627
| Buckner Shelter Placement-REV Stamp PE |
| Lexington Shelter Placement-REV Stamp PE |
| Nature Center Shelter Placement-REV Stamp PE |