Attachment C - Specifications - Pages 1-5.docx

DOCX document 29 KB Posted

Attached to
Generator Installation - LDH
Solicitation number
3000026852
Issued by
East Baton Rouge Parish, Baton Rouge City, Louisiana

About this file

This specifications document outlines the generator installation requirements for the Louisiana Department of Health (LDH) at the Villa Feliciana Medical Complex in Jackson, Louisiana. The scope of work includes the supply and installation of four standby generator systems with four automatic transfer switches (ATS). The project requires installation of one 150kW diesel generator for the sewer plant, one 60kW diesel generator for the recreation building, one 125kW diesel generator serving residences 2-5, and one 30kW natural gas generator for residence #1. Each generator must include a Deep Sea Controller with remote annunciator enclosure (except the 125kW unit), emergency stop kit, Level 1 weather enclosure, critical grade exhaust silencer, 96-hour UL-142 double wall sub-base fuel tank, main circuit breaker, engine block heater, and battery charger. All generators are rated for either 208/120V or 480/277V, 3-phase power at 60Hz with 0.8 power factor and include a 2-year/2,000-hour limited warranty. Each ATS shall be ASCO 300 Series rated between 200-400 amperes at 208V or 480V, 3-phase, service entrance rated with 3-pole solid neutral delayed transition and NEMA 3R enclosure with 44G strip heater. Bidders may propose equal alternatives with manufacturer specifications for any specified items.

The contractor shall provide all labor, equipment, materials, and permits to complete the project, including concrete foundations with rebar reinforcement for both generator and ATS pads, installation and securement of equipment, all control and power cable runs, remote annunciator panels, remote emergency stop buttons in breaker glass enclosures, conduit installation through concrete slabs, and fuel system setup filled to 80% capacity with clear diesel. The contractor must perform comprehensive testing including a 2-hour load bank test at 50% and 80% loads, a 1-hour building load transfer test coordinated with LDH representatives, functional verification of all operations and safety systems, and operational training for facility personnel. All work shall comply with local building, electrical, and fire codes, with on-site work scheduled Monday through Friday from 7:00 a.m. to 3:30 p.m. The contractor shall provide a minimum one-year warranty on materials and workmanship from final acceptance, in addition to manufacturer warranties.

View the file

Other files

File Type Posted
3000026852.pdf PDF
Attachment B - Job Site Verification Form - Page 1.docx DOCX document
Attachment A - Special Terms and Conditions Pages 1-15.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment C – Specifications RFx 3000026852

**If bidding other than specified, please provide manufacturer’s specs for “or equal” items. ** Scope of Work:

The Contractor shall supply all labor, equipment, and materials to install four standby generator systems complete with four Automatic Transfer Switches for the Louisiana Department of Health (LDH).

Location:

Villa Feliciana Medical Complex 5002 Hwy 10 Jackson, La 70748

Agency Contact:

Derick Herring - (225) 634-4086 Daniel Gore - (225) 634-4090

Specifications:

The Contractor shall be responsible for the following:

150kW Standby Diesel Generator – for Sewer Plant

· The Contractor shall provide and install Blue Star JD150-01 or Equal Specify Brand/Model Bidding: ____________________

· Rating: 480/277V, 3 Phase, 60Hz, 0.8 PF

· KW: 150kW

· Deep Sea Controller with Remote Annunciator Enclosure

· Emergency Stop Kit

· Level 1 Weather Enclosure, powder-coated, 14-gauge steel, 200 MPH wind-rated

· Critical Grade Exhaust Silencer

· 96-hour (1,500-gallon) UL-142 Double Wall Sub-base Fuel Tank

· 225 Amp, 3-Pole, 600V Main Circuit Breaker

· Engine Block Heater: 2000W, 240V

· 12V 10A Battery Charger

· 2-Year / 2,000-Hour Limited Warranty Automatic Transfer Switch (ATS) – for Sewer Plant

· The Contractor shall provide and install ASCO 300 Series or Equal

Specify Brand/Model Bidding: ____________________

· Rating: 225A, 480V, 3 Phase

· Controller: 300 Series with 11BE Exerciser Kit

· Service Entrance Rated, 3-Pole with Solid Neutral, Delayed Transition

· NEMA 3R Enclosure with 44G Strip Heater

· 2-Year Limited Warranty 60kW Standby Diesel Generator – for Recreation Building

· The Contractor shall provide and install Blue Star JD60-02 or Equal Specify Brand/Model Bidding: ____________________

· Rating: 208/120V, 3 Phase, 60Hz, 0.8 PF

· KW: 60kW

· Deep Sea Controller with Remote Annunciator Enclosure

· Emergency Stop Kit

· Level 1 Weather Enclosure, powder-coated, 14-gauge steel, 200 MPH wind-rated

· Critical Grade Exhaust Silencer

· 96-hour (1,500-gallon) UL-142 Double Wall Sub-base Fuel Tank

· 225 Amp, 3-Pole, 240V Main Circuit Breaker

· Engine Block Heater: 1500W, 120V

· 12V 10A Battery Charger

· 2-Year / 2,000-Hour Limited Warranty Automatic Transfer Switch (ATS) – for Recreation Building

· The Contractor shall provide and install ASCO 300 Series or Equal Specify Brand/Model Bidding: ____________________

· Rating: 200A, 208V, 3 Phase

· Controller: 300 Series with 11BE Exerciser Kit

· Service Entrance Rated, 3-Pole with Solid Neutral, Delayed Transition

· NEMA 3R Enclosure with 44G Strip Heater

· 2-Year Limited Warranty 125kW Standby Diesel Generator – for Residences 2, 3, 4, & 5

· The Contractor shall provide and install Blue Star JD125 or Equal

Specify Brand/Model Bidding: ____________________

· Rating: 208/120V, 3 Phase, 60Hz, 0.8 PF

· KW: 125kW

· Emergency Stop Kit

· Level 1 Weather Enclosure, powder-coated, 14-gauge steel, 200 MPH wind-rated

· Critical Grade Exhaust Silencer

· 96-hour (1,500-gallon) UL-142 Double Wall Sub-base Fuel Tank

· 225 Amp, 3-Pole, 240V Main Circuit Breaker

· Engine Block Heater: 1500W, 120V

· 12V 10A Battery Charger

· 2-Year / 2,000-Hour Limited Warranty Automatic Transfer Switch (ATS) – Residences 2, 3, 4, & 5

· The Contractor shall provide and install ASCO 300 Series or Equal

Specify Brand/Model Bidding: ____________________

· Rating: 400A, 208V, 3 Phase

· Controller: 300 Series with 11BE Exerciser Kit

· Service Entrance Rated, 3-Pole with Solid Neutral, Delayed Transition

· NEMA 3R Enclosure with 44G Strip Heater

· 2-Year Limited Warranty 30kW Standby Natural Gas Generator – for Residence #1

· The Contractor shall provide and install Kohler Standby Whole Home Generator or Equal Specify Brand/Model Bidding: ____________________

· Rating: 208/120V, 3 Phase, 60Hz, 0.8 PF

· KW: 30kW

· Deep Sea Controller with Remote Annunciator Enclosure

· Emergency Stop Kit

· Level 1 Weather Enclosure, powder-coated, 14-gauge steel, 200 MPH wind-rated

· Critical Grade Exhaust Silencer

· 225 Amp, 3-Pole, 240V Main Circuit Breaker

· Engine Block Heater: 1500W, 120V

· 12V 10A Battery Charger

· 2-Year / 2,000-Hour Limited Warranty

Automatic Transfer Switch (ATS) – for Residence #1

· The Contractor shall provide and install ASCO 300 Series or Equal

Specify Brand/Model Bidding: ____________________

· Rating: 200A, 208V, 3 Phase

· Controller: 300 Series with 11BE Exerciser Kit

· Service Entrance Rated, 3-Pole with Solid Neutral, Delayed Transition

· NEMA 3R Enclosure with 44G Strip Heater

· 2-Year Limited Warranty

Concrete Foundations The Contractor shall provide:

· Four Generator Pads: Reinforced with rebar

· Four ATS Pads: Reinforced with rebar

· Concrete shall meet applicable structural standards for equipment loading and vibration control.

Generator Installation

· The Contractor shall set and secure generators on the prepared concrete pads.

· The Contractor shall install all required control cables, main power cables, and two dedicated circuits each for the battery chargers and block heaters.

Automatic Transfer Switch (ATS)

· The Contractor shall mount and secure ATS on concrete pads.

· The Contractor shall coordinate scheduled shutdown for final connections between ATS, building service, and transformer.

· The Contractor shall terminate and label all power and control wiring per code and manufacturer standards.

Remote Annunciator Panels and Remote Emergency Stops

· The Contractor shall install conduit from generator through concrete slab to each building.

· The Contractor shall mount and wire remote annunciator panel inside each building.

· The Contractor shall install remote emergency stop button in a breaker glass enclosure in an accessible and code-compliant location for each.

Fueling

· The Contractor shall supply and fill fuel to 80% of each tank’s capacity using Clear Diesel (on road).

Load Testing

· The Contractor shall perform 2-hour load bank test:

· 30 minutes at 50% load

· 1.5 hours at 80% load

· The Contractor shall conduct 1-hour building load transfer test (to be coordinated with LDH’s representative).

Functional Testing

· The Contractor shall verify all generator and ATS operations, alarms, safety interlocks, and control functions.

· The Contractor shall confirm proper function of remote annunciator and emergency stop circuits.

Training and Demonstration

· The Contractor shall conduct operational demonstration with the project coordinator and facility maintenance personnel.

· The Contractor shall provide training on start-up, shut-down, fault response, and maintenance requirements.

General Terms:

· All work shall comply with local building, electrical, and fire codes.

· The Contractor shall coordinate with facility management to minimize downtime.

· The Contractor shall provide all necessary equipment, labor, materials, and permits.

· All materials and workmanship shall be guaranteed for a minimum of one year from final acceptance unless otherwise stated by manufacturer warranty.

· On site work schedule is Monday – Friday, 7:00am to 3:30pm.

File details come from the government source that posted it. Updated .