Attachment C - Specifications - Pages 1-3.docx

DOCX document 33 KB Posted

Attached to
Rebid* Fire Alarm System - LSMSA - Addendum No. 1 – Extending Bid Opening Date Date Issued: 05/15/2025 Y
Solicitation number
3000024726
Issued by
Ouachita Parish, New Orleans City, Louisiana

About this file

This document is a Specification Attachment for a Request for Proposal (RFx 3000024726) issued by the Louisiana School for Math, Science, and the Arts (LSMSA) in Natchitoches, Louisiana. The project involves upgrading fire alarm systems in three buildings: the Music and Arts Building, High School Building, and Robert A. Alost Gymnasium. The contractor will replace existing fire panels with Edwards Technology System (EST) iO1000 panels, install new voice evacuation amplifiers, and replace various detection and notification devices to meet current NFPA72 fire safety code requirements. The project requires replacing multiple components including fire alarm control panels, pull stations, smoke detectors, heat detectors, strobes, batteries, and related accessories. A site visit contact is provided (Hillary Ward at 318-471-1825), and bidders are required to specify brand/model information for "or equal" components.

The specification emphasizes minimal disruption to the school's operations, noting that LSMSA is a statewide residential high school with students present continuously. The document includes detailed equipment lists for two building zones, specifying exact quantities and part numbers for each component. Bidders must maintain a clean work site, avoid tobacco use on campus, and obtain prior approval for any replacement or repair work. The general terms indicate standard industry warranties will apply, and special consideration must be given to the school's unique residential educational environment. No specific budget, funding source, or contract term is explicitly stated in the attachment.

View the file

Other files

File Type Posted
3000024726-1.pdf PDF
Attachment B - Job Site Verification Form - Page 1.docx DOCX document
Attachment A - Special Terms and Conditions Pages 1-14.docx DOCX document
3000024726.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment C – Specifications RFx 3000024726

**If bidding other than specified, please provide manufacturer’s specs for “or equal” items. **

Scope of Work:

The Contractor shall furnish all labor, tools, specialized equipment, materials, and supplies to upgrade and enhance two existing fire alarm systems serving three buildings for the Louisiana School for Math, Science, and the Arts (LSMSA).

Location:

Louisiana School for Math, Science, and the Arts 715 University Parkway Natchitoches, LA 71457

Site Visit Contact:

Hillary Ward

318-471-1825 hward@lsmsa.edu

Specifications:

Building #1: Music and Arts Building (MAB)

· The Contractor shall replace the existing fire panel (EST2) with an Edwards Technology System (EST) iO1000 or equal.

Specify Brand/Model Bidding: ___________________

· The Contractor shall install an ANS50MDR2 voice evacuation amplifier or equal.

Specify Brand/Model Bidding: ___________________

These will be installed to NFPA72 requirements by the Contractor. All existing NAC and IDC devices will remain insofar as they are compatible with the new panel and amplifier.

The Contractor shall replace all components necessary to provide a working fire alarm system capable of serving the MAB according to current Fire Safety Codes including the following or equal:

ItemQtyPartDescription
11.00IO1000GFACP, 1 Loop, 4NAC, Gray
21.00SIGA – CC1SSIGA – CC1 w/Strobe Sync
31.00SA - DACTTwo Line Dialer/Modem, RJ31
41.00SA - 232RS232 Interface, 4 Terminal
51.00RLCD - CLCD Annunciator w/Control, Beige
62.0012V17ABattery, 12V, 18AH
72.0012V10ABattery, 10V, 10AH
81.00ANS50MDR2Audio Evacuation Panel, 50W, Red
92.00ANSZM482AZone Splitter Module, ANS25, ANS50, or

ANS100 to be split into multiple circuits

1010.00EOL - 4747K EOL Resistor (P260072)
111.00ANSREMSUPAudio Evacuation Accessory, Supervisory

Card, Remote Microphone 12 1.00 ANSREMG Audio Evacuation Accessory, Remote Microphone Cabinet, Gray

131.00SIGA – CT1Single Output Module
141.00---Miscellaneous Cable and Consumables

** If bidding “or equal” to any of the above components, please provide on a document the components you are bidding. **

Buildings 1 & 2: High School Building (HSB) and Robert A. Alost Gymnasium (Gym)

· The Contractor shall replace the existing Notifier FACP which serves both buildings with an Edwards Technology System (EST) iO1000 or equal

Specify Brand/Model Bidding: ___________________

· The Contractor shall replace existing IDC devices with SIGA devices or equal to ensure compatibility.

Specify Brand/Model Bidding: ___________________

These will be installed to NFPA72 requirements by the Contractor. Reuse existing Faraday as a junction box.

The Contractor shall replace all components necessary to provide a working fire alarm system capable of serving the HSB and Gym according to current Fire Safety Codes including the following or equal:

ItemQtyPartDescription
11.00---Misc. Conduit Fittings and Wire at Headend
228.00SIGA – 278Double Action Pull Station
334.00SIGA - OSDPhoto Smoke Detector, Optica
47.00SIGA - HRDFT/ROR Heat Detector, 3rd Gen.
5 41.00SIGA – SB4Standard Base w/Trim Skirt
61.00SIGA - SDSuperDuct Detector
71.00SD - PHSuperDuct Protective Housing
81.00SD – T60SuperDuct Air Sample Tube, 60-in.
91.00IO1000GFACP, 1 Loop, 4NAC, Gray
101.00SA - 232RS232 Interface, 4 Terminal
111.00SA - DACTTwo Line Dialer/Modem, RJ31
122.00BPS10A10-Amp Booster Power Supply
132.00SIGA – CC1SSIGA – CC1 w/Strobe Sync
146.00SIGA - CHRControl Relay, High Power
155.0012V6A5Battery, 12V, 7.6 AH
162.0012V17ABattery, 12V, 18 AH

** If bidding “or equal” to any of the above components, please provide on a document the components you are bidding. **

General Terms and Conditions:

· Warranties shall be industry standard or as otherwise provided.

· LSMSA is a statewide residential high school providing college-level educational experiences to sophomores, juniors, and seniors. Because of the residential nature of the school, students are present on campus throughout the day and night on weekdays and weekend days. Special care must be taken to minimize interruption of instruction, and interaction with students, faculty, and staff shall be minimal.

· LSMSA is a tobacco-free campus. Use any tobacco products in any LSMSA buildings or on the grounds of LSMSA is prohibited.

· The work site must be maintained in good order with no clutter or debris present.

· Any defective areas found during inspection shall not be replaced or repaired without prior approval of owner.