Attachment C - Specifications - 124 pages.pdf
PDF 676 KB Posted
- Solicitation number
- 36C26325Q0089
About this file
This file is a technical specification section containing requirements for firestopping, low voltage electrical power conductors and cables, wiring devices, and communications installations. The document provides detailed standards and specifications across multiple sections including firestopping requirements for closures in walls/floors/roofs, requirements for electrical conductors rated 600V and below, specifications for wiring devices like receptacles and switches, and comprehensive requirements for communications installations including testing, documentation and quality assurance. Key technical requirements include using UL or equivalent approved firestopping systems, copper conductors with THHN-THWN and XHHW-2 insulation, hospital-grade receptacles in patient care areas, and detailed communications installation standards referencing BICSI, TIA, NECA and other industry specifications. The document provides thorough installation, testing and documentation requirements including submittals, closeout documents, maintenance manuals, and as-built record drawings.
The specifications require contractors to have completed three or more similar installations, be certified by original equipment manufacturers, and provide warranty and maintenance service within 4-8 hours. Quality assurance requirements include manufacturer qualifications of at least 3 years producing specified equipment, three reference installations operating for minimum 3 years, and technician certification by equipment manufacturers. Detailed submittal requirements cover shop drawings, product data, test reports, warranties, maintenance manuals and record documentation showing exact installation details and cable routing.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06 Attachment 1 - Question and Answer - 1 page.pdf | ||
| 36C26325Q0089 0001.docx | DOCX document | |
| Attachment A - Redacted J and A - 3 pages.pdf | ||
| Attachment D - Past Performance Quest. - 3 Pages.docx | DOCX document | |
| 36C26325Q0089.docx | DOCX document | |
| Attachment B - Wage Determ. 6-7-24 - 11 pages.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABLE OF CONTENTS
PAGE
07-84-00 FIRESTOPPING 2
26-05-19 LOW VOLTAGE CONDUCTORS 8
26-27-26 WIRING DEVICES 17
27-05-11 REQUIREMENTS FOR CUMMUNICATION INSTALLATIONS 25
27-05-33 RACEWAYS AND BOXES FOR COMMUNICATION SYSTEMS 71
27-12-12 TELECOMMUNICATION EXPANSIONS 86
27-15-00 COMMUNICATIONS STRUCTURED CABLING 100
SECTION 07 84 00
FIRESTOPPING
SPEC WRITER NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs.
PART 1 - GENERAL
1.1 DESCRIPTION
A. Provide UL or equivalent approved firestopping system for the closures of openings in walls, floors, and roof decks against penetration of flame, heat, and smoke or gases in fire resistant rated construction.
B. Provide UL or equivalent approved firestopping system for the closure of openings in walls against penetration of gases or smoke in smoke partitions.
1.2 RELATED WORK
A. //Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Sustainable
Design Requirements.//
B. Section 07 95 13, EXPANSION JOINT COVER ASSEMBLIES: Expansion and seismic joint firestopping.
C. Section 07 81 00, APPLIED FIREPROOFING: Spray applied fireproofing.
D. Section 07 92 00, JOINT SEALANTS: Sealants and application.
E. Section 23 31 00, HVAC DUCTS AND CASINGS: Fire and smoke damper assemblies in ductwork.
F. Section 23 37 00, AIR OUTLETS AND INLETS: Fire and smoke damper assemblies in ductwork.
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. //Sustainable Design Submittals, as described below:
1. //Volatile organic compounds per volume as specified in
PART 2 - PRODUCTS.// //
C. Installer qualifications.
D. Inspector qualifications.
E. Manufacturers literature, data, and installation instructions for types of firestopping and smoke stopping used.
F. List of FM, UL, or WH classification number of systems installed.
G. Certified laboratory test reports for ASTM E814 tests for systems not listed by FM, UL, or WH proposed for use.
H. Submit certificates from manufacturer attesting that firestopping materials comply with the specified requirements.
1.4 DELIVERY AND STORAGE
A. Deliver materials in their original unopened containers with manufacturer’s name and product identification.
B. Store in a location providing protection from damage and exposure to the elements.
1.5 QUALITY ASSURANCE
A. FM, UL, or WH or other approved laboratory tested products will be acceptable.
B. Installer Qualifications: A firm that has been approved by FM Global according to FM Global 4991 or been evaluated by UL and found to comply with UL’s “Qualified Firestop Contractor Program Requirements.” Submit qualification data.
C. Inspector Qualifications: Contractor to engage a qualified inspector to perform inspections and final reports. The inspector to meet the criteria contained in ASTM E699 for agencies involved in quality assurance and to have a minimum of two years’ experience in construction field inspections of firestopping systems, products, and assemblies. The inspector to be completely independent of, and divested from, the Contractor, the installer, the manufacturer, and the supplier of material or item being inspected. Submit inspector qualifications.
1.6 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.
B. ASTM International (ASTM):
E84-20..................Surface Burning Characteristics of Building
Materials
E699-16.................Standard Specification for Agencies Involved in
Testing, Quality Assurance, and Evaluating of
Manufactured Building Components
E814-13a(2017)..........Fire Tests of Penetration Firestop Systems
E2174-20a...............Standard Practice for On-Site Inspection of
Installed Firestop Systems
E2393-20................Standard Practice for On-Site Inspection of
Installed Fire Resistive Joint Systems and
Perimeter Fire Barriers
C. FM Global (FM):
Annual Issue Approval Guide Building Materials
4991-13.................Approval of Firestop Contractors
D. Underwriters Laboratories, Inc. (UL):
Annual Issue Building Materials Directory
E. Annual Issue Fire Resistance Directory 723-Edition 11(2018)....Standard for Test for Surface Burning
Characteristics of Building Materials
1479-04(2015)...........Fire Tests of Penetration Firestops
F. Intertek Testing Services - Warnock Hersey (ITS-WH):
Annual Issue Certification Listings
G. Environmental Protection Agency (EPA):
40 CFR 59(2014).........National Volatile Organic Compound Emission
Standards for Consumer and Commercial Products
PART 2 - PRODUCTS
2.1 FIRESTOP SYSTEMS
A. Provide either factory built (Firestop Devices) or field erected
(through-Penetration Firestop Systems) to form a specific building system maintaining required integrity of the fire barrier and stop the passage of gases or smoke. Firestop systems to accommodate building movements without impairing their integrity.
B. Through-penetration firestop systems and firestop devices tested in accordance with ASTM E814 or UL 1479 using the "F" or "T" rating to maintain the same rating and integrity as the fire barrier being sealed. "T" ratings are not required for penetrations smaller than or equal to 101 mm (4 inches) nominal pipe or 0.01 square meter (16 square inches) in overall cross sectional area.
C. Firestop sealants used for firestopping or smoke sealing to have the following properties:
1. Contain no flammable or toxic solvents.
2. Release no dangerous or flammable out gassing during the drying or curing of products.
3. Water-resistant after drying or curing and unaffected by high humidity, condensation or transient water exposure.
4. When installed in exposed areas, capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface.
5. //VOC Content: Firestopping sealants and sealant primers to comply with the following limits for VOC content when calculated according to 40 CFR 59, (EPA Method 24):
a. Sealants: 250 g/L.
b. Sealant Primers for Nonporous Substrates: 250 g/L.
c. Sealant Primers for Porous Substrates: 775 g/L. //
D. Firestopping system or devices used for penetrations by glass pipe, plastic pipe or conduits, unenclosed cables, or other non-metallic materials to have following properties:
1. Classified for use with the particular type of penetrating material used.
2. Penetrations containing loose electrical cables, computer data cables, and communications cables protected using firestopping systems that allow unrestricted cable changes without damage to the seal.
E. Maximum flame spread of 25 and smoke development of 50 when tested in accordance with ASTM E84 or UL 723. Material to be an approved firestopping material as listed in UL Fire Resistance Directory or by a nationally recognized testing laboratory.
F. FM, UL, or WH rated or tested by an approved laboratory in accordance with ASTM E814.
G. Materials to be nontoxic and noncarcinogen at all stages of application or during fire conditions and to not contain hazardous chemicals.
Provide firestop material that is free from Ethylene Glycol, PCB, MEK, and asbestos.
H. For firestopping exposed to view, traffic, moisture, and physical damage, provide products that do not deteriorate when exposed to these conditions.
1. For piping penetrations for plumbing and wet-pipe sprinkler systems, provide moisture-resistant through-penetration firestop systems.
2. For floor penetrations with annular spaces exceeding 101 mm (4 inches) or more in width and exposed to possible loading and traffic, provide firestop systems capable of supporting the floor loads involved either by installing floor plates or by other means acceptable to the firestop manufacturer.
3. For penetrations involving insulated piping, provide through-penetration firestop systems not requiring removal of insulation.
2.2 SMOKE STOPPING IN SMOKE PARTITIONS
A. Provide silicone sealant in smoke partitions as specified in Section
07 92 00, JOINT SEALANTS.
B. Provide mineral fiber filler and bond breaker behind sealant.
C. Sealants to have a maximum flame spread of 25 and smoke developed of 50 when tested in accordance with ASTM E84.
D. When used in exposed areas capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Submit product data and installation instructions, as required by article, submittals, after an on-site examination of areas to receive firestopping.
B. Examine substrates and conditions with installer present for compliance with requirements for opening configuration, penetrating items, substrates, and other conditions affecting performance of firestopping.
Do not proceed with installation until unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Remove dirt, grease, oil, laitance and form-release agents from concrete, loose materials, or other substances that prevent adherence and bonding or application of the firestopping or smoke stopping materials.
B. Remove insulation on insulated pipe for a distance of 150 mm (6 inches) on each side of the fire rated assembly prior to applying the firestopping materials unless the firestopping materials are tested and approved for use on insulated pipes.
C. Prime substrates where required by joint firestopping system manufacturer using that manufacturer’s recommended products and methods. Confine primers to areas of bond; do not allow spillage and migration onto exposed surfaces.
D. Masking Tape: Apply masking tape to prevent firestopping from contacting adjoining surfaces that will remain exposed upon completion of work and that would otherwise be permanently stained or damaged by such contact or by cleaning methods used to remove smears from firestopping materials. Remove tape as soon as it is possible to do so without disturbing seal of firestopping with substrates.
3.3 INSTALLATION
A. Do not begin firestopping work until the specified material data and installation instructions of the proposed firestopping systems have been submitted and approved.
B. Install firestopping systems with smoke stopping in accordance with FM, UL, WH, or other approved system details and installation instructions.
C. Install smoke stopping seals in smoke partitions.
3.4 CLEAN-UP
A. As work on each floor is completed, remove materials, litter, and debris.
B. Clean up spills of liquid type materials.
C. Clean off excess fill materials and sealants adjacent to openings and joints as work progresses by methods and with cleaning materials approved by manufacturers of firestopping products and of products in which opening and joints occur.
D. Protect firestopping during and after curing period from contact with contaminating substances or from damage resulting from construction operations or other causes so that they are without deterioration or damage at time of Substantial Completion. If, despite such protection, damage or deterioration occurs, cut out and remove damaged or deteriorated firestopping immediately and install new materials to provide firestopping complying with specified requirements.
3.5 INSPECTIONS AND ACCEPTANCE OF WORK
A. Do not conceal or enclose firestop assemblies until inspection is complete and approved by the Contracting Officer Representative (COR).
B. Furnish service of approved inspector to inspect firestopping in accordance with ASTM E2393 and ASTM E2174 for firestop inspection, and document inspection results. Submit written reports indicating locations of and types of penetrations and type of firestopping used at each location; type is to be recorded by UL listed printed numbers.
- - - E N D - - -
SECTION 26 05 19
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SPEC WRITER NOTE: Delete between //_____// if not applicable to project.
Also delete any other item or paragraph not applicable to the section and renumber the paragraphs.
A. This section specifies the furnishing, installation, connection, and testing of the electrical conductors and cables for use in electrical systems rated 600 V and below, indicated as cable(s), conductor(s), wire, or wiring in this section.
1.2 RELATED WORK
A. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire-resistant rated construction.
B. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS:
Requirements that apply to all sections of Division 26.
C. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path for possible ground fault currents.
D. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits for conductors and cables.
E. Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION: Installation of conductors and cables in manholes and ducts.
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS
(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR
ELECTRICAL INSTALLATIONS.
1.4 SUBMITTALS
A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1. Shop Drawings:
a. Submit sufficient information to demonstrate compliance with drawings and specifications.
b. Submit the following data for approval:
1) Electrical ratings and insulation type for each conductor and cable.
2) Splicing materials and pulling lubricant.
2. Certifications: Two weeks prior to final inspection, submit the following.
a. Certification by the manufacturer that the conductors and cables conform to the requirements of the drawings and specifications.
b. Certification by the Contractor that the conductors and cables have been properly installed, adjusted, and tested.
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are reference in the text by designation only.
B. American Society of Testing Material (ASTM):
D2301-10................Standard Specification for Vinyl Chloride
Plastic Pressure-Sensitive Electrical
Insulating Tape
D2304-18................Test Method for Thermal Endurance of Rigid
Electrical Insulating Materials
D3005-17................Low-Temperature Resistant Vinyl Chloride
Plastic Pressure-Sensitive Electrical
Insulating Tape
C. National Electrical Manufacturers Association (NEMA):
WC 70-21................Power Cables Rated 2000 Volts or Less for the
Distribution of Electrical Energy
D. National Fire Protection Association (NFPA):
70-23...................National Electrical Code (NEC)
E. Underwriters Laboratories, Inc. (UL):
44-18...................Thermoset-Insulated Wires and Cables
83-17...................Thermoplastic-Insulated Wires and Cables
467-13..................Grounding and Bonding Equipment
486A-486B-18............Wire Connectors
486C-18.................Splicing Wire Connectors
486D-15.................Sealed Wire Connector Systems
486E-15.................Equipment Wiring Terminals for Use with
Aluminum and/or Copper Conductors
493-18..................Thermoplastic-Insulated Underground Feeder and
Branch Circuit Cables
514B-12.................Conduit, Tubing, and Cable Fittings
PART 2 - PRODUCTS
2.1 CONDUCTORS AND CABLES
A. Conductors and cables shall be in accordance with ASTM, NEMA, NFPA, UL, as specified herein, and as shown on the drawings.
B. Conductors shall be copper.
C. Single Conductor:
1. No. 12 AWG: Minimum size, except where smaller sizes are specified herein or shown on the drawings.
2. No. 8 AWG and larger: Stranded.
3. No. 10 AWG and smaller: Solid; except shall be stranded for final connection to motors, transformers, and vibrating equipment.
4. Insulation: THHN-THWN and XHHW-2. XHHW-2 shall be used for isolated power systems.
SPEC WRITER NOTE: Delete the paragraph below if these cables types are not required. These cables types are used only for temporary installation of normal power.
//D. Direct Burial Cable: UF or USE cable.//
E. Conductor Color Code:
1. No. 10 AWG and smaller: Solid color insulation or solid color coating.
2. No. 8 AWG and larger: Color-coded using one of the following methods:
a. Solid color insulation or solid color coating.
b. Stripes, bands, or hash marks of color specified.
c. Color using 19 mm (0.75 inches) wide tape.
4. For modifications and additions to existing wiring systems, color coding shall conform to the existing wiring system.
5. Conductors shall be color-coded as follows:
208/120 V Phase 480/277 V
Black A Brown
Red B Orange
Blue C Yellow
White Neutral Gray *
* or white with colored (other than green) tracer.
6. Lighting circuit “switch legs”, and 3-way and 4-way switch
“traveling wires,” shall have color coding that is unique and distinct (e.g., pink and purple) from the color coding indicated above. The unique color codes shall be solid and in accordance with the NEC. Coordinate color coding in the field with the //Resident
Engineer// //COR///.
7. Color code for isolated power system wiring shall be in accordance with the NEC.
2.2 SPLICES
A. Splices shall be in accordance with NEC and UL.
B. Above Ground Splices for No. 10 AWG and Smaller:
1. Solderless, screw-on, reusable pressure cable type, with integral insulation, approved for copper and aluminum conductors.
2. The integral insulator shall have a skirt to completely cover the stripped conductors.
3. The number, size, and combination of conductors used with the connector, as listed on the manufacturer's packaging, shall be strictly followed.
C. Above Ground Splices for No. 8 AWG to No. 4/0 AWG:
1. Compression, hex screw, or bolt clamp-type of high conductivity and corrosion-resistant material, listed for use with copper and aluminum conductors.
2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.
3. Splice and insulation shall be product of the same manufacturer.
4. All bolts, nuts, and washers used with splices shall be //zinc-plated//cadmium-plated// steel.
D. Above Ground Splices for 250 kcmil and Larger:
1. Long barrel “butt-splice” or “sleeve” type compression connectors, with minimum of two compression indents per wire, listed for use with copper and aluminum conductors.
2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.
3. Splice and insulation shall be product of the same manufacturer.
SPEC WRITER NOTE: Delete the paragraphs below if underground splices types are not required.
//E. Underground Splices for No. 10 AWG and Smaller:
1. Solderless, screw-on, reusable pressure cable type, with integral insulation. Listed for wet locations, and approved for copper and aluminum conductors.
2. The integral insulator shall have a skirt to completely cover the stripped conductors.
3. The number, size, and combination of conductors used with the connector, as listed on the manufacturer's packaging, shall be strictly followed.
F. Underground Splices for No. 8 AWG and Larger:
1. Mechanical type, of high conductivity and corrosion-resistant material. Listed for wet locations, and approved for copper and aluminum conductors.
2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.
3. Splice and insulation shall be product of the same manufacturer.//
G. Plastic electrical insulating tape: Per ASTM D2304, flame-retardant, cold and weather resistant.
2.3 CONNECTORS AND TERMINATIONS
A. Mechanical type of high conductivity and corrosion-resistant material, listed for use with copper and aluminum conductors.
B. Long barrel compression type of high conductivity and corrosion-resistant material, with minimum of two compression indents per wire, listed for use with copper and aluminum conductors.
C. All bolts, nuts, and washers used to connect connections and terminations to bus bars or other termination points shall be //zinc-plated//cadmium-plated// steel.
2.4 CONTROL WIRING
A. Unless otherwise specified elsewhere in these specifications, control wiring shall be as specified herein, except that the minimum size shall be not less than No. 14 AWG, or as required by the control wiring equipment manufacturer.
B. Control wiring shall be sized such that the voltage drop under in-rush conditions does not adversely affect operation of the controls.
2.5 WIRE LUBRICATING COMPOUND
A. Lubricating compound shall be suitable for the wire insulation and conduit, and shall not harden or become adhesive.
B. Shall not be used on conductors for isolated power systems.
PART 3 - EXECUTION
3.1 GENERAL
A. Installation shall be in accordance with the NEC, as shown on the drawings, and manufacturer’s instructions.
B. Install conductors in raceway systems.
C. Splice conductors only in outlet boxes, junction boxes, pullboxes, manholes, or handholes.
D. Conductors of different systems (e.g., 120 V and 277 V) shall not be installed in the same raceway.
E. For conductors installed in vertical raceways, provide conductor support (also known as cable support), to counter gravity pull on conductor weight. Conductor support shall be split-wedge conductor support type. Prior to installing the conductor support plug, remove all pulling compound from conductors where they pass through the conductor support body. After installing the conductor support plug, tap the conductor support plug firmly in the conductor support body.
F. In panelboards, cabinets, wireways, switches, enclosures, and equipment assemblies, neatly form, train, and tie the conductors with non-metallic “zip” ties.
G. For connections to motors, transformers, and vibrating equipment, stranded conductors shall be used only from the last fixed point of connection to the motors, transformers, or vibrating equipment.
H. Use expanding foam or non-hardening duct-seal to seal conduits entering a building, after installation of conductors.
I. Conductor Pulling:
1. Provide installation equipment that will prevent the cutting or abrasion of insulation during pulling. Use lubricants approved for the cable.
2. Use nonmetallic pull ropes.
3. Attach pull ropes by means of either woven basket grips or pulling eyes attached directly to the conductors.
4. All conductors in a single conduit shall be pulled simultaneously.
5. Do not exceed manufacturer’s recommended maximum pulling tensions and sidewall pressure values.
J. Number of conductors for branch circuits shall not exceed more than three branch circuits in any one conduit.
K. When stripping stranded conductors, use a tool that does not damage the conductor or remove conductor strands.
3.2 INSTALLATION IN MANHOLES
A. Train the conductors around the manhole walls, but do not bend to a radius less than six times the overall conductor diameter.
//B. Fireproofing:
1. Install fireproofing on low-voltage conductors where the low-voltage conductors are installed in the same manholes with medium-voltage conductors.
2. Use fireproofing tape as specified in Section 26 05 13, MEDIUM-
VOLTAGE CABLES, and apply the tape in a single layer, half-lapped, or as recommended by the manufacturer. Install the tape with the coated side towards the cable and extend it not less than 25 mm (1 inch) into each duct.
3. Secure the fireproofing tape in place by a random wrap of glass cloth tape.//
3.3 SPLICE AND TERMINATION INSTALLATION
A. Splices and terminations shall be mechanically and electrically secure, and tightened to manufacturer’s published torque values using a torque screwdriver or wrench.
B. Where the Government determines that unsatisfactory splices or terminations have been installed, replace the splices or terminations at no additional cost to the Government.
3.4 CONDUCTOR IDENTIFICATION
A. When using colored tape to identify phase, neutral, and ground conductors larger than No. 8 AWG, apply tape in half-overlapping turns for a minimum of 75 mm (3 inches) from terminal points, and in junction boxes, pullboxes, and manholes. Apply the last two laps of tape with no tension to prevent possible unwinding. Where markings are covered by tape, apply tags to conductors, stating size and insulation type.
3.5 FEEDER CONDUCTOR IDENTIFICATION
A. In each interior pullbox and each underground manhole and handhole, install brass tags on all feeder conductors to clearly designate their circuit identification and voltage. The tags shall be the embossed type, 40 mm (1-1/2 inches) in diameter and 40 mils thick. Attach tags with plastic ties.
3.6 EXISTING CONDUCTORS
A. Unless specifically indicated on the plans, existing conductors shall not be reused.
3.7 CONTROL WIRING INSTALLATION
A. Unless otherwise specified in other sections, install control wiring and connect to equipment to perform the required functions as specified or as shown on the drawings.
SPEC WRITER NOTE: Each separate system shall have a dedicated power supply circuit.
B. Install a separate power supply circuit for each system, except where otherwise shown on the drawings.
3.8 CONTROL WIRING IDENTIFICATION
A. Install a permanent wire marker on each wire at each termination.
B. Identifying numbers and letters on the wire markers shall correspond to those on the wiring diagrams used for installing the systems.
C. Wire markers shall retain their markings after cleaning.
D. In each manhole and handhole, install embossed brass tags to identify the system served and function.
SPEC WRITER NOTE: Delete the paragraph below if these cables types are not required. These cables types are used only for temporary installation of normal power.
//3.9 DIRECT BURIAL CABLE INSTALLATION
A. Tops of the cables:
1. Below the finished grade: Minimum 600 mm (24 inches) unless greater depth is shown.
2. Below road and other pavement surfaces: In conduit as specified, minimum 760 mm (30 inches) unless greater depth is shown.
3. Do not install cables under railroad tracks.
B. Under road and paved surfaces: Install cables in concrete-encased galvanized steel rigid conduits. Size as shown on plans, but not less than 50 mm (2 inches) trade size with bushings at each end of each conduit run. Provide size/quantity of conduits required to accommodate cables plus one spare.
C. Work with extreme care near existing ducts, conduits, cables, and other utilities to prevent any damage.
D. Excavation and backfill is specified in Section 31 20 00, EARTH MOVING.
In addition:
1. Place 75 mm (3 inches) bedding sand in the trenches before installing the cables.
2. Place 75 mm (3 inches) shading sand over the installed cables.
3. Install continuous horizontal 25 mm by 200 mm (1 inch x 8 inches) preservative-impregnated wood planking 75 mm (3 inches) above the cables before backfilling.
E. Provide horizontal slack in the cables for contraction during cold weather.
F. Install the cables in continuous lengths. Splices within cable runs shall not be accepted.
G. Connections and terminations shall be listed submersible-type designed for the cables being installed.
H. Warning tape shall be continuously placed 300 mm (12 inches) above the buried cables.//
3.10 ACCEPTANCE CHECKS AND TESTS
A. Perform in accordance with the manufacturer's recommendations. In addition, include the following:
1. Visual Inspection and Tests: Inspect physical condition.
2. Electrical tests:
a. After installation but before connection to utilization devices, such as fixtures, motors, or appliances, test conductors phase-to-phase and phase-to-ground resistance with an insulation resistance tester. Existing conductors to be reused shall also be tested.
b. Applied voltage shall be 500 V DC for 300 V rated cable, and 1000
V DC for 600 V rated cable. Apply test for one minute or until reading is constant for 15 seconds, whichever is longer. Minimum insulation resistance values shall not be less than 25 megohms for 300 V rated cable and 100 megohms for 600 V rated cable.
c. Perform phase rotation test on all three-phase circuits.
---END---
SECTION 26 27 26
WIRING DEVICES
SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to the section and renumber the paragraphs.
A. This section specifies the furnishing, installation, connection, and testing of wiring devices.
1.2 RELATED WORK
A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section of
Division 26.
B. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES:
Cables and wiring.
C. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents.
D. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduit and boxes.
E. Section 26 51 00, INTERIOR LIGHTING: Fluorescent ballasts and LED drivers for use with manual dimming controls.
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS
(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR
ELECTRICAL INSTALLATIONS.
1.4 SUBMITTALS
A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1. Shop Drawings:
a. Submit sufficient information to demonstrate compliance with drawings and specifications.
b. Include electrical ratings, dimensions, mounting details, construction materials, grade, and termination information.
2. Manuals:
a. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and operating manuals, including technical data sheets and information for ordering replacement parts.
b. If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.
3. Certifications: Two weeks prior to final inspection, submit the following.
a. Certification by the manufacturer that the wiring devices conform to the requirements of the drawings and specifications.
b. Certification by the Contractor that the wiring devices have been properly installed and adjusted.
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by basic designation only.
B. National Electrical Manufacturers Association (NEMA):
WD 1-99(R2020)..........General Color Requirements for Wiring Devices
WD 6-16 ................Wiring Devices – Dimensional Specifications
C. National Fire Protection Association (NFPA):
70-23...................National Electrical Code (NEC)
99-21...................Health Care Facilities
D. Underwriter’s Laboratories, Inc. (UL):
5-16....................Surface Metal Raceways and Fittings
20-18...................General-Use Snap Switches
231-16..................Power Outlets
467-13..................Grounding and Bonding Equipment
498-17..................Attachment Plugs and Receptacles
943-16..................Ground-Fault Circuit-Interrupters
1449-21.................Surge Protective Devices
1472-15.................Solid State Dimming Controls
PART 2 - PRODUCTS
SPEC WRITER NOTE: Hospital grade receptacles shall be specified and installed in patient care buildings.
2.1 RECEPTACLES
A. General: All receptacles shall comply with NEMA, NFPA, UL, and as shown on the drawings.
1. Mounting straps shall be nickel plated brass, brass, nickel plated steel or galvanize steel with break-off plaster ears, and shall include a self-grounding feature. Terminal screws shall be brass, brass plated or a copper alloy metal.
2. Receptacles shall have provisions for back wiring with separate metal clamp type terminals (four minimum) and side wiring from four captively held binding screws.
B. Duplex Receptacles - Hospital-grade: shall be listed for hospital grade, single phase, 20 ampere, 120 volts, 2-pole, 3-wire, NEMA 5-20R, with break-off feature for two-circuit operation.
1. Bodies shall be //ivory// // // in color.
2. Switched duplex receptacles shall be wired so that only the top receptacle is switched. The lower receptacle shall be unswitched.
3. Duplex Receptacles on Emergency Circuit:
a. In rooms without emergency powered general lighting, the emergency receptacles shall be of the self-illuminated type.
4. Ground Fault Current Interrupter (GFCI) Duplex Receptacles: Shall be an integral unit, hospital-grade, suitable for mounting in a standard outlet box, with end-of-life indication and provisions to isolate the face due to improper wiring. GFCI receptacles shall be self-test receptacles in accordance with UL 943.
a. Ground fault interrupter shall consist of a differential current transformer, self-test, solid state sensing circuitry and a circuit interrupter switch. Device shall have nominal sensitivity to ground leakage current of 4-6 milliamperes and shall function to interrupt the current supply for any value of ground leakage current above five milliamperes (+ or – 1 milliampere) on the load side of the device. Device shall have a minimum nominal tripping time of 0.025 second.
b. Self-test function shall be automatically initiated within 5 seconds after power is activated to the receptacles. Self-test function shall be periodically and automatically performed every
3 hours or less.
c. End-of-life indicator light shall be a persistent flashing or blinking light to indicate that the GFCI receptacle is no longer in service.
5. Tamper-Resistant Duplex Receptacles:
a. Bodies shall be //gray// // // in color.
1) Shall permit current to flow only while a standard plug is in the proper position in the receptacle.
2) Screws exposed while the wall plates are in place shall be the tamperproof type.
C. Duplex Receptacles – Non-hospital Grade: shall be the same as duplex receptacles – hospital grade in accordance with sections 2.1A and 2.1B of this specification, except for the hospital grade listing.
1. Bodies shall be //brown// // // nylon.
D. Receptacles - 20, 30, and 50 ampere, 250 Volts: Shall be complete with appropriate cord grip plug.
SPEC WRITER NOTE: Specify type of receptacle.
E. Weatherproof Receptacles: Shall consist of a duplex receptacle, mounted in box with a gasketed, weatherproof, cast metal cover plate and cap over each receptacle opening. The cap shall be permanently attached to the cover plate by a spring-hinged flap. The weatherproof integrity shall not be affected when heavy duty specification or hospital grade attachment plug caps are inserted. Cover plates on outlet boxes mounted flush in the wall shall be gasketed to the wall in a watertight manner.
F. Surge Protective Receptacles shall have integral surge suppression in line to ground, line to neutral, and neutral to ground modes.
1. Surge Protective Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 400 Volts, and minimum single transient pulse energy dissipation of 210 Joules.
2. Active Surge Protective Indication: LED, visible in face of device to indicate device is active or no longer in service.
G. Cable Reel Receptacles:
1. Reel shall have a heavy-duty spring motor, with self-contained rewind power and non-sparking ratchet assembly, a 4-way roller and adjustable cable stop, and a safety chain. Reel shall lock when desired cable has been payed out, and unlock and retract when cable is pulled to release lock.
2. Reel shall be provided with minimum 40 foot [12m] cable rated for
//20// //30// //50// // // amperes with required phase conductors, neutral, and equipment grounding conductor. Provide device with
//NEMA configuration as shown// //two NEMA 5-20R GFCI receptacles//.
2.2 TOGGLE SWITCHES
A. Toggle switches shall be totally enclosed tumbler type with nylon bodies. Handles shall be //ivory// // // in color unless otherwise specified or shown on the drawings.
1. Switches installed in hazardous areas shall be explosion-proof type in accordance with the NEC and as shown on the drawings.
2. Shall be single unit toggle, butt contact, quiet AC type, heavy-duty general-purpose use with an integral self grounding mounting strap with break-off plasters ears and provisions for back wiring with separate metal wiring clamps and side wiring with captively held binding screws.
3. Switches shall be rated 20 amperes at 120-277 Volts AC.
2.3 MANUAL DIMMING CONTROL
A. Electronic full-wave manual slide dimmer with on/off switch and audible frequency and EMI/RFI suppression filters.
B. Manual dimming controls shall be fully compatible with //fluorescent electronic dimming ballasts and approved by the ballast manufacturer//
//LED dimming driver and be approved by the driver manufacturer//, shall operate over full specified dimming range, and shall not degrade the performance or rated life of the electronic dimming ballast and lamp.
C. Provide single-pole, three-way or four-way, as shown on the drawings.
D. Manual dimming control and faceplates shall be //ivory// // // in color unless otherwise specified.
SPEC WRITERS NOTE: Coordinate the material type and color of wall plate with VA. If stainless steel is utilized, delete paragraph B regarding ivory color.
2.4 WALL PLATES
A. Wall plates for switches and receptacles shall be type // 302 stainless steel // or // smooth nylon //. Oversize plates are not acceptable.
//B. Color shall be ivory unless otherwise specified.//
C. For receptacles or switches mounted adjacent to each other, wall plates shall be common for each group of receptacles or switches.
D. In areas requiring tamperproof wiring devices, wall plates shall be type 302 stainless steel, and shall have tamperproof screws and beveled edges.
E. Duplex Receptacles on Emergency Circuit: // Wall plates shall be red nylon with the word "EMERGENCY" engraved in 6 mm (1/4 inch) white letters.// // Wall plates shall be type 302 stainless steel, with the word “EMERGENCY” engraved in 6 mm (1/4 inch) red letters.//
2.5 SURFACE MULTIPLE-OUTLET ASSEMBLIES
A. Shall have the following features:
1. Enclosures:
a. Thickness of steel shall be not less than 1 mm (0.040 inch) for base and cover. Nominal dimensions shall be 40 mm x 70 mm (1-1/2 inches by 2-3/4 inches) with inside cross sectional area not less than 2250 square mm (3-1/2 square inches). The enclosures shall be thoroughly cleaned, phosphatized, and painted at the factory with primer and the manufacturer's standard baked enamel finish.
2. Receptacles shall be duplex, //hospital grade// // //. See paragraph 'RECEPTACLES' in this Section. Device cover plates shall be the manufacturer's standard corrosion resistant finish and shall not exceed the dimensions of the enclosure.
3. Unless otherwise shown on drawings, receptacle spacing shall be 600 mm (24 inches) on centers.
4. Conductors shall be as specified in Section 26 05 19, LOW-VOLTAGE
ELECTRICAL POWER CONDUCTORS AND CABLE.
5. Installation fittings shall be the manufacturer’s standard bends, offsets, device brackets, inside couplings, wire clips, elbows, and other components as required for a complete system.
6. Bond the assemblies to the branch circuit conduit system.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Installation shall be in accordance with the NEC and as shown as on the drawings.
B. Install wiring devices after wall construction and painting is complete.
C. The ground terminal of each wiring device shall be bonded to the outlet box with an approved green bonding jumper, and also connected to the branch circuit equipment grounding conductor.
D. Outlet boxes for toggle switches and manual dimming controls shall be mounted on the strike side of doors.
E. Provide barriers in multi-gang outlet boxes to comply with the NEC.
F. Coordinate the electrical work with the work of other trades to ensure that wiring device flush outlets are positioned with box openings aligned with the face of the surrounding finish material. Pay special attention to installations in cabinet work, and in connection with laboratory equipment.
G. Exact field locations of floors, walls, partitions, doors, windows, and equipment may vary from locations shown on the drawings. Prior to locating sleeves, boxes and chases for roughing-in of conduit and equipment, the Contractor shall coordinate exact field location of the above items with other trades.
H. Install wall switches 1.2 M (48 inches) above floor, with the toggle
OFF position down.
I. Install wall dimmers 1.2 M (48 inches) above floor.
J. Install receptacles 450 mm (18 inches) above floor, and 152 mm (6 inches) above counter backsplash or workbenches. Install specific-use receptacles at heights shown on the drawings.
K. Install horizontally mounted receptacles with the ground pin to the right.
L. When required or recommended by the manufacturer, use a torque screwdriver. Tighten unused terminal screws.
M. Label device plates with a permanent adhesive label listing panel and circuit feeding the wiring device.
3.2 ACCEPTANCE CHECKS AND TESTS
A. Perform manufacturer’s required field checks in accordance with the manufacturer's recommendations, and the latest NFPA 99. In addition, include the following:
1. Visual Inspection and Tests:
a. Inspect physical and electrical conditions.
b. Vacuum-clean surface metal raceway interior. Clean metal raceway exterior.
c. Test wiring devices for damaged conductors, high circuit resistance, poor connections, inadequate fault current path, defective devices, or similar problems using a portable receptacle tester. Correct circuit conditions, remove malfunctioning units and replace with new, and retest as specified above.
d. Test GFCI receptacles.
2. Receptacle testing in the Patient Care Spaces, such as retention force of the grounding blade of each receptacle, shall comply with the latest NFPA 99.
---END---
SECTION 27 05 11
REQUIREMENTS FOR COMMUNICATIONS INSTALLATIONS
SPEC WRITER NOTES:
1. Edit this specification section between //____//, to fit project, or delete if not applicable.
2. Contact VA’s AHJ, Spectrum Management and COMSEC Service (SMCS 005OP2H3), (202- 461-5310), for all technical assistance.
3. Included throughout this specification are references to system’s interface capability and various related features.
System designer must verify availability of this system and coordinate associated requirements and subsequent interfaces.
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section includes common requirements to communications installations and applies to all sections of Division 27 //and Division
28//.
B. Provide completely functioning communications systems.
C. Comply with VAAR 852.236.91 and FAR clause 52.236-21 in circumstance of a need for additional detail or conflict between drawings, specifications, reference standards or code.
1.2 REFERENCES
A. Abbreviations and Acronyms
1. Refer to http://www.cfm.va.gov/til/sdetail.asp for Division 00, ARCHITECTURAL ABBREVIATIONS.
2. Additional Abbreviations and Acronyms:
A Ampere
AC Alternating Current
AE Architect and Engineer
AFF Above Finished Floor
AHJ Authority Having Jurisdiction
ANSI American National Standards Institute
AWG American Wire Gauge (refer to STP and UTP)
AWS Advanced Wireless Services
BCT Bonding Conductor for Telecommunications (also
Telecommunications Bonding Conductor (TBC))
BDA Bi-Directional Amplifier
BICSI Building Industry Consulting Service International
BIM Building Information Modeling
BOM Bill of Materials
BTU British Thermal Units
BUCR Back-up Computer Room
BTS Base Transceiver Station
CAD AutoCAD
CBOPC Community Based Out Patient Clinic
CBC Coupled Bonding Conductor
CBOC Community Based Out Patient Clinic (refer to CBOPC, OPC, VAMC)
CCS TIP's Cross Connection System (refer to VCCS and HCCS)
CFE Contractor Furnished Equipment
CFM US Department of Veterans Affairs Office of Construction and Facilities Management
CFR Consolidated Federal Regulations
CIO Communication Information Officer (Facility, VISN or
Region) cm Centimeters CO Central Office
COR Contracting Officer Representative
CPU Central Processing Unit
CSU Customer Service Unit
CUP Conditional Use Permit(s) – Federal/GSA for VA dB Decibel dBm Decibel Measured dBmV Decibel per milli-Volt
DC Direct Current
DEA United States Drug Enforcement Administration
DSU Data Service Unit
EBC Equipment Bonding Conductor
ECC Engineering Control Center (refer to DCR, EMCR)
EDGE Enhanced Data (Rates) for GSM Evolution
EDM Electrical Design Manual
EMCR Emergency Management Control Room (refer to DCR, ECC)
EMI Electromagnetic Interference (refer to RFI)
EMS Emergency Medical Service
EMT Electrical Metallic Tubing or thin wall conduit
ENTR Utilities Entrance Location (refer to DEMARC, POTS, LEC)
EPBX Electronic Digital Private Branch Exchange
ESR Vendor’s Engineering Service Report
FA Fire Alarm
FAR Federal Acquisition Regulations in Chapter 1 of Title 48 of
Code of Federal Regulations
FMS VA’s Headquarters or Medical Center Facility’s Management
Service
FR Frequency (refer to RF)
FTS Federal Telephone Service
GFE Government Furnished Equipment
GPS Global Positioning System
GRC Galvanized Rigid Metal Conduit
GSM Global System (Station) for Mobile
HCCS TIP’s Horizontal Cross Connection System (refer to CCS &
VCCS)
HDPE High Density Polyethylene Conduit
HDTV Advanced Television Standards Committee High-Definition
Digital Television
HEC Head End Cabinets(refer to HEIC, PA)
HEIC Head End Interface Cabinets(refer to HEC, PA)
HF High Frequency (Radio Band; Re FR, RF, VHF & UHF)
HSPA High Speed Packet Access
HZ Hertz
IBT Intersystem Bonding Termination (NEC 250.94)
IC Intercom
ICRA Infectious Control Risk Assessment
IDEN Integrated Digital Enhanced Network
IDC Insulation Displacement Contact
IDF Intermediate Distribution Frame
ILSM Interim Life Safety Measures
IMC Rigid Intermediate Steel Conduit
IRM Department of Veterans Affairs Office of Information
Resources Management
ISDN Integrated Services Digital Network
ISM Industrial, Scientific, Medical
IWS Intra-Building Wireless System
LAN Local Area Network
LBS Location Based Services, Leased Based Systems
LEC Local Exchange Carrier (refer to DEMARC, PBX & POTS)
LED Light Emitting Diode
LMR Land Mobile Radio
LTE Long Term Evolution, or 4G Standard for Wireless Data
Communications Technology
M Meter
MAS Medical Administration Service
MATV Master Antenna Television
MCR Main Computer Room
MCOR Main Computer Operators Room
MDF Main Distribution Frame
MH Manholes or Maintenance Holes
MHz Megaherts (106 Hz) mm Millimeter
MOU Memorandum of Understanding
MW Microwave (RF Band, Equipment or Services)
NID Network Interface Device (refer to DEMARC)
NEC National Electric Code
NOR Network Operations Room
NRTL OSHA Nationally Recognized Testing Laboratory
NS Nurse Stations
NTIA U.S. Department of Commerce National Telecommunications and
Information Administration
OEM Original Equipment Manufacturer
OI&T Office of Information and Technology
OPC VA’s Outpatient Clinic (refer to CBOC, VAMC)
OSH Department of Veterans Affairs Office of Occupational
Safety and Health
OSHA United States Department of Labor Occupational Safety and
Health Administration
OTDR Optical Time-Domain Reflectometer
PA Public Address System (refer to HE, HEIC, RPEC)
PBX Private Branch Exchange (refer to DEMARC, LEC, POTS)
PCR Police Control Room (refer to SPCC, could be designated
SCC)
PCS Personal Communications Service (refer to UPCS)
PE Professional Engineer
PM Project Manager
PoE Power over Ethernet
POTS Plain Old Telephone Service (refer to DEMARC, LEC, PBX)
PSTN Public Switched Telephone Network
PSRAS Public Safety Radio Amplification Systems
PTS Pay Telephone Station
PVC Poly-Vinyl Chloride
PWR Power (in Watts)
RAN Radio Access Network
RBB Rack Bonding Busbar
RE Resident Engineer or Senior Resident Engineer
RF Radio Frequency (refer to FR)
RFI Radio Frequency Interference (refer to EMI)
RFID RF Identification (Equipment, System or Personnel)
RMC Rigid Metal Conduit
RMU Rack Mounting Unit
RPEC Radio Paging Equipment Cabinets(refer to HEC, HEIC, PA)
RTLS Real Time Location Service or System
RUS Rural Utilities Service
SCC Security Control Console (refer to PCR, SPCC)
SMCS Spectrum Management and Communications Security (COMSEC)
SFO Solicitation for Offers
SME Subject Matter Experts (refer to AHJ)
SMR Specialized Mobile Radio
SMS Security Management System
SNMP Simple Network Management Protocol
SPCC Security Police Control Center (refer to PCR, SMS)
STP Shielded Balanced Twisted Pair (refer to UTP)
STR Stacked Telecommunications Room
TAC VA’s Technology Acquisition Center, Austin, Texas
TCO Telecommunications Outlet
TER Telephone Equipment Room
TGB Telecommunications Grounding Busbar (also Secondary Bonding
Busbar (SBB))
TIP Telecommunications Infrastructure Plant
TMGB Telecommunications Main Grounding Busbar (also Primary
Bonding Busbar (PBB))
TMS Traffic Management System
TOR Telephone Operators Room
TP Balanced Twisted Pair (refer to STP and UTP)
TR Telecommunications Room (refer to STR)
TWP Twisted Pair
UHF Ultra High Frequency (Radio)
UMTS Universal Mobile Telecommunications System
UPCS Unlicensed Personal Communications Service (refer to PCS)
UPS Uninterruptible Power Supply
USC United States Code
UTP Unshielded Balanced Twisted Pair (refer to TP and STP)
UV Ultraviolet
V Volts
VAAR Veterans Affairs Acquisition Regulation
VACO Veterans Affairs Central Office
VAMC VA Medical Center (refer to CBOC, OPC, VACO)
VCCS TIP’s Vertical Cross Connection System (refer to CCS and
HCCS)
VHF Very High Frequency (Radio)
VISN Veterans Integrated Services Network (refers to geographical region)
VSWR Voltage Standing Wave Radio
W Watts
WEB World Electronic Broadcast
WiMAX Worldwide Interoperability (for MW Access)
WI-FI Wireless Fidelity
WMTS Wireless Medical Telemetry Service
WSP Wireless Service Providers
B. Definitions:
1. Access Floor: Pathway system of removable floor panels supported on adjustable pedestals to allow cable placement in area below.
2. BNC Connector (BNC): United States Military Standard MIL-C-39012/21 bayonet-type coaxial connector with quick twist mating/unmating, and two lugs preventing accidental disconnection from pulling forces on cable.
3. Bond: Permanent joining of metallic parts to form an electrically conductive path to ensure electrical continuity and capacity to safely…