Attachment_B_-_TRWRP_MCC_Replacement_Bid_Set_Submittal_Drawings.pdf
PDF 2 MB Posted
- Attached to
- TRWRP 93 Motor Control Center Replacement
- Solicitation number
- RFB-TH-0120
- Issued by
- Los Angeles County, California
About this file
This document is a set of submittal drawings for the Torrance Refinery Water Reclamation Plant (TRWRP) 93 Motor Control Center (MCC2) replacement project issued by West Basin Municipal Water District in Torrance, California. The electrical bid set includes comprehensive design documentation consisting of eight drawing sheets prepared by Hazen and Sawyer engineering firm, dated December 2025. The drawings specify the complete demolition of the existing 93MCC2 motor control center and installation of a new 480-volt replacement unit on the existing equipment pad. The project requires coordination with West Basin Operations staff for power shutdowns, protection and reuse of existing conduits and cables where viable, and identification of all cable origins and destinations during demolition to ensure proper reconnection. Contractors must verify existing underground utility locations prior to construction, conduct site visits to familiarize themselves with existing conditions, and implement proper construction sequencing as outlined in project specifications. The drawings indicate existing equipment connections including motors M-9355-01, M-9236-06, M-9326-02, M-9326-01, and pumps P-9364-02, P-9346-02, and P-9341-03 that will remain operational during the upgrade.
The electrical design requires installation of new cables in existing ductbanks and conduits, with all existing cables to be tested per electrical cable testing requirements prior to re-energization, and non-compliant cables to be replaced at contractor expense. The grounding system must achieve a maximum 48-hour dry resistance of 10 ohms, with primary building grounding consisting of an embedded grid of minimum #4/0 bare tinned copper wire installed in the foundation and around the building perimeter. All material in corrosive areas must be NEMA 4X stainless steel (316) or non-metallic, and all exposed runs of conduit must be installed parallel or perpendicular to walls and structural members with right-angle turns. The contractor bears responsibility for obtaining all necessary permits and inspections, providing all conduit and wiring for vendor-supplied equipment, modifying breaker sizes as required based on packaged system specifications, and supplying all labor, materials, equipment, and temporary facilities needed for complete project execution with no additional cost to the owner.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WEST BASIN MUNICIPAL WATER DISTRICT ENGINEERING DIVISION
TORRANCE, CALIFORNIA
TORRANCE REFINERY WATER RECLAMATION
PLANT (TRWRP) 93MCC2 REPLACEMENT
HAZEN NO.: 20011-015
DECEMBER 2025
LOCATION MAP
NOT TO SCALE
BID SET
HAZEN AND SAWYER
7700 IRVINE CENTER DRIVE, SUITE 200
IRVINE, CALIFORNIA 92618
PROJECT
LOCATION
INDEX OF DRAWINGS
DRAWING NUMBER DRAWING TITLE
GENERAL
G01 COVER SHEET
ELECTRICAL
E01 ELECTRICAL LEGEND, SYMBOLS, AND NOTES
E02 ELECTRICAL OVERALL SITE PLAN
E03 ELECTRICAL DEMOLITION PLAN
E04 ELECTRICAL DEMOLITION SINGE LINE DIAGRAM
E05 ELECTRICAL SITE PLAN
E06 ELECTRICAL SINGLE LINE DIAGRAM
E07 ELECTRICAL STANDARD DETAILS AND RISER DIAGRAMS
WIRING
ELEMENTARY CONTROL SCHEMATICS SINGLE-LINE DIAGRAMS
MISC PLAN VIEW SYMBOLS
DUCTBANK SECTION CUT IDENTIFIER:
DBXX DENOTES DUCTBANK ID
EXX DENOTES DRAWING NUMBER
WHERE SECTION CUT IS LOCATED
EQUIPMENT CONNECTION
CONDUIT HOME RUN
CONDUIT EXPOSED
CONCRETE ENCASED CONDUIT
CONDUIT CONCEALED
3-POSITION SELECTOR SWITCH:
HOA DENOTES HAND/OFF/AUTO
LOR DENOTES LOCAL/OFF/REMOTE
FOR DENOTES FORWARD/OFF/REVERSE
PUSHBUTTON SWITCHES:
LEFT: N.O.
RIGHT: N.C.
TEXT DENOTES LEGEND PLATE
EMERGENCY STOP MUSHROOM HEAD PUSHBUTTON SWITCH (N.C.):
TEXT DENOTES LEGEND PLATE
PUSHBUTTON SWITCH N.C. WITH LOCK-OUT:
TEXT DENOTES LEGEND PLATE
INDICATOR LIGHT:
LEFT: STANDARD/RIGHT: PUSH-TO-TEST
X DENOTES COLOR
RUN TIME METER
MECHANICAL INTERLOCK CONNECTION
TRANSFORMER
MOTOR AND TYPICAL ADDITIONAL DEVICES:
TSH: TEMPERATURE SWITCH
MSH: MOTOR SPACE HEATER
CF: COOLING FAN
TE: TEMPERATURE ELEMENT
ME: MOISTURE DETECTOR
FUSE
LOW-VOLTAGE POWER CIRCUIT BREAKER:
LEFT: FIXED-MOUNT
RIGHT: DRAWOUT
E.O. DENOTES ELECTRICALLY OPERATED
LSIG DENOTES INSTALLED TRIP FUNCTIONS:
L DENOTES LONG-TIME
S DENOTES SHORT-TIME
I DENOTES INSTANTANEOUS
G DENOTES GROUND FAULT
Z DENOTES ZONE-SELECTIVE INTERLOCKING
CTR DENOTES BREAKER-SPECIFIC CT AND RATIOS
GROUND
CT:
NUMBERS DENOTE CT WINDING RATIO AND CT QUANTITY
LEFT: FVNR STARTER:
X DENOTES NEMA SIZE
DP DENOTES DEFINITE PURPOSE CONTACTOR
RIGHT: FVR STARTER
EXX
DBXX
CONDUIT TAGS:
P DENOTES POWER
C DENOTES CONTROL
I DENOTES INSTRUMENTATION
XXXX DENOTES CONDUIT ID
XXX-XXX DENOTES CONDUIT ID
INSTRUMENT TAG:
X DENOTES INSTRUMENT TYPE
# DENOTES INSTRUMENT NUMBER
SEE DRAWING I1 FOR INSTRUMENT ABBREVIATIONS
X
DUCTBANK TAG:
X DENOTES DUCTBANK ID
SOLENOID VALVE
CONTROL POWER TRANSFORMER
MOTOR SPACE HEATER
SELECTOR SWITCH:
LEFT: STANDARD
RIGHT: SPRING-RETURN
TEXT DENOTES LEGEND PLATE
50:5 (1)
GFCT:
NUMBERS DENOTE GFCT WINDING RATIO AND GFCT QUANTITY
MOTOR CIRCUIT PROTECTOR
GROUND RODS:
LEFT: BURIED
RIGHT: IN TESTWELL
LEFT: CONDUIT RISE (TURN UP)
RIGHT: CONDUIT DROP (TURN DOWN)
MOTOR PROTECTION RELAY
NORC NOFC NCRO NCFO
TEMPERATURE
SWITCHES/
THERMOSTATS
PRESSURE
SWITCHES
LEVEL
SWITCHES
FLOW
SWITCHES
NOTC NOTO NCTO NCTC
TIME
DELAY
SWITCHES
NO NC
DISCONNECT
SWITCHES
NOTATION LEGEND:
NO/NC: NORMALLY OPEN/CLOSED
RO/RC: RISE-TO-OPEN/CLOSE
FO/FC: FALL-TO-OPEN/CLOSE
TO/TC: TIME-OPEN/CLOSE
CONTACTS:
TEXT DENOTES COIL ID
SWITCHES:
TEXT DENOTES TAG NUMBER
X
LIMIT
SWITCHES
TORQUE
SWITCH
CONTACTS
SOLID-STATE OVERLOAD RELAY
TSH MSH CF
TE ME
CABLE TRAY TAG:
X DENOTES CABLE TRAY ID
Y DENOTES SCHEDULE REFERENCE
X Y
AF
AT
HP RPM
DISCONNECT SWITCH
100A 3P
100A
FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MCP
30A
100A
X
DB
X
TRAY
X
Y
A
MCP
X
A
MCP
M
F R
X
LOW-VOLTAGE MOLDED CASE CIRCUIT BREAKER
LEFT: THERMAL-MAGNETIC TRIP UNIT
RIGHT: ELECTRONIC TRIP UNIT
X
NS
LS LS
TS TS
PS PSPS PS
LS LSLS LS
FS FSFS FS
TD TDTD TD
G
PTT
G
ETM
SV
MPR
MSH
CPT 480/120VAC
XFMR
kVA 480-120/208V
3P/4W
DRY TRANS
30A 3P
30A 3P
30A 3P
30A 3P
800AF
800AP
800AT
LSIGZ
CTR
N.C.
800AF
800AP
800AT
LSIGZ
CTR
N.C.
ETU
800AF
800AP
800AT
LSIG
600:5 (3)
START STOP
E-STOP
STOP - L.O.
ON OFF
H AO
XOO
OOX
P-XXXX
P-XXX-XXX
ON OFF
COIL:
X DENOTES TYPE:
M DENOTES MOTOR STARTER
CR DENOTES CONTROL RELAY
TD DENOTES TIME DELAY RELAY
TR DENOTES TIMER RANGE
TS DENOTES TIMER SETPOINT
PR DENOTES INTERPOSING PILOT RELAY
LC DENOTES LIGHTING CONTACTOR
Y DENOTES REFERENCE LINE NUMBER
EQUIPMENT/DEVICE LOCATION SYMBOLS
LOCATED AT PANEL:
X DENOTES PANEL ID:
L DENOTES LOCAL CONTROL STATION
LOCATED IN FIELD
LOCATED IN STAND-ALONE MOTOR STARTER/CONTROLLER
LOCATED IN MCC
X
XX
YYY
TR TS
THERMAL OVERLOAD RELAY
OL
SSOL
20011-015
D W
G fi le na m e:
C :\U
SE
R
S\
AT
O H
M
EH
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \2
-0
_W
ES
T
BA
SI
N
O
PE
R
AT
IO
N S
SU
PP
O R
T
\P R
O
JE
C T
FI
LE
S\
ZM
C C
R
EP
LA
C
EM
EN
T\
EL
EC
\E
.D
W G
P lo t D at e
Ti m e:
2/ 5/
:3
5:
A M tte d by
To hm eh
, A nn as
REVISIONS
NO. DATE BY
SHEET OF
PR. NO.
DATEDATE
DATE
DATE
DESIGN
DRAWN
CHECK
DIG ALERT:
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO WORKING DAYS
BEFORE YOU DIG
UNDERGROUND SERVICE ALERT OF SOUTHERN CA.
ELECTRICAL ENGINEER P. E.
WEST BASIN MUNICIPAL WATER DISTRICT
ENGINEERING DIVISION
SPECIAL NOTE:
PRECISE LOCATION OF EXISTING UNDERGROUND
UTILITIES TO BE VERIFIED
BY THE CONTRACTOR IN THE FIELD PRIOR TO
CONSTRUCTION.
DRAWING NO.
HAZEN AND SAWYER
800 W 6th STREET, SUITE 400
LOS ANGELES, CA 90017
DEC 202512/2025
12/2025 12/2025
JY
ABBREVIATIONS
AE ANALYSIS ELEMENT
AIC AMPERE INTERRUPTING CAPACITY
AIT ANALYSIS INDICATING TRANSMITTER
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
AF AMPERE FRAME
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
BC BYPASS CONTACTOR
BKR BREAKER
(L/V)CP (LOCAL/VENDOR) CONTROL PANEL
CEC CALIFORNIA ELECTRICAL CODE
CPB CONTROL PULL BOX
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
DB DUCTBANK
DSW DISCONNECT SWITCH
EF EXHAUST FAN
EHH ELECTRIC HAND HOLE
EMH ELECTRIC MANHOLE
EO ELECTRICALLY OPERATED
ETM ELAPSED TIME METER
ETU ELECTRONIC TRIP UNIT
FACP FIRE ALARM CONTROL PANEL
FS FLOW SWITCH
FSL FLOW SWITCH LOW
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRD GROUND
HOA HAND-OFF-AUTO
IC INPUT CONTACTOR
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
ISO INTERNATIONAL ORGANIZATION FOR STANDARDIZATION
JB JUNCTION BOX
LCS LOCAL CONTROL STATION
LP LIGHTING PANEL
LS LEVEL SWITCH
LSL LEVEL SWITCH LOW
LSLL LEVEL SWITCH LOW-LOW
LSH LEVEL SWITCH HIGH
LSHH LEVEL SWITCH HIGH-HIGH
LT LEVEL TRANSMITTER
MFR MULTI-FUNCTION RELAY
MH MANHOLE
MOV MOTOR OPERATED VALVE
MPR MOTOR PROTECTION RELAY
MTS MANUAL TRANSFER SWITCH
MWTS MOTOR WINDING TEMPERATURE SWITCH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSN
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
OC OUTPUT CONTACTOR
OL OVERLOAD
PB PULLBOX
PC PHOTOCELL
PCC POINT OF COMMON COUPLING
PE PRESSURE ELEMENT
PIT PRESSURE INDICATING TRANSMITTER
PLC PROGRAMMABLE LOGIC CONTROLLER
PP POWER PANEL
PT POTENTIAL TRANSFORMER
PTT PUSH TO TEST
RCS REMOTE CONTROL STATION
RECP RECEPTACLE
RIO REMOTE I/O
RM ROOM
RTD RESISTANCE THERMAL DEVICE
RTU REMOTE TELEMETRY UNIT
RVSS REDUCED VOLTAGE SOLID STATE
S.E. SERVICE ENTRANCE
SP. C. SPARE CONDUIT
SPD SURGE PROTECTIVE DEVICE
SS STAINLESS STEEL
TB TEST BLOCK
TSH TWISTED SHIELDED
TX TRANSFORMER
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
VFD VARIABLE FREQUENCY DRIVE
WPCR WEATHER PROOF CORROSION RESISTANT
WT WALK THROUGH
XFMR TRANSFORMER
NOTES
1. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY
PERMITS, INSPECTIONS AND APPROVALS AND TO
INCLUDE ALL FEES AS PART OF HIS BID IF NOT
OTHERWISE NOTED.
2. THE CONTRACTOR SHALL COORDINATE THEIR WORK
WITH THE ENGINEER, OWNER, AND OWNER'S
CONTRACT OPERATORS.
3. THE CONTRACTOR SHALL, BEFORE SUBMITTING THEIR
BID, VISIT THE SITE OF THE PROJECT AND BECOME
FAMILIAR WITH THE EXISTING CONDITIONS. NO
ALLOWANCE WILL BE MADE FOR EXISTING
CONDITIONS OR FAILURE OF THE CONTRACTOR TO
OBSERVE THEM.
4. ALL EQUIPMENT AND MATERIAL SHALL BE UNUSED
AND U.L. LISTED. ALL REFERENCES TO A PARTICULAR
MANUFACTURER ARE GIVEN ON AN "APPROVED
EQUAL" BASIS.
5. ALL EQUIPMENT FURNISHED AND INSTALLED BY THE
CONTRACTOR SHALL BE GUARANTEED AGAINST
DEFECTS IN MATERIAL AND WORKMANSHIP FOR A
PERIOD AS DESCRIBED IN THE AGREEMENT.
6. THE DRAWINGS ARE NOT INTENDED TO SHOW THE
EXACT LOCATION OF CONDUIT RUNS. THESE ARE TO
BE COORDINATED WITH THE OTHER TRADES SO THAT
CONFLICTS ARE AVOIDED PRIOR TO INSTALLATIONS.
7. ALL LOCATIONS OF EQUIPMENT, PANELS ETC. ARE
SHOWN FOR ILLUSTRATION PURPOSES. CONTRACTOR
SHALL VERIFY AND COORDINATE EXACT LOCATION
AND SIZE WITH ALL SUBCONTRACTORS AND
EQUIPMENT SUPPLIERS PRIOR TO ANY INSTALLATION
AND THEN INSTALL AS SUCH WITH CORRESPONDING
CONDUIT STUB-UPS.
8. NOT ALL CONDUITS SHOWN ON ONE-LINE DIAGRAMS
ARE SHOWN ON BUILDING LAYOUTS. CONTRACTOR
SHALL SUPPLY ALL CONDUITS AND CABLES AS SHOWN
ON ONE-LINE DIAGRAMS.
9. EXPOSED RUNS OF CONDUITS SHALL BE INSTALLED
WITH RUNS PARALLEL OR PERPENDICULAR TO WALLS,
STRUCTURAL MEMBERS OR INTERSECTIONS OF
VERTICAL PLANES AND CEILINGS, WITH RIGHT ANGLE
TURNS CONSISTING OF SYMMETRICAL BENDS OR PULL
BOXES AS INDICATED ON THE DRAWINGS. BENDS AND
OFFSETS SHALL BE AVOIDED WHERE POSSIBLE.
10. INSTRUMENTATION IS LOW VOLTAGE SIGNALS SUCH
AS 4-20MA, TELEPHONE COMMUNICATION, FIRE ALARM
COMMUNICATION. POWER CONDUIT SHALL ONLY
CROSS INSTRUMENTATION CONDUIT
PERPENDICULARLY AT RIGHT ANGLES WITH 6"
SEPARATION.
11. CONDUCTOR PULLING TENSIONS SHALL NOT EXCEED
MANUFACTURER'S RECOMMENDATION. CONTRACTOR
SHALL INSTALL PULL BOXES TO MEET
MANUFACTURER'S REQUIREMENTS.
12. MINIMUM PARALLEL DISTANCE ALLOWED BETWEEN
POWER CONDUITS AND INSTRUMENTATION CONDUITS
SHALL BE:
VOLTAGE DISTANCE
4160V 3 FT
480V 2 FT
120V 1 FT
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CONDUIT AND WIRING INSTALLATION FOR ALL VENDOR
PROVIDED EQUIPMENT (PACKAGE SYSTEMS). IF THE
SHOP DRAWINGS DIFFER FROM THE DESIGNED
FACILITIES, THE CONTRACTOR SHALL REDESIGN THE
FACILITIES AND SUBMIT THE REVISED DESIGN FOR THE
ENGINEER'S APPROVAL ALONG WITH THE SHOP
DRAWINGS. THERE SHALL BE NO ADDITIONAL COST TO
THE OWNER FOR THE REDESIGN NOR FOR ANY
ADDITIONAL CONDUITS AND WIRING. DURING
SUBMITTAL THE CONTRACTOR SHALL VERIFY ALL
SUPPLIED BREAKER SIZES FOR ALL PACKAGED
SYSTEMS SUCH AS HVAC, EXHAUST FANS, MIXERS,
CHEMICAL PUMPS ETC. AND MODIFY ALL BREAKERS IN
MCC'S AND PANELBOARDS ACCORDINGLY WITHOUT
ANY ADDITIONAL COST TO THE OWNER.
14. GROUNDING SHALL BE INSTALLED IN ACCORDANCE
WITH CEC AND NEC ARTICLE 250. THE GROUNDING
SYSTEM TEST SHALL NOT EXCEED A 48 HOUR SPAN
DRY RESISTANCE OF 10 OHMS. ADDITIONAL
GROUNDING TO MEET THIS REQUIREMENT SHALL BE
INSTALLED AT NO EXTRA COST. GROUNDING AND
BONDING CONNECTIONS SHALL NOT BE PAINTED. ALL
GROUNDING CONNECTIONS SHALL BE EXOTHERMIC
UNLESS SPECIFICALLY INDICATED OTHERWISE.
15. AN EQUIPMENT GROUND WIRE SIZED PER CEC SHALL
BE PULLED IN ALL ELECTRICAL CONDUITS, POWER
AND CONTROL, WHETHER OR NOT INDICATED ON THE
PLANS. CONNECT GROUNDING OF ALL INSTRUMENT IN
THE FIELD TO THE NEAREST GROUNDING GRID. IF
THERE IS NO GROUNDING GRID NEAR THE
INSTRUMENT, DRIVE A NEW GROUND ROD INTO THE
GROUND AND CONNECT TO THE INSTRUMENT.
16. A SEPARATE EQUIPMENT GROUNDING CONDUCTOR
SHALL BE PROVIDED FOR EACH CIRCUIT (SEPARATE
CONDUCTOR IN THE CONDUIT). THE CONDUCTOR
SHALL BE TERMINATED AT THE PROPER DEVICE,
TERMINAL, OR LUG AT THE POWER SOURCE (MCC
GROUND BUS, PANELBOARD GROUND BUS, ETC.).
GROUND CONDUCTOR SIZE SHALL BE PER THE LATEST
EDITION OF THE NEC.
E01
LEGEND, SYMBOLS, AND NOTES
ELECTRICAL
JY
AT
DL
NOTES, CONT'D.
18. ALL ENCLOSURES, TERMINATION JUNCTION BOXES,
WIREWAY, PULL BOXES ETC. SHALL CONTAIN A
GROUNDING BUS. CONNECT ALL RACEWAY BONDS TO
THIS BUS VIA GROUNDING BUSHING AND EXTEND
BONDING JUMPER FROM THIS BUS TO THE
ENCLOSURE.
19. PRIMARY BUILDING GROUNDING SHALL BE AN
EMBEDDED GRID OF MINIMUM #4/0 BARE TINNED
COPPER (BTC) AWG WIRE INSTALLED IN THE
FOUNDATION AND AROUND THE BUILDING PERIMETER
TO FORM A COMPLETE LOOP. BOND #4/0 BARE TINNED
COPPER (BTC) AWG WIRE WITH MAJOR ELECTRICAL
EQUIPMENT SUCH AS MAIN, ATS, SWITCHBOARD,
TRANSFORMERS TO THE PRIMARY BUILDING
GROUNDING LOOP. SECONDARY GROUND
CONNECTIONS TO ALL OTHER METAL EQUIPMENT,
HAND RAILS, STRUCTURAL STEEL, CONCRETE PADS,
REBAR ETC. SHALL HAVE A MINIMUM #4 BTC
STRANDED COPPER CONDUCTOR BONDED USING
APPROVED LUGS OR EXOTHERMIC CONNECTIONS. ALL
EQUIPMENT GROUNDING CONDUCTORS PENETRATING
CONCRETE SLABS OR FINISHED GRADE SHALL HAVE A
72" CONDUCTOR PIGTAIL AT EACH LOCATION FOR
CONNECTION TO EQUIPMENT.
20. PROVIDE CONDUIT DUCT SEAL AT ALL CONDUIT ENDS.
21. ALL SPARE CONDUITS SHALL BE SEALED WITH A CAP
AT BOTH ENDS AND A PULL STRING INSTALLED WITH
IDENTIFICATION ON BOTH ENDS.
22. FLEXIBLE CONDUITS SHALL BE USED TO TERMINATE
ALL MOTORS AND OTHER VIBRATING EQUIPMENT AND
SHALL BE BETWEEN 18" AND 3' IN LENGTH.
23. ALL MATERIAL IN DESIGNATED CORROSIVE AREAS
SHALL BE NEMA 4X STAINLESS STEEL OR
NON-METALLIC.
24. ALL REFERENCES TO SS OR STAINLESS STEEL SHALL
BE 316 STAINLESS STEEL.
25. BOND ALL NEW CONCRETE ENCASED GROUND
CONDUCTORS TO EXISTING GROUND CONDUCTORS IN
ALL MANHOLES, PULL BOXES, CABLE TRAYS, AND
SIMILAR LOCATIONS WHERE APPLICABLE.
26. UNLESS OTHERWISE SPECIFIED OR NOTED, ALL WALL
MOUNTED ELECTRICAL PANELS, ENCLOSURES, AND
SIMILAR EQUIPMENT SHALL BE MOUNTED 6'-6" (MAX)
FROM THE TOP OF THE PANEL TO FINISHED FLOOR OR
GRADE.
27. UNLESS OTHERWISE NOTED, ALL LIGHTING SWITCHES,
CONTROL SWITCHES, AND SIMILAR EQUIPMENT SHALL
BE MOUNTED WITH THEIR CENTERLINE
APPROXIMATELY 4'-0" ABOVE FINISHED FLOOR, SLAB,
OR GRADE.
SURGE PROTECTIVE DEVICESPD
XXXkA
12-5-2025
HHC9
HHC7
H H
P3
H H
P4
HHC5
HHP5
HHC8
H H
P1
HHC1
HHC4
TRANSITION
H H
C
HHC3
HHP2
FRONT
FRONT
FRONT
20011-015
D W
G fi le na m e:
C :\U
SE
R
S\
AT
O H
M
EH
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \2
-0
_W
ES
T
BA
SI
N
O
PE
R
AT
IO
N S
SU
PP
O R
T
\P R
O
JE
C T
FI
LE
S\
ZM
C C
R
EP
LA
C
EM
EN
T\
EL
EC
\E
.D t D at e
Ti m e:
2/ 5/
:3
5:
tte d by
To hm eh
, A nn as
REVISIONS
NO. DATE BY
SHEET OF
PR. NO.
DATEDATE
DATE
DATE
DESIGN
DRAWN
CHECK
DIG ALERT:
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO WORKING DAYS
BEFORE YOU DIG
UNDERGROUND SERVICE ALERT OF SOUTHERN CA.
ELECTRICAL ENGINEER P. E.
WEST BASIN MUNICIPAL WATER DISTRICT
ENGINEERING DIVISION
SPECIAL NOTE:
PRECISE LOCATION OF EXISTING UNDERGROUND
UTILITIES TO BE VERIFIED
BY THE CONTRACTOR IN THE FIELD PRIOR TO
CONSTRUCTION.
DRAWING NO.
HAZEN AND SAWYER
800 W 6th STREET, SUITE 400
LOS ANGELES, CA 90017
DEC 202512/2025
12/2025 12/2025
JY
E02
OVERALL SITE PLAN
ELECTRICAL
JY
AT
DL
ELECTRICAL OVERALL SITE PLAN
SCALE: 1" = 20'
ELECTRICAL SITE PLAN
SEE DRAWING E03 AND E05
20011-015
D W
G fi le na m e:
C :\U
SE
R
S\
AT
O H
M
EH
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \2
-0
_W
ES
T
BA
SI
N
O
PE
R
AT
IO
N S
SU
PP
O R
T
\P R
O
JE
C T
FI
LE
S\
ZM
C C
R
EP
LA
C
EM
EN
T\
EL
EC
\E
.D t D at e
Ti m e:
2/ 5/
:3
5:
tte d by
To hm eh
, A nn as
REVISIONS
NO. DATE BY
SHEET OF
PR. NO.
DATEDATE
DATE
DATE
DESIGN
DRAWN
CHECK
DIG ALERT:
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO WORKING DAYS
BEFORE YOU DIG
UNDERGROUND SERVICE ALERT OF SOUTHERN CA.
ELECTRICAL ENGINEER P. E.
WEST BASIN MUNICIPAL WATER DISTRICT
ENGINEERING DIVISION
SPECIAL NOTE:
PRECISE LOCATION OF EXISTING UNDERGROUND
UTILITIES TO BE VERIFIED
BY THE CONTRACTOR IN THE FIELD PRIOR TO
CONSTRUCTION.
DRAWING NO.
HAZEN AND SAWYER
800 W 6th STREET, SUITE 400
LOS ANGELES, CA 90017
DEC 202512/2025
12/2025 12/2025
JY
NOTES:
1. EXISTING MOTOR CONTROL CENTER 93MCC2 "91MCC2" SHALL
BE REMOVED AND NEW MOTOR CONTROL CENTER 93MCC2
SHALL BE INSTALLED. SEE DRAWING E05 FOR LOCATION OF
NEW MOTOR CONTROL CENTER.
2. REFERENCE SPECIFICATIONS FOR CONSTRUCTION
SEQUENCING REQUIREMENTS.
3. THE CONTRACTOR SHALL COORDINATE REMOVAL OF
EXISTING MOTOR CONTROL CENTER 93MCC2 "91MCC2" WITH
WEST BASIN OPERATIONS AND STAFF. CONTRACTOR SHALL
FOLLOW PROPER PROCEDURES, SEQUENCING OF WORK AND
SHUTDOWN REQUIREMENTS AS DESCRIBED BY THE PROJECT
DRAWINGS AND SPECIFICATIONS TO ALLOW DISCONNECTION
OF ALL EXISTING POWER AND CONTROL WIRE ASSOCIATED
WITH EXISTING MOTOR CONTROL CENTER 93MCC2 "91MCC2".
4. PRIOR TO PERFORMING A SHUTDOWN THE CONTRACTOR
SHALL COORDINATE WITH THE OWNER ON DURATION OF
POWER SHUTDOWNS AND PROVIDE THE NECESSARY
TEMPORARY POWER AS REQUIRED.
5. EXISTING CONDUITS SHALL BE PROTECTED AND PREPARED
FOR REUSE DURING THE REMOVAL OF EQUIPMENT.
6. EXISTING POWER AND CONTROL CABLES ASSOCIATED WITH
THE EQUIPMENT TO BE DEMOLISHED SHALL BE
DE-TERMINATED AND BE PROTECTED AND PREPARED FOR
REUSE. THE REUSE OF POWER AND CONTROL CABLES SHALL
FOLLOW APPROVED METHODS DESCRIBED IN THE PROJECT
SPECIFICATIONS.
7. ALL EXISTING CABLES TO BE REUSED SHALL BE TESTED PER
ELECTRICAL CABLE TESTING REQUIREMENTS IN THE
PROJECT SPECIFICATION PRIOR TO RE-ENERGIZING.
EXISTING CABLES THAT FAIL TO MEET TESTING
REQUIREMENTS SHALL BE REPLACED.
8. FOR EXISTING CABLES IDENTIFIED FOR REUSE BY THE
PROJECT DRAWINGS, THE CONTRACTOR SHALL IDENTIFY THE
ORIGIN AND DESTINATION OF EACH EXISTING CABLE DURING
DEMOLITION IN ORDER TO PROPERLY RECONNECT TO
EQUIPMENT.
9. EXISTING CONTROL PANEL ACP-93 "PLC 93" IS LOCATED
INSIDE TRAILER.
SECTION
DEMOLITION
A
93 SB1 (EXISTING)93MCC1 (EXISTING)
93MCC2 "91MCC2" (EXISTING)
M-9355-01 (EXISTING)
M-9236-06 (EXISTING)
M-9326-02 (EXISTING)
M-9326-01 (EXISTING)
P-9364-02 (EXISTING)
P-9346-02 (EXISTING) P-9341-03 (EXISTING)
HIGH SERVICE PUMP 3
MOTOR STARTER (EXISTING)
E03
DEMOLITION PLAN
ELECTRICAL
JY
AT
DL
ELECTRICAL DEMOLITION PLAN
SCALE: 1/8" = 1'
WASH WATER
SURGE BASIN
TRAILER
HIGH SERVICE &
BWS PUMP STATION
RESERVOIR
BIOFOR UNITS
CO2 TANK
A
THIS DWG.
VFD-P-9341-02 (EXISTING)
AFD-P-9341-01 (EXISTING)
SEE NOTE 9
W
G fi le na m e:
C :\U
SE
R
S\
AT
O H
M
EH
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \2
-0
_W
ES
T
BA
SI
N
O
PE
R
AT
IO
N S
SU
PP
O R
T
\P R
O
JE
C T
FI
LE
S\
ZM
C C
R
EP
LA
C
EM
EN
T\
EL
EC
\E
.D t D at e
Ti m e:
2/ 5/
:3
5:
tte d by
To hm eh
, A nn as
REVISIONS
NO. DATE BY
SHEET OF
PR. NO.
DATEDATE
DATE
DATE
DESIGN
DRAWN
CHECK
DIG ALERT:
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO WORKING DAYS
BEFORE YOU DIG
UNDERGROUND SERVICE ALERT OF SOUTHERN CA.
ELECTRICAL ENGINEER P. E.
WEST BASIN MUNICIPAL WATER DISTRICT
ENGINEERING DIVISION
SPECIAL NOTE:
PRECISE LOCATION OF EXISTING UNDERGROUND
UTILITIES TO BE VERIFIED
BY THE CONTRACTOR IN THE FIELD PRIOR TO
CONSTRUCTION.
DRAWING NO.
HAZEN AND SAWYER
800 W 6th STREET, SUITE 400
LOS ANGELES, CA 90017
DEC 202512/2025
12/2025 12/2025
JY
NOTES:
1. EXISTING MOTOR CONTROL CENTER 93MCC2 "91MCC2"
SHALL BE REMOVED AND NEW MOTOR CONTROL
CENTER 93MCC2 SHALL BE INSTALLED. SEE DRAWING
E05 FOR LOCATION OF NEW MOTOR CONTROL
CENTER.
2. REFERENCE SPECIFICATIONS FOR CONSTRUCTION
SEQUENCING REQUIREMENTS.
3. THE CONTRACTOR SHALL COORDINATE REMOVAL OF
EXISTING MOTOR CONTROL CENTER 93MCC2 "91MCC2"
WITH WEST BASIN OPERATIONS AND STAFF.
CONTRACTOR SHALL FOLLOW PROPER PROCEDURES,
SEQUENCING OF WORK AND SHUTDOWN
REQUIREMENTS AS DESCRIBED BY THE PROJECT
DRAWINGS AND SPECIFICATIONS TO ALLOW
DISCONNECTION OF ALL EXISTING POWER AND
CONTROL WIRE ASSOCIATED WITH EXISTING MOTOR
CONTROL CENTER 93MCC2 "91MCC2".
4. THE CONTRACTOR SHALL COORDINATE WITH THE
OWNER ON DURATION OF POWER SHUTDOWNS AND
PROVIDE THE NECESSARY TEMPORARY POWER AS
REQUIRED.
5. EXISTING CONDUITS SHALL BE PROTECTED AND
PREPARED FOR REUSE DURING THE REMOVAL OF
EQUIPMENT.
6. EXISTING POWER AND CONTROL CABLES IDENTIFIED
FOR REUSE SHALL BE DE-TERMINATED AND BE
PROTECTED. THE REUSE OF POWER AND CONTROL
CABLES SHALL FOLLOW APPROVED METHODS
DESCRIBED IN THE PROJECT SPECIFICATIONS.
7. ALL EXISTING CABLES TO BE REUSED SHALL BE
TESTED PER ELECTRICAL CABLE TESTING
REQUIREMENTS IN THE PROJECT SPECIFICATION
PRIOR TO RE-ENERGIZING. EXISTING CABLES THAT
FAIL TO MEET TESTING REQUIREMENTS SHALL BE
REPLACED.
8. FOR EXISTING CABLES IDENTIFIED FOR REUSE BY THE
PROJECT DRAWINGS, THE CONTRACTOR SHALL
IDENTIFY THE ORIGIN AND DESTINATION OF EACH
EXISTING CABLE DURING DEMOLITION IN ORDER TO
PROPERLY RECONNECT TO EQUIPMENT.
9. EXISTING CONDUITS ASSOCIATED WITH THE
EQUIPMENT TO BE DEMOLISHED SHALL BE
PROTECTED AND PREPARED FOR REUSE. THE REUSE
OF CONDUITS SHALL FOLLOW APPROVED METHODS
DESCRIBED IN THE PROJECT SPECIFICATIONS.
E04
DEMOLITION SINGLE LINE DIAGRAM
ELECTRICAL
JY
AT
DL
93MCC2
(SEE NOTE 1 AND 6)
20011-015
D W
G fi le na m e:
C :\U
SE
R
S\
AT
O H
M
EH
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \2
-0
_W
ES
T
BA
SI
N
O
PE
R
AT
IO
N S
SU
PP
O R
T
\P R
O
JE
C T
FI
LE
S\
ZM
C C
R
EP
LA
C
EM
EN
T\
EL
EC
\E
.D t D at e
Ti m e:
2/ 5/
:3
5:
tte d by
To hm eh
, A nn as
REVISIONS
NO. DATE BY
SHEET OF
PR. NO.
DATEDATE
DATE
DATE
DESIGN
DRAWN
CHECK
DIG ALERT:
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO WORKING DAYS
BEFORE YOU DIG
UNDERGROUND SERVICE ALERT OF SOUTHERN CA.
ELECTRICAL ENGINEER P. E.
WEST BASIN MUNICIPAL WATER DISTRICT
ENGINEERING DIVISION
SPECIAL NOTE:
PRECISE LOCATION OF EXISTING UNDERGROUND
UTILITIES TO BE VERIFIED
BY THE CONTRACTOR IN THE FIELD PRIOR TO
CONSTRUCTION.
DRAWING NO.
HAZEN AND SAWYER
800 W 6th STREET, SUITE 400
LOS ANGELES, CA 90017
DEC 202512/2025
12/2025 12/2025
JY
93 SB1 (EXISTING)93MCC1 (EXISTING)
M-9355-01 (EXISTING)
P-9364-02 (EXISTING)
P-9346-02 (EXISTING) P-9341-03 (EXISTING)
M-9326-02 (EXISTING)
M-9326-01 (EXISTING)M-9236-06 (EXISTING)
NOTES:
1. MOTOR CONTROL CENTER 93MCC2 SHALL BE SIMILAR
TO MAKE AND MODEL OF RECENTLY REPLACED
93MCC1. REFER TO 93MCC1 SHOP DRAWINGS
ATTACHED TO SPECIFICATIONS FOR REFERENCE.
2. ALL EXISTING CABLES TO BE REUSED SHALL BE
TESTED PER ELECTRICAL CABLE TESTING
REQUIREMENTS IN THE PROJECT SPECIFICATION
PRIOR TO RE-ENERGIZING. EXISTING CABLES THAT
FAIL TO MEET TESTING REQUIREMENTS SHALL BE
REPLACED.
3. FOR EXISTING CABLES IDENTIFIED FOR REUSE BY THE
PROJECT DRAWINGS, THE CONTRACTOR SHALL
IDENTIFY THE ORIGIN AND DESTINATION OF EACH
EXISTING CABLE DURING DEMOLITION IN ORDER TO
PROPERLY RECONNECT TO EQUIPMENT.
4. EXISTING DUCTBANKS ARE NOT SHOWN ON PLANS.
CABLES ARE ROUTED IN EXISTING DUCTBANKS FROM
93MCC2 TO THE LOADS AS IDENTIFIED ON THE SINGLE
LINE DIAGRAM.
5. EXISTING CONTROL PANEL ACP-93 "PLC 93" IS
LOCATED INSIDE TRAILER.
6. MCC 93MCC2 SHALL BE INSTALLED ON EXISTING
EQUIPMENT PAD. IF MODIFICATIONS TO EXISTING
EQUIMPENT PAD ARE REQUIRED TO ALLOW FOR THE
INSTALLATION OF 93MCC2 IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO MAKE
THOSE MODIFICATIONS.
E05
SITE PLAN
ELECTRICAL
JY
AT
DL
ELECTRICAL SITE PLAN
SCALE: 1/8" = 1'
WASH WATER
SURGE BASIN
TRAILER
CO2 TANK
HIGH SERVICE &
BWS PUMP STATION
BIOFOR UNITS
AFD- P-9341-01 (EXISTING)
VFD- P-9341-02 (EXISTING)
RESERVOIR
SEE NOTE 5
W
G fi le na m e:
C :\U
SE
R
S\
AT
O H
M
EH
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \2
-0
_W
ES
T
BA
SI
N
O
PE
R
AT
IO
N S
SU
PP
O R
T
\P R
O
JE
C T
FI
LE
S\
ZM
C C
R
EP
LA
C
EM
EN
T\
EL
EC
\E
.D t D at e
Ti m e:
2/ 5/
:3
5:
tte d by
To hm eh
, A nn as
REVISIONS
NO. DATE BY
SHEET OF
PR. NO.
DATEDATE
DATE
DATE
DESIGN
DRAWN
CHECK
DIG ALERT:
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO WORKING DAYS
BEFORE YOU DIG
UNDERGROUND SERVICE ALERT OF SOUTHERN CA.
ELECTRICAL ENGINEER P. E.
WEST BASIN MUNICIPAL WATER DISTRICT
ENGINEERING DIVISION
SPECIAL NOTE:
PRECISE LOCATION OF EXISTING UNDERGROUND
UTILITIES TO BE VERIFIED
BY THE CONTRACTOR IN THE FIELD PRIOR TO
CONSTRUCTION.
DRAWING NO.
HAZEN AND SAWYER
800 W 6th STREET, SUITE 400
LOS ANGELES, CA 90017
DEC 202512/2025
12/2025 12/2025
JY
3C 2C 1C 1F 3F 2F 4J 3J
NOTES:
1. MOTOR CONTROL CENTER 93MCC2 SHALL BE SIMILAR
TO MAKE AND MODEL OF RECENTLY REPLACED
93MCC1. REFER TO 93MCC1 SHOP DRAWINGS
ATTACHED TO SPECIFICATIONS FOR REFERENCE.
2. ALL EXISTING CABLES TO BE REUSED SHALL BE
TESTED PER ELECTRICAL CABLE TESTING
REQUIREMENTS IN THE PROJECT SPECIFICATION
PRIOR TO RE-ENERGIZING. EXISTING CABLES THAT
FAIL TO MEET TESTING REQUIREMENTS SHALL BE
REPLACED.
3. FOR EXISTING CABLES IDENTIFIED FOR REUSE BY THE
PROJECT DRAWINGS, THE CONTRACTOR SHALL
IDENTIFY THE ORIGIN AND DESTINATION OF EACH
EXISTING CABLE DURING DEMOLITION IN ORDER TO
PROPERLY RECONNECT TO EQUIPMENT.
4. CONTRACTOR SHALL INSTALL NEW CABLES IN
EXISTING CONDUITS AS IDENTIFIED ON DRAWING.
5. CONTRACTOR SHALL DETERMINE IF EXISTING
CONDUITS ASSOCIATED WITH THE INSTALLATION OF
THE NEW EQUIPMENT ARE VIABLE FOR REUSE. IF
EXISTING CONDUITS ARE NOT VIABLE FOR REUSE
CONTRACTOR SHALL NOTIFY OWNER AND BE
RESPONSIBLE FOR INSTALLATION OF NEW CONDUITS.
4A
E06
SINGLE LINE DIAGRAM
ELECTRICAL
JY
AT
DL
SECTION 1 SECTION 2 SECTION 3 SECTION 4
3C1C
1F
2C
2F
3F
4A
3J 4J
SPACE SPACE
SPACE
4E
SPD
4E
SPACE
M
L
K
J
H
G
F
E
D
C
B
A
SPACE
1 2 3 4
SPACE
W
G fi le na m e:
C :\U
SE
R
S\
AT
O H
M
EH
\D C
\A C
C D
O C
S\ H
AZ
EN
A N
D S
AW
YE
R \2
-0
_W
ES
T
BA
SI
N
O
PE
R
AT
IO
N S
SU
PP
O R
T
\P R
O
JE
C T
FI
LE
S\
ZM
C C
R
EP
LA
C
EM
EN
T\
EL
EC
\E
.D t D at e
Ti m e:
2/ 5/
:3
5:
tte d by
To hm eh
, A nn as
REVISIONS
NO. DATE BY
SHEET OF
PR. NO.
DATEDATE
DATE
DATE
DESIGN
DRAWN
CHECK
DIG ALERT:
DIAL TOLL FREE
1-800-227-2600
AT LEAST TWO WORKING DAYS
BEFORE YOU DIG
UNDERGROUND SERVICE ALERT OF SOUTHERN CA.
ELECTRICAL ENGINEER P. E.
WEST BASIN MUNICIPAL WATER DISTRICT
ENGINEERING DIVISION
SPECIAL NOTE:
PRECISE LOCATION OF EXISTING UNDERGROUND
UTILITIES TO BE VERIFIED
BY THE CONTRACTOR IN THE FIELD PRIOR TO
CONSTRUCTION.
DRAWING NO.
HAZEN AND SAWYER
800 W 6th STREET, SUITE 400
LOS ANGELES, CA 90017
DEC 202512/2025
12/2025 12/2025
JY
E07
STANDARD DETAILS AND
RISER DIAGRAMS
ELECTRICAL
JY
AT
DL
NOTES:
1. EQUIPMENT GROUNDING CONDUCTOR LUG SHALL BE ATTACHED WITH NUT AND
LOCKWASHER TO THE MOTOR GROUNDING STUD. WHERE PROVIDED, FACTORY
INSTALLED EQUIPMENT GROUNDING CONDUCTOR LUGS ARE ACCEPTABLE IN
LIEU OF THE FIELD INSTALLED EQUIPMENT GROUNDING CONDUCTOR LUG.
2. RING TERMINALS ON MOTOR LEADS SHALL BE FACTORY INSTALLED BY THE
MOTOR MANUFACTURER.
3. INSTALL SHORT BARREL COMPRESSION CONNECTOR ON FIELD WIRING WITH
MANUFACTURER'S RECOMMENDED COMPRESSION TOOL AND CRIMPING DIE.
CONNECTORS SHALL HAVE SMOOTHLY ROUNDED EDGES.
4. HEAT SHRINK OR COLD APPLIED CONNECTOR INSULATION LISTED FOR THE
PURPOSE AND AS SPECIFIED.
LOW VOLTAGE MOTOR TERMINATION
E-26-0301
EQUIPMENT GROUNDING
CONDUCTOR LUG, SEE
NOTE 1
MOTOR
TERMINATION BOX
RING TERMINAL
CONNECTION
INSULATION,
SEE NOTE 4
SS NUT, BOLT AND
LOCKWASHER
SHORT BARREL ONE-HOLE
COMPRESSION LUG
MOTOR WIRING
CONNECTIONS
MOTOR LEAD WIRING
FIELD WIRING
MSH
HP
HOA G
LCS
NOTES:
1. CONTRACTOR SHALL INSTALL NEW POWER CABLES IN
EXISTING CONDUIT AS IDENTIFIED ON RISER
DIAGRAMS.
2. CONTRACTOR SHALL UTILIZE EXISTING POWER
CABLES AND CONDUITS AS IDENTIFIED ON RISER
DIAGRAMS.
3. CONTRACTOR SHALL UTILIZE EXISTING CONTROL
CABLES AND CONDUITS AS IDENTIFIED ON RISER
DIAGRAMS AND BE RESPONSIBLE FOR INSTALLING A
COMPLETE FUNCTIONING CONTROL SYSTEM.
ELEMENTARY CONTROL SCHEMATICS ARE PROVIDED
FOR INFORMATION ONLY. SEE APPENDICES FOR
ADDITIONAL INFORMATION.
4. REFER TO SINGLE LINE DIAGRAM FOR 93MCC2 ON
DRAWING E-06 REGARDING CONDUIT AND CABLE
SIZES.
5. CONTRACTOR SHALL FIELD VERIFY AND IDENTIFY THE
MAIN POWER SOURCE FOR THE MOTOR SPACE
HEATER AND BE RESPONSIBLE FOR INSTALLING A
COMPLETE FUNCTIONING SYSTEM.
6. RISER DIAGRAMS ARE INTENDED TO GIVE
CONTRACTOR GENERAL INFORMATION BETWEEN
CONNECTIONS OF EXISTING AND NEW EQUIPMENT.
CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS BEFORE PERFORMING ALL WORK.
7. NEW MOTOR CONTROL CENTER MOTOR STARTERS
SHALL BE IDENTICAL IN FUNCTION TO EXISTING
MOTOR CONTROL CENTER MOTOR STARTERS AND
SHALL MAINTAIN ALL CURRENT MOTOR CONTROL
FUNCTIONS.
P-9341-03
HOA
LCS
M-9326-06 M-9326-01 M-9326-02
HP
FROM 93 SB1
SEE NOTE 3 SEE NOTE 393MCC2
(SEE NOTE 7) ACP-93 "PLC 93" ACP-93 "PLC 93"
93MCC2
(SEE NOTE 7)
SE
E
N O
TE
SE
E
N O
TE
2#
G R
D (S
EE
N
O
TE
A
N D
SE
E
N O
TE
A N
D
LCS
P-9355-01
FROM 93 SB1
SEE NOTE 393MCC2
(SEE NOTE 7) ACP-93 "PLC 93"
SE
E
N O
TE
HOA
HP
HOA G
LCS
P-9364-02
FROM 93 SB1
SEE NOTE 393MCC2
(SEE NOTE 7) ACP-93 "PLC 93"
SE
E
N O
TE
SE
E
N O
TE
A N
D
FROM 93 SB1
SE
E
N O
TE
A N
D
MSH
HP
2#
G R
D (S
EE
N
O
TE
A
N D
SE
E
N O
TE
A N
D
File details come from the government source that posted it. Updated .