This document contains equipment specifications and schedules for chiller replacement projects at multiple facilities operated by the Armed Forces Retirement Home. Key details include specifications for chillers, cooling towers, air handlers, pumps, and other mechanical equipment to be provided by vendors. Offerors must submit quotes by 2:00 PM EST on September 9, 2020 in response to solicitation RFQ-AFRHW-22-0001 issued by the Department of the Treasury Bureau of the Fiscal Service on behalf of the Armed Forces Retirement Home. The solicitation seeks replacement of 3 chillers and 1 cooling tower located at various AFRH facilities, with an anticipated period of performance of 60-90 days after award. While the solicitation is currently only for equipment, vendors are asked to provide information on their installation capabilities or recommended installation vendors. The requirement is set aside exclusively for small businesses under NAICS code 238220.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NAME:

B

IM

/A

F R

H -0

S h e rm a n B u ild in g C h ill e r

R e p la c e m e n t/ A

F R

H -0

M

E P

.r v t

/1

/2

:2

:0

P

M

SHERMAN BUILDING

CHILLER REPLACEMENT

CH-1 DAIKIN WMC048SDSNA

NORTH

CONVERTER

CENTRIFUGAL, WATER

COOLED

147.3 79 43.5 142.3 53.82 44 358.9 85 94.3 455.5 138 100.6 300 460/3/60

MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F)

FLOW

(GPM)

RLA (A) KW MOCP (A) V/PH/HZ

MARK

BASIS OF DESIGN

LOCATION TYPE TONS

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

EVAPORATOR CONDENSER ELECTRICAL

CHILLER SCHEDULE

HX-1 BELL & GOSSETT AP47

NORTH

CONVERTER

GASKETED, WATER 2,284.25 72.5 20.5 39.4 150 2,610 61.65 49 360 46 56 455

MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F) FLOW (GPM)

MARK

BASIS OF DESIGN

LOCATION TYPE CAPACITY (MBH)

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

DESIGN

PRESSURE

(PSI)

WEIGHT

(LBS)

EVAPORATOR CONDENSER

PLATE AND FRAME HEAT EXCHANGER SCHEDULE

CT-1 EVAPCO AT 19-3G8

NORTH

CONVERTER

(OUTDOORS)

AIR COOLED,

COUNTER FLOW

150 2,250 450 95 85 7.5 8.5 11.7 6,200 6.7 5 460/3/60

MANUFACTURER MODEL

MARK

BASIS OF DESIGN

LOCATION TYPE TONS CAPACITY (MBH)

CIRCULATING WATER

FLOW (GPM)

EWT (DEG F) LWT (DEG F)

LENGTH

(FT)

WIDTH (FT) HEIGHT (FT)

WEIGHT

(LBS)

FLA/MOTOR HP/MOTOR V/PH/HZ

COOLING TOWER SCHEDULE

AS-1

AMERICAN

WHEATLEY

TASS006 NORTH CONVERTER 44.625 28 20 6 150 220

MANUFACTURER MODEL

MARK

BASIS OF DESIGN

LOCATION HEIGHT (IN)

WIDTH WITH FLANGES

(IN)

DIAMETER

(IN)

CONNECTION SIZE

(IN)

WORKING PRESSURE

(PSI)

WEIGHT

(LBS)

AIR SEPARATOR

ET-1

AMERICAN

WHEATLEY

BDT-026 NORTH CONVERTER 16 40 16 3/4 150 98

MANUFACTURER MODEL

MARK

BASIS OF DESIGN

LOCATION

ACCEPTANCE VOLUME

(GAL)

HEIGHT (IN)

DIAMETER

(IN)

CONNECTION SIZE

(IN)

WORKING PRESSURE

(PSI)

WEIGHT

(LBS)

EXPANSION TANK

HWP-2 BELL & GOSSETT BG-E1510-5GB-SS-324T-L HEATING WATER NORTH CONVERTER END SUCTION, VFD 324T 120 1000 29.5 24.6 56 81.2 40 38 1770 460/60

HWP-1 BELL & GOSSETT BG-E1510-5GB-SS-324T-L HEATING WATER NORTH CONVERTER END SUCTION, VFD 324T 120 1000 29.5 24.6 56 81.2 40 38 1770 460/60

CWP-2 BELL & GOSSETT BG-E1532-300BD-213-SS CONDENSER WATER NORTH CONVERTER END SUCTION, VFD 213JM 50 460 15.5 20.63 26 80.7 10 7.34 1770 460/60

CWP-1 BELL & GOSSETT BG-E1532-300BD-213-SS CONDENSER WATER NORTH CONVERTER END SUCTION, VFD 213JM 50 460 15.5 20.63 26 80.7 10 7.34 1770 460/60

CHWP-2 BELL & GOSSETT BG-E1532-300GB-256-SS CHILLED WATER NORTH CONVERTER END SUCTION, VFD 256JM 120 360 19.5 21.07 29.11 72.3 20 15 1750 460/60

CHWP-1 BELL & GOSSETT BG-E1532-300GB-256-SS CHILLED WATER NORTH CONVERTER END SUCTION, VFD 256JM 120 360 19.5 21.07 29.11 72.3 20 15 1750 460/60

MANUFACTURER MODEL V/HZ

MARK

BASIS OF DESIGN

SYSTEM LOCATION TYPE FRAME HEAD (FT)

FLOW

(GPM)

HEIGHT (IN) WIDTH (IN)

LENGTH

(IN)

EFFICIENCY (%) HP BHP RPM

ELECTRICAL

PUMP SCHEDULE

AHU-4 DAIKIN CAH017GDCM

SHERMAN SOUTH

ATTIC

SXA-1600-MW 0.25 460/60/3 3000 0.75 4.07 52 68 254 2 3.3 2.83 208/60/3 15 9.2 4.1 2500 0.5 1.95 52 68 138 1 2.3 1.18 460/60/3 15 6.8 3

AHU-3 DAIKIN CAH008GDCM

SHERMAN ANNEX

ATTIC

- - - 3500 0.75 2.75 42 46 168 1 3.5 2.22 208/60/3 20 12.92 9.95 - - - - - - - - - - - - -

AHU-2 DAIKIN CAH012GDCM

SHERMAN NORTH

ATTIC

- - - 5000 0.75 2.67 46 56 172 1 3.5 3.15 208/60/3 20 12.92 9.95 - - - - - - - - - - - - -

AHU-1 DAIKIN CAH012GDCM

SHERMAN NORTH

ATTIC

- - - 5000 0.75 2.67 46 56 172 1 3.5 3.15 208/60/3 20 12.92 9.95 - - - - - - - - - - - - -

HP V/HZ/PH EXTERNAL (IN. WC) TOTAL (IN. WC) HEIGHT (IN) WIDTH (IN) LENGTH (IN) HP BHP V/HZ/PH MOP MCA FLA EXTERNAL (IN. WC) TOTAL (IN. WC) HEIGHT (IN) WIDTH (IN) LENGTH (IN) HP BHP V/HZ/PH MOP MCA FLA

MANUFACTURER MODEL MODEL

ELECTRICAL AIR VOLUME

(CFM)

STATIC PRESSURE EXTERNAL DIMENSIONS

QTY

ELECTRICAL AIR VOLUME

(CFM)

STATIC PRESSURE EXTERNAL DIMENSIONS

QTY

ELECTRICALMARK

BASIS OF DESIGN

LOCATION

ENERGY RECOVERY WHEEL SUPPLY FAN RETURN/EXHAUST FAN

AIR HANDLING UNITS

AHU-4 5WB1202B 435.878 180 159.9 43.3 5WH1204C 264.363 176.556 44 56.1 43.6

AHU-3 5WQ0901C 145.811 180 159.4 14.2 5WH1106B 135.114 95.735 44 56.1 22.3

AHU-2 5WQ1101B 204.975 180 159.7 20.2 5WH1006B 196.479 137.477 44 56.3 31.8

AHU-1 5WQ1101B 204.975 180 159.7 20.2 5WH1006B 196.479 137.477 44 56.3 31.8

MODEL

TOTAL CAPACITY

(MBH)

EWT (DEG F) LWT (DEG F) FLOW (GPM) MODEL TOTAL CAPACITY (MBH)

SENSIBLE CAPACITY

(MBH)

EWT (DEG F) LWT (DEG F) FLOW (GPM)

MARK

HOT WATER COIL CHILLED WATER COIL

AIR HANDLING UNITS (CONTINUED)

Attachment B - Equipment Specifications

Brand Name or Equal, if Equal is provided please provide, Manufacturer data, all specs highlighted that are Equivalent to the Brand Name provided.

IM

/A

F R

H -0

S h e ri d a n

S ta n le y C h ill e r

D e s ig n /A

F R

H -0

M

E P

.r v t

/1

/2

:4

:1

P

M

STANLEY CHAPEL

CHILLER REPLACEMENT

AHU-1 DAIKIN CAH014GDAM

STANLEY CHAPEL

BASEMENT

STANLEY

CHAPEL

124 74 42 60 16 6500 0.75 2.38 20.18 22 7.5 208/60/3 24.2 5WB1302B 285.196 160 139.9 28.4 5WL1205B 259.555 44 54 54.3

EXTERNAL (IN. WC) TOTAL (IN. WC) HEIGHT (IN) WIDTH (IN) HP V/HZ/PH FLA

MANUFACTURER MODEL LENGTH (IN) WIDTH (IN) HEIGHT (IN) HEIGHT (IN) WIDTH (IN)

AIR VOLUME

(CFM)

STATIC PRESSURE SA CONNECTIONS ELECTRICAL

MODEL

TOTAL CAPACITY

(MBH)

EWT (DEG F) LWT (DEG F) FLOW (GPM) MODEL

TOTAL

CAPACITY (MBH)

EWT (DEG F) LWT (DEG F)

FLOW

(GPM)

MARK

BASIS OF DESIGN

LOCATION

LOCATION

SERVED

OVERALL DIMENSIONS OA/RA CONNECTIONS (IN) SUPPLY FAN HOT WATER COIL CHILLED WATER COIL

AIR HANDLING UNIT - STANLEY CHAPEL

CH-1 DAIKIN AGZ065E

STANLEY CHAPEL

(OUTDOORS)

AIR-COOLED, SCROLL COMPRESSOR 59.13 100 88 94 3155 16.07 54 44 141.5 67.03 300 208/3/60

MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) KW MOCP (A) V/PH/HZ

MARK

BASIS OF DESIGN

LOCATION TYPE TONS

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

WEIGHT

(LBS)

IPLV

(EER)

EVAPORATOR ELECTRICAL

CHILLER SCHEDULE - STANLEY CHAPEL

CHWP-2 BELL & GOSSETT BG-E1532-200BD-184-SS CHILLED WATER

STANLEY CHAPEL

BASEMENT

BASE MOUNTED, END

SUCTION

184JM 60 145 15 17.37 23.75 73.4 5 3.07 1750 208/60

CHWP-1 BELL & GOSSETT BG-E1532-200BD-184-SS CHILLED WATER

STANLEY CHAPEL

BASEMENT

BASE MOUNTED, END

SUCTION

184JM 60 145 15 17..37 23.75 73.4 5 3.07 1750 208/60

MANUFACTURER MODEL V/HZ

MARK

BASIS OF DESIGN

SYSTEM LOCATION TYPE FRAME HEAD (FT)

FLOW

(GPM)

HEIGHT (IN) WIDTH (IN)

LENGTH

(IN)

EFFICIENCY (%) HP BHP RPM

ELECTRICAL

PUMP SCHEDULE - STANLEY CHAPEL

AS-1

AMERICAN

WHEATLEY

TASS004

STANLEY CHAPEL

BUNKER

32.625 21.75 14 4 150 118

MANUFACTURER MODEL

MARK

BASIS OF DESIGN

LOCATION HEIGHT (IN)

WIDTH WITH FLANGES

(IN)

DIAMETER

(IN)

CONNECTION SIZE

(IN)

WORKING PRESSURE

(PSI)

WEIGHT

(LBS)

AIR SEPARATOR- STANLEY CHAPEL

ET-1

AMERICAN

WHEATLEY

BDT-016

STANLEY CHAPEL

BASEMENT

16 32 14 3/4 150 65

MANUFACTURER MODEL

MARK

BASIS OF DESIGN

LOCATION

ACCEPTANCE VOLUME

(GAL)

HEIGHT (IN)

DIAMETER

(IN)

CONNECTION SIZE

(IN)

WORKING PRESSURE

(PSI)

WEIGHT

(LBS)

EXPANSION TANK - STANLEY CHAPEL

Brand Name or Equal, if Equal is provided please provide, Manufacturer data, all specs highlighted that are Equivalent to the Brand Name provided.

IM

/A

F R

H -0

S h e ri d a n

S ta n le y C h ill e r

D e s ig n /M

E P

A

F R

H -0

S h e ri d a n .r v t

/2

/2

:2

:1

P

M

SHERIDAN CHILLER

REPLACEMENT

HX-1 BELL & GOSSETT AP100

SHERIDAN

MECHANICAL ROOM

GASKETED, WATER 6,114.80 88.9 32.5 51.2 150 5,945 61.7 49 960 46 56 1,218

MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F)

FLOW

(GPM)

MARK

BASIS OF DESIGN

LOCATION TYPE CAPACITY (MBH)

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

DESIGN

PRESSURE (PSI)

WEIGHT

(LBS)

EVAPORATOR CONDENSER

PLATE AND FRAME HEAT EXCHANGER SCHEDULE - SHERIDAN

AS-1

AMERICAN

WHEATLEY

TASS008

SHERIDAN

MECHANICAL ROOM

44.625 28 20 8 150 260

MANUFACTURER MODEL

MARK

BASIS OF DESIGN

LOCATION HEIGHT (IN)

WIDTH WITH FLANGES

(IN)

DIAMETER

(IN)

CONNECTION SIZE

(IN)

WORKING PRESSURE

(PSI)

WEIGHT

(LBS)

AIR SEPARATOR

ET-1

AMERICAN

WHEATLEY

BDT-060

SHERIDAN

MECHANICAL ROOM

60 48 24 1-1/2" 150 220

MANUFACTURER MODEL

MARK

BASIS OF DESIGN

LOCATION

ACCEPTANCE VOLUME

(GAL)

HEIGHT (IN)

DIAMETER

(IN)

CONNECTION SIZE

(IN)

WORKING PRESSURE

(PSI)

WEIGHT

(LBS)

EXPANSION TANK - SHERIDAN

CH-2 DAIKIN WMC 400TR 44-54 85-95

SHERIDAN

MECHANICAL ROOM

CENTRIFUGAL, WATER

COOLED

400 94.5 55.2 184.3 15,054 56 42 667.6 85 95 1118 340 383 238.7 500 460/3/60

CH-1 DAIKIN WMC 400TR 42-56 85-95

SHERIDAN

MECHANICAL ROOM

CENTRIFUGAL, WATER

COOLED

400 94.5 55.2 184.3 15,054 56 42 667.6 85 95 1118 340 383 238.7 500 460/3/60

MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F) FLOW (GPM) RLA (A) MCA KW MOCP (A) V/PH/HZ

MARK

BASIS OF DESIGN

LOCATION TYPE TONS

HEIGHT

(IN)

WIDTH

(IN)

LENGTH

(IN)

WEIGHT

(LBS)

EVAPORATOR CONDENSER ELECTRICAL

CHILLER SCHEDULE - SHERIDAN

CWP-2 BELL & GOSSETT VIS 8X8X13C CONDENSER WATER

SHERIDAN COOLING TOWER

BUILDING

INLINE, VFD 365 150 1,200 84.1 75 1800 460/60

CWP-1 BELL & GOSSETT

BGE80SC6X6X135-365P-1-I

N

CONDENSER WATER

SHERIDAN COOLING TOWER

BUILDING

INLINE, VFD 365 150 1,200 84.1 75 1800 460/60

CHWP-S2 BELL & GOSSETT BG-E1510-4GC-SS-326T-L

SECONDARY CHILLED

WATER

SHERIDAN MECHANICAL ROOM END SUCTION, VFD 326 150 800 82 50 1800 460/60

CHWP-S1 BELL & GOSSETT BG-E1510-4GC-SS-326T-L

SECONDARY CHILLED

WATER

SHERIDAN MECHANICAL ROOM END SUCTION, VFD 326 150 800 82 50 1800 460/60

CHWP-P2 BELL & GOSSETT BG-E1510-4BD-SS-215T-S PRIMARY CHILLED WATER SHERIDAN MECHANICAL ROOM END SUCTION, VFD 215 40 700 81.1 10 1800 460/60

CHWP-P1 BELL & GOSSETT BG-E1510-4BD-SS-215T-S PRIMARY CHILLED WATER SHERIDAN MECHANICAL ROOM END SUCTION, VFD 215 40 700 81.1 10 1800 460/60

MANUFACTURER MODEL V/HZ

MARK

BASIS OF DESIGN

SYSTEM LOCATION TYPE NEMA FRAME HEAD (FT)

FLOW

(GPM)

EFFICIENCY (%) HP RPM

ELECTRICAL

PUMP SCHEDULE - SHERIDAN

Brand Name or Equal, if Equal is provided please provide, Manufacturer data, all specs highlighted that are Equivalent to the Brand Name provided.

Sherman Equipment Schedules
Sheets
H601 - MECHANICAL SCHEDULES
AFRH-007-Stanley Equipment Schedules
Sheets
H601 - MECHANICAL SCHEDULES

AFRH-007-Sheridan Equipment Schedules

File details come from the government source that posted it. Updated .