Attachment B - Equipment Specifications.pdf
PDF 552 KB Posted
- Solicitation number
- RFQ-AFRHW-22-0001
About this file
This document contains equipment specifications and schedules for chiller replacement projects at multiple facilities operated by the Armed Forces Retirement Home. Key details include specifications for chillers, cooling towers, air handlers, pumps, and other mechanical equipment to be provided by vendors. Offerors must submit quotes by 2:00 PM EST on September 9, 2020 in response to solicitation RFQ-AFRHW-22-0001 issued by the Department of the Treasury Bureau of the Fiscal Service on behalf of the Armed Forces Retirement Home. The solicitation seeks replacement of 3 chillers and 1 cooling tower located at various AFRH facilities, with an anticipated period of performance of 60-90 days after award. While the solicitation is currently only for equipment, vendors are asked to provide information on their installation capabilities or recommended installation vendors. The requirement is set aside exclusively for small businesses under NAICS code 238220.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Warehouse Photos - AFRH.pdf | ||
| Attachment A - Pricing Spreadsheet Chillers R2 9-21.xls | XLS spreadsheet | |
| Attachment F - DRAFT PWS Chiller Replacement 6-15-2021.doc | DOC document | |
| Chillers - CI-SOL. Combination Effective 091021.docx | DOCX document | |
| Attachment C Sherman-Construction Dwgs_Redacted.pdf | ||
| Attachment D Sheridan-Construction Dwgs_Redacted.pdf | ||
| Attachment E Stanley Chapel-Construction Dwgs_Redacted.pdf | ||
| Attachment A - Pricing Spreadsheet Chillers.xls | XLS spreadsheet | |
| Attachment C - DRAFT PWS Chiller Replacement 6-15-2021.doc | DOC document | |
| Chillers - CI-SOL. Combination Effective 091021.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NAME:
B
IM
/A
F R
H -0
S h e rm a n B u ild in g C h ill e r
R e p la c e m e n t/ A
F R
H -0
M
E P
.r v t
/1
/2
:2
:0
P
M
SHERMAN BUILDING
CHILLER REPLACEMENT
CH-1 DAIKIN WMC048SDSNA
NORTH
CONVERTER
CENTRIFUGAL, WATER
COOLED
147.3 79 43.5 142.3 53.82 44 358.9 85 94.3 455.5 138 100.6 300 460/3/60
MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F)
FLOW
(GPM)
RLA (A) KW MOCP (A) V/PH/HZ
MARK
BASIS OF DESIGN
LOCATION TYPE TONS
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
EVAPORATOR CONDENSER ELECTRICAL
CHILLER SCHEDULE
HX-1 BELL & GOSSETT AP47
NORTH
CONVERTER
GASKETED, WATER 2,284.25 72.5 20.5 39.4 150 2,610 61.65 49 360 46 56 455
MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F) FLOW (GPM)
MARK
BASIS OF DESIGN
LOCATION TYPE CAPACITY (MBH)
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
DESIGN
PRESSURE
(PSI)
WEIGHT
(LBS)
EVAPORATOR CONDENSER
PLATE AND FRAME HEAT EXCHANGER SCHEDULE
CT-1 EVAPCO AT 19-3G8
NORTH
CONVERTER
(OUTDOORS)
AIR COOLED,
COUNTER FLOW
150 2,250 450 95 85 7.5 8.5 11.7 6,200 6.7 5 460/3/60
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION TYPE TONS CAPACITY (MBH)
CIRCULATING WATER
FLOW (GPM)
EWT (DEG F) LWT (DEG F)
LENGTH
(FT)
WIDTH (FT) HEIGHT (FT)
WEIGHT
(LBS)
FLA/MOTOR HP/MOTOR V/PH/HZ
COOLING TOWER SCHEDULE
AS-1
AMERICAN
WHEATLEY
TASS006 NORTH CONVERTER 44.625 28 20 6 150 220
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION HEIGHT (IN)
WIDTH WITH FLANGES
(IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
AIR SEPARATOR
ET-1
AMERICAN
WHEATLEY
BDT-026 NORTH CONVERTER 16 40 16 3/4 150 98
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION
ACCEPTANCE VOLUME
(GAL)
HEIGHT (IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
EXPANSION TANK
HWP-2 BELL & GOSSETT BG-E1510-5GB-SS-324T-L HEATING WATER NORTH CONVERTER END SUCTION, VFD 324T 120 1000 29.5 24.6 56 81.2 40 38 1770 460/60
HWP-1 BELL & GOSSETT BG-E1510-5GB-SS-324T-L HEATING WATER NORTH CONVERTER END SUCTION, VFD 324T 120 1000 29.5 24.6 56 81.2 40 38 1770 460/60
CWP-2 BELL & GOSSETT BG-E1532-300BD-213-SS CONDENSER WATER NORTH CONVERTER END SUCTION, VFD 213JM 50 460 15.5 20.63 26 80.7 10 7.34 1770 460/60
CWP-1 BELL & GOSSETT BG-E1532-300BD-213-SS CONDENSER WATER NORTH CONVERTER END SUCTION, VFD 213JM 50 460 15.5 20.63 26 80.7 10 7.34 1770 460/60
CHWP-2 BELL & GOSSETT BG-E1532-300GB-256-SS CHILLED WATER NORTH CONVERTER END SUCTION, VFD 256JM 120 360 19.5 21.07 29.11 72.3 20 15 1750 460/60
CHWP-1 BELL & GOSSETT BG-E1532-300GB-256-SS CHILLED WATER NORTH CONVERTER END SUCTION, VFD 256JM 120 360 19.5 21.07 29.11 72.3 20 15 1750 460/60
MANUFACTURER MODEL V/HZ
MARK
BASIS OF DESIGN
SYSTEM LOCATION TYPE FRAME HEAD (FT)
FLOW
(GPM)
HEIGHT (IN) WIDTH (IN)
LENGTH
(IN)
EFFICIENCY (%) HP BHP RPM
ELECTRICAL
PUMP SCHEDULE
AHU-4 DAIKIN CAH017GDCM
SHERMAN SOUTH
ATTIC
SXA-1600-MW 0.25 460/60/3 3000 0.75 4.07 52 68 254 2 3.3 2.83 208/60/3 15 9.2 4.1 2500 0.5 1.95 52 68 138 1 2.3 1.18 460/60/3 15 6.8 3
AHU-3 DAIKIN CAH008GDCM
SHERMAN ANNEX
ATTIC
- - - 3500 0.75 2.75 42 46 168 1 3.5 2.22 208/60/3 20 12.92 9.95 - - - - - - - - - - - - -
AHU-2 DAIKIN CAH012GDCM
SHERMAN NORTH
ATTIC
- - - 5000 0.75 2.67 46 56 172 1 3.5 3.15 208/60/3 20 12.92 9.95 - - - - - - - - - - - - -
AHU-1 DAIKIN CAH012GDCM
SHERMAN NORTH
ATTIC
- - - 5000 0.75 2.67 46 56 172 1 3.5 3.15 208/60/3 20 12.92 9.95 - - - - - - - - - - - - -
HP V/HZ/PH EXTERNAL (IN. WC) TOTAL (IN. WC) HEIGHT (IN) WIDTH (IN) LENGTH (IN) HP BHP V/HZ/PH MOP MCA FLA EXTERNAL (IN. WC) TOTAL (IN. WC) HEIGHT (IN) WIDTH (IN) LENGTH (IN) HP BHP V/HZ/PH MOP MCA FLA
MANUFACTURER MODEL MODEL
ELECTRICAL AIR VOLUME
(CFM)
STATIC PRESSURE EXTERNAL DIMENSIONS
QTY
ELECTRICAL AIR VOLUME
(CFM)
STATIC PRESSURE EXTERNAL DIMENSIONS
QTY
ELECTRICALMARK
BASIS OF DESIGN
LOCATION
ENERGY RECOVERY WHEEL SUPPLY FAN RETURN/EXHAUST FAN
AIR HANDLING UNITS
AHU-4 5WB1202B 435.878 180 159.9 43.3 5WH1204C 264.363 176.556 44 56.1 43.6
AHU-3 5WQ0901C 145.811 180 159.4 14.2 5WH1106B 135.114 95.735 44 56.1 22.3
AHU-2 5WQ1101B 204.975 180 159.7 20.2 5WH1006B 196.479 137.477 44 56.3 31.8
AHU-1 5WQ1101B 204.975 180 159.7 20.2 5WH1006B 196.479 137.477 44 56.3 31.8
MODEL
TOTAL CAPACITY
(MBH)
EWT (DEG F) LWT (DEG F) FLOW (GPM) MODEL TOTAL CAPACITY (MBH)
SENSIBLE CAPACITY
(MBH)
EWT (DEG F) LWT (DEG F) FLOW (GPM)
MARK
HOT WATER COIL CHILLED WATER COIL
AIR HANDLING UNITS (CONTINUED)
Attachment B - Equipment Specifications
Brand Name or Equal, if Equal is provided please provide, Manufacturer data, all specs highlighted that are Equivalent to the Brand Name provided.
IM
/A
F R
H -0
S h e ri d a n
S ta n le y C h ill e r
D e s ig n /A
F R
H -0
M
E P
.r v t
/1
/2
:4
:1
P
M
STANLEY CHAPEL
CHILLER REPLACEMENT
AHU-1 DAIKIN CAH014GDAM
STANLEY CHAPEL
BASEMENT
STANLEY
CHAPEL
124 74 42 60 16 6500 0.75 2.38 20.18 22 7.5 208/60/3 24.2 5WB1302B 285.196 160 139.9 28.4 5WL1205B 259.555 44 54 54.3
EXTERNAL (IN. WC) TOTAL (IN. WC) HEIGHT (IN) WIDTH (IN) HP V/HZ/PH FLA
MANUFACTURER MODEL LENGTH (IN) WIDTH (IN) HEIGHT (IN) HEIGHT (IN) WIDTH (IN)
AIR VOLUME
(CFM)
STATIC PRESSURE SA CONNECTIONS ELECTRICAL
MODEL
TOTAL CAPACITY
(MBH)
EWT (DEG F) LWT (DEG F) FLOW (GPM) MODEL
TOTAL
CAPACITY (MBH)
EWT (DEG F) LWT (DEG F)
FLOW
(GPM)
MARK
BASIS OF DESIGN
LOCATION
LOCATION
SERVED
OVERALL DIMENSIONS OA/RA CONNECTIONS (IN) SUPPLY FAN HOT WATER COIL CHILLED WATER COIL
AIR HANDLING UNIT - STANLEY CHAPEL
CH-1 DAIKIN AGZ065E
STANLEY CHAPEL
(OUTDOORS)
AIR-COOLED, SCROLL COMPRESSOR 59.13 100 88 94 3155 16.07 54 44 141.5 67.03 300 208/3/60
MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) KW MOCP (A) V/PH/HZ
MARK
BASIS OF DESIGN
LOCATION TYPE TONS
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
WEIGHT
(LBS)
IPLV
(EER)
EVAPORATOR ELECTRICAL
CHILLER SCHEDULE - STANLEY CHAPEL
CHWP-2 BELL & GOSSETT BG-E1532-200BD-184-SS CHILLED WATER
STANLEY CHAPEL
BASEMENT
BASE MOUNTED, END
SUCTION
184JM 60 145 15 17.37 23.75 73.4 5 3.07 1750 208/60
CHWP-1 BELL & GOSSETT BG-E1532-200BD-184-SS CHILLED WATER
STANLEY CHAPEL
BASEMENT
BASE MOUNTED, END
SUCTION
184JM 60 145 15 17..37 23.75 73.4 5 3.07 1750 208/60
MANUFACTURER MODEL V/HZ
MARK
BASIS OF DESIGN
SYSTEM LOCATION TYPE FRAME HEAD (FT)
FLOW
(GPM)
HEIGHT (IN) WIDTH (IN)
LENGTH
(IN)
EFFICIENCY (%) HP BHP RPM
ELECTRICAL
PUMP SCHEDULE - STANLEY CHAPEL
AS-1
AMERICAN
WHEATLEY
TASS004
STANLEY CHAPEL
BUNKER
32.625 21.75 14 4 150 118
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION HEIGHT (IN)
WIDTH WITH FLANGES
(IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
AIR SEPARATOR- STANLEY CHAPEL
ET-1
AMERICAN
WHEATLEY
BDT-016
STANLEY CHAPEL
BASEMENT
16 32 14 3/4 150 65
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION
ACCEPTANCE VOLUME
(GAL)
HEIGHT (IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
EXPANSION TANK - STANLEY CHAPEL
Brand Name or Equal, if Equal is provided please provide, Manufacturer data, all specs highlighted that are Equivalent to the Brand Name provided.
IM
/A
F R
H -0
S h e ri d a n
S ta n le y C h ill e r
D e s ig n /M
E P
A
F R
H -0
S h e ri d a n .r v t
/2
/2
:2
:1
P
M
SHERIDAN CHILLER
REPLACEMENT
HX-1 BELL & GOSSETT AP100
SHERIDAN
MECHANICAL ROOM
GASKETED, WATER 6,114.80 88.9 32.5 51.2 150 5,945 61.7 49 960 46 56 1,218
MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F)
FLOW
(GPM)
MARK
BASIS OF DESIGN
LOCATION TYPE CAPACITY (MBH)
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
DESIGN
PRESSURE (PSI)
WEIGHT
(LBS)
EVAPORATOR CONDENSER
PLATE AND FRAME HEAT EXCHANGER SCHEDULE - SHERIDAN
AS-1
AMERICAN
WHEATLEY
TASS008
SHERIDAN
MECHANICAL ROOM
44.625 28 20 8 150 260
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION HEIGHT (IN)
WIDTH WITH FLANGES
(IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
AIR SEPARATOR
ET-1
AMERICAN
WHEATLEY
BDT-060
SHERIDAN
MECHANICAL ROOM
60 48 24 1-1/2" 150 220
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION
ACCEPTANCE VOLUME
(GAL)
HEIGHT (IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
EXPANSION TANK - SHERIDAN
CH-2 DAIKIN WMC 400TR 44-54 85-95
SHERIDAN
MECHANICAL ROOM
CENTRIFUGAL, WATER
COOLED
400 94.5 55.2 184.3 15,054 56 42 667.6 85 95 1118 340 383 238.7 500 460/3/60
CH-1 DAIKIN WMC 400TR 42-56 85-95
SHERIDAN
MECHANICAL ROOM
CENTRIFUGAL, WATER
COOLED
400 94.5 55.2 184.3 15,054 56 42 667.6 85 95 1118 340 383 238.7 500 460/3/60
MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F) FLOW (GPM) RLA (A) MCA KW MOCP (A) V/PH/HZ
MARK
BASIS OF DESIGN
LOCATION TYPE TONS
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
WEIGHT
(LBS)
EVAPORATOR CONDENSER ELECTRICAL
CHILLER SCHEDULE - SHERIDAN
CWP-2 BELL & GOSSETT VIS 8X8X13C CONDENSER WATER
SHERIDAN COOLING TOWER
BUILDING
INLINE, VFD 365 150 1,200 84.1 75 1800 460/60
CWP-1 BELL & GOSSETT
BGE80SC6X6X135-365P-1-I
N
CONDENSER WATER
SHERIDAN COOLING TOWER
BUILDING
INLINE, VFD 365 150 1,200 84.1 75 1800 460/60
CHWP-S2 BELL & GOSSETT BG-E1510-4GC-SS-326T-L
SECONDARY CHILLED
WATER
SHERIDAN MECHANICAL ROOM END SUCTION, VFD 326 150 800 82 50 1800 460/60
CHWP-S1 BELL & GOSSETT BG-E1510-4GC-SS-326T-L
SECONDARY CHILLED
WATER
SHERIDAN MECHANICAL ROOM END SUCTION, VFD 326 150 800 82 50 1800 460/60
CHWP-P2 BELL & GOSSETT BG-E1510-4BD-SS-215T-S PRIMARY CHILLED WATER SHERIDAN MECHANICAL ROOM END SUCTION, VFD 215 40 700 81.1 10 1800 460/60
CHWP-P1 BELL & GOSSETT BG-E1510-4BD-SS-215T-S PRIMARY CHILLED WATER SHERIDAN MECHANICAL ROOM END SUCTION, VFD 215 40 700 81.1 10 1800 460/60
MANUFACTURER MODEL V/HZ
MARK
BASIS OF DESIGN
SYSTEM LOCATION TYPE NEMA FRAME HEAD (FT)
FLOW
(GPM)
EFFICIENCY (%) HP RPM
ELECTRICAL
PUMP SCHEDULE - SHERIDAN
Brand Name or Equal, if Equal is provided please provide, Manufacturer data, all specs highlighted that are Equivalent to the Brand Name provided.
| Sherman Equipment Schedules |
| Sheets |
| H601 - MECHANICAL SCHEDULES |
| AFRH-007-Stanley Equipment Schedules |
| Sheets |
| H601 - MECHANICAL SCHEDULES |
AFRH-007-Sheridan Equipment Schedules
File details come from the government source that posted it. Updated .