This is a Scope of Work attachment for a Request for Proposals issued by Paulding County School Nutrition (Georgia) seeking qualified vendors to provide and install a walk-in cooler/freezer unit and shelving at Northside Elementary School located at 2223 Cartersville Highway, Dallas, Georgia 30132. The project is a turnkey installation requiring the supply, delivery, and installation of pre-fabricated, NSF-approved metal-clad walk-in cooler/freezer units (approximately 23 feet by 17 feet by 8 feet) partitioned into separate cooler and freezer compartments, along with shelving. The scope includes demolition of existing equipment, full installation by licensed contractors (electrical, refrigeration, and plumbing), refrigerant charging, final trim work, debris removal, and site cleanup. Respondents may propose alternative manufacturers (such as American Panel or Thermal Kool) if proof of quality meeting all specifications is provided prior to the final written question deadline. All vendors must attend a pre-proposal meeting on site, and the awarded vendor must be present at delivery to inspect for damage. Prior to final completion, the freezer must maintain 0°F or below continuously for five consecutive days, and the cooler must maintain 34°F to 38°F continuously for five consecutive days.
The proposal price must include all labor, materials, demolition, installation, electrical work, refrigeration line installation and charging, floor preparation, trim work, and debris removal as a complete turnkey solution. The walk-in cooler/freezer unit is guaranteed for ten years against poor workmanship and defective materials. Shelving shall be Fermod or equal, with removable and dishwasher-safe inserts rated for 800-pound shelf capacity and a lifetime warranty against rust and corrosion. The file specifies detailed technical requirements including refrigeration specifications (R-448A refrigerant, specific temperature maintenance parameters), insulation standards (4-inch foamed-in-place urethane), door specifications (36 inches by 76 inches flush-mounted with stainless steel construction), LED lighting with break-proof guards, condensate drain lines with heated cable tape in the freezer section, and high-temperature alarms for each section. Contractors should demonstrate experience with similar projects in educational settings that have been completed and operational for a minimum of one year.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Walk_in Cooler_ Frezer Soliciation SY27.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment B
Northside Elementary Walk-In Cooler/ Freezer and Shelving Replacement
Respondents should note that all specifications list in this RFP are based on general criteria that the Paulding County School Nutrition Program (SFA) feels is important for our walk-in cooler/freezer/shelving providers. The SFA is open to reviewing all system proposals for our walk-in cooler/freezer/shelving that may meet or exceed our needs. Our intent in listing these specifications in the RFP is to give the Respondents a general idea of some of the functions we would like to see. The SFA is looking to the Respondents to provide us with as much information as possible about their particular product and how it can meet the SFA needs. Any similarity in the specifications listed in this RFP document and any manufacturer’s specifications is unintentional and should not be perceived as such.
Scope of Work Paulding County School Nutrition has issued a Request for Proposals seeking qualified vendors to provide and install a walk-in freezer/cooler and shelving at Northside Elementary located at:
2223 Cartersville Hwy.
Dallas, GA 30132
This is a turnkey installation. Price must include demolition, full installation including electrical by a licensed electrician and running refrigeration lines and charging all refrigeration, any final trim needed for floor and ceiling. All debris must be cleaned up and removed.
The scope of this solicitation encompasses the supply, delivery, and installation of a walk-in cooler/freezer unit and shelving. Prospective contractors are expected to furnish a turnkey solution that meets all applicable safety, quality, and performance standards.
Key objectives of this procurement include the provision of a reliable, energy-efficient freezer system with sufficient capacity to meet the school's current and anticipated storage requirements. The expected deliverables consist of a fully operational walk-in cooler/freezer, installed and tested to confirm compliance with all relevant codes, specifications and performance requirements.
GENERAL SPECIFICATIONS:
Furnish pre-fabricated, NSF approved metal-clad Walk-In Cooler/Freezer Units Bally (spec of design) or approved equal - American Panel, Thermal Kool (any other must provide proof of quality to all specs prior to final date of written questions).
Walk-in units should be designed and constructed for fast and easy assembly, disassembly, relocation and enlargement by additional matching panels. Walk-in Cooler/ Freezer unit should be approximately 23’ x 17’ x 8’ and should be field measured for exact measurements needed to fit exact job site. Cooler and Freezer Section to be the same as what is being removed.
Cooler/Freezer Unit shall be partitioned into compartments, size, and shape to fit current freezer and cooler.
Flooring:
4” thick floor panels have a 3/8” inside coved radius built in around the perimeter of skins and are NSF Certified. Reinforced floor to be installed in 4” recess for smooth transition to kitchen floor. Reinforced floor to have ¾” plywood foamed in panel and to be designed to support rolling loads up to 1,000 lbs. per sq. foot. Interior floor finish to be.16GA galvanized steel. Floors to be covered in Protect-All (spec of design) or equal. Non-Slip rubber flooring. Non-slip rubber flooring shall have 8” cove base that will be capped off with stainless steel.
Finished floor to be 1/8” of existing kitchen floor.
Panels:
Interior wall finish to be 190 Series embossed white galvanized. Exposed exterior finish to be 22GA embossed stainless steel, remainder of the exterior finish to be 190 Series embossed white galvanized. Interior ceiling finish to be 190 Series embossed white galvanized. Exterior ceiling finish to be 190 Series embossed white galvanized.
Freezer shall be equipped with a two-way heated pressure relief vent to equalize pressure between the interior and exterior caused by defrost cycles and opening of door.
Panels must have cam lock device. Locks should not exceed 46”. Each device shall consist of a cam action, hooked locking arm placed in one panel, and a steel rod positioned in the adjoining panel, so that when the arm is rotated, the hood engages the rod and draws the panels tightly together with cam action. Arms and rods shall be housed in individual steel pockets. Pockets on one side of the panel shall be connected to pockets on the other side in width, by use of 2” wide metal straps set into and completely surrounded by insulation. When panels are joined these straps shall form lock-to-lock connections for superior strength. Locking device shall be accessible from the inside to facilitate installations in confined areas and shall be provided with flush press-fit caps. Surface mounted plastic plugs will not be accepted.
Panels shall consist of interior and exterior metal skins precisely foamed with steel dies and roll-form equipment and thoroughly checked with gauges for accuracy.
Metal skins shall be treated on the inside surface with a bonding agent to ensure a stable adhesion with the chemical bonding agents of the urethane. Urethane shall be foamed in place (poured, not frothed) and, when completely cured, shall bind tenaciously to metal skins to form an insulated panel. Panels shall contain 100% urethane insulation and have no internal wood or structural members between skins unless required as structural support for external accessories. To ensure tight joints, panel edges must have foamed-in place tongue and groove with flexible vinyl gasket foamed-in place on the interior and exterior of all tongue edges. Gaskets shall be resistant to damage from oil, fats, water and detergents and must be NSF-approved.
Gaskets shall not be stapled or glued to metal skins. All panels (except corner panels) shall be made fully interchangeable for fast, easy assembly. To ensure perfect alignment and maximum strength, corner panels shall employ a right-angle configuration with exterior horizontal dimensions of 12” on each side.
Exterior:
Exposed front panels shall have aluminum diamond treadbrite 36" high on the exterior. Diamond treadbrite shall be mounted with adhesive and sealed with silicone. No external fasteners.
Where units are adjacent to walls or columns, there shall be provided a matching trim to close spaces between the wall(s) and Unit. All crevices and panel seams are to be sealed with clear polysulfide sealant. Furnish a matching panel to close area between the top of Unit and ceiling with removable access panel for required maintenance service on top of Unit.
Furnish a matching panel to close area between top of the unit and ceiling with removable access panel for required maintenance service on top of unit.
Ceiling should include center support needed for maintenance service on top of Unit.
Insulation:
Insulation shall be shall be of 4-inch thick “foamed in-place” urethane to bond permanently to complete inner surfaces of both interior and exterior metal pans to form strong rigid unit. The door will have the same type of insulation.
Perimeter structure shall be formed of Durathane, high density urethane insulation forming tongues and grooves to assure vapor and airtight joints and to prevent pre-installation damage and deterioration of exposed urethane surfaces. Insulation shall be 4” thick rigid, zero ozone depleting HFC 134a blown Class I urethane foam classified according to UL 723 (ASTM-E 84) as tested by Underwriters Laboratories, Inc. The core material has a flame spread of 25 or less and a smoke density of 250.
The urethane foam is foamed-in-place to bond to inner surfaces of metal pans having an average thermal conductivity (K factor) of 0.13 BTU/hr./sq. ft. per degrees /Fahrenheit/inch. As tested in accordance with ASTM C 518-2004, the R factor for coolers at temperatures of 55 F˚ is greater than 29.0 for 4” thick; for freezers at temperatures of 20 F˚ the R factor is greater than 32.0 for 4” thick. (R-value of R-25 for Coolers and R-32 for Freezers required to meet 2009 Energy Code). The prefabricated urethane foamed panels shall be supplied with a Class I fire hazard classification according to UL 723 (ASTM-E-84) as tested by Underwriters Laboratories, Inc. Panels shall have a flame spread rating of 25 or less and bear a certifying Underwriters Laboratories, Inc. label. This rating is not intended to reflect hazards presented by this or any other material under actual fire conditions. NSF listed double-bead vinyl gasket shall be applied to the tongue side of all panels, on both interior and exterior. Gaskets shall be impervious to stains, grease, oils, mildew, sunlight, etc.
Doors:
(2) 36" x 76" Flush Mounted Entrance Door(s), with hardware, Pilot light & switch assembly, vapor proof light & dial thermometer. NSF LISTED The door will be flush-mounted. Door to be metal clad with 22 gauge Type 304 stainless steel, with smooth corner seams. Super doors with a reinforced 14 ga. U-Channel steel frame, backed with additional 1/8” steel plate drilled and tapped where all hardware is mounted.
This steel frame with an internal thermal breaker will prevents twisting, sagging, and eliminates the need for structural members. The bottom edge to contain an adjustable rubber wiper gasket. The door will have heater cables in the door jamb to prevent condensation and frost formation. The door hinge will be the self-closing type with lift-cam hinges. The door will be provided with safety release inside latch.
Door to be provided with hardware for locking with a padlock. Door jamb and outer door edge surfaces shall be constructed of stainless steel. Plastic composition material shall not be accepted. (2) 36"H 1/8" Aluminum Treadplate kickplates and jamb guards int & ext.
Provide 14 x 14 inch heated triple-pane observation window type with sealed air spaces between panes. Windows shall be removable for easy replacement. Each door shall be provided with an observation window.
Provide a door with an adjustable hydraulic door closer. Mount door closer on the exterior side of the door. Adjust the closing speed at installation as required. Metal threshold with slip prevention traction strips at each door. (2) Pressure relief vent(s)
Doors shall be made to properly fit over the entrance door opening. Swinging doors shall be supported on sides of the door opening with mounting hardware on the inside of sections.
Gaskets:
All panel sections to be furnished with PVC compression gaskets. Tape or plain sealant not acceptable.
Lights:
Lights will be LED type and provided with a break-proof and shatterproof guard.
Provide each Section with flush-mounted light switches on the outside of Section.
The fixture will be capable of withstanding temperatures as low as -40 degree F and be provided with shatterproof enclosure cover. Provide the following quantities
a. Cooler: Five fixtures, plus standard light over the door.
b. Freezer: Five Fixtures plus, standard light over the door.
Thermometer to be a minimum of 2-1/2 inch diameter and flush-mounted on outside of each Section and have a rust-resistant case.
Drains:
Drain line piping shall be A.C.R. Type “L” hard copper, properly graded and trapped outside of the compartments. Condensate drain lines shall be of Type “L” copper tubing in Walk-In Unit, and directed to outside of Unit. Provide condensate drain lines directed to the lowest possible level. Wrap all condensate drain lines in the freezer section with electrically heated cable tape. Heat tape to be on separate/dedicated circuit.
Run pipes through walls and ceiling panels in sleeves. All refrigerator sleeves shall be furnished as part of the installation. All plugs and cut-outs shall be fully resealed.
All connection requirements including tubing, electrical hook-up, drain line and refrigerant charge shall be supplied by qualified refrigeration, electrical and plumbing contractors.
Condenser and Evaporator Unit:
Capacities shall be based on the following:
a. Compartment temperature and evaporator temperature greater than 32 degrees, 18 to 20 hours of operation.
b. Compartment temperature greater than 32 degrees and evaporating temperature less than 32 degrees, 16 hours of operation.
c. Compartment temperature and evaporator temperature less than 32 degrees, 18 hours of operation.
d. Systems shall be designed to operate not more than 18 hours per day in a 100 degree ambient condensing temperature. Walk-in compartment shall operate at 35 degrees F with an evaporator at 10 degrees T.D. Walk-in freezer compartments shall operate at -10 degrees F with a 10 degree T.D. at -20 degree suction temperature. Suction lines shall be sized for maximum pressure drop of 2# on medium temperature and 1# on low temperature systems.
The length of the refrigeration line runs between each condensing unit and evaporator coil to be verified and confirmed with Manufacturer prior to installation.
Provide Unit with at least the following components:
1. Heavy-gauge housing for outside use.
2. Scroll motor compressor for Cooler Section with built-in overload protection. 3. Scroll motor compressors for Freezer Section with built-in overload protection.
4. Aluminum-finned, copper tube air-cooled condenser with direct driven condenser fan, arranged for horizontal airflow.
5. Refrigerant receiver with inlet, outlet, purge, relief and charging valves.
6. All systems shall utilize R-448A refrigerant.
7. Suction and discharge line vibration eliminators. Defrost controls.
8. Defrost timer to be at/in the condensing unit.
9. Low-ambient pressure and starting controls.
10. Safety operating controls.
Safety controls will include:
1. High pressure cut-out with manual reset.
2. Magnetic control for the motor-compressor with ambient compensated manual reset overloads.
3. Operating control to be automatic recycling, low-pressure cut-out switch. A low ambient control system will be fully automatic, and will not require auxiliary heat or heated receivers.
4. Each Section is to be provided with a high-temperature alarm.
Each alarm is to have a dry contact for wiring to a central or remote control point.
Defrost of all freezer evaporator coil surfaces, drain pans and drain lines will be by electric defrost systems. Defrost to be controlled by SmartVap+ system. Defrost timer for freezer to be at/in the condensing unit.
Each evaporator Unit to be supported on a metal angle iron frame constructed as part of the Condensing Unit. Propeller-fan, free delivery type, arranged for horizontal airflow. The evaporator coil will be of copper tube, aluminum-finned constructions housed in a heavy gauge aluminum casing.
The balanced Refrigeration Systems for the specified Walk-In Unit’s Sections will be capable of maintaining the required temperature for each Section as follows:
1.Cooler 34 degree F to 38 degrees
2. Freezer -10 degree F to 0 degrees
Provide a system with the following Specialty Items:
a. Refrigerant sight glass and moisture indicator.
b. Hermetically-sealed refrigerant-filter dehydrator.
c. Liquid solenoid valve.
d. Thermostatic expansion valve.
e. Heat exchanger.
f. Suction strainer and Armaflex insulation for suction line - complete.
Refrigeration systems shall be installed by a knowledgeable, skilled and where applicable licensed refrigeration contractor.
Shelving:
Fermod Shelving or equal.
Shelving shall be measured and sized to properly fit the new freezer and cooler box construction.
· Shelving inserts should be removable, heavy duty and dishwasher safe.
· Shelf capacity 800 lbs.
· Lifetime warranty against rust and corrosion.
· Internal angle configuration to allow full use of corners.
Warranty:
Walk-In Cooler/Freezer Unit will be guaranteed for a period of ten years, against poor workmanship and defective materials.
Demolition:
Remove any unused cable, wires safely according to building code.
All debris must be cleaned up and removed.
Final Notes:
All vendors must be on site for pre-proposal meeting. No third parties will be allowed.
The awarded vendor must be on site for the delivery to inspect for damage before the driver leaves. Any damage must be documented on delivery receipt.
Preferred installer will be well versed in product installation, warranty, and detail oriented.
Price must include demolition, full installation including electrical and running refrigeration lines and charging all refrigeration, any final trim needed for floor and ceiling.
All debris must be cleaned up and removed.
The existing pit shall be prepared as necessary to ensure the new walk-in cooler/freezer floor can be installed level and in accordance with the manufacturer's requirements. Proposers may include a floor preparation allowance in their proposal to address any unforeseen conditions or adjustments that may be required during installation.
All space between the sides of the box and the school walls must be flashed. The space between the existing kitchen quarry tile floor and the new walk-in must be filled and waterproof sealed. Appropriate trim must be installed on the walls and floor joints to create flush finish. All penetrations and conduit into the walk-in must be properly sealed. All penetrations through the school walls must be properly sealed.
Leave all current freezer and cooler monitoring equipment for SNP to reuse.
Contractors should be prepared to demonstrate experience with similar projects in educational settings from project having been completed and in service for a minimum of one year.
Prior to final completion, the freezer shall continuously maintain a temperature of 0°F or below for a period of five (5) consecutive days.
Prior to final completion, the cooler shall continuously maintain a temperature of 34°F - 38°F for a period of five (5) consecutive days.