This document provides a statement of work for upgrading an energy management system and building automation system at the Tennessee Valley Healthcare System Nashville Campus. The statement of work requires converting direct digital controls systems from V-LAN to a fiber optic backbone serving all fan rooms. It also requires replacing Honeywell, Siemens, and Alerton control panels with native BACnet panels and integrating non-BACnet devices and protocols. Additional requirements include installing air flow management systems, upgrading graphics, providing a combined front-end system, and certifying the completed upgrades. The work must be completed within 210 calendar days of the notice to proceed. The solicitation number is 36C24923B0019 and is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The opportunity type is a pre-solicitation for modification of electrical and electronic equipment components with an estimated value between $2-5 million.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| revised_ 626-15-106 EMS Drawings_01.pdf | ||
| 626-15-106 EMS Specifications.pdf | ||
| 36C24923B0019.docx | DOCX document | |
| revised_ Attachment A- 230923 Direct Digital Control System for HVAC_01.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Control Panel Schedule
| Location | Control Panel ID | Manufacturer | Air Handlers and Devices Controlled | whats inside | comms type |
| fan room 1 | CP-fr1-H-1 | Honeywell | AHU-5, RF-5, AHU-11, ER-58, | R7044 | bnps |
| fan room 1 | CP fr1 H 2 | Honeywell | AHU-5 Accessories | Pneumatic | |
| fan room 1 | CP fr1 H 3 | Honeywell | AHU-11 Accessories | Excel 800 | cbus |
| fan room 1 | CP fr1 H 4 | Honeywell | DCP-19 | Excel 800 | cbus |
| fan room 1 | CP fr1 H 5 | Honeywell | EF-2, EF-57 | R7044 | bnps |
| fan room 1 | CP fr1 H 6 | Honeywell | C-HX-E26A-5 (Heat Exchanger 5) | Excel 800 | cbus |
| fan room 1 | CP fr1 H 7 | Honeywell | AHU-6, EF-147 | Excel 800 | cbus |
| fan room 1 | CP fr1 H 8 | Honeywell | AHU-6 Accessories | Pneumatic | |
| fan room 1 | CP fr1 H 9 | Honeywell | Hot Water Pumps Start/Stop | Pneumatic | |
| fan room 2 | CP fr2 H 1 | Honeywell | Proton con | Proton Coms | bacnet |
| fan room 2 | CP fr2 H 2 | Honeywell | AHU-50, RF-50 | Excel 800 | cbus |
| fan room 2 | CP fr2 S 1 | Siemens | Tower 2 Valves, Fans | Siemens Controller | bacnet |
| fan room 2 | CP fr2 A 1 | Alerton | AHU-3A, RF-3A | Alerton Controller | bacnet |
| fan room 2 | CP fr2 A 2 | Alerton | ?? | BCM-ETH, BCM-MSTP | bacnet |
| fan room 3 | CP fr3 H 1 | Honeywell | DCP-2, Old Cond Pumps 19,20,21, CT-1, CT-2 | R7044 | bnps |
| fan room 3 | CP fr3 H 2 | Honeywell | AHU-9, EF-25, EF-27 , EF-30 | Excel 800 | cbus |
| fan room 3 | CP fr3 H 3 | Honeywell | AHU-9 Accessory | Pneumatic, Power Supply | |
| fan room 3 | CP fr3 H 4 | Honeywell | Control EF-11, EF-14, EF-17, EF-18, EF-23, EF-43 | R7044 | bnps |
| fan room 3 | CP fr3 H 5 | Honeywell | AUX Accessory | Pneumatic | |
| fan room 3 | CP fr3 S 1 | Siemens | Cond Pumps 19,20,21, DP, Tower 1 | Siemens Controller | bacnet |
| fan room 4 | CP fr4 H 1 | Honeywell | DCP-7 old AHU-17, EF-74 | Excel 800 | cbus |
| fan room 4 | CP fr4 H 2 | Honeywell | Pneumatic | Pneumatic | |
| fan room 4 | CP fr4 H 3 | Honeywell | DCP-16 Old OR Rooms | Power Supplies | |
| fan room 4 | CP fr4 H 4 | Honeywell | DCP-8, Old AHU-18, EF-78, WCM 4, 7 Fire Sys | Excel 800 | cbus |
| fan room 4 | CP fr4 H 5 | Honeywell | Pneumatic | Power Supplies Pneumatic | |
| fan room 4 | CP fr4 H 6 | Honeywell | AHU-21 | Honey Spiders | bacnet |
| fan room 4 | CP fr4 H 7 | Honeywell | DCP-9, old AHU-21, AHU-22, EF 83, EF-86 , EF-87, EF-88 | 21 Accessorys | |
| fan room 4 | CP fr4 H 8 | Honeywell | Flow Meters | Ebtron Flow Meters | |
| fan room 4 | CP fr4 AH 1 | Alerton, Honeywell | Honeywell Bacnet Router/Alerton BCM-TH | Bacnet Router | bacnet |
| fan room 4 | CP fr4 S 1 | Siemens | AHU-17 | Siemens Controller | bacnet |
| fan room 4 | CP fr4 S 2 | Siemens | AHU-18 | Siemens Controller | bacnet |
| fan room 5 | CP fr5 H 1 | Honeywell | DCP-13, AHU-20, EF 85 | Excel 800 | cbus |
| fan room 5 | CP fr5 H 2 | Honeywell | DCP-12 old AHU-16, EF-82, CV-1, CV-2, HWP-1, Gen | Excel 800 | cbus |
| fan room 5 | CP fr5 H 3 | Honeywell | Pneumatic | Pneumatic Accessory | |
| fan room 5 | CP fr5 A 1 | Alerton | ?? | Alerton Controller | bacnet |
| fan room 5 | CP fr5 S 1 | Siemens | AHU-16 | Siemens Controller | bacnet |
| fan room 6 | CP fr6 H 1 | Honeywell | DCP-14 Med Gas Air OA RH | R7044 | bnps |
| fan room 6 | CP fr6 H 2 | Honeywell | DCP-10 AHU-23, AHU-24, EF-89, EF-90, EF-92 | Excel 800 | cbus |
| fan room 6 | CP fr6 H 3 | Honeywell | Pneumatic | Pneumatic | |
| fan room 7 | CP fr7 H 1 | Honeywell | ?? | R7044, Excel 800 | bnps ,cbus |
| fan room 7 | CP fr7 H 2 | Honeywell | AHU-3B, AHU-7 | Excel 800 | cbus |
| fan room 7 | CP fr7 H 3 | Honeywell | DCP-6 | R7044, Excel 800 | bnps,cbus |
| fan room 7 | CP fr7 H 4 | Honeywell | ?? | Power Supplies | |
| fan room 8 | CP fr8 H 1 | Honeywell | Excel 800 | Excel 800 | cbus |
| fan room 8 | CP fr8 H 2 | Honeywell | Pneumatic- (Abandoned in Place) | Excel 800 (Abandoned in Place) | |
| fan room 8 | CP fr8 S 1 | Siemens | AHU-2 | Siemens Controller | bacnet |
| fan room 9 | CP fr9 H 1 | Honeywell | AHU-32 | Excel 800 | cbus |
| fan room 9 | CP fr9 H 2 | Honeywell | ?? | Excel 800 | cbus |
| fan room 9 | CP fr9 H 3 | Honeywell | AHU-30 | Excel 800 | cbus |
| fan room 9 | CP fr9 H 4 | Honeywell | EF-51, EF-52, EF-53, EF-57, EF-58, EF-59 | Honeywell Comfort Point | bacnet |
| fan room 9 | CP fr9 S 1 | Siemens | Gylcol for 32 | Siemens Controller | bacnet |
| fan room 9 | CP fr9 A 1 | Alerton | ERV for 32 | Alerton controller | bacnet |
| fan room 10 | CP fr10 H 1 | Honeywell | AHU-33 | Excel 800 | cbus |
| fan room 10 | CP fr10 H 2 | Honeywell | DCP-27, AHU-26, FR-26 | Excel 800 | cbus |
| fan room 10 | CP fr10 H 3 | Honeywell | Pneumatic Accessory | Pneumatic | |
| fan room 10 | CP fr10 H 4 | Honeywell | EF-54, EF-55, EF-56, EF-60 | Honeywell Comfort Point | bacnet |
| fan room 10 | CP fr10 S 1 | Siemens | Gylcol for 33 | Siemens Controller | bacnet |
| fan room 11 | CP fr11 H1 | Honeywell | DCP-27, AHU-26, RF-26 | Excel 800 | cbus |
| fan room 11 | CP fr11 H2 | Honeywell | Pneumatic Accessory | Pneumatic | |
| fan room 10 | CP fr10 A 1 | Alerton | ERV for 33 | Alerton Controller | bacnet |
| fan room 12 | CP fr12 H 1 | Honeywell | DCP-23, old AHU-4, EF-13 | Honeywell Excel 800 | cbus |
| fan room 12 | CP fr12 A 1 | Alerton | AHU-4, EF-13 | Alerton Controller | bacnet |
| fan room 13 | CP fr12 A 1 | Alerton | AHU-27 | Alerton Controller | bacnet |
| fan room 14 | CP fr14 H 1 | Honeywell | DCP-28, AHU-37, AHU-38, EF-182, EF-183, EF-184, EF-185 | Pneumatic | |
| fan room 14 | CP fr14 H 2 | Honeywell | AHU-37, AHU-38 Accessory | R7044, Excel 800 | Bnps, cbus |
| fan room 14 | CP fr14 H 3 | Honeywell | ?? | Honeywell Excel 800 | cbus |
| fan room 15 | CP fr15 H 1 | Honeywell | AHU-39, DCP-4, 2 North | R7044, Honeywell Excel 800 | bnps cbus |
| fan room 15 | CP fr15 H 2 | Honeywell | AHU-40, DCP-5, 4 North | Honeywell Excel 800 | cbus |
| fan room 15 | CP fr15 H 3 | Honeywell | AHU-41, DCP-6, 3 North | Honeywell Excel 800 | cbus |
| fan room 15 | CP fr15 H 4 | Honeywell | Veltron 39,40,41, EF-13 | Veltron Flow Meters | |
| fan room 15 | CP fr15 H 5 | Honeywell | Pneumatic | Pneumatic 39 | |
| fan room 15 | CP fr15 H 6 | Honeywell | Pneumatic | Pneumatic 40 | |
| fan room 15 | CP fr15 H 7 | Honeywell | Pneumatic | Pneumatic 41 | |
| fan room 15 | CP fr15 S 1 | Siemens | DP, Critical Valve Pos | Siemens Controller | bacnet |
| fan room 16 | CP fr16 H 1 | Honeywell | AHU-52 | Honeywell Excel 800 | cbus |
| fan room 16 | CP fr16 H 2 | Honeywell | AHU-52 | Pneumatic | |
| fan room 16 | CP fr16 H 3 | Honeywell | AHU-51 | honeywell Excel 800 | cbus |
| fan room 16 | CP fr16 H 4 | Honeywell | AHU-51 | Pneumatic | |
| fan room 16 | CP fr16 S 1 | Siemens | AHU-56 | Siemens controler | bacnet |
| fan room 16 | CP fr16 S 2 | Siemens | DP | Siemens controler | bacnet |
| fan room 16 | CP fr16 A 1 | Alerton | ?? | BCM-ETH Alerton | bacnet |
| fan room 17 | CP fr17 AH 1 | Alerton, Honeywell | AHU-54, RF-54 | Alerton controller for AHU-54, Honeywell EL 800 | bacnet |
| fan room 18 | CP fr18 AH 1 | Alerton | AHU-55 | Alerton Controller | bacnet |
| D 24 | not labeled | Honeywell | Angio Controller (Above Ceiling) | Honeywell thru JACE | bacnet |
| D119 | CP D119 H 1 | Honeywell | Old AHU-25 | Excel 800 | cbus |
| D119 | CP D119 H 2 | Honeywell | DCP-29, MRI, CT, F8 Air & Med Gas | R7044 | bnps |
| D119 | CP D119 H 3 | Honeywell | Bacnet Router | Bacnet Router | bacnet |
| D119 | CP D119 H 4 | Honeywell | RF-42 | Excel 800 | cbus |
| D119 | CP D119 H 5 | Honeywell | DCP-3, AHU-42 | R7044, Excel 800 | bnps, cbus |
| D119 | CP D119 H 6 | Honeywell | AHU-42 Pneumatics | Pneumatic | |
| D119 | CP D119 S 1 | Siemens | AHU 25 VFD | Siemens Controller | bacnet |
| D119a | CP D119a H 1 | Honeywell | DCP 2-1 Old AHU-35, EF-19 | R7044, Excel 800 | Bnps, cbus |
| d119a | CP D119a H 2 | Honeywell | AHU-35 Accessory | Veltron Flow Meter, Honeywell Flow Meter | |
| d119a | CP D119a H 3 | Honeywell | Excel 800 | Excel 800 | cbus |
| E-11a | CP E11a H 1 | Honeywell | AHU-19, EF-80, EF-81, MAF-3 | R7044 | bnps |
| E-11a | CP E11a H 2 | Honeywell | Pneumatic | Pneumatic | bnps |
| E-26b | CP E26b H 1 | Honeywell | Hiller | R7044 | |
| E-26b | CP E26b H 2 | Honeywell | Pneumatic | Pneumatic | |
| E-26b | CP E26b H 3 | Honeywell | DCP-19 Old AHU-25, RF-25 | R7044 | bnps |
| E-26b | CP E26b H 4 | Honeywell | Pneumatic | Pneumatic | |
| E-26b | CP E26b H 5 | Honeywell | Pneumatic | Pneumatic | |
| E-26b | CP E26b H 6 | Honeywell | Excel 800 abandoned in place | Excel 800 abandoned in place | |
| E-26 | CP E26 H 1 | Honeywell | DCP-15, Old CH 1&2, Dom Ht Water, Fuel Oil | R7044 | bnps |
| E-26 | CP E26 H 2 | Honeywell | Summer Winter | R7044 | bnps |
| E-26 | CP E26 S 1 | Siemens | Chiller 1, Chiller 2 | Siemens controller | bacnet |
| E-26 | CP E26 S 2 | Siemens | DXR Control | Siemens DXR controller | bacnet |
| E-26 | CP E26 S 3 | Siemens | Switch Gear | Siemens Digital Energy Meter | bacnet |
| F8 | CP F8 H 1 | Honeywell | ?? | Excel 800 | cbus |
| F8 | CP F8 H 2 | Honeywell | ?? | Pneumatic | |
| F8 | CP F8 H 3 | Honeywell | ?? | Excel 800 | cbus |
| F8 | CP F8 H 4 | Honeywell | EF Fans | Honeywell Comfort Point | bacnet |
| F8 | CP F8 S 1 | Siemens | Chiller 6 | Siemens controller | bacnet |
| F8 | CP F8 A 1 | Alerton | BCM-MSTP Alerton Controllers | BCM-MSTP Alerton controllers | bacnet |
| F8 | CP F8 A 2 | Alerton | AHU-29 | Alerton controller | bacnet |
| F8 | CP F8 A 3 | Alerton | AHU-28 | Alerton controller | bacnet |
| Roof 2South | CP Roof 2south S 1 | Siemens | AHU-25 | Siemens controler | bacnet |
| ACRE 3rd floor | not labeled | Honeywell | Several Comfortpoints (Above Ceiling) | Honeywell comfort point | bacnet |
| ACRE 4th floor | not labeled | Honeywell | Several Comfortpoints (Above Ceiling) | Honeywell comfort point | bacnet |
| ACRE 5th floor | not labeled | Honeywell | Several Comfortpoints (Above Ceiling) | Honeywell comfort point | bacnet |
Detailed Breakout
| Devices (Air Handlers, Chillers, Exhaust Fans, Heat Exchangers, etc.) | Location | Control Panel ID | Manufacturer | Contractor to Install Air Flow Management System (AFMS) | |
| AHU-2 | fan room 8 | CP fr8 S 1 | Siemens | Yes (Outside Air) | |
| AHU-3A | fan room 2 | CP fr2 A 1 | Alerton | No | |
| AHU-3B | Honeywell | No | |||
| AHU-4 | Alerton | Yes | |||
| AHU-5 | Honeywell | Yes | |||
| AHU-6 | Honeywell | Yes | |||
| AHU-7 | Honeywell | ||||
| AHU-8 | |||||
| AHU-9 | Honeywell | Yes | |||
| AHU-10 | |||||
| AHU-11 | Honeywell | Yes | |||
| AHU-12 | |||||
| AHU-13 | |||||
| AHU-14 | |||||
| AHU-15 | |||||
| AHU-16 | Siemens | ||||
| AHU-17 | Siemens | ||||
| AHU-18 | Siemens | ||||
| AHU-19 | Honeywell | ||||
| AHU-20 | Honeywell | ||||
| AHU-21 | Honeywell | ||||
| AHU-22 | |||||
| AHU-23 | Honeywell | Yes | |||
| AHU-24 | Honeywell | Yes | |||
| AHU-25 | Siemens | Yes (Outside Air) | |||
| AHU-26 | Honeywell | Yes | |||
| AHU-27 | Alerton | Yes | |||
| AHU-28 | |||||
| AHU-29 | |||||
| AHU-30 | Honeywell | Yes | |||
| AHU-31 | |||||
| AHU-32 | Honeywell | Yes | |||
| AHU-33 | Honeywell | Yes | |||
| AHU-34 | |||||
| AHU-35 | |||||
| AHU-36 | |||||
| AHU-37 | Honeywell | Yes | |||
| AHU-38 | Honeywell | Yes | |||
| AHU-39 | Honeywell | Yes | |||
| AHU-40 | Honeywell | Yes | |||
| AHU-41 | Honeywell | Yes | |||
| AHU-42 | Honeywell | Yes | |||
| AHU-43 | |||||
| AHU-44 | |||||
| AHU-45 | |||||
| AHU-46 | |||||
| AHU-47 | |||||
| AHU-48 | Honeywell | Yes | |||
| AHU-49 | Honeywell | Yes | |||
| AHU-50 | Honeywell | Yes | |||
| AHU-51 | Honeywell | Yes | |||
| AHU-52 | Honeywell | Yes | |||
| AHU-53 | Alerton | Yes | |||
| AHU-54 | Alerton | No | |||
| AHU-55 | Alerton | No | |||
| AHU-56 | Alerton | Yes (Outside Air) | |||
| Chiller 1 & Chiller 2 | Siemens | N/A | |||
| Chiller 3 | N/A | ||||
| Chiller 4/Operating Room Panel | Honeywell | N/A | |||
| Chiller 5/Operating Room Panel | Honeywell | N/A | |||
| Chiller 6 | F8 | Siemens | N/A | ||
| Chiller 7 Panel Controller & Interface | Honeywell | N/A | |||
| Convertible Heat Exchangers, | |||||
| C-HX-fr5-1 & C-HX-fr5-2 | Fan Room 5 | Honeywell | N/A | ||
| Convertible Heat Exchanger, | |||||
| C-HX-E26A-3 & C-HX-E26A-4 | E26A | Honeywell | N/A | ||
| Convertible Heat Exchanger, | |||||
| C-HX-E26A-5 & C-HX-E26A-6 | E26A | Honeywell | N/A | ||
| Convertible Heat Exchanger, | |||||
| C-HX-fr15-7 & C-HX-fr15-8 | Fan Room 15 | Honeywell | N/A | ||
| Convertible Heat Exchanger, | |||||
| C-HX-fr1-9 & C-HX-fr1-10 | Fan Room 1 | Honeywell | N/A | ||
| Convertible Heat Exchanger, | |||||
| C-HX-fr16-11 & C-HX-fr16-12 | Fan Room 16 | Honeywell | N/A | ||
| Convertible Heat Exchanger, | |||||
| C-HX-F8-13 | ACRE Building | Honeywell | N/A | ||
| South ERV-1-AHU-31 | ACRE Building, 6th | Alerton | |||
| North ERV-2-AHU-30 | ACRE Building, 6th | Alerton | |||
| Exhaust Fan, EF-13 | Honeywell | ||||
| Exhaust Fan, EF-35 | Honeywell | ||||
| Exhaust Fan, EF-77 | Honeywell | ||||
| Exhaust Fan, EF-82 | Honeywell | ||||
| Exhaust Fan, EF-83 | Honeywell | ||||
| Exhaust Fan, EF-86 | Honeywell | ||||
| Exhaust Fan, EF-87 | Honeywell | ||||
| Exhaust Fan, EF-88 | Honeywell | ||||
| Exhaust Fan, EF-155 | Honeywell | ||||
| Exhaust Fan, EF-182 | Honeywell | ||||
| Exhaust Fan, EF-183 | Honeywell | ||||
| Exhaust Fan, EF-184 | Honeywell | ||||
| Exhaust Fan, EF-185 | Honeywell | ||||
| Exhaust Fan, EF-194 | Honeywell | ||||
| Exhaust Fan, EF-197 | Honeywell | ||||
| Exhaust Fan, EF-206 | Honeywell | ||||
| Exhaust Fan, EF-213 | Honeywell | ||||
| Exhaust Fan, EF-214 | Honeywell | ||||
| Exhaust Fan, EF-222 | Honeywell | ||||
| Exhaust Fan, EF-223 | Honeywell | ||||
| Exhaust Fan, EF-228 | Honeywell | ||||
| Exhaust Fan, EF-238 | Honeywell | ||||
| Exhaust Fan, EF-252 | Honeywell | ||||
| Fan Coil Unit, FCU-10 | Alerton | ||||
| Fan Coil Unit, FCU-11 | Alerton | ||||
| Fan Coil Unit, FCU-12 | Alerton | ||||
| Fan Coil Unit, FCU-A | Alerton | ||||
| Fan Coil Unit, FCU-B | Alerton |