This document provides details on a federal contract opportunity to replace domestic hot water heaters at a Veterans Affairs medical center. The solicitation seeks replacement of combustion-type liquid propane or natural gas-fired domestic hot water heaters with an instantaneous steam-to-water heating system. The system described uses a high-efficiency plate and frame heat exchanger to produce hot water from low-pressure steam on demand, eliminating the need for large hot water storage tanks. This provides benefits such as reduced floor space needs, lower risks of stagnation and Legionella growth, and decreased heat loss compared to traditional hot water tank systems. The solicitation also includes requirements for control panels, valves, condensate removal options, and other auxiliary equipment to provide a turnkey steam-to-water heating solution. Interested vendors must submit responses by the deadline given in solicitation number 36C24821Q1311 issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| COMBINED SYNOPSIS SOLICITATION 36C24821Q1311.pdf | ||
| Attachment 2 SOW CLC Water Heaters.pdf | ||
| 36C24821Q1311.docx | DOCX document | |
| Attachment 1 PRICE SCHEDULE.docx | DOCX document | |
| Attachment A Wage Determination.pdf | ||
| Attachment D Mask Specification.pdf | ||
| Attachment E West Palm Beach VAMC Campus Map.pdf | ||
| Attachment C Limitations on Subcontracting Certification.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Steam to
W ater H eater
Heat Miser Instantaneous Steam to Water Heaters for Domestic and Process Water Heating Applications
Heat Miser www.watsonmcdaniel.com •• 428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 •• Tel: 610-495-5131
St ea m t o W at er
H ea te r
Heat MiserInstantaneous Steam to Water Heater
The Heat Miser is an Instantaneous Steam to Water Heater which produces hot water from steam.
The Watson McDaniel fully-assembled Heat Miser eliminates the need for large hot water storage tanks and saves significant energy which is required for large standing tanks of hot water.
Common Applications: Hospitals, Schools & Universities, Hotels, Process Washdown Stations, Residential Apartment Buildings or any other facility with an existing steam boiler.
System Benefits
• Meets the rigorous demands of domestic water heating
• Accommodates extreme load fluctuations without the need or storage tanks
• Accurate control of outlet water temperature for many systems to +/- 2ºF, and +/- 8ºF for wide and sudden load fluctuations
• High-efficiency Plate & Frame Heat Exchanger optimized for use with low pressure steam and offers typical flow rates up to 300 GPM, with higher flow rate designs available
• Integral Control Panel included for ease of operation and system feedback
• Electric and Pneumatic Control Valves available for precise steam control
• Excellent for washdown stations
The Watson McDaniel Difference
• ASME qualified welders and certifications
• ASME U and UM Stamp availability on appropriate components
• Complete assembly and pressure testing prior to shipment
• Better control of design, cost and quality by avoiding 3rd party fabricators
• Unparalleled turn-around and deliveries with many units available for shipment within days
Standard Auxiliary Items
• Steam and Condensate Inlet Y-Strainers
• Stainless Steel Recirculation Pump
• Over-temperature Protection – Solenoid-actuated Cold Water Injection
• Steam Inlet Pressure Gauge
• Stainless Steel RTD Electronic Temperature Sensor
• Stainless Steel Waterside Piping with Safety Valve
Old Hot Water System Negatives
• Takes up excessive floor space
• Stagnating hot water
• Danger of Legionella Growth
• Corrosion of tanks
• Significant radiant heat loss
New Heat Miser System
• Small footprint (typical floor space of 14ft2)
• Efficient plate & frame heat exchanger maximizes turbulent flow for instantaneous hot water on demand
• Stainless Steel waterside components
• Simple maintenance and reduced overall costs www.watsonmcdaniel.com •• Pottstown PA • USA • Tel: 610-495-5131
Steam to
W ater H eater
Heat MiserInstantaneous Steam to Water Heater
Condensate Drainage Options
Float & Thermostatic Steam Trap (gravity drainage option)
• All Stainless Steel Internals
• Body Material options include Ductile Iron, Carbon Steel and Stainless Steel
Pump-Trap Combination (pumped drainage option)
• Patented Snap-Assure mechanism with stainless steel wear parts
• Ductile Iron Tank
• Gauge Glass
• Motive PRV, Drip Trap, and Motive and Vent Piping
Control Panel
• NEMA 4X Electrical Enclosure
• Electronic PID Controller with Full Auto-Tune Capability
• Selector Switches – Controller On/Off and Pump On/Off
• All components to be pre-wired for 120V service
Control Valve
• Cast Iron, Bronze or Steel Globe Body
• Fail Closed Pneumatic Actuator
• Electro-Pneumatic Positioner
• Single Seat, Equal Percentage, Stainless Steel Trim
Heat Exchanger
• High-efficiency Plate & Frame Counterflow Type
• Single or Double Wall 316 Stainless Steel Plates
• Steam-rated EPDM gaskets
• Plates may easily be added, removed or replaced on site
Common Optional Items
• High-limit Steam Isolation Package including dedicated sensor and actuated ball valve
• HDP Pressure Reducing Valve for reducing inlet steam supply pressure to the control valve
Cold Water Inlet
Steam Inlet
Hot Water Outlet
Condensate Outlet
Tel: 610-495-5131 • Pottstown PA • USA •• www.watsonmcdaniel.com